• Meets ANSI Z358.1-2009
• Reliable Liquid-Filled Thermostat with 10-Year Warranty
• Integral Strainer Checkstops on Inlets
• Adjustable Set Point within Temperature Range
• Accurate Temperature Control to within ±3° F
• Built-in Cold Water Bypass, Assuring Cold Flow
• Positive Shutoff of Hot Supply When Cold Supply is Lost
• Easy Installation and Serviceability
• Dirt and Lime Resistant
• Dial Thermometer
• Factory Assembled and Tested
• Universal Mounting Capability
• Cabinet Features:
— 18 Gauge Body & Door
— Left-Hand Hinge
— Cylinder Lock
— Inlet/Outlet Knock-Out Holes for Mounting Flexibility
— Stainless Steel or Baked White Enamel Finishes
— Surface-Mounted or Recessed Style
S19-2300
Emergency Fixture Thermostatic Mixing Valves
S19-2300
Valve Specifications
Maximum Operating Pressure
125 PSI (860 kPA)
Maximum Inlet Temperature
180° F (82° C)
Recommended Inlet Temperature
120° F (49° C) – 140° F (60° C)
Temperature Range Set Point
Std.
Flow Capacities – GPM (L/Min)
Model
S19-2300
Cold Bypass Only
65° F (18° C) to 95° F (35° C) 85° F (29° C)
Min.
Flow
3.0
(11.5)
5
(.5)
33.5
(153.0)
25.5
(117.3)
Pressure Drop – PSI (Bar)
10
47.5
36.5
15
(1.5)
58.0
(265.0)
44.5
(203.0)
(306.0)
(234.5)
(1.0)
(216.3)
(166.0)
20
(2.0)
67.0
51.5
30
(2.5)
82.0
(342.0)
63.0
(262.0)
This plumbing fixture is not intended to dispense water for human
consumption through drinking or for preparation of food or beverages.
Engineer's Approval
Page 1 of 4 4/25/2014
This information is subject to change without notice.
Bradley_TMV_Emergency_EFX125
45
(3.0)
100.5
(374.5)
77.0
(287.0)
60
(4.0)
116.0
(432.5)
89.0
(331.5)
Optional Selections
Finish
¨C
Bracket
¨B
Piped Assembly
¨P
¨N
Cabinets
¨SS
¨RS
¨SE
¨RE
¨W
Chrome Plated
Wall Mounting Bracket
Piped Assembly with Inlet and Outlet Shutoff
Piped Assembly only
Surface Mount Stainless Steel
Recessed Stainless Steel
Surface Mount White Enamel
Recessed White Enamel
Plexi-glass Window in Door
P.O. Box 309, Menomonee Falls, WI 53052-0309
© 2015 Bradley
800 BRADLEY (800 272 3539) +1 262 251 6000
bradleycorp.com

Recirculation Diagram
Cold
Water
Check Valve (Typ)
Cold
Heat
Trap 28”
Drop
HOT
Alternate
Recirculation
(More than 5 GPM)
Balancing
Valve (Typ)
S19-2300
Emergency Fixture Thermostatic Mixing Valves
(mm)
Tempered Water Flow
Check Valve
Temperature
Switch
Recirculated
Return
Flow
Recirculating
Pump
Tempered Water
Water
Heater
Storage
Tank
Dimensions
Model A B C D E F G H I X
S19-2300 2-3/4" (70) 10-1/2" (267) 14" (356) 1-3/4" (45) 5" (127) 6-5/8" (169) 13-1/2" (343) 4-7/8" (124) 22" (559) 1-1/4" 1-1/2" 3/4"
NPT
Y
NPT
A
NPT
X
B
C
Z
I
Min.
G
F
D
E
NPT
X
H
NPTYNPTZNPT
Page 2 of 4 4/25/2014