Bosch LM024, LM060, LM036, LM070, LM048 Operating Instructions Manual

LM CS Series Heat Pump
LM024 | LM036 | LM048 | LMO60 | LM070
Installation, Operation and Maintenance Manual
8 733 920 847 (2014/01)
2 | LM CS Series Heat Pump
CONTENTS
Key to Symbols.................................................................. 3
Safety Warnings ................................................................ 3
LM CS Standard package.................................................... 4
GENERAL DESCRIPTION .................................................... 4
MOVING AND STORAGE ..................................................... 4
INITIAL INSPECTION .......................................................... 4
LOCATION......................................................................... 5
Condensing Section ..................................................... 5
Air Handler ................................................................. 5
INSTALLATION .................................................................. 5
CONDENSATE DRAIN ......................................................... 6
WATER PIPING .................................................................. 6
ELECTRICAL ...................................................................... 6
Safety Devices and the UPM Controller ........................... 7
COMFORT ALERT MODULE............................................... 10
OPTIONS......................................................................... 12
Pump Status Switch ................................................... 12
DPS Water Flow Proving ............................................. 12
Valve End Switch ....................................................... 12
Pump Relay............................................................... 12
SEQUENCE OF OPERATION .............................................. 13
Cooling Mode ............................................................ 13
Heating Mode............................................................ 13
APPLICATION CONSIDERATIONS...................................... 15
Well Water Systems ................................................... 15
Cooling Tower/Boiler Systems ..................................... 15
Geothermal Systems .................................................. 17
SYSTEM CHECKOUT ........................................................ 18
UNIT START-UP ............................................................... 18
MAINTENANCE................................................................ 19
UNIT CHECK-OUT SHEET .................................................. 20
TROUBLESHOOTING ........................................................ 21
OPERATING TEMPERATURES AND PRESSURES ................. 25
WIRING DIAGRAMS ......................................................... 30
DIMENSIONAL DRAWINGS ............................................... 31
NOTES ............................................................................ 32
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
LM CS MODEL NOMENCLATURE
LM 024 - 1 CS C - F
SERIES WATER CONNECTIONS
LM F - Front
SIZE
COAX OPTIONS
024 C - Copper 036 N - Cupro-Nickel 048 060
CABINET CONFIGURATION
070 CS - Condensing Section
VOLTAGE DESIGNATIONS
1
- 208/1/60 & 230/1/60
Revision Level A
CS/AH Pairing | 3LM CS Series Heat
CS/AH PAIRING
UNIT MODEL
LM024-1CSC LM036-1CSC LM048-1CSC LM060-1CSC LM070-1CSC
Paired Air Handler
Unit 1 Unit 2
LM024-1AVX LM036-1AVX LM048-1AVX LM060-1AVX LM070-1AVX
LM024-1AHX LM036-1AHX LM048-1AHX LM060-1AHX LM070-1AHX
KEY TO SYMBOLS
Warnings
Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of the warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:
NOTE indicates a situation that could result in damage to property or equipment.
CAUTION indicates a situation that could result in minor to medium injury.
WARNING indicates a situation that could result in sever injury or death.
DANGER indicates a situation that will result in severe injury or death.
Important Information
This symbol indicates important information where there is no risk to property or people.
SAFETY WARNINGS
Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could
cause personal injury or death.
Installation and servicing of this equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service the equipment.
All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
R410A is flammable when exposed to open flame. Recover all refrigerant prior to brazing.
8 733 920 847 (2014/01)Revised 01-14
4 | LM CS Standard package LM CS Series Heat Pump
1
2
LM CS STANDARD PACKAGE
Figure # 1
[1] LM Split Series Water-to-Air Heat Pump Condensing Section
[2] Installation and Operation Manual
GENERAL DESCRIPTION
LM Split Series Water-to-Air Heat Pumps provide the best combination of performance and efficiency available. All units are performance certified to American Heating and Refrigeration Institute (AHRI) ISO Standard 13256-1. All LM Water-to-Air Heat Pumps conform to UL1995 standard and are certified to CAN/CSA C22.1 No 236 by Intertek-ETL.
