Bosch GEH12WW, GEH12WR Specsheet

Fire Alarm Systems | GEH12 Low‑frequency Horns
GEH12 Low‑frequency Horns
www.boschsecurity.com
u Evacuation tone
u Use the SuperSlide feature for easy testing
u Wide voltage range; 8 VDC to 17.5 VDC
The Gentex GEH12 Low‑frequency Horns offer a dependable audible alarm and a low current draw.
Functions
Easy Installation and Testing
The user can wire then install the entire system, reducing installation and operating costs. Use the SuperSlide feature to test supervision.
Horn Output
The horns provide a selection of high or low volumes with a peak sound of 100 dBA or greater at 10 ft (3 m). They offer a choice between a 2400 Hz (remote signaling) tone or a broadband low frequency (1500 Hz to 3000 Hz) mechanical sounding (evacuation) tone where closed doors could be a problem. The user can also select either continuous or temporal Code 3 tone output, and synchronize the temporal signals by using the AVS Series Synchronization Modules or a compatible control panel.
Certifications and approvals
Gentex Corporation holds these Listings and Approvals:
and Temporal Code 3 or Continuous tone pattern
u Wire then install the entire system
Region
Certification
USA UL ULSZ: Audible Signal Appliances
(UL464)
CSFM see our website
Installation/configuration notes
Compatible Products
The following products are compatible with the GEH12 Series Horns:
Category Product ID Product Description
Control Panels
D7022
Compatible with all Bosch G Series, 6000 Series, 2000 Series, DS7400Xi and DS7400XiV4, DS7080iP‑32, DS7200 Series, and DS7060 Series Control Panels
2
Conventional FACP
1
Modules AVS‑44 Synchronization module (red)
AVS44‑W Synchronization module (white)
AVSM‑R Synchronization module (red)
AVSM‑W Synchronization module (white)
1
For synchronization, use the AVS44 or AVSM
Synchronization Modules with these control panels.
2 | GEH12 Low‑frequency Horns
2
The D7022 must be set for 12 VDC operation and requires the AVS44 or AVSM Synchronization Modules for synchronization.
Mounting Considerations
Outdoor Applications For an outdoor application or a severe environment (NEMA 3R) application, the GEH12 Series Horns must be surface mounted on a flat wall in a GOE Outdoor Enclosure. Use a watertight conduit fitting. Indoor Applications Install the horns with their tops at least 90 in. (2.3 m) above the floor and no closer than 6 in. (15.2 cm) to the ceiling. The horns are equipped with a four-inch square mounting plate that can be attached as follows:
Conduit
Applications
Single‑gang
Double‑gang
Four‑inch square
GSB
Surface Mounted
Semi‑flush Mounted
Shipping Information
The horns are delivered from the factory set to the temporal lower frequency mode. Also included is a locking mechanism that secures the product to the bracket without any screws showing.
Wiring
The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).
Parts included
Quant. Component
1 Horn with finish plate
1 Die‑cast mounting plate
1 Plastic test card
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
Voltage Range: 8 VDC to 17.5 VDC
Voltage (Input): 12 VDC nominal
Mechanical
Dimensions (HxWxD): 5.0 in. x 4.5 in. x 2.5 in.
(12.7 cm x 11.4 cm x 6.4 cm)
Alarm Ratings
Horn (Continuous, 2400 Hz)
Audible Device Current (maximum): 29 mA RMS
Sound output at 10 ft (3 m) at 12 VDC: High output: 78 dBA
Low output: 73 dBA
Horn (Continuous, Mechanical)
Audible Device Current (maximum): 26 mA RMS
Sound output at 10 ft (3 m) at 12 VDC: High output: 81 dBA
Low output: 75 dBA
Horn (Temporal Code 3, 2400 Hz)
Audible Device Current (maximum): 29 mA RMS
Sound output at 10 ft (3 m) at 12 VDC: High output: 78 dBA
Low output: 73 dBA
Horn (Temporal Code 3, Mechanical)
Audible Device Current (maximum): 26 mA RMS
Sound output at 10 ft (3 m) at 12 VDC: High output: 78 dBA
Low output: 72 dBA*
Chime (Continuous)
Audible Device Current (maximum): 13 mA RMS
Sound output at 10 ft (3 m) at 12 VDC: High output: 64 dBA*
Low output: 63 dBA*
Chime (Temporal Code 3)
Audible Device Current (maximum): 13 mA RMS
Sound output at 10 ft (3 m) at 12 VDC: High output: 63 dBA*
Low output: 62 dBA*
Whoop
Audible Device Current (maximum): 55 mA RMS
Sound output at 10 ft (3 m) at 12 VDC: High output: 79 dBA
Low output: 74 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
Environmental
Relative Humidity Up to 93% non‑condensing
Temperature (Operating): +32°F to +120°F (0°C to +49°C)
Notice
The sound output for the temporal (Code 3) tone is rated lower because the time the horn is off is averaged into the sound output rating. When the horn is producing a tone in the Temporal mode, its sound pressure is the same as the Continuous mode.
Loading...