Bosch LM024, LM060, LM036, LM070, LM048 Operating Instructions Manual

LM CS Series Heat Pump
LM024 | LM036 | LM048 | LMO60 | LM070
Installation, Operation and Maintenance Manual
8 733 920 847 (2014/01)
2 | LM CS Series Heat Pump
CONTENTS
Key to Symbols.................................................................. 3
Safety Warnings ................................................................ 3
LM CS Standard package.................................................... 4
GENERAL DESCRIPTION .................................................... 4
MOVING AND STORAGE ..................................................... 4
INITIAL INSPECTION .......................................................... 4
LOCATION......................................................................... 5
Condensing Section ..................................................... 5
Air Handler ................................................................. 5
INSTALLATION .................................................................. 5
CONDENSATE DRAIN ......................................................... 6
WATER PIPING .................................................................. 6
ELECTRICAL ...................................................................... 6
Safety Devices and the UPM Controller ........................... 7
COMFORT ALERT MODULE............................................... 10
OPTIONS......................................................................... 12
Pump Status Switch ................................................... 12
DPS Water Flow Proving ............................................. 12
Valve End Switch ....................................................... 12
Pump Relay............................................................... 12
SEQUENCE OF OPERATION .............................................. 13
Cooling Mode ............................................................ 13
Heating Mode............................................................ 13
APPLICATION CONSIDERATIONS...................................... 15
Well Water Systems ................................................... 15
Cooling Tower/Boiler Systems ..................................... 15
Geothermal Systems .................................................. 17
SYSTEM CHECKOUT ........................................................ 18
UNIT START-UP ............................................................... 18
MAINTENANCE................................................................ 19
UNIT CHECK-OUT SHEET .................................................. 20
TROUBLESHOOTING ........................................................ 21
OPERATING TEMPERATURES AND PRESSURES ................. 25
WIRING DIAGRAMS ......................................................... 30
DIMENSIONAL DRAWINGS ............................................... 31
NOTES ............................................................................ 32
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
LM CS MODEL NOMENCLATURE
LM 024 - 1 CS C - F
SERIES WATER CONNECTIONS
LM F - Front
SIZE
COAX OPTIONS
024 C - Copper 036 N - Cupro-Nickel 048 060
CABINET CONFIGURATION
070 CS - Condensing Section
VOLTAGE DESIGNATIONS
1
- 208/1/60 & 230/1/60
Revision Level A
CS/AH Pairing | 3LM CS Series Heat
CS/AH PAIRING
UNIT MODEL
LM024-1CSC LM036-1CSC LM048-1CSC LM060-1CSC LM070-1CSC
Paired Air Handler
Unit 1 Unit 2
LM024-1AVX LM036-1AVX LM048-1AVX LM060-1AVX LM070-1AVX
LM024-1AHX LM036-1AHX LM048-1AHX LM060-1AHX LM070-1AHX
KEY TO SYMBOLS
Warnings
Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of the warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:
NOTE indicates a situation that could result in damage to property or equipment.
CAUTION indicates a situation that could result in minor to medium injury.
WARNING indicates a situation that could result in sever injury or death.
DANGER indicates a situation that will result in severe injury or death.
Important Information
This symbol indicates important information where there is no risk to property or people.
SAFETY WARNINGS
Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could
cause personal injury or death.
Installation and servicing of this equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service the equipment.
All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
R410A is flammable when exposed to open flame. Recover all refrigerant prior to brazing.
8 733 920 847 (2014/01)Revised 01-14
4 | LM CS Standard package LM CS Series Heat Pump
1
2
LM CS STANDARD PACKAGE
Figure # 1
[1] LM Split Series Water-to-Air Heat Pump Condensing Section
[2] Installation and Operation Manual
GENERAL DESCRIPTION
LM Split Series Water-to-Air Heat Pumps provide the best combination of performance and efficiency available. All units are performance certified to American Heating and Refrigeration Institute (AHRI) ISO Standard 13256-1. All LM Water-to-Air Heat Pumps conform to UL1995 standard and are certified to CAN/CSA C22.1 No 236 by Intertek-ETL.
Split system heat pumps consist of two independently installed sections allowing for centralized air distribution while remotely locating the section containing the compressor and water­to-refrigerant heat exchanger.
The Water-to-Air Heat Pumps are designed to operate with entering fluid temperature between 20°F to 80°F in the heating mode and between 50°F to 110°F in the cooling mode.
50°F Minimum Entering Water Temperature (EWT) for well water applications with sufficient water flow to prevent freezing. Antifreeze solution is required for all closed loop applications.
Cooling Tower/Boiler and Geothermal applications without antifreeze must have means to protect against extreme conditions and equipment failure. Frozen water coils are not covered under warranty. Other equivalent methods of temperature control are acceptable.
Several factory installed options are available: Differential Pressure Switch (DPS) Water Flow Proving Switch, Auxiliary Pump Relay, Zone Valve and Internal Water Pump. See Pg#12 for more detail.
Safety devices are built into each unit to provide the maximum system protection possible when properly installed and maintained.
MOVING AND STORAGE
If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean, dry area. Units must only be sto r ed or m o v ed in t h e normal upright position as indicated by the “UP” arrows on each carton at all times.
In the cooling mode, the air coil in the air handler section serves as an evaporator and the water-to­refrigerant heat exchanger serves as a condenser. In the heating mode, their roles are reversed.
In cooling mode, the refrigerant lines connecting the two sections consist of one line carrying liquid refrigerant and another carrying refrigerant vapor. The liquid carrying line will be referred to as the liquid line while the vapor carrying line will be referred to as the suction line.
INITIAL INSPECTION
Be certain to inspect all cartons or crates on each unit as received at the job site before signing the freight bill. Verify that all items have been received and that there are no visible damages; note any shortages or damages on all copies of the freight bill. In the event of damage or shortage, remember that the purchaser is responsible for filing the necessary claims with the carrier. Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt.
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Location | 5LM CS Series Heat
Vibration Pad is recommended
LOCATION
To maximize system performance, efficiency and reliability, and to minimize installation costs, it is always best to keep the refrigerant lines as short as possible. Every effort should be made to locate the air handler and the condensing section as close as possible to each other.
Condensing Section
Locate the condensing section in an area that provides sufficient room to make water and electrical connections, and allows easy removal of the access panels, for service personnel to perform maintenance or repair.
The condensing section is designed for indoor use; however, if the condensing section must be installed in an outdoors location where ambient temperatures can fall below freezing, some form of freeze protection should be employed such as a freeze-stat and/or a pump timer/starter to prevent possible condenser freeze-up and to optimize overall system performance.
Air Handler
Locate the air handler unit in an indoor area that allows easy removal of the filter and access panels, and has enough room for service personnel to perform maintenance or repair. Provide sufficient room to make electrical and duct connections. If the unit is located in a confined space such as a closet, provisions must be made for return air to freely enter that space.
Reference the Factory Manual for your AH, or Air Handler section of this manual for detailed installation and operation.
INSTALLATION
Loosen compressor mounting bolts.
NOTE: The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedent over any recommendations contained in these instructions. In lieu of local codes, the equipment should be installed in accordance with the recommendations made by the National electric code, and in accordance with the recommendations made by the National Board of Fire Underwriters.