Split system heat pumps consist of two independently installed sections allowing for centralized air distribution while remotely locating the section containing the compressor and water­to-refrigerant heat exchanger.
The Water-to-Air Heat Pumps are designed to operate with entering fluid temperature between 20°F to 80°F in the heating mode and between 50°F to 110°F in the cooling mode.
50°F Minimum Entering Water Temperature (EWT) for well water applications with sufficient water flow to prevent freezing. Antifreeze solution is required for all closed loop applications.
Cooling Tower/Boiler and Geothermal applications without antifreeze must have means to protect against extreme conditions and equipment failure. Frozen water coils are not covered under warranty. Other equivalent methods of temperature control are acceptable.
Several factory installed options are available: Differential Pressure Switch (DPS) Water Flow Proving Switch, Auxiliary Pump Relay, Zone Valve and Internal Water Pump. See Pg#12 for more detail.
Safety devices are built into each unit to provide the maximum system protection possible when properly installed and maintained.
MOVING AND STORAGE
If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean, dry area. Units must only be sto r ed or m o v ed in t h e normal upright position as indicated by the “UP” arrows on each carton at all times.
In the cooling mode, the air coil in the air handler section serves as an evaporator and the water-to­refrigerant heat exchanger serves as a condenser. In the heating mode, their roles are reversed.
In cooling mode, the refrigerant lines connecting the two sections consist of one line carrying liquid refrigerant and another carrying refrigerant vapor. The liquid carrying line will be referred to as the liquid line while the vapor carrying line will be referred to as the suction line.
INITIAL INSPECTION
Be certain to inspect all cartons or crates on each unit as received at the job site before signing the freight bill. Verify that all items have been received and that there are no visible damages; note any shortages or damages on all copies of the freight bill. In the event of damage or shortage, remember that the purchaser is responsible for filing the necessary claims with the carrier. Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt.
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Location | 5LM CS Series Heat
Vibration Pad is recommended
LOCATION
To maximize system performance, efficiency and reliability, and to minimize installation costs, it is always best to keep the refrigerant lines as short as possible. Every effort should be made to locate the air handler and the condensing section as close as possible to each other.
Condensing Section
Locate the condensing section in an area that provides sufficient room to make water and electrical connections, and allows easy removal of the access panels, for service personnel to perform maintenance or repair.
The condensing section is designed for indoor use; however, if the condensing section must be installed in an outdoors location where ambient temperatures can fall below freezing, some form of freeze protection should be employed such as a freeze-stat and/or a pump timer/starter to prevent possible condenser freeze-up and to optimize overall system performance.
Air Handler
Locate the air handler unit in an indoor area that allows easy removal of the filter and access panels, and has enough room for service personnel to perform maintenance or repair. Provide sufficient room to make electrical and duct connections. If the unit is located in a confined space such as a closet, provisions must be made for return air to freely enter that space.
Reference the Factory Manual for your AH, or Air Handler section of this manual for detailed installation and operation.
INSTALLATION
Loosen compressor mounting bolts.
NOTE: The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedent over any recommendations contained in these instructions. In lieu of local codes, the equipment should be installed in accordance with the recommendations made by the National electric code, and in accordance with the recommendations made by the National Board of Fire Underwriters.
Condensing Section
The condensing section should be mounted on a vibration absorption pad on a cement slab or similar support to provide a good base and some degree of levelness. The cement pad should not come in contact with the foundation or side of the dwelling, because sound may be transmitted into the residence. See Figure #2 below.
DO NOT remove the protective caps or plugs from the service valves until the refrigerant lines are run and ready for final connections.
Figure # 2
8 733 920 847 (2014/01)Revised 01-14
6 | Condensate Drain LM CS Series Heat Pump
CONDENSATE DRAIN
Use cupra-nickel condenser in ground water application due to possibility of containing high mineral and corrosive properties
Both the supply and discharge water lines will sweat if subjected to low water temperature. These lines should be insulated to prevent damage from condensation. All manual flow valves used in the system must be ball valves. Globe and gate valves must not be used due to high pressure drop
Figure # 3
A drain line must be connected to the air handler and pitched away from the unit a minimum of 1/8” per foot to allow the condensate to flow away from the unit.
