Flush the water supply lines before beginning installation and after installation is complete. Test the unit for
leaks and adequate water flow. Main water supply to the eyewash should be “ON” at all times. Provisions
shall be made to prevent unauthorized shutoff.
CAUTION
Emergency equipment must be supplied with tepid water (60°F to 100°F/15.6°C to 37.8°C). Any prolonged
exposure to near freezing water affects the body's ability to maintain body temperature, increasing the risk of
hypothermia.
NOTICE
Before installing this product, ensure that there are adequate clearances around the product and activation of
the product does not interfere with other products or obstructions.
Avoid cleaners containing organic solvents, alcohols and hydrocarbons. Rinse with water after cleaning.
IMPORTANT
The installation and location of all safety drench showers, eye and eye/face washes must comply with the
requirements of ANSI/ISEA Z358.1.
Read this installation manual completely to ensure proper installation, then file it with the owner or
maintenance department. Compliance and conformity to drain requirements and other local codes and
ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before discarding any packaging
material. If any parts are missing, do not begin installation until you obtain the missing parts.
The ANSI/ISEA Z358.1 standard requires an uninterrupted supply of flushing fluid. Bradley plumbed
emergency fixtures require a minimum of 30 PSI (0.21MPa) flowing pressure.
Self-closing spring-loaded valves are not UL classified to ANSI/ISEA Z358.1.
Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable flushing
fluid supply is present and any sediment build-up in the supply line is cleared. Emergency equipment should
be inspected monthly to address any maintenance issues ensuring the equipment is in good operating
condition and that there are no signs of wear.
Workers who may come in contact with potentially hazardous materials should be trained regarding the
placement and proper operation of emergency equipment per ANSI/ISEA Z358.1.
For questions regarding the operation or installation of this product, visit www.bradleycorp.com or call
800-BRADLEY (272.3539).
Product warranties and parts information may also be found under ”Products” on our web site at
bradleycorp.com.
Local codes may require the installation of a backflow
prevention valve to complete proper installation.
Compliance with local codes is the responsibility of the
installer. Valve must be tested annually to verify that it
is functioning properly. Backflow prevention valves are
not included with the fixture and may be supplied by
the contractor or purchased from Bradley Corporation.
Halo eye/face wash unit is shown on a sample 25" (635mm) deck. Other units are similar.
Minimum dimensions necessary to contain splashing from Halo units are shown.
Apply pipe sealant (supplied by installer) to all male-threaded pipe joints. The top of the eyewash heads should be positioned
a minimum of 33" (838mm) and a maximum of 45" (1143mm) from the floor and 6" (152mm) from the nearest obstruction.
Proper faucet shank/handle
clearance and recommended
minimum splash containment
dimensions must be considered
when selecting the desired
location for mounting.
25"
(635mm)
A
1¼"
(32mm)
Deck Mounting Pattern.
Drill (3) holes as shown.
¼"
(6mm)
Ø ⁷⁄₈"
B
Ø ³⁄₁₆"
Deck
"OFF" Position
11¹⁄₈"
(283mm)
Ref.
15¼"
(387mm)
Ref.
2¹⁄₈"
(54mm)
Min.
D
To
Wall
114-051
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY FAX: (262-251-5817)
http://www.bradleycorp.com
Connect the water supply using
piping (supplied by installer) with
C
½" NPT female threaded end.
"ON" Position
3¾"
(95mm)
Ref.
Slowly open the water
supply lines to relieve air
and pressurize the valve.
TEST THIS UNIT EACH WEEK
DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.
30
bradleycorp.com
114-051
ESSAI HEBDOMADAIRE
Test-operate valve(s) each week and sign below.
Report any malfunctions immediately.
Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt
durch Unterschrift. Jegliche Störung sofort melden.
Test le fonctionnement des valves chaque semaine et
signe en bas. S'il y à quelque chose qui ne va pas fait
un rapport immédiatement.
TEST THIS UNIT EACH WEEK
DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.
30
bradleycorp.com
114-051
1
ESSAI HEBDOMADAIRE
Test-operate valve(s) each week and sign below.
Report any malfunctions immediately.
Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt
durch Unterschrift. Jegliche Störung sofort melden.
Test le fonctionnement des valves chaque semaine et
signe en bas. S'il y à quelque chose qui ne va pas fait
un rapport immédiatement.
Date
Signed
Date Signed
Datum
Unterschrift
Date
Date
Signe
Date
2
31
Signed
Signed
19
1
Deck
13
14
15
16
Prepack S65-339 includes items 26, 27, 28
Prepack S88-068 includes items 25, 26, 27, 28
28
27
26
25
22
23
27
26
25
20
28
21
29
Eyewash Cover Prepack
S45-2675 includes items
22 and 23
Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt
durch Unterschrift. Jegliche Störung sofort melden.
Test le fonctionnement des valves chaque semaine et
signe en bas. S'il y à quelque chose qui ne va pas fait
un rapport immédiatement.