Fire Alarm Systems | Bosch EVAX System - High-rise Applications
Bosch EVAX System - High-rise
Applications
www.boschsecurity.com
u Master panel with capability for multiple distributed
panels
The Bosch EVAX System for high-rise applications is a
networked emergency relocation and paging system
with integrated two‑way fireman’s telephone system. It
operates with the Fire Alarm Control Panel (FACP) in a
building to provide automatic response to life safety
emergencies. While providing all necessary features
for an effective voice evacuation system, it can easily
convey evacuation, stay-in-place, or other public
address announcements and automatic messages with
multiple channels of simultaneous audio.
Configure your system to include Fire Fighter Phones
or Warden Stations as required, for fire fighter
communications to supplement 2‑way radios and for
use in areas of refuge assistance so trapped
individuals can communicate with fire command.
Smoke control features include automatic or manual
positive or negative pressurization for compartments,
floors, or stairwells. The simple to use interfaces allow
fire department authorities to take over controls and
communicate effectively.
u Operates as stand‑alone or connected to an FACP
u Network transmission over fiber optic or copper pair
cable
u Digitized live voice and prerecorded messaging
u Zone paging control
System overview
The maximum system configuration contains up to 256
Distributed Panels providing up to 2028 monitor and
control points.
2 | Bosch EVAX System - High-rise Applications
Distributed Panels
The Distributed Panels communicate with the Master
Panel through the NetCom Loop. They typically
provide:
• Voice Evacuation Speaker Loops – dedicated data
and audio loops using a minimum of 18 AWG wire
with end-of-line resistors (EOLR).
• Fire Phone Loops – dedicated audio loop using a
minimum of 20 AWG twisted pair wiring with an
EOLR.
• Fan and Damper Loops – data loop using a minimum
20 AWG twisted pair wiring on which up to 32
modules can be attached. Each module provides two
points (one control and one monitor) for a total of 64
points on the circuit.
• Additionally, local Audio Amplifiers can be connected
to the Distributed Panels.
The Bosch Distributed Panels additional provide
specific accessories to support specific functions. The
HMB‑DP provides four audio circuits, the HMB‑DP/P
provides four Fire Phone circuits, and the HMB‑DP‑42
provides 16 audio circuits.
Certifications and approvals
1 Master Panel
2 NetComm Loop
3 Distributed Panels
4 Voice Evacuation Speaker Circuits
5 Fire Phone
6 Fan and Damper Control and Monitor
7 Local Audio Amplifiers (25 W, 50 W, 100 W or combinations
yielding 150 W or 200 W)
Functions
Master Panel
The Master Panel provides the high‑speed
communication loop (NetComm Loop), master
microphone control for live voice (PA) messages, dual
channel Digital Message Repeater (DMR) for up to
1000 prerecorded messages, and a 16‑switch control
module.
NetComm Loop
The NetComm Loop provides high‑speed RS‑485
communications over twisted pair, Category 5 UTP
cable. The network can be wired as Style 4 or Style 7
with a maximum of 4000 ft between panels and a total
loop length of 50,000 ft. The loop carries data and six
audio channels.
Region Certification
USA UL UOXX: Control Unit Accessories, System
CSFM see our website
(ANSI/UL 864)
Installation/configuration notes
Compatible Products
Main Panel Accessories
Designator Description Part Number
MB‑SLC Switch/LED Card F.01U.201.669
MB‑SSC Switch Scan Card F.01U.201.670
MB‑MFA Master Fire Phone Assembly F.01U.201.671
MB‑XI Extended Input Interface F.01U.201.672
MB‑OI Output Interface Card F.01U.201.673
Distributed Panel Accessories
Designator Description Part Number
EVX‑25E Expander Module 25 W 4.998.143.753
EVX‑50E Expander Module 50 W 4.998.143.785
EVX-100E Expander Module 100 W 4.998.143.761
EVX‑T2885 Power transformer for
EVX‑25E
EVX‑T17528 Power transformer for
EVX‑50E/100E
MB‑MBK Mother Board Relays F.01U.201.677
MB‑AMI Audio Module Interface F.01U.201.678
4.998.143.738
4.998.143.739