FPD-7024 | Operation and Installation Guide | FCC Compliance Notice
You will be informed of your right to file a
FCC Compliance Notice
This equipment was tested and found to comply
with the limits for a Class A digital device, pursuant
to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against
harmful interference in a residential installation. This
equipment generates, uses, and can radiate radio
frequency energy, and if not installed and used in
accordance with the instructions, might cause
harmful interference to radio communications.
There is no guarantee that interference will not
occur in a particular installation. If this equipment
does cause harmful interference to radio or
television reception, that can be determined by
turning the equipment off and on, the user is
encouraged to try to correct the interference by one
or more of the following measures:
Re-orient or relocate the receiving antenna.
Increase the separation between the equipment and
the receiver.
Connect the equipment into an outlet on a circuit
different from that to which the receiver is
connected.
Consult the dealer or an experienced radio or TV
technician for help.
FCC Phone Connection to Users
This control panel complies with Part 68 of the FCC
rules.
On the inside of the enclosure is a label that
contains, among other information, the ringer
equivalence number (REN) for this equipment. You
must, upon request, provide this information to your
local telephone company.
The REN is useful to determine the quantity of
devices that can be connected to your telephone line
and still have all of those devices ring when your
telephone number is called. In most, but not all
areas, the sum of the RENs of all devices connected
to one line should not exceed five. To ascertain the
number of devices that you can connect to your line,
contact your local telephone company to determine
the maximum REN for your local calling area.
This equipment can not be used on coin service
provided by the telephone company. Do not
connect this control panel to party lines. If this
equipment causes harm to the telephone network,
the telephone company might discontinue your
service temporarily. If possible, they will notify you
in advance. But if advance notice isn’t practical, you
will be notified as soon as possible.
complaint with the FCC. The telephone company
might make changes in its facilities, equipment,
operations, or procedures that could affect the
proper functioning of your equipment. If they do,
you will be notified in advance to give you an
opportunity to maintain uninterrupted telephone
service.
If you experience trouble with this equipment,
contact the manufacturer for information on
obtaining service or repairs.
The telephone company might ask that you
disconnect this equipment from the network until
the problem is corrected or until you are sure that
the equipment is not malfunctioning. The
manufacturer, not the user, must make the repairs to
this equipment.
To guard against accidental disconnection, there is
ample room to mount the telco jack inside of the
control panel cabinet.
The operation of this control panel might also be
affected if events such as accidents or acts of God
cause an interruption in telephone service.
Industry Canada Notice
The Industry Canada label identifies certified
equipment. This certification means that the
equipment meets certain telecommunications
network protective, operational, and safety
requirements. Industry Canada does not guarantee
the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure
that it is permissible to be connected to the facilities
of the local telecommunications company. The
equipment must also be installed using an
acceptable method of connection. The customer
should be aware that compliance with the above
conditions might not prevent degradation of service
in some situations.
Repairs to certified equipment should be made by
an authorized Canadian maintenance facility
designated by the supplier. Any repairs or
alterations made by the user to this equipment, or
equipment malfunctions, might give the
telecommunications company cause to request the
user to disconnect the equipment.
Users should ensure for their own protection that
the electrical ground connections of the power
utility, telephone lines, and internal metallic water
pipe system, if present, are connected together.
Users should not attempt to make such connections
2
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
.
themselves, but should contact the appropriate
electric inspection authority, or electrician.
Trademarks
Microsoft®, Windows®, Windows NT® are either
registered trademarks or trademarks of Microsoft
Corporation in the United States and/or other
countries.
®
CYCOLOY
Electric Company.
POLYLAC
Industrial Corporation, LTD.
Chamber Check
Security Systems, Inc. in the United States.
CleanMe
the United States and/or other countries.
is a registered trademark of General
®
is a registered trademark of CHI MEI
®
is a registered trademark of Bosch
™
is a trademark of GE Interlogix, Inc. in
FPD-7024 | Operation and Installation Guide | Trademarks
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
3
FPD-7024 | Operation and Installation Guide | Contents
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
.