Condensing Section
The condensing section should be mounted on a vibration absorption pad on a cement slab or similar support to provide a good base and some degree of levelness. The cement pad should not come in contact with the foundation or side of the dwelling, because sound may be transmitted into the residence. See Figure #2 below.
DO NOT remove the protective caps or plugs from the service valves until the refrigerant lines are run and ready for final connections.
Figure # 2
8 733 920 847 (2014/01)Revised 01-14
6 | Condensate Drain LM CS Series Heat Pump
CONDENSATE DRAIN
Use cupra-nickel condenser in ground water application due to possibility of containing high mineral and corrosive properties
Both the supply and discharge water lines will sweat if subjected to low water temperature. These lines should be insulated to prevent damage from condensation. All manual flow valves used in the system must be ball valves. Globe and gate valves must not be used due to high pressure drop
Figure # 3
A drain line must be connected to the air handler and pitched away from the unit a minimum of 1/8” per foot to allow the condensate to flow away from the unit.
This connection must be in conformance with local plumbing codes. A trap must be installed in the condensate line to insure free condensate flow.
Drain Pan is not internally sloped.
and poor throttling characteristics.
Never exceed the recommended water flow rates, as serious damage or erosion of the water-to-refrigerant heat exchanger could occur.
Teflon tape sealer should be used when connecting water piping connections to the units to insure against leaks and possible heat exchanger fouling.
A vertical air vent is sometimes required to avoid air pockets. The length of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included.
WATER PIPING
Supply and return piping must be as large as the unit connections on the heat pump (See manual Pg#10 for any line size at installation length longer than 25 feet).
Never use flexible hoses of a smaller inside diameter than that of the fluid connections on the unit.
LM units are supplied with either a copper or optional cupro-nickel condenser. Copper is adequate for ground water that is not high in mineral content.
Proper testing is recommended to assure the well water quality is suitable for use with water source equipment.
In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended.
Flexible hoses should be used between the unit and the rigid system to avoid possible vibration. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing.
ELECTRICAL
Refer to electrical component box layout. (Figures #5,6)
Field wiring must comply with local and national electric codes. Properly sized fuses or HACR circuit breakers must be installed for branch circuit protection. See unit nameplate for maximum fuse or breaker size.
Power to the unit must be within the operating voltage range indicated on the unit nameplate or on the performance data sheet.
Operation of unit on improper line voltage or with excessive phase imbalance will be hazardous to the unit, constitutes abuse and may void the warranty.
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Electrical | 7LM CS Series Heat
4
5
3
2
15
6
7
8
1
10
12
14
13
11
9
1
2
3
4
5
6
78
9
10
11
1213
17
14
15
16
The unit is provided with a concentric knock-out for attaching common trade sizes of conduit, route power supply wiring through this opening.
Always connect the ground lead to the grounding lug provided in the control box and power leads to the line side of compressor contactor as indicated on the wiring diagram (Figures#17 through #25, Pg#30 through Pg#40).
[9] ECM Interface Board(Option, mounts on E-Box cover)
[10] Comfort Alert Module (Option) [11] DDC (Option) [12] LonWorks Card (Option) [13] Input Expansion Module (Option) [14] Smart Start Assist (Option) [15] Ground Lug
Safety Devices and the UPM Controller
Figure # 4 - Single Phase unit
Figure # 6 Typical UPM Board
[1] Board Power Indicator [2] UPM Status LED Indicator [3] Water Coil Freeze Protection Temperature
Selection [R30] [4] Air Coil Freeze Protection Temperature
Selection [5] UPM Board Settings [6] Water Coil Freeze Connection [7] Air Coil Freeze Connection
Figure # 5 EBox Cover
[1] Compressor contactor [2] Energy Management System Relay (Option) [3] Hot Gas Reheat Relay (Option) [4] Cooling Relay [5] Unit Protection Module (UPM) [6] Terminal block Low-Voltage [7] Auxiliary Relay (Option) [8] Capacitor
[8] LED Status-Diagnostic Connection [9] 24VAC Power Input [10] Compressor Contact Output [11] High Pressure Switch Connection [12] Call for Compressor Y1 [13] Low Pressure Switch Connection [14] 24VAC Power Common [15] Condensate Overflow Sensor [16] Dry Contact [17] UPM Ground Standoff
8 733 920 847 (2014/01)Revised 01-14
8 | Electrical LM CS Series Heat Pump
If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit malfunction output or relay. Refer to Figure #6.
If the thermostat is provided with a malfunction light powered off of the common (C) side of the transformer, a jumper between “R” and “COM” terminal of “ALR” contacts must be made.
If the thermostat is provided with a malfunction light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected directly to the (ALR) contact on the unit’s UPM board.
Each unit is factory provided with a Unit Protection Module (UPM) that controls the compressor
operation and monitors the safety controls that protect the unit.
Safety controls include the following:
High pressure switch located in the refrigerant discharge line and wired across the HPC terminals on the UPM
Low pressure switch located in the unit refrigerant suction line and wired across terminals LPC1 and LPC2 on the UPM.
UPM Board Dry Contacts are Normally Open (NO)
Water side freeze protection sensor, mounted close to condensing water coil, monitors refrigerant temperature between condensing water coil and thermal expansion valve. If temperature drops below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 30°F, however this can be changed to 15°F by cutting the R30 or Freeze1 resistor located on top of DIP switch SW1. Refer to Figure #6, item [3] for resistor location. (Refer to Figure #7 for sensor location)
Figure # 7
If unit is employing a fresh water system (no anti-freeze protection), it is extremely important to have the Freeze1 R30 resistor set to 30°F in order to shut down the unit at the appropriate leaving water temperature and protect your heat pump from freezing if a freeze sensor is included.
The condensate overflow protection sensor is located in the drain pan of the unit and connected to the ‘COND’ terminal on the UPM board. (Figure #8)
Figure # 8
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
UPM Board Factory Default Settings
TEMP
LOCKOUT
RESET
ALARM
TEST
30°F
2
Y
PULSE
NO
UPM DIP SWITCH DEFAULT POSITION
lockout 42
Electrical | 9LM CS Series Heat
MALFUNCTION OUTPUT: Alarm output is
Normally Open (NO) dry contact.
If pulse is selected the alarm output will be pulsed. The fault output will depend on the dip switch setting for "ALARM". If it is set to "CONST", a constant signal will be produced to indicate a fault has occurred and the unit requires inspection to determine the type of fault. If it is set to "PULSE", a pulse signal is produced and a fault code is detected by a remote device indicating the fault. See LED Fault Indication below for blink code explanation. The remote device must have a malfunction detection capability when the UPM board is set to "PULSE".
reset
alarm
test
RY
Cont pulse
yes no
The UPM Board includes the following features:
ANTI-SHORT CYCLE TIMER:
break timer to prevent compressor short cycling.
5 minute delay on
RANDOM START: Each controller has an unique
random start delay ranging from 270 to 300 seconds on initial power up to reduce the chance of multiple unit simultaneously starting at the same time after power up or after a power interruption, thus avoiding creating large electrical spike.
