• Exceeds ANSI Z358.1
• ASSE 1071 Certified
• Reliable Liquid-Filled Thermostat with 10-Year Warranty
• Integral Strainer Checkstops on Inlets
• Adjustable Set Point within Temperature Range
• Accurate Temperature Control to within ±3° F
• Built-in Cold Water Bypass, Assuring Cold Flow
• Positive Shutoff of Hot Supply When Cold Supply is Lost
• Easy Installation and Serviceability
• Dirt and Lime Resistant
• Dial Thermometer
• Factory Assembled and Tested
• Universal Mounting Capability
• Cabinet Features:
— 18 Gauge Body & Door
— Left-Hand Hinge
— Cylinder Lock
— Inlet/Outlet Knock-Out Holes for Mounting Flexibility
— Stainless Steel or Baked White Enamel Finishes
— Surface-Mounted or Recessed Style
Valve Specifications
Maximum Operating Pressure
125 PSI (860 kPA)
Maximum Inlet Temperature
180° F (82° C)
Recommended Inlet Temperature
120° F (49° C) – 140° F (60° C)
Temperature Range Set Point
Std.
Flow Capacities – GPM (L/Min)
Model
S19-2150
Minimum cold water bypass at 30 PSID: 8.0 GPM
65° F (18° C) to 90° F (32° C) 85° F (29° C)
Min.
Flow
3.0
(11.5)
5
(.5)
6.0
(29.0)
Pressure Drop – PSI (Bar)
10
9.5
15
(1.5)
12.5
(60.0)
(2.0)
(72.0)
(1.0)
(46.0)
20
15.0
30
(2.5)
19.5
(83.5)
This plumbing fixture is not intended to dispense water for human
consumption through drinking or for preparation of food or beverages.
45
(3.0)
25.5
(96.5)
S19-2150
Emergency Fixture Thermostatic Mixing Valve
Models (Must select one)
Model Description
EFX20-Thermostatic Mixing Valve
Chrome Plated
Wall Mounting Bracket
Piped Assembly with Inlet and Outlet Shutoff
Piped Assembly only
Surface Mount Stainless Steel
Recessed Stainless Steel
Surface Mount White Enamel
Recessed White Enamel
Plexi-glass Window in Door
60
(4.0)
30.5
(113.5)
¨S19-2150
Optional Selections
Finish
¨C
Bracket
¨B
Piped Assembly
¨P
¨N
Cabinets
¨SS
¨RS
¨SE
¨RE
¨W
Code Compliance and Certifications
ASSE 1071 & UPC certified.
Engineer's Approval
Page 1 of 4 3/17/2014
This information is subject to change without notice.
Bradley_TMV_Emergency_EFX20
P.O. Box 309, Menomonee Falls, WI 53052-0309
© 2015 Bradley
800 BRADLEY (800 272 3539) +1 262 251 6000
bradleycorp.com

Recirculation Diagram
S19-2150
Emergency Fixture Thermostatic Mixing Valve
(mm)
Check Valve (Typ)
Cold
Water
Water
Heater
Cold
Heat
Trap 28”
Drop
Storage
Tank
HOT
Alternate
Recirculation
(More than 5 GPM)
Valve (Typ)
Check Valve
Balancing
Return
Flow
Tempered Water Flow
Tempered Water
Recirculating
Pump
Recirculated
Temperature
Switch
Dimensions
Model A B C D E F G H X
NPT
S19-2150 7" (178) 2" (51) 3-1/4" (84) 4-3/4" (119) 8" (203) 14" (356) 3-1/8" (79) 9-1/4" (234) 3/4" 1" 3/4"
NPT
Y
NPT
Z
NPT
Y
NPT
X
Page 2 of 4 3/17/2014
This information is subject to change without notice.
Bradley_TMV_Emergency_EFX20
B
NPT
Z
E
D
C
NPT
A
H
X
G
P.O. Box 309, Menomonee Falls, WI 53052-0309
800 BRADLEY (800 272 3539) +1 262 251 6000
Min.
F
© 2015 Bradley
bradleycorp.com