1.0 Overview
1.1 System Overview
This guide applies to control panels
equipped with version V1.00 or later
The FPD-7024 Fire Alarm Control Panel is a fully
integrated hard-wire fire alarm system. It can
support four input points (expandable to 255 using
D7039 Multiplex Expansion Module and the FPC7034 Four-Point Expander) and 16 individual users
(expandable to 100 with the D7039). The control
panel has a built-in LCD keypad. Up to four
additional keypads can be used to provide user
interface with the system and programming access
for the installer. The FPD-7024 also includes the
following features:
•Built-in dual-line communicator
software.
FPD-7024 | Operation and Installation Guide | 1.0 Overview
• Menu driven keypad programming
• Freely programmable
alphanumeric/alphabetical display
• 99 event history buffer
• 16 user codes
• UL Listed, CSFM, MEA Approved
When the D7039 Multiplex Expansion Module is
installed, these additional features are available:
•247 additional addressable input points
(255 total points)
• 499 Non-volatile event history buffer
• 100 user codes
Refer to Figure 1 for the location of the major items
on the FPD-7024 Control Board.
Figure 1: FPD-7024 Control Board
11
10
AUX-
AUX+
A+
N
A
B+
C
B1
A-
A+
N
A
B+
C
B2
A-
BAT24V
BAT+
9
8
7
1. Telco Terminal Strip
2 - Relay Terminal Strip
3 - Smoke Power Terminal Strip
4 - Zone Input Terminal Strip
5 - Option Bus Terminal Strip
6 - FPC-7034 Point Expander Connector Pins
The standard enclosure is 18 ga., cold-rolled steel,
and measures 20.75 in. x 15 in. x 4.25 in. (52.7 cm x
38.1 cm x 10.8 cm). A keyed lock is included, and
the LEDs and LCD display are visible through the
door.
1.2.4 Remote LCD Keypads
Maximum number of keypads: Four FMR-7033
LCD Fire Keypads.
Wiring Requirements: Refer to Section 2.2 Option Bus Wiring Requirements on page 19.
1.2.5 Remote LED Annunciators
Maximum number of annunciators: Eight D7030
eight-zone LED Annunciators.
Wiring Requirements: Refer to Section 2.2 Option Bus Wiring Requirements on page 19.
1.2.6 D7032 with the D7030X Use
When a D7032 Eight-Zone LED Annunciator
Expander is connected to the D7030X, eight
additional LED zones appear. This allows the
All on-board points, and points activated with the
FPC-7034 Four Point Expander, are continuously
monitored for detectors signaling a dirty condition
using the Bosch Security Systems, Inc. Chamber
Check and GE Interlogix, Inc. CleanMe protocols.
D7030X/D7032 combination to show 16 LED
zones. Up to eight D7030X/D7032 combinations
can be connected to the FPD-7024 Fire Alarm
Control Panel. Refer to Table 2 on page 9 for zones
shown by each D7030X/D7032 combination.
To prevent nuisance reports, a two-minute delay
occurs before a dirty detector is annunciated. A sixminute delay occurs after the detector restores from
the dirty condition before the control panel restores
the condition.
D7039 Multiplex Expansion Module)
Signaling Line Circuits (SLCs)
connection to the common bus (when over ten
points are troubled, up to ten troubles are
shown per bus and the balance of the troubles is
indicated by a common bus failure message).
programmed from 1 to 89 seconds.
a D7042 Eight Input Remote Module.
Each D7030X processes 16 zones of
information. If no D7032 is attached, only
the lower eight zones are shown.
The column labeled Shown on D7030X” In
Table 2 on page 9 applies regardless if an
attachment of a D7032 to any D7030X is
made.
8
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
FPD-7024 | Operation and Installation Guide | 1.0 Overview
.