LOW PRESSURE BYPASS TIMER: If the
compressor is running and the low pressure switch opens, the controller will keep the compressor ON for 120 seconds. If, after 120 seconds the low pressure switch remains open, the controllers will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low pressure switch closes and the anti-short cycle time delay expires. If the low pressure switch opens 2-4 times in 1 hour, the unit will enter a hard lockout. In order to exit hard lockout power to the unit would need to be reset.
BROWNOUT/SURGE/POWER INTERRUPTION PROTECTION:
protection in the UPM board will shut does the compressor if the incoming power falls below 18 VAC. The compressor will remain OFF until the voltage is above 18 VAC and ANTI-SHORT CYCLE TIMER (300 seconds) times out. The unit will not go into a hard lockout.
The brownout
If 24 VAC output is needed R must be wired to ALR-COM terminal; 24 VAC will be available o the ALR-OUT terminal when the unit is in the alarm condition.
TEST DIP SWITCH:
to reduce all time delays settings to 10 seconds during troubleshooting or verification of unit operation.
Operation of unit in test mode can lead to accelerated wear and premature failure of components. The "TEST" switch must be set back to "NO" after troubleshooting/ servicing.
A test dip switch is provided
FREEZE SENSOR: The default setting for the
freeze limit trip is 30°F (sensor number 1); however this can be changed to 15°F by cutting the R30 resistor located on top of the DIP switch SW1.
default setting for the freeze limit trip is 30°F (sensor number 1); however this can be changed to 15°F by cutting the R24 resistor located on top of the DIP switch SW1. Since freeze sensor 2 is dedicated to monitor the evaporator coil it is recommended to leave the factory default setting on the board. The UPM controller will constantly monitor the refrigerant temperature with the sensor mounted close to the condensing water coil between the thermal expansion valve and water coil. If temperature drops below or remains at the freeze limit trip for 30 seconds, the controller will shut the compressor down and enter into a soft lockout condition. Both the status LED and the Alarm contact will be active. The LED will flash (three (3) times) the code associated with this alarm condition. If this alarm occurs 2 times (or 4 if Dip switch is
The
8 733 920 847 (2014/01)Revised 01-14
10 | Comfort Alert Module LM CS Series Heat Pump
set to 4) within an hour the UPM controller will enter into a hard lockout condition. It will constantly monitor the refrigerant temperature with the sensor mounted close to the evaporator between the thermal expansion valve and evaporator coil as shown in Figure #4. If temperature drops below or remains at the freeze limit trip for 30 seconds, the controller will shut the compressor down and enter into a soft lockout condition. Both the status LED and the Alarm contact will be active. The LED will flash (three (6) times) the code associated with this alarm condition. If this alarm occurs 2 times (or 4 if Dip switch is set to 4) within an hour the controller will enter into a hard lockout condition. Refer to page #10 for more information.
Freeze sensor will not guard against loss of water. Flow switch is recommended to prevent unit from running, if water flow is lost or reduced.
INTELLIGENT RESET: If a fault condition is initiated, the 5 minute delay on break time period is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition still exists or occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. A single condensate overflow fault will cause the unit to go into a hard lockout immediately, and will require a manual lockout reset.
LOCKOUT RESET: A hard lockout can be reset by turning the unit thermostat off and then back on when the “RESET” dip switch is set to “Y” or by shutting off unit power at the circuit breaker when the “RESET” dip switch is set to “R”.
The blower motor will remain active during a lockout condition.
COMFORT ALERT MODULE
The Comfort Alert diagnostics module (CADM) is a breakthrough innovation for troubleshooting heat pump system failures. (Figure #9)
Figure # 9
By monitoring and analyzing data from the compressor and the thermostat demand, the module can accurately detect the cause of electrical and system related failures without any sensors. A flashing LED indicator communicates the ALERT code and guides the service technician more quickly and accurately to the root cause of a problem.
This module does not provide safety protection! The Comfort Alert module is a monitoring device and cannot shut down the compressor directly.
When an abnormal system condition occurs, the Comfort Alert module displays the appropriate ALERT and/or TRIP LED.
The yellow ALERT LED will flash a number of times consecutively, pause and then repeat the process.
To identify a Flash Code number, count the number of consecutive flashes.
Every time the module powers up, the last ALERT Flash Code that occurred prior to shut down is displayed for one minute.
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Figure 10: Refrigerant Charge, Line Sizing and Capacity Multiplier Chart
Comfort Alert Module | 11LM CS Series Heat
SYSTEM MODEL
LM024
LM036
LM048
LM060
LM070
Factory
R410A
Charge
(Oz)*
80
86
93
115
127
CAPACITY MULTIPLIER
Example 1:
Model LM036 with 45ft of equivalent length of 3/8” O.D Liquid Line. Total system charge= Factory charge + (45ft - 25 ft) x .60 oz/ft Total System Charge = 93 oz + (20ft x .60 oz/ft) = 105 oz. Additional 12 oz of R410A refrigerant required.
Refrigerant Line O.D. Size (Based on Equivalent Line Length)
25 FT. 35 FT. 45 FT. 50 FT. 75 FT
LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC.
3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8
3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8
3/8 7/8 3/8 7/8 3/8 7/8 3/8 7/8 3/8 7/8
3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8
3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8
1.00 .995 0.990 0.990 0.980
Figure 11: Liquid Line Charge Per Linear Foot
Liquid Line Size, O.D.
Suct. Line
Riser Max.
3/4
3/4
7/8
7/8
7/8
Example 2:
Model LM060 with 10ft of equivalent length of 3/8” O.D Liquid Line. Total system charge= Factory charge + (25ft ­10ft) x .60 oz/ft Total System Charge = 150 oz + (15ft x .60 oz/ft) = 141 oz. Additional 12 oz of R410A refrigerant required.
R410A oz per foot
1/4 5/16 3/8 1/2 5/8 .25 .44 .60 1.15 1.95
8 733 920 847 (2014/01)Revised 01-14
12 | Options LM CS Series Heat Pump
OPTIONS
Number of factory installed options are available on LM CS Series of Heat Pumps. The following details the purpose, function and components of each option.
Pump Status Switch
The pump status switch is a Current Transformer (CT) that monitors the current flow from the condenser pump motor. It’s default is Normally Open (NO) when the motor is not running, and closes once it senses current flow.
DPS Water Flow Proving
The DPS water flow proving switch is a factory installed option available for the LM series. The DPS prevents compressor operation if there is inadequate water flow through the water to refrigerant heat exchanger in the heat pump.
The DPS operates by monitoring the water side pressure drop across the water to the refrigerant heat exchanger. When the pressure drop between the water in and water out lines reaches a pre-set value, compressor operation is enabled.
Valve End Switch
The leaving water valves are all equipped with Valve End Switches (VES) and it is a factory installed option available for the LM series.
The VES prevents compressor operation if the valve is not fully open. This prevents short-cycling due to low water through the water-to-refrigerant heat exchanger in the heat pump.
The VES only closes once the leaving water valve is fully open. The valve is activated by the compressor call (Y1) signal.
Pump Relay
The factory installed pump relay can be used to energize a supply pump or solenoid valve when there is a call for compressor operation. This relay can be used to switch either high or low voltage power.