This connection must be in conformance with local plumbing codes. A trap must be installed in the condensate line to insure free condensate flow.
Drain Pan is not internally sloped.
and poor throttling characteristics.
Never exceed the recommended water flow rates, as serious damage or erosion of the water-to-refrigerant heat exchanger could occur.
Teflon tape sealer should be used when connecting water piping connections to the units to insure against leaks and possible heat exchanger fouling.
A vertical air vent is sometimes required to avoid air pockets. The length of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included.
WATER PIPING
Supply and return piping must be as large as the unit connections on the heat pump (See manual Pg#10 for any line size at installation length longer than 25 feet).
Never use flexible hoses of a smaller inside diameter than that of the fluid connections on the unit.
LM units are supplied with either a copper or optional cupro-nickel condenser. Copper is adequate for ground water that is not high in mineral content.
Proper testing is recommended to assure the well water quality is suitable for use with water source equipment.
In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended.
Flexible hoses should be used between the unit and the rigid system to avoid possible vibration. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing.
ELECTRICAL
Refer to electrical component box layout. (Figures #5,6)
Field wiring must comply with local and national electric codes. Properly sized fuses or HACR circuit breakers must be installed for branch circuit protection. See unit nameplate for maximum fuse or breaker size.
Power to the unit must be within the operating voltage range indicated on the unit nameplate or on the performance data sheet.
Operation of unit on improper line voltage or with excessive phase imbalance will be hazardous to the unit, constitutes abuse and may void the warranty.
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Electrical | 7LM CS Series Heat
4
5
3
2
15
6
7
8
1
10
12
14
13
11
9
1
2
3
4
5
6
78
9
10
11
1213
17
14
15
16
The unit is provided with a concentric knock-out for attaching common trade sizes of conduit, route power supply wiring through this opening.
Always connect the ground lead to the grounding lug provided in the control box and power leads to the line side of compressor contactor as indicated on the wiring diagram (Figures#17 through #25, Pg#30 through Pg#40).
[9] ECM Interface Board(Option, mounts on E-Box cover)
[10] Comfort Alert Module (Option) [11] DDC (Option) [12] LonWorks Card (Option) [13] Input Expansion Module (Option) [14] Smart Start Assist (Option) [15] Ground Lug
Safety Devices and the UPM Controller
Figure # 4 - Single Phase unit
Figure # 6 Typical UPM Board
[1] Board Power Indicator [2] UPM Status LED Indicator [3] Water Coil Freeze Protection Temperature
Selection [R30] [4] Air Coil Freeze Protection Temperature
Selection [5] UPM Board Settings [6] Water Coil Freeze Connection [7] Air Coil Freeze Connection
Figure # 5 EBox Cover
[1] Compressor contactor [2] Energy Management System Relay (Option) [3] Hot Gas Reheat Relay (Option) [4] Cooling Relay [5] Unit Protection Module (UPM) [6] Terminal block Low-Voltage [7] Auxiliary Relay (Option) [8] Capacitor
[8] LED Status-Diagnostic Connection [9] 24VAC Power Input [10] Compressor Contact Output [11] High Pressure Switch Connection [12] Call for Compressor Y1 [13] Low Pressure Switch Connection [14] 24VAC Power Common [15] Condensate Overflow Sensor [16] Dry Contact [17] UPM Ground Standoff
8 733 920 847 (2014/01)Revised 01-14
8 | Electrical LM CS Series Heat Pump
If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit malfunction output or relay. Refer to Figure #6.
If the thermostat is provided with a malfunction light powered off of the common (C) side of the transformer, a jumper between “R” and “COM” terminal of “ALR” contacts must be made.
If the thermostat is provided with a malfunction light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected directly to the (ALR) contact on the unit’s UPM board.
Each unit is factory provided with a Unit Protection Module (UPM) that controls the compressor
operation and monitors the safety controls that protect the unit.
Safety controls include the following:
High pressure switch located in the refrigerant discharge line and wired across the HPC terminals on the UPM
Low pressure switch located in the unit refrigerant suction line and wired across terminals LPC1 and LPC2 on the UPM.