Table 2: LED Assignments for LED Annunciators 4 and 8
D7030X Zones
Covered
Shown on
7030X
Shown on
D7032 (if
COMMENTS
attached)
1 1 to 16 1 to 8 9 to 16 Combination with lowest option bus address (such as Address 1)
2 17 to 32 17 to 24 25 to 32 Combination with second lowest option bus address (such as
Address 2)
3 33 to 48 33 to 40 41 to 48 Combination with third lowest option bus address (such as
Address 3)
4 49 to 64 49 to 56 57 to 64 Combination with fourth lowest option bus address (such as
Address 4)
5 1 to 16 1 to 8 9 to 16 Fifth combination repeats first combination
6 17 to 32 17 to 24 25 to 32 Sixth combination repeats second combination
7 33 to 48 33 to 40 41 to 48 Seventh combination repeats third combination
8 49 to 64 49 to 56 57 to 64 Eighth combination repeats forth combination
Refer to Table 3 for the LED display for Zones 49 to 64.
Table 3: LED Display for Zone 49 to 64
LED Zone Description
1 49 User defined
2 50 User defined
3 (reserved)
4 52 General fire alarm monitor waterflow (non-silencable)
5 53 General fire alarm monitor (silencable)
6 (reserved)
7 55 General Supervisory (silencable)
8 56 General Waterflow (silencable)
9 (reserved)
10 58 General supervisory alarm (non-silencable)
11 (reserved)
12 (reserved)
13 61 General waterflow alarm (non-silencable)
14 (reserved)
15 63 General alarm monitor waterflow (non-silencable)
16 (reserved)
1.2.7 Communicator
The communicator can report to two phone
numbers or IP addresses with full single, double,
and back-up reporting. Communicates in SIA,
Modem IIIa2, Contact ID, BFSK, and 3/1 and 4/2
The communicator must be enabled and
configured to operate. The communicator
and phone line monitors are disabled in
the default factory configuration.
Tone burst formats.
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
9
FPD-7024 | Operation and Installation Guide | 1.0 Overview
Phone Line and Phone Number/IP Selection: To
ensure the delivery of critical reports, the fire panel
has two phone lines and two phone numbers or IP
addresses that can be used for reporting. Reports
can be directed to one or both of two phone
numbers or IP addresses using the Report Steering
feature (refer to Section 5.6.3 Report Steering on page
65) in the control panel programming. Note that
Account Number 1 is used with Phone Number/IP
Supplemental Reporting: While two independent
phone lines are required for UL864 Central Station
service, the FACP can be configured with one
phone line if the control panel is used only for
supplemental reporting on a local, remote station or
auxiliary system.
Connect a jumper from T1 to T2 and R1 to R2 if
the control panel is installed with only one phone
line. Refer to Figure 2.
1, and Account Number 2 is used with Phone
Number/IP 2. Except for test reports, the control
panel automatically selects the phone line or IP
address to use. If the report is not successful after
two attempts on Line 1, the control panel
automatically switches and uses Phone Line 2. One
exception is when test reports (manual or automatic)
Figure 2: Supplemental Reporting
are sent. Test reports are sent every 4 hours to 28
days. Each time a Test report is sent, the control
panel alternates phone lines. This happens even if
the monitor says the line is bad. If the user sends
two manual test reports both phone lines can be
tested. The first report uses one line and the second
uses the other line. During normal operation, the
automatic test uses a different line each day.
Because the control panel automatically selects
which line to use, both phone lines must use the
same dialing sequences for sending reports. For
example, a line that requires a 9 to be dialed for an
outside line cannot be paired with a line that does
not require a 9.
PBX lines and ground start phone lines do
not comply with NFPA requirements for
digital communication.
While the control panel is idle, the FACP monitors
the primary and alternate telephone lines by
monitoring the line for trouble. The FACP monitors
each line every 12 seconds. When a trouble still
exists after three samples (36 seconds), the FACP
sends a trouble report and activates the yellow
trouble LED and trouble relay.