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Sequence of Operation | 13LM CS Series Heat
SEQUENCE OF OPERATION
Cooling Mode
Energizing the “O” terminal energizes the unit reversing valve thus placing the unit into cooling mode. The fan motor starts when the “G” terminal is energized.
The fan motor will take 30 seconds to ramp up to operating speed and will run at fan only rated air flow, as long as there is no call for compressor or heater operation.
When the thermostat calls for first stage cooling (Y1) the loop pump or solenoid valve if present is energized and the first stage of compressor capacity starts.
Some options will have a built in delay, and hence, compressor operation is not immediate. See ‘Options’ section for more detail.
When the thermostat calls for second stage cooling (Y2) the second stage (or full compressor capacity) is initiated. The fan ramps up to full cooling air flow.
Once the thermostat is satisfied, the compressor shuts down and the fan ramps down to either fan only mode or off over a span of 30 seconds.
Once the thermostat is satisfied, the compressor shuts down and the fan ramps down either fan only mode or off over a span of 30 seconds. If thermostat has two different output points one for Auxiliary heat and a different one for Emergency heat the two outputs must be terminated on W1 units equipped with one stage of Electric heat. (Figure #12)
When using a 2-cool, 3-heat thermostat both the W1 & W2 on the Heat Pump and W2 & EM on the thermostat must be connected together via a jumper. (See Figure#22)
A fault condition initiating a lockout will de­energize the compressor irrespective of which stage is engaged.
Heating Mode
The first two stages of heating (Y1 & Y2) operate in the same manner as cooling, but with the reversing valve de-energized. On a call for auxiliary heat (W1), the fan ramps up to auxiliary heat air fl ow immediately and the electric heater package is energized along with the compressor. As the thermostat is satisfied, the heaters will shut off as soon as W1 is de-energized, and the compressors will remain on until the thermostat stages are satisfied.
If the unit compressor lock out for any reason at this time, the electric heaters will continue to function normally.
8 733 920 847 (2014/01)Revised 01-14
14 | Sequence of Operation LM CS Series Heat Pump
UPM Sequence of Operation (SOO) Flow Chart
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Y1=1
V
>
18VAC
HPC = 1
LPC = 1
FRZ
>
TEMP
LIM
CON
>
0
INITIAL
POWER UP
T
>
ASC OR
RS SEC
TIME
>
30
SEC
TIME
>
120
SEC
COUNT = 2
Start Timer
Start Timer
CC Output = On
CC Output = Off
Blink Code On Status LED
Report Alarm Fault
Hard Lockout
ALR Output = On/Pulse
Blink Code On Status LED
Soft Lockout
Record Alarm
Start Counter (If Applicable)
Start
Anti Short Cycle
Start
Random Start Up
Lockout Can Be Set To
4 Via Dip Switch
Power/Switchs/Sensor
Status Check
LEGEND: HPC - HIGH PRESSURE CUTOUT LPC - LOW PRESSURE CUTOUT FRZ - FREEZE PROTECTION CONDITION CON - CONDENSATE OVERFLOW CONDITION CC - COMPRESSOR COIL ASC - ANTI SHORT CYCLE RS - RANDDOM START
Figure # 12
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Application Considerations | 15LM CS Series Heat
1
2
3
4
5
6
7
Typical Installation shown for illustration purposes only.
9
8
10
11
12
13
APPLICATION CONSIDERATIONS
Well Water Systems
Copper is adequate for ground water that is not high in mineral content. Should your well driller express concern regarding the quality of the well water available or should any known hazards exist in your area, we recommend proper testing to assure the well water quality is suitable for use with water source equipment. In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended. In well water applications water
pressure must always be maintained in the heat exchanger. This can be accomplished with either control valve or a bladder type expansion tank. When using a single water well to supply both domestic water and the heat pump care must be taken to insure that the well can provide sufficient flow for both. In well water applications a slow closing solenoid valve must be used to prevent water hammer. Solenoid valves should be connected across Y1 and C1 on the interface board for all. Make sure that the VA draw of the valve does not exceed the contact rating of the thermostat. (Figure #13)
[1] Flex Duct Connection [2] Low Voltage Control Connection [3] Vibration Pad [4] Ball Valves [5] Solenoid Valve Slow Closing [6] Condensate Drain Connection [7] Drain Valves [8] Hose Kits (optional) [9] Pressure Tank (optional) [10] P/T Ports (optional) [11] Line Voltage Connection [12] Electric Heater Line Voltage Disconnect [13] Unit Line Voltage Disconnect
Figure # 13 Example System Set-up
Cooling Tower/Boiler Systems
The cooling tower and boiler water loop temperature is usually maintained between 50° F to 100 ° F to assure adequate cooling and heating performance.
In the cooling mode, heat is rejected from the unit into the water loop. A cooling tower provides evaporative cooling to the loop water thus maintaining a constant supply temperature to the unit. When utilizing open cooling towers, chemical water treatment is mandatory to ensure the water is free from corrosive elements. A secondary heat exchanger (plate frame) between the unit and the open cooling tower may also be used.
8 733 920 847 (2014/01)Revised 01-14
16 | Application Considerations LM CS Series Heat Pump
Note: Diagram shows typical installation and is for illustration purposes only. Ensure access to Heat
Pump is not restricted.
It is imperative that all air be eliminated from the closed loop side of the heat exchanger to insure against fouling. In the heating mode, heat is absorbed from the water loop. A boiler can be utilized to maintain the loop at the desired temperature.
Water piping exposed to extreme low ambient temperatures is subject to freezing.
Consult the specification sheets for piping sizes. Teflon tape sealer should be used when connecting to the unit to insure against leaks and possible heat exchanger fouling.
Do not overtighten the connections. Flexible hoses should be used between the unit and the rigid system to avoid possible vibration. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing.
Pressure/temperature ports are recommended in both supply and return lines for system flow balancing. Water flow can be accurately set by measuring the water-to-refrigerant heat exchangers water side pressure drop.
See specification sheets for water flow vs. pressure drop information.
No unit should be connected to the supply or return piping until the water system has been completely cleaned and flushed to remove any dirt, piping chips or other foreign material. Supply and return hoses should be connected together during this process to ensure the entire system is properly flushed.
After the cleaning and flushing has taken place the unit may be connected to the water loop and should have all valves wide open. (Figure #14)
[1] Line voltage disconnect (unit) [2] Low voltage control connection [3] P/T ports (optional) [4] Hose kits (optional) [5] Ball valves
Figure # 14
[6] Supply and return line of central system [7] Flex duct connection [8] Hanging bracket assembly [9] Threaded rod [10] Hanging bracket assembly
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Application Considerations | 17LM CS Series Heat
Note: Diagram shows typical installation and is for illustration purposes only. Ensure access to Heat
Pump is not restricted.
Geothermal Systems
Closed loop and pond applications require specialized design knowledge. No attempt at these installations should be made unless the dealer has received specialized training. Utilizing the Ground Loop Pumping Package (GLP), makes the
installation easy. Anti-freeze solutions are utilized when low evaporating conditions are expected to occur. Refer to the GLP installation manuals for more specific instructions. (Figure #16)
[1] Line voltage disconnect (unit) [2] Flex duct Connection [3] Low voltage control connection [4] Line voltage connection (unit) [5] P/T ports [6] Vibration pad [7] Condensate drain connection [8] Ground loop connection kit [9] Ground loop pumping package [10] Polyethylene with insulation [11] Line voltage disconnect (electric heater)
Figure # 15
8 733 920 847 (2014/01)Revised 01-14
18 | System Checkout LM CS Series Heat Pump
SYSTEM CHECKOUT
After completing the installation, and before energizing the unit, the following system checks should be made:
Verify that the supply voltage to the heat pump is in accordance with the nameplate ratings.
