Fire Alarm Systems | GEH24 Low frequency Horns
GEH24 Low frequency Horns
www.boschsecurity.com
u Evacuation tone
u Use the SuperSlide feature for easy testing
u Wide voltage range; 16 to 33 VDC or FWR
u Select high or low frequency, high or low volume, and temporal Code 3 or continuous tone pattern
u Wire then install the entire system
The Gentex Commander² Low frequency Horns (GEH24) offer a dependable audible alarm and a low current draw.
Functions
Easy Installation and Testing
The user can wire then install the entire system, reducing installation and operating costs. Use the SuperSlide feature to test supervision.
Horn Output
The horns provide a selection of high or low volumes with a peak sound of 100 dBA or greater at 10 ft
(3 m). They offer a choice between a 2400 Hz (remote signaling) tone or a broadband low frequency
(1500 Hz to 3000 Hz) mechanical sounding (evacuation) tone where closed doors could prevent hearing the other tone. The user can also select either continuous or temporal Code 3 tone output, and synchronize the temporal signal by using the AVS Series Synchronization Modules or a compatible control panel.
Certifications and approvals
GentexCorporation holds these Listings and Approvals:
Region |
Certification |
|
|
|
|
USA |
UL |
ULSZ: Audible Signal Appliances |
|
|
(UL464), ULSZ7: Audible Signal Appli- |
|
|
ances Certified for Canada (cULus) |
|
FM |
|
|
CSFM |
see our website |
|
|
|
Installation/configuration notes
Compatible Products
The following products are compatible with the GEH24 Horns:
Category |
Product ID |
Product Description |
Control |
D70221 |
Conventional FACP |
Panels |
|
|
|
D70242 |
Addressable FACP |
|
D7024 |
Conventional FACP |
|
D80243 |
Analog FACP |
|
D91243 |
Addressable FACP |
|
D10024A3 |
Analog FACP |
|
FPD-70242, 4 |
Addressable FACP |
|
FPD-7024 |
Conventional FACP |
2 | GEH24 Low frequency Horns
Modules |
AVS 44 |
Synchronization module (red) |
|
AVS44 W |
Synchronization module (white) |
|
AVSM R |
Synchronization module (red) |
|
AVSM W |
Synchronization module (white) |
1 The D7022 must be set for 24 VDC operation and requires the AVS44 or AVSM Synchronization Modules for synchronization.
2 When used with a D7039 Multiplex Expansion Module, the FPD-7024 and D7024 become addressable FACPs.
3 For synchronization, use the AVS44 or AVSM Synchronization Modules with these control panels. 4 The FPD-7024 is not UL864 9th edition approved for use with the Gentex synch protocol.
Mounting Considerations
Outdoor Applications
For an outdoor application or a severe environment (NEMA 3R) application, the GEH24 Series Horns must be surface mounted on a flat wall in a GOE Outdoor Enclosure. Use a watertight conduit fitting.
Indoor Applications
Install the horns with their tops at least 90 in. (2.3 m) above the floor and no closer than 6 in. (15.2 cm) to the ceiling. The horns are equipped with a four inch square mounting plate that can be attached as follows:
|
Conduit |
Surface |
Semi flush |
|
Applications |
Mounted |
Mounted |
Single gang |
• |
|
• |
|
|
||
Double gang |
• |
• |
• |
|
|||
Four inch square |
• |
• |
• |
|
|||
GSB |
• |
• |
|
|
|
||
GOE |
• * |
• |
|
* The GOE Outdoor Enclosure has knockout holes sized for half inch conduit and matching connector. Use a watertight conduit fitting.
Shipping Information
The horns are delivered from the factory set to the temporal lower frequency mode. Also included is a locking mechanism that secures the product to the bracket without any screws showing.
Wiring
The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).
Parts included
Quant. Component
1Horn with finish plate
1Die cast mounting plate
1Plastic test card
1Hardware pack
1Literature pack
Technical specifications
Electrical
Voltage Range: |
16 VDC or FWR to 33 VDC or FWR |
|
|
Voltage (Input): |
24 VDC or FWR nominal |
|
|
Environmental |
|
|
|
Relative Humidity |
Up to 93% non condensing |
|
|
Temperature (Operating): |
+32°F to +120°F (0°C to +49°C) |
|
|
Mechanical |
|
|
|
Dimensions (H x W x D): |
5.0 in. x 4.5 in. x 2.5 in. |
|
(12.7 cm x 11.4 cm x 6.4 cm) |
|
|
Alarm Ratings
Horn (Continuous, 2400 Hz)
Audible Device Current (maximum): |
28 mA RMS; |
|
48 mA FWR |
|
|
Sound output at 10 ft (3 m) at 24 VDC: |
High output: 86 dBA |
|
Low output: 78 dBA |
|
|
Horn (Continuous, Mechanical) |
|
|
|
Audible Device Current (maximum): |
25 mA RMS; |
|
44 mA FWR |
|
|
Sound output at 10 ft (3 m) at 24 VDC: |
High output: 84 dBA |
|
Low output: 76 dBA |
|
|
Horn (Temporal Code 3, 2400 Hz) |
|
|
|
Audible Device Current (maximum): |
28 mA RMS; |
|
48 mA FWR |
|
|
Sound output at 10 ft (3 m) at 24 VDC: |
High output: 83 dBA |
|
Low output: 75 dBA |
|
|
Horn (Temporal Code 3, Mechanical) |
|
|
|
Audible Device Current (maximum): |
25 mA RMS; |
|
44 mA FWR |
|
|
Sound output at 10 ft (3 m) at 24 VDC: |
High output: 81 dBA |
|
Low output: 73 dBA* |
|
|
Chime (Continuous) |
|
|
|
Audible Device Current (maximum): |
15 mA RMS; |
|
30 mA FWR |
|
|
Sound output at 10 ft (3 m) at 24 VDC: |
High output: 71 dBA* |
|
Low output: 68 dBA* |
|
|
Chime (Temporal Code 3) |
|
|
|
Audible Device Current (maximum): |
15 mA RMS; |
|
30 mA FWR |
|
|
Sound output at 10 ft (3 m) at 24 VDC: |
High output: 71 dBA* |
|
Low output: 68 dBA* |
|
|