UPM Board Dry Contacts are Normally Open (NO)
Water side freeze protection sensor, mounted close to condensing water coil, monitors refrigerant temperature between condensing water coil and thermal expansion valve. If temperature drops below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 30°F, however this can be changed to 15°F by cutting the R30 or Freeze1 resistor located on top of DIP switch SW1. Refer to Figure #6, item [3] for resistor location. (Refer to Figure #7 for sensor location)
Figure # 7
If unit is employing a fresh water system (no anti-freeze protection), it is extremely important to have the Freeze1 R30 resistor set to 30°F in order to shut down the unit at the appropriate leaving water temperature and protect your heat pump from freezing if a freeze sensor is included.
The condensate overflow protection sensor is located in the drain pan of the unit and connected to the ‘COND’ terminal on the UPM board. (Figure #8)
Figure # 8
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
UPM Board Factory Default Settings
TEMP
LOCKOUT
RESET
ALARM
TEST
30°F
2
Y
PULSE
NO
UPM DIP SWITCH DEFAULT POSITION
lockout 42
Electrical | 9LM CS Series Heat
MALFUNCTION OUTPUT: Alarm output is
Normally Open (NO) dry contact.
If pulse is selected the alarm output will be pulsed. The fault output will depend on the dip switch setting for "ALARM". If it is set to "CONST", a constant signal will be produced to indicate a fault has occurred and the unit requires inspection to determine the type of fault. If it is set to "PULSE", a pulse signal is produced and a fault code is detected by a remote device indicating the fault. See LED Fault Indication below for blink code explanation. The remote device must have a malfunction detection capability when the UPM board is set to "PULSE".
reset
alarm
test
RY
Cont pulse
yes no
The UPM Board includes the following features:
ANTI-SHORT CYCLE TIMER:
break timer to prevent compressor short cycling.
5 minute delay on
RANDOM START: Each controller has an unique
random start delay ranging from 270 to 300 seconds on initial power up to reduce the chance of multiple unit simultaneously starting at the same time after power up or after a power interruption, thus avoiding creating large electrical spike.
LOW PRESSURE BYPASS TIMER: If the
compressor is running and the low pressure switch opens, the controller will keep the compressor ON for 120 seconds. If, after 120 seconds the low pressure switch remains open, the controllers will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low pressure switch closes and the anti-short cycle time delay expires. If the low pressure switch opens 2-4 times in 1 hour, the unit will enter a hard lockout. In order to exit hard lockout power to the unit would need to be reset.
BROWNOUT/SURGE/POWER INTERRUPTION PROTECTION:
protection in the UPM board will shut does the compressor if the incoming power falls below 18 VAC. The compressor will remain OFF until the voltage is above 18 VAC and ANTI-SHORT CYCLE TIMER (300 seconds) times out. The unit will not go into a hard lockout.
The brownout
If 24 VAC output is needed R must be wired to ALR-COM terminal; 24 VAC will be available o the ALR-OUT terminal when the unit is in the alarm condition.
TEST DIP SWITCH:
to reduce all time delays settings to 10 seconds during troubleshooting or verification of unit operation.
Operation of unit in test mode can lead to accelerated wear and premature failure of components. The "TEST" switch must be set back to "NO" after troubleshooting/ servicing.
A test dip switch is provided
FREEZE SENSOR: The default setting for the
freeze limit trip is 30°F (sensor number 1); however this can be changed to 15°F by cutting the R30 resistor located on top of the DIP switch SW1.