Make sure that all electrical connections are tight and secure.
Check the electrical fusing and wiring for the correct size.
Ensure cabinet and Electrical Box are properly grounded.
Verify that the low voltage wiring between the thermostat and the unit is correct.
Verify that the water piping is complete and correct.
Check that the water flow is correct, and adjust if necessary.
Check the blower for free rotation, and that it is secured to the shaft.
Verify that vibration isolation has been provided.
Unit is serviceable. Be certain that all access panels are secured in place.
Considerations:
1. Always check incoming line voltage power supply and secondary control voltage for adequacy. Transformer primaries are dual tapped for 208 and 230 volts. Connect the appropriate tap to ensure a minimum of 18 volts secondary control voltage. 24 volts is ideal for best operation.
2. Long length thermostat and control wiring leads may create voltage drop. Increase wire gauge or up-size transformers may be required to insure minimum secondary voltage supply.
3. FHP recommends the following guidelines for wiring between a thermostat and the unit: 18 GA up to 60 foot, 16 GA up to 100 ft and 14 GA up to 140 ft.
4. Do not apply additional controlled devices to the control circuit power supply without consulting the factory. Doing so may void equipment warranties.
5. Check with all code authorities on requirements involving condensate disposal/ over flow protection criteria.
UNIT START-UP
1. Put the UPM board in “test” mode.
2. Set the thermostat to the highest setting.
3. Set the thermostat system switch to “COOL”, and the fan switch to the “AUTO” position. The reversing valve solenoid should energize. The compressor and fan should not run.
4. Reduce the thermostat setting approximately 5 degrees below the room temperature.
5. Verify the heat pump is operating in the cooling mode.
6. Turn the thermostat system switch to the “OFF” position. The unit should stop running and the reversing valve should de energize.
7. Leave the unit off for approximately (5) minutes to allow for system equalization.
8. Turn the thermostat to the lowest setting.
9. Set the thermostat switch to “HEAT”.
10. Increase the thermostat setting approximately 5 degrees above the room temperature.
11. Verify the heat pump is operating in the heating mode.
12. Set the thermostat to maintain the desired space temperature.
13. Check for vibrations, leaks, etc.
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
MAINTENANCE
1. Filter changes or cleanings are required at regular intervals. The time period between filter changes will depend upon type of environment the equipment is used in. In a single family home, that is not under construction, changing or cleaning the filter every 60 days is sufficient. In other applications such as motels, where daily vacuuming produces a large amount of lint, filter changes may need to be as frequent as biweekly.
Equipment should never be used during construction due to likelihood of wall board dust accumulation in the air coil of the equipment which permanently affects the performance and may shorten the life of the equipment.
2. An annual “checkup” is recommended by a licensed refrigeration mechanic. Recording the performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. This data should be compared to the information on the unit’s data plate and the data taken at the original startup of the equipment.
3. Lubrication of the blower motor is not required, however may be performed on some motors to extend motor life. Use SAE-20 non­detergent electric motor oil.
4. The condensate drain should be checked annually by cleaning and flushing to insure proper drainage.
5. Periodic lockouts almost always are caused by air or water flow problems. The lockout (shutdown) of the unit is a normal protective measure in the design of the equipment. If continual lockouts occur call a mechanic immediately and have them check for: water flow problems, water temperature problems, air flow problems or air temperature problems. Use of the pressure and temperature charts for the unit may be required to properly determine the cause.
Maintenance | 19LM CS Series Heat
Figure 16: Water side pressure drop in PSIG
Series GPM
3 4
LM024
LM036
LM048
LM060
LM070
5 6 7 8 6
8 10 12 14 16
6
8 10 12 14 16
7.5 10
12.5 15
17.5 20
7.5 10
12.5 15
17.5 20
Water PD @ 77°EWT
with Water
0.7
1.2
1.7
2.4
3.2
4.0
1.1
1.8
2.7
3.7
4.9
6.2
1.1
1.8
2.7
3.7
4.9
6.2
1.1
1.9
2.8
3.9
5.2
6.6
1.1
1.9
2.8
3.9
5.2
6.6
8 733 920 847 (2014/01)Revised 01-14
20 | Unit Check-Out Sheet LM CS Series Heat Pump
Bosch Group 601 NW 65th Court Fort Lauderdale, FL 33309 Phone: (954) 776-5471 Fax: (800) 776-5529
MAIL TO: Bosch.Fhp.TechSupport@us.bosch.com
or scan the QR code and attach picture of this form with the information requested.
UNIT CHECK-OUT SHEET
Customer Data
Customer Name _____________________________________________ Date ___________________________________ Address ______________________________________________________ _______________________________________________________________ Phone _______________________________________________________ Unit Number ___________________________
Unit Nameplate Data
Unit Make _________________________________________ Model Number ____________________________________ Serial Number ____________________________________ Refrigerant Charge (oz) __________________________ Compressor: RLA ____________________ LRA ___________________________ Blower Motor: FLA (or NPA) ___________ HP ____________________________ Maximum Fuse Size (Amps) ____________ Maximum Circuit Ampacity _____________
Operating Conditions
Cooling Mode Heating Mode
Entering / Leaving Air Temp Entering Air Measured at: Leaving Air Measured at: Entering / Leaving Fluid Temp Fluid Flow (gpm) Compressor Volts / Amps Blower Motor Volts / Amps Source Fluid Type Fluid Flow (gpm)* Fluid Side Pressure Drop* Suction / Discharge Pressure (psig)*
Suction / Discharge Temp* _______________ / _____________ _______________ / _____________ Suction Superheat* ______________________________ ______________________________ Entering TXV / Cap Tube Temp* ______________________________ ______________________________
Liquid Subcooling* * Required for Troubleshooting ONLY
_______________ / _____________ _______________ / _____________ ______________________________ ______________________________ ______________________________ ______________________________ _______________ / _____________ _______________ / _____________ ______________________________ ______________________________ _______________ / _____________ _______________ / _____________ _______________ / _____________ _______________ / _____________ ______________________________ ______________________________ ______________________________ ______________________________ ______________________________ ______________________________ _______________ / _____________ _______________ / _____________
______________________________ ______________________________
Auxiliary Heat
Unit Make __________________________________ Model Number: ______________________________ Serial Number _____________________________
Max Fuse Size (Amps) _______________________ Volts / Amps _______________________________
Entering Air Temperature _____________________ Leaving Air Temperature ______________________
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
TROUBLESHOOTING
Troubleshooting Information Solution column may reflect a possible fault that may be one of, or a combination of causes and solutions. Check each cause and adopt "process of elimination" and or verification of each before making any conclusion.