1 - Jumper from R1 to R2
2 - Jumper from T1 to T2
3 - House phone
4 - Telco Line
1.2.8 Users
The system allows up to 16 individual users, or up
to 100 users when the D7039 is installed. A personal
identification number (PIN) the four-digit code
entered at the keypads, and an authority level to
determine which functions can be performed (refer
to Section 5.2.1 Personal Identification Numbers on
page 41) can be assigned to each user.
1.2.9 Lightning Protection
Control panel reports can be delayed if the
dialer outputs are not connected together
on an installation where the control panel
has only one phone line
R2
1
2
HR2
HT2
T2
R1
RH1
TH 1
T1
3
4
10
If the central station receives the automatic
test report only every other day, this
indicates that one phone line at the
protected premises is inoperative. Correct
this condition immediately, because other
critical reports can be delayed when the
communicator is trying to send the test
signal through the inoperative phone line
(once each 48 hours).
This system is intended for installation
entirely within one building.
Metal-oxide varistors (MOV) and spark gaps
provide protection from lightning surges and static
discharges.
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
FPD-7024 | Operation and Installation Guide | 1.0 Overview
.
1.2.10 Backup Battery Calculation
Use Table 4 to calculate the standby battery capacity required by NFPA when using the FPD-7024.
Table 4: Standby Battery Capacity Calculations
Device Quantity Standby
Existing/Device
FPD-7024 Control panel 1 200 mA 200 mA 380 mA 380 mA
FPC-7034 Four-Point Expander 44 mA 156 mA
D7035/B Octal Relay1 8 Ma + 30 mA2 8 Ma + 30 mA2
D7048/B Octal Driver Module 10 mA 10 mA
FMR-7036 Annunciator Keypad 80 mA 100 mA
D7030X Eight-Point LED Annunciator1 27 mA 132 mA
D7030X-S2 Eight-Point LED Annunciator 35 mA 175 mA
D7030X-S8 Eight-Point LED Annunciator 35 mA 175 mA
D7032 Eight-Point LED Annunciator
1 mA 90 mA
Expander
FMR-7033 Keypad1 80 mA 100 mA
D7039 MUX Expansion Module 150 mA 150 mA
D7042/B Addressable Eight Point Input 18 mA 18 mA
D7050 MUX Photoelectric Smoke
0.50 mA 0.56 mA
Detector
D7050TH MUX Photoelectric Smoke
0.50 mA 0.56 mA
Detector
FMM-7045 Mux Pull Station 0.55 mA 0.55 mA
D7044 Mux Single Input Fire 0.55 mA 0.55 mA
D7044M Mux Mini Contact Module 0.55 mA 0.55 mA
D7052 Mux Dual Input Fire 0.55 mA 0.55 mA
D7053 Mux I/O Module Fire 0.70 mA 0.70 mA
Smoke Detectors
Bells, Horns, and so on
Other Sensors
Other
Grand Total
Standby Existing
1
The 24 VDC existing requirements for the D7030X, FMR-7033 and D7035 are shown at 75% of the 12 VDC level shown on
the specification sheets for these models. The FPD-7024 regulates 24 VDC power from the battery to 12 VDC for these
accessories.
2
Add 30 mA for each relay activated
Total
Standby
Alarm
Existing/Device
Grand Total
Alarm Existing
Total Alarm
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
11
FPD-7024 | Operation and Installation Guide | 1.0 Overview
The units shown in Table 5 are Amp hours (Ah), and the figures include a 20% derating factor.
Table 5: Required Battery Size Calculation
Grand Total Standby Existing (in amps) CS
Total Hours of Standby Required (usually 24 or 60): HS
Total Standby Capacity (multiply CS X HS) TS= CS X HS
Grand Total Alarm Existing (in amps) CA
Total Hours of Alarm Time Required (usually 0.083 or 0.25): HA
Total Standby Capacity (multiply CA X HA) TA= CA X HA
Total Capacity Required (add TA + TS): TC = TA + TS
Required Capacity with 20% Derating (TC X 1.2) C = TC X 1.2
The required battery size to support the system can be calculated using Table 6 and Table 7
on page 13.