default setting for the freeze limit trip is 30°F (sensor number 1); however this can be changed to 15°F by cutting the R24 resistor located on top of the DIP switch SW1. Since freeze sensor 2 is dedicated to monitor the evaporator coil it is recommended to leave the factory default setting on the board. The UPM controller will constantly monitor the refrigerant temperature with the sensor mounted close to the condensing water coil between the thermal expansion valve and water coil. If temperature drops below or remains at the freeze limit trip for 30 seconds, the controller will shut the compressor down and enter into a soft lockout condition. Both the status LED and the Alarm contact will be active. The LED will flash (three (3) times) the code associated with this alarm condition. If this alarm occurs 2 times (or 4 if Dip switch is
The
8 733 920 847 (2014/01)Revised 01-14
10 | Comfort Alert Module LM CS Series Heat Pump
set to 4) within an hour the UPM controller will enter into a hard lockout condition. It will constantly monitor the refrigerant temperature with the sensor mounted close to the evaporator between the thermal expansion valve and evaporator coil as shown in Figure #4. If temperature drops below or remains at the freeze limit trip for 30 seconds, the controller will shut the compressor down and enter into a soft lockout condition. Both the status LED and the Alarm contact will be active. The LED will flash (three (6) times) the code associated with this alarm condition. If this alarm occurs 2 times (or 4 if Dip switch is set to 4) within an hour the controller will enter into a hard lockout condition. Refer to page #10 for more information.
Freeze sensor will not guard against loss of water. Flow switch is recommended to prevent unit from running, if water flow is lost or reduced.
INTELLIGENT RESET: If a fault condition is initiated, the 5 minute delay on break time period is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition still exists or occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. A single condensate overflow fault will cause the unit to go into a hard lockout immediately, and will require a manual lockout reset.
LOCKOUT RESET: A hard lockout can be reset by turning the unit thermostat off and then back on when the “RESET” dip switch is set to “Y” or by shutting off unit power at the circuit breaker when the “RESET” dip switch is set to “R”.
The blower motor will remain active during a lockout condition.
COMFORT ALERT MODULE
The Comfort Alert diagnostics module (CADM) is a breakthrough innovation for troubleshooting heat pump system failures. (Figure #9)
Figure # 9
By monitoring and analyzing data from the compressor and the thermostat demand, the module can accurately detect the cause of electrical and system related failures without any sensors. A flashing LED indicator communicates the ALERT code and guides the service technician more quickly and accurately to the root cause of a problem.
This module does not provide safety protection! The Comfort Alert module is a monitoring device and cannot shut down the compressor directly.
When an abnormal system condition occurs, the Comfort Alert module displays the appropriate ALERT and/or TRIP LED.
The yellow ALERT LED will flash a number of times consecutively, pause and then repeat the process.
To identify a Flash Code number, count the number of consecutive flashes.
Every time the module powers up, the last ALERT Flash Code that occurred prior to shut down is displayed for one minute.
LM CS Series Heat Pump8 733 920 847 (2014/01) Subject to change without prior notice
Figure 10: Refrigerant Charge, Line Sizing and Capacity Multiplier Chart
Comfort Alert Module | 11LM CS Series Heat
SYSTEM MODEL
LM024
LM036
LM048
LM060
LM070
Factory
R410A
Charge
(Oz)*
80
86
93
115
127
CAPACITY MULTIPLIER
Example 1:
Model LM036 with 45ft of equivalent length of 3/8” O.D Liquid Line. Total system charge= Factory charge + (45ft - 25 ft) x .60 oz/ft Total System Charge = 93 oz + (20ft x .60 oz/ft) = 105 oz. Additional 12 oz of R410A refrigerant required.
Refrigerant Line O.D. Size (Based on Equivalent Line Length)
25 FT. 35 FT. 45 FT. 50 FT. 75 FT
LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC.
3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8
3/8 3/4 3/8 3/4 3/8 3/4 3/8 7/8 3/8 7/8
3/8 7/8 3/8 7/8 3/8 7/8 3/8 7/8 3/8 7/8
3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8
3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8 3/8 1-1/8
1.00 .995 0.990 0.990 0.980
Figure 11: Liquid Line Charge Per Linear Foot
Liquid Line Size, O.D.
Suct. Line
Riser Max.
3/4
3/4
7/8
7/8
7/8
Example 2:
Model LM060 with 10ft of equivalent length of 3/8” O.D Liquid Line. Total system charge= Factory charge + (25ft ­10ft) x .60 oz/ft Total System Charge = 150 oz + (15ft x .60 oz/ft) = 141 oz. Additional 12 oz of R410A refrigerant required.
R410A oz per foot
1/4 5/16 3/8 1/2 5/8 .25 .44 .60 1.15 1.95
8 733 920 847 (2014/01)Revised 01-14
Loading...
+ 25 hidden pages