Unit Troubleshooting
Problem Possible Cause Checks and Correction
Troubleshooting | 21LM CS Series Heat
ENTIRE UNIT DOES NOT RUN
UNIT OFF ON HIGH PRESSURE CONTROL
UNIT OFF ON LOW PRESSURE CONTROL
Power Supply Off Apply power, close disconnect
Blown Fuse
Voltage Supply Low
Thermostat
Discharge pressure too high
Refrigerant charge
High pressure
Suction pressure too low
Replace fuse or reset circuit breaker. Check for correct fuses
If voltage is below minimum voltage specified on unit data plate, contact local power company.
Set the fan to “ON”, the fan should run. Set thermostat to “COOL” and lowest temperature setting, the unit should run in the cooling mode (reversing valve energized). Set unit to “HEAT” and the highest temperature setting, the unit should run in the heating mode. If neither the blower or compressor run in all three cases, the thermostat could be miswired or faulty. To ensure miswired or faulty thermostat verify 24 volts is available on the condensing section low voltage terminal strip between “R” and “C”, “Y” and “C”, and “O” and “C”. If the blower does not operate, verify 24 volts between terminals “G” and “C” in the air handler. Replace the thermostat if defective.
In “COOLING” mode: Lack of or inadequate water flow. Entering water temperature is too warm. Scaled or plugged condenser. In “HEATING” mode: Lack of or inadequate air flow. Blower inoperative, clogged filter or restrictions in duct work
The unit is overcharged with refrigerant. Reclaim refrigerant, evacuate and recharge with factor recommended charge.
Check for defective or improperly calibrated high pressure switch.
In “COOLING” mode: Lack of or inadequate air flow. Entering air temperature is too cold. Blower inoperative, clogged filter or restrictions in duct work. In “HEATING” mode: Lack of or inadequate water flow. Entering water temperature is too cold. Scaled or plugged condenser.
Refrigerant charge
Low pressure switch
UNIT SHORT CYCLES
Unit oversized Recalculate heating and or cooling loads.
Thermostat
Wiring and controls
The unit is low on refrigerant. Check for refrigerant leak, repair, evacuate and recharge with factory recommended charge.
Check for defective or improperly calibrated low pressure switch.
Thermostat installed near a supply air grill; relocate thermostat. Readjust heat anticipator.
Check for defective or improperly calibrated low pressure switch.
8 733 920 847 (2014/01)Revised 01-14
22 | Troubleshooting LM CS Series Heat Pump
Unit Troubleshooting
Problem Possible Cause Checks and Correction
INSUFFICIENT COOLING OR HEATING
Unit undersized Recalculate heating and or cooling loads. If excessive, possibly adding
insulation and shading will rectify the problem
Loss of conditioned air by leakage
Airflow
Refrigerant charge
Compressor
Reversing Valve Defective reversing valve creating bypass of refrigerant from discharge
Operating pressures
TXV
Moisture, noncondensables
Check for leaks in duct work or introduction of ambient air through doors or windows
Lack of adequate air flow or improper distribution of air. Replace dirty filter
Low on refrigerant charge causing inefficient operation
Check for defective compressor. If discharge is too low and suction pressure is too high, compressor is not pumping properly. Replace compressor.
of suction side of compressor. Replace reversing valve
Compare unit operation pressures to the pressure/temperature chart for the unit.
Check TXV for possible restriction or defect. Replace if necessary.
The refrigerant system may be contaminated with moisture or noncondensables. Reclaim refrigerant, replace filter dryer, evacuate the refrigerant system, and recharge with factory recommended charge.
Compressor Ohms
Model Start Winding Run Winding
LM024 1.64 1.3
LM036 1.52 0.88
LM048 1.86 0.52
LM060 1.63 0.39
LM070 1.85 0.34
Tolerance +/- 7%. All resistance values must be
measured with compressor at room temperature.
UPM Board LED Indications
Indication
Color
GREEN Solid 18-30 VAC Power is present
RED 1 High pressure lockout
RED 2 Low pressure lockout
RED 3 Freeze sensor lockout
RED 4 Condensate overflow
RED 5 Brownout
RED 6 Evaporator Freeze condition
Blinks Description
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Troubleshooting | 23LM CS Series Heat
HRP Troubleshooting
Problem Possible Cause Checks and Corrections
NO FLOW LOW FLOW
HIGH WATER TEMPERATURE
No Power Check power supply
On/Off Switch Position
Compressor Contactor
Broken or loose wires
Air Lock
Stuck pump shaft/impeller
Defective pump
Kinked or under sized water piping
Set switch to “ON” position
Engage heat pump contactor
Repair or tighten wires
Purge air from piping system
Remove pump cartridge and clean
Replace pump
Repair kink and check for proper line size
Water temp limit closed Stuck limit switch
Sensor not attached securely to line
LOW HEAT OUTPUT Scaled or fouled heat exchanger Clean heat exchanger
Comfort Alert Module -Flash Codes
Status LED
Status LED
YELLOW "ALERT" FLASH CODE 3
Description
Short Cycling Compressor is running only briefly
Status LED Troubleshooting Information Solution
1. Thermostat demand signal is intermittent
2. Time delay relay or control board defective
3. If high pressure switch present go to Flash Code 2 information
4. If low pressure switch present go to Flash Code 1 information
YELLOW "ALERT" FLASH CODE 4
YELLOW "ALERT” FLASH CODE 5
Locked Rotor
Open Circuit
1. Run capacitor has failed (may not be bad, verify)
2. Low line voltage (contact utility if voltage at disconnect is low)
Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Measure compressor oil level
1. Outdoor unit power disconnect is open
2. Compressor circuit breaker or fuse(s) is open
3. Compressor contactor has failed open
Check compressor contactor wiring and connectors
Check for compressor contactor failure (burned, pitted or open)