1.2.11 Standby Existing Load
Use Table 6 to estimate the size of the battery required to support the standby load, then use Table 7 on page 13 to
estimate the size of the battery required to support the alarm load. Add the results together for the total battery
size. Select the next larger standard battery for the system. If the results show a requirement for a battery over 40
Ah, reduce the existing or add an external regulated fire protective signaling power supply.
Table 6: Standby Load Battery Size (Ah)
Standby Load Battery Size Chart Capacity Required for
24 Hours
Grand Total Standby Existing
100 to 200 mA 5.8 11.5 14.4
201 to 300 mA 8.6 17.3 21.6
301 to 400 mA 11.5 23.0 28.8
401 to 500 mA 14.4 28.8 36.0
501 to 600 mA 17.3 34.6 X
601 to 700 mA 20.2 X X
701 to 800 mA 23.0 X X
801 to 900 mA 25.9 X X
901 to 1000 mA 28.8 X X
1001 to 1100 mA 31.7 X X
Capacity Required for
48 Hours
Capacity Required for
60 Hours
12
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
.
Table 7: Alarm Load Battery Size (Ah)
FPD-7024 | Operation and Installation Guide | 1.0 Overview
Alarm Load Battery Size Chart Capacity
Required for 5
Minutes
Grand Total Standby Existing
250 to 500 mA 0.1 0.1 0.2 0.3 0.5
501 to 999 mA 0.1 0.2 0.3 0.6 0.9
1.0 to 1.5 A 0.2 0.3 0.5 0.9 1.4
1.6 to 2.0 A 0.2 0.4 0.6 1.2 1.8
2.1 to 2.5 A 0.3 0.5 0.8 1.5 2.3
2.6 to 3.0 A 0.3 0.6 0.9 1.8 2.7
3.1 to 3.5 A 0.4 0.7 1.1 2.1 3.2
3.6 to 4.0 A 0.4 0.8 1.2 2.4 3.6
Capacity
Required for 10
Minutes
Capacity
Required for 15
Minutes
Capacity
Required for 30
Minutes
Capacity
Required for 45
Minutes
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
13
FPD-7024 | Operation and Installation Guide | 1.0 Overview
1.2.12 Compatible Devices
Table 8: Compatible Devices
Device Function
D7030 Eight Point LED
Annunciator
D7030X Eight Point LED
Annunciator
D7030X-S2 Eight Point
LED Annunciator
D7030X-S8 Eight Point
LED Annunciator
D7032 Eight Point LED
Annunciator Expander
FMR-7033 Alphanumeric
LCD Keypad
FPC-7034 Four Point
Expander
D7035/B Octal Relay
Module
FMR-7036 Fire
Annunciator Keypad
FPP-RNAC-8A-4C Remote
NAC Power Supply
D7039 Multiplex
Expansion Module
D7042/B Eight-Input
Remote Module
D7048/B Octal Driver
Module
FMM-7045 Mux Pull
Station
D7044 Mux Single Input
Fire
D7044M Mux Mini Contact
Module
Identifies the location of a fire alarm for up to eight zones allowed per system.
Identifies the location of a fire alarm for up to eight zones allowed per system.
An eight-zone LED annunciator, of which two zones are reserved for supervisory functions. It has
Power and Trouble LEDs plus eight-zone LEDs that can be labeled individually.
An eight-zone LED annunciator, of which all eight zones are reserved for supervisory functions. It
has Power and Trouble LEDs plus eight-zone LEDs that can be labeled individually.
Attaches to a D7030X and identifies the location of a fire alarm for eight additional zones.
Connects up to four-keypads per system.
