Bradley Corporation S19-2100 User Manual

• Reliable Liquid-Filled Thermostat with 10-Year Warranty
• Integral Strainer Checkstops on Inlets
• Adjustable Set Point within Temperature Range
• Accurate Temperature Control to within ±3° F
• Built-in Cold Water Bypass, Assuring Cold Flow
• Positive Shutoff of Hot Supply When Cold Supply is Lost
• Easy Installation and Serviceability
• Dirt and Lime Resistant
• Dial Thermometer
• Factory Assembled and Tested
• Universal Mounting Capability
• Cabinet Features:
— 18 Gauge Body & Door
— Left-Hand Hinge
— Cylinder Lock
— Inlet/Outlet Knock-Out Holes for Mounting Flexibility
— Stainless Steel or Baked White Enamel Finishes
— Surface-Mounted or Recessed Style
S19-2100
Emergency Fixture Thermostatic Mixing Valve
Valve Specifications
Maximum Operating Pressure
125 PSI (860 kPA)
Maximum Inlet Temperature
180° F (82° C)
Recommended Inlet Temperature
120° F (49° C) – 140° F (60° C)
Temperature Range Set Point
Std.
Flow Capacities – GPM (L/Min)
Model
S19-2100
Cold Bypass Only
65° F (18° C) to 90° F (32° C) 85° F (29° C)
Min. Flow
2.0
(5.5)
5
(.5)
10.5
(48.5)
8.0
(37.0)
Pressure Drop – PSI (Bar)
10
15
11.5
15
(1.5)
18.5
(84.0)
14
(64.5)
(1.0)
(68.5)
(52.0)
20
(2.0)
21.3
(97.0)
16.5
(74.0)
30
(2.5)
26.0
(108.5)
20.0
(83.0)
This plumbing fixture is not intended to dispense water for human
consumption through drinking or for preparation of food or beverages.
Engineer's Approval
Page 1 of 4 3/17/2014 This information is subject to change without notice. Bradley_TMV_Emergency_EFX25
45
(3.0)
32.0
(119.0)
24.5
(91.0)
60
(4.0)
37.0
(137.0)
28.0
(105.0)
Models (Must select one)
Model Description
¨S19-2100
EFX25-Thermostatic Mixing Valve
Optional Selections
Finish
¨C
Bracket
¨B
Piped Assembly
¨P ¨N
Cabinets
¨SS ¨RS ¨SE ¨RE ¨W
Chrome Plated
Wall Mounting Bracket
Piped Assembly with Inlet and Outlet Shutoff Piped Assembly only
Surface Mount Stainless Steel Recessed Stainless Steel Surface Mount White Enamel Recessed White Enamel Plexi-glass Window in Door
P.O. Box 309, Menomonee Falls, WI 53052-0309
© 2015 Bradley
800 BRADLEY (800 272 3539) +1 262 251 6000
bradleycorp.com
Recirculation Diagram
S19-2100
Emergency Fixture Thermostatic Mixing Valve
(mm)
Check Valve (Typ)
Cold Water
Water
Heater
Cold
Heat
Trap 28”
Drop
Storage
Tank
HOT
Alternate
Recirculation
(More than 5 GPM)
Valve (Typ)
Check Valve
Balancing
Return
Flow
Tempered Water Flow
Tempered Water
Recirculating
Pump
Recirculated
Temperature
Switch
Dimensions
Model A B C D E F G H X
NPT
S19-2100 7" (178) 2" (51) 3-1/4" (84) 4-3/4" (119) 8" (203) 14" (356) 3-1/8" (79) 9-1/4" (234) 3/4" 1" 3/4"
NPT
Y
NPT
Z
NPT
Y
NPT
X
Page 2 of 4 3/17/2014 This information is subject to change without notice. Bradley_TMV_Emergency_EFX25
B
NPT
Z
E
D
C
NPT
A
H
X
G
P.O. Box 309, Menomonee Falls, WI 53052-0309
800 BRADLEY (800 272 3539) +1 262 251 6000
Min.
F
© 2015 Bradley
bradleycorp.com