Check wiring and connectors between supply and compressor
Check for low pilot voltage at compressor contactor coil
4. High pressure switch is open and requires manual reset
5. Open circuit in compressor supply wiring or connections
6. Unusually long compressor protector reset time due to extreme ambient temperature
7. Compressor windings are damaged
Check compressor motor winding resistance
8 733 920 847 (2014/01)Revised 01-14
24 | Troubleshooting LM CS Series Heat Pump
Comfort Alert Module -Flash Codes
Status LED
Status LED
Description
Status LED Troubleshooting Information Solution
YELLOW "ALERT” FLASH CODE 6
YELLOW "ALERT” FLASH CODE 7
YELLOW "ALERT" FLASH CODE 8
YELLOW "ALERT" FLASH CODE 9
Open Start Circuit Current only in run circuit
Open Run Circuit Current only in start circuit
Welded Contactor Compressor always runs
Low Voltage Control circuit < 17VAC
1. Run capacitor has failed (may not be bad, verify)
2. Open circuit in compressor start wiring or connections
Check wiring and connectors between supply and the compressor "S'" terminal
3. Compressor start winding is damaged
Check compressor motor winding resistance
1. Open circuit in compressor run wiring or connections
Check wiring and connectors between supply and the compressor "R” terminal
2. Compressor run winding is damaged
Check compressor motor winding resistance
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
1. Control circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low)
Check wiring connections Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Operating Temperatures and Pressures | 25LM CS Series Heat
OPERATING TEMPERATURES AND PRESSURES
Operating Temperatures and Pressures
COOLING HEATING
Model
Water
Temp. F
Entering
30°
40°
50°
LM024
Part
Load
LM024
Full
Load
60°
70°
80°
90°
100°
30°
40°
50°
60°
70°
80°
90°
100°
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
Wat
Flow
Suction
er
Pressure
PSIG
4 75-91 264-322 5-6 15-17
8 79-96 270-331 3-4 16-18
4 88-107 277-339 6-7 17-20
8 115-140 175-214 8-9 19-23 92-112 284-348 4-5 18-21
4 129-157 218-267 14-17 18-20 98-122 291-356 7-8 20-23
8 124-151 204-250 8-9 19-22 110-130 298-364 5-6 21-24
4 134-163 249-305 13-16 17-20 112-136 304-372 8-10 22-26
8 128-156 233-287 8-9 18-21 117-143 312-381 6-7 23-28
4 138-168 281-341 13-16 17-19 124-152 318-389 9-11 24-29
8 133-161 263-323 7-9 18-21 131-159 325-398 6-8 26-31
4 143-174 317-388 13-16 16-19 136-166 331-405 11-13 27-32
8 137-167 297-366 7-9 17-20 143-174 339-415 7-9 28-33
4 147-179 357-437 13-16 16-18
8 141-172 335-411 7-9 17-20
4 151-185 402-492 13-15 15-18
8 146-177 378-459 7-9 16-19
4 76-92 242-297 3-4 13-14
8 80-97 249-304 2-3 13-15
4 125-151 180-221 14-18 19-22 89-108 255-312 4-5 15-17
8 120-146 169-207 8-10 20-23 93-113 261-320 3-3 16-18
4 134-163 211-258 14-18 18-21 106-118 267-327 5-6 17-19
8 129-157 198-242 8-10 19-23 110-126 274-335 3-4 18-21
4 139-169 241-295 14-17 18-21 113-138 280-342 6-7 19-22
8 134-163 227-278 8-10 19-22 119-145 287-351 4-5 20-23
4 144-175 272-333 14-17 17-20 126-155 292-358 7-8 21-24
8 138-168 255-313 8-10 18-21 133-162 300-367 5-6 22-26
4 148-181 307-375 14-17 17-19 138-168 305-373 8-9 23-27
8 143-174 288-353 8-10 18-21 145-177 312-382 5-6 24-29
4 153-186 346-423 14-17 16-19
8 147-179 325-398 8-9 17-20
4 158-191 389-477 13-16 16-18
8 152-185 366-448 8-9 17-20
Discharge
Pressure
PSIG
Water
Temp
Rise °F
Air
Temp
Drop °F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop
Rise °F
Air
Temp
8 733 920 847 (2014/01)Revised 01-14
26 | Operating Temperatures and Pressures LM CS Series Heat Pump
Operating Temperatures and Pressures
COOLING HEATING
4.5 73-89 266-325 5-6 15-18
30°
40°
50°
LM036
Part
Load
LM036
Full
Load
60°
70°
80°
90°
100°
30°
40°
50°
60°
70°
80°
90°
100°
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
9.0 77-94 272-333 3-4 16-19
4.5 117-143 189-231 14-17 18-22 86-105 279-341 6-7 17-21
9.0 112-137 178-217 8-9 19-24 90-110 286-350 4-5 18-22
4.5 126-154 221-270 14-17 18-21 105-125 293-358 7-8 20-24
9.0 121-148 207-253 8-9 19-23 109-130 300-366 5-6 21-25
4.5 131-160 252-308 13-16 17-21 110-134 306-374 8-10 22-27
9.0 125-153 237-290 8-9 18-22 115-141 314-383 6-7 23-29
4.5 135-165 284-347 13-16 17-20 122-150 320-391 9-11 24-30
9.0 130-158 266-326 7-9 18-22 129-157 327-400 6-8 26-32
4.5 140-171 320-391 13-16 16-20 134-164 333-407 11-13 27-33
9.0 134-164 300-367 7-9 17-21 141-172 341-417 7-9 28-35
4.5 144-176 360-440 13-16 16-19 147-179 347-424 12-14 29-36
9.0 138-169 338-414 7-9 17-21 154-188 355-434 8-10 31-38
4.5 149-182 405-495 13-15 15-19
9.0 143-174 381-465 7-9 16-20
4.5 74-90 244-299 3-4 13-15
9.0 78-95 251-306 2-3 13-16
4.5 122-149 183-224 14-18 19-23 87-106 257-314 4-5 15-18
9.0 117-143 172-210 8-10 20-24 91-111 263-322 3-3 16-19
4.5 131-160 214-261 14-18 18-22 95-105 269-329 5-6 17-20
9.0 126-154 201-245 8-10 19-24 100-125 276-337 3-4 18-22
4.5 136-166 244-298 14-17 18-22 111-136 282-344 6-7 19-23
9.0 131-160 230-281 8-10 19-23 117-143 289-353 4-5 20-24
4.5 141-172 275-336 14-17 17-21 124-152 294-360 7-8 21-25
9.0 135-165 258-316 8-10 18-22 131-160 302-369 5-6 22-27
4.5 145-178 310-378 14-17 17-20 136-166 307-375 8-9 23-28
9.0 140-171 291-356 8-10 18-22 143-175 314-384 5-6 24-30
4.5 150-183 349-426 14-17 16-20
9.0 144-176 328-401 8-9 17-21
4.5 155-189 392-480 13-16 16-19
9.0 149-182 369-451 8-9 17-21
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Operating Temperatures and Pressures | 27LM CS Series Heat
Operating Temperatures and Pressures
COOLING HEATING
6.0 64-78 248-303 5-6 15-18
30°
40°
50°
LM048
Part
Load
LM048
Full
Load
60°
70°
80°
90°
100°
30°
40°
50°
60°
70°
80°
90°
100°
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
12.0 67-82 254-311 3-4 16-19
6.0 109-134 183-224 18-22 19-23 75-91 261-319 6-8 17-21
12.0 105-128 172-210 10-12 20-25 79-96 267-327 4-5 18-23
6.0 118-144 214-261 18-22 19-23 78-90 273-334 8-10 20-24
12.0 113-138 201-245 10-12 20-24 82-95 280-342 5-7 21-26
6.0 122-149 244-298 17-21 18-22 96-117 286-349 9-11 22-27
12.0 117-143 230-281 10-12 19-24 101-123 293-358 6-8 24-29
6.0 126-154 275-336 17-21 18-22 107-131 299-365 11-13 25-30
12.0 121-148 258-316 10-12 19-23 113-138 306-374 7-9 26-32
6.0 130-159 310-378 17-21 17-21 117-143 311-380 12-15 27-33
12.0 132-153 291-356 10-12 18-22 123-151 319-390 8-10 29-35
6.0 134-164 349-426 17-20 17-20
12.0 129-158 328-401 9-12 18-22
6.0 139-170 392-480 16-20 16-20
12.0 133-163 369-451 9-11 17-21
6.0 71-87 277-339 6-7 15-19
12.0 75-92 284-347 4-5 16-20
6.0 118-144 194-237 21-25 19-23 84-102 291-356 7-9 18-22
12.0 113-138 182-223 12-14 20-24 88-108 299-365 5-6 19-23
6.0 127-155 226-276 21-25 18-22 92-110 305-373 9-11 20-25
12.0 122-149 213-260 12-14 19-24 98-120 313-383 6-7 21-26
6.0 131-160 259-316 21-25 18-22 108-132 320-391 10-13 23-28
12.0 126-154 243-297 12-14 19-23 113-138 328-400 7-9 24-29
6.0 136-166 291-355 20-25 17-21 120-147 334-408 12-15 25-31
12.0 130-159 273-334 12-14 18-22 126-154 342-418 8-10 27-32
6.0 140-171 328-401 20-24 17-20 131-161 348-425 14-17 27-34
12.0 135-165 308-377 11-14 18-22 138-169 356-436 9-11 29-36
6.0 145-177 369-451 20-24 16-20
12.0 139-170 347-424 11-14 17-21
6.0 149-183 415-508 19-24 16-19
12.0 143-175 391-477 11-14 17-21
8 733 920 847 (2014/01)Revised 01-14
28 | Operating Temperatures and Pressures LM CS Series Heat Pump
Operating Temperatures and Pressures
COOLING HEATING
7.0 68-84 256-313 5-7 19-23
30°
40°
50°
LM060
Part
Load
LM060
Full
Load
60°
70°
80°
90°
100°
30°
40°
50°
60°
70°
80°
90°
100°
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
14.0 73-89 261-319 4-5 20-25
7.0 113-138 172-210 18-22 19-23 81-99 277-339 7-8 22-26
14.0 110-134 161-196 12-14 20-24 86-105 283-346 5-6 23-28
7.0 116-142 206-252 17-21 19-23 93-114 299-365 8-9 24-29
14.0 112-137 193-236 12-14 19-24 99-121 305-373 6-7 25-31
7.0 118-145 241-294 17-21 18-23 106-129 321-392 9-11 26-32
14.0 115-140 225-275 11-14 19-23 113-138 327-400 7-8 28-34
7.0 121-148 275-336 17-21 18-22 118-145 342-418 10-12 29-35
14.0 117-143 257-314 11-14 19-23 126-154 349-427 8-9 30-37
7.0 123-151 309-378 16-20 18-22 131-160 364-444 11-14 31-38
14.0 120-146 289-353 11-13 19-23 139-170 371-454 8-10 33-40
7.0 132-161 348-426 13-16 18-22
14.0 128-156 326-398 10-12 19-23
7.0 128-157 378-462 16-19 17-21
14.0 125-152 353-432 11-13 18-22
7.0 68-84 256-313 5-7 19-23
14.0 73-89 261-319 4-5 20-25
7.0 117-143 182-222 15-19 21-26 81-99 277-339 7-8 22-26
14.0 114-139 170-208 11-14 22-27 86-105 283-346 5-6 23-28
7.0 120-147 215-263 15-18 20-25 93-114 299-365 8-9 24-29
14.0 117-143 201-246 11-14 21-26 99-121 305-373 6-7 25-31
7.0 123-150 248-304 14-17 20-24 106-129 321-392 9-11 26-32
14.0 119-146 232-284 11-13 21-25 113-138 327-400 7-8 28-34
7.0 126-154 282-344 14-17 19-24 118-145 342-418 10-12 29-35
14.0 122-149 263-322 10-13 20-25 126-154 349-427 8-9 30-37
7.0 129-157 315-385 13-16 19-23 131-160 364-444 11-14 31-38
14.0 125-153 294-360 10-12 19-24 139-170 371-454 8-10 33-40
7.0 132-161 348-426 13-16 18-22
14.0 128-156 326-398 10-12 19-23
7.0 134-164 382-466 12-15 17-21
14.0 131-160 357-436 9-11 18-22
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Operating Temperatures and Pressures | 29LM CS Series Heat
Operating Temperatures and Pressures
COOLING HEATING
9.0 71-87 259-316 5-7 19-23
30°
40°
50°
LM070
Part
Load
LM070
Full
Load
60°
70°
80°
90°
100°
30°
40°
50°
60°
70°
80°
90°
100°
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development, specifications are subject to change without notice.
18.0 76-92 264-322 4-5 20-25
9.0 116-141 175-213 18-22 19-23 84-102 280-342 7-8 22-26
18.0 113-137 164-199 12-14 20-24 89-108 286-349 5-6 23-28
9.0 119-145 209-255 17-21 19-23 96-117 302-368 8-9 24-29
18.0 115-140 196-239 12-14 19-24 102-124 308-376 6-7 25-31
9.0 121-148 244-297 17-21 18-23 109-132 324-395 9-11 26-32
18.0 118-143 228-278 11-14 19-23 116-141 330-403 7-8 28-34
9.0 124-151 278-339 17-21 18-22 121-148 345-421 10-12 29-35
18.0 120-146 260-317 11-14 19-23 129-157 352-430 8-9 30-37
9.0 126-154 312-381 16-20 18-22 134-163 367-447 11-14 31-38
18.0 123-149 292-356 11-13 19-23 142-173 374-457 8-10 33-40
9.0 129-157 347-423 16-20 18-22
18.0 125-152 324-395 11-13 18-22
9.0 131-160 381-465 16-19 17-21
18.0 128-155 356-435 11-13 18-22
9.0 71-87 259-316 5-7 19-23
18.0 76-92 264-322 4-5 20-25
9.0 120-146 185-225 15-19 21-26 84-102 280-342 7-8 22-26
18.0 117-142 173-211 11-14 22-27 89-108 286-349 5-6 23-28
9.0 123-150 218-266 15-18 20-25 96-117 302-368 8-9 24-29
18.0 120-146 204-249 11-14 21-26 102-124 308-376 6-7 25-31
9.0 126-153 251-307 14-17 20-24 109-132 324-395 9-11 26-32
18.0 122-149 235-287 11-13 21-25 116-141 330-403 7-8 28-34
9.0 129-157 285-347 14-17 19-24 121-148 345-421 10-12 29-35
18.0 125-152 266-325 10-13 20-25 129-157 352-430 8-9 30-37
9.0 132-160 318-388 13-16 19-23 134-163 367-447 11-14 31-38
18.0 128-156 297-363 10-12 19-24 142-173 374-457 8-10 33-40
9.0 135-164 351-429 13-16 18-22
18.0 131-159 329-401 10-12 19-23
9.0 137-167 385-469 12-15 17-21
18.0 134-163 360-439 9-11 18-22
8 733 920 847 (2014/01)Revised 01-14
30 | Wiring Diagrams LM CS Series Heat Pump
WIRING DIAGRAMS
Figure # 17
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
DIMENSIONAL DRAWINGS
Dimensional Drawings | 31LM CS Series Heat
8 733 920 847 (2014/01)Revised 01-14
32 | Notes LM CS Series Heat Pump
NOTES
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Notes | 33LM CS Series Heat
8 733 920 847 (2014/01)Revised 01-14
34 | Notes LM CS Series Heat Pump
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Notes | 35LM CS Series Heat
8 733 920 847 (2014/01)Revised 01-14
601 N.W. 65th Court, Ft. Lauderdale, FL 33309 Phone: 866-642-3198 | Fax: 954-776-5529 www.boschtaxcredit.com | www.FHP-MFG.com Revised 01-14
Loading...