Allows the FPD-7024 Control Panel to support four additional points. The FPC-7034 plugs into
the control panel and provides four Class B, Style 4 loops that are identical in characteristics to
the loops on the control panel. One FPC-7034 is allowed per system.
Provides eight Form C relay outputs for addition to the system. The outputs are programmable
and can be activated by system events. Each output operates independently of the other seven
outputs for complete flexibility. The D7035 connects to the option bus; up to two are allowed
per system. Refer to the D7035 Installation Guide (P/N: 37280) for required enclosure
modification. The D7035B comes installed on a mounting skirt.
Establishes the location of a fire alarm.
Adds four NFPA 72 Class B, Style Y Notification Appliance Circuits through the option bus and
is supervised by the control panel. The FPP-RNAC-8A-4C connects to the option bus of the
FPD-7024 control panel and up to four are allowed per system.
Provides either 2 two-wire (Class B, Style 4) multiplex buses or 1 four-wire (Class A, Style 6)
multiplex bus. In Class A mode, up to 120 addressable points can be added. In Class B Mode,
up to 247 addressable points can be added. The D7039 connects directly to the control panel.
One is allowed per system.
Provides eight Class B, Style 4 input points. Connect up to 15 modules to MUX Bus A, and 15
on MUX Bus B. The D7042 is powered by 12 VDC supplied by the option bus power terminals,
in addition to the two-wire data connection. The D7042 can not be used on a signal line circuit
(SLC) configured for Class A, Style 6 operation.
Provides eight open collector transistor outputs for addition to the FPD-7024 Fire Alarm Control
panels. It connects to the control panels through the option bus.
UL Listed fire alarm initiating device.
Connects a contact device to the multiplex bus of the FPD-7024 with a supervised local loop.
The D7044 draws operating power from the FPD-7024.
Connects a contact device to the multiplex bus of the FPD-7024 with a supervised input loop.
The D7044 draws operating power from the FPD-7024.
14
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
FPD-7024 | Operation and Installation Guide | 1.0 Overview
.
Table 8: Compatible Devices (continued)
D7052 Mux Dual Input Fire
D7053 Mux I&O Module
Fire
D7050/TH Mux Smoke
Detector
Connects to the multiplex bus of the FPD-7024 and provides two supervised input zones for
connecting conventional normally-open inputs. The D7052 draws operating power from the
FPD-7024.
Connects to the multiplex bus of the FPD-7024 and implements a supervised local loop, and a
Form C relay output. Up to 20 modules can be connected to each MUX bus. The D7053 draws
operating power from the FPD-7024.
The D7050/TH is a photo-electric smoke detector with a heat option. It connects to the
multiplex bus of the FPD-7024. The D7050 draws operating power from the
FPD-7024.
Table 9: Address Restrictions for the D7042, D7052, and D7053
Install D7042 modules only at addresses:
9 17 25 33 41 49 57 65
73 81 89 97 105 113 121 129
137 145 153 161 169 177 185 193
201 209 217 225 233 241
Do not install D7052 and D7053 modules at these addresses
16 24 32 40 48 56 64
80 88 96 104 112 120 128 136
144 152 160 168 176 184 192 200
208 216 224 232 240 248 255
72
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
15
FPD-7024 | Operation and Installation Guide | 1.0 Overview
1.3 Parts List
Figure 3: Enclosure Installation
•One FPD-7024 Control/Communicator in staticresistant bag
• One enclosure with transformer
• One hardware pack
• One enclosure lock, washer, and keys
• Six end-of-line (EOL) resistors
The hardware necessary for installing the control
panel in the enclosure is located in the hardware
pack.
1.4 Installing the Enclosure
1. Using the enclosure as a template, mark the top
mounting holes on the mounting surface
(Figure 3).
2. Start the mounting screws (not supplied) for
these two holes.
3. Slide the enclosure onto these screws so that the
screws rest on the thinner section of the holes.
4. Tighten the screws.
5. Install and tighten the remaining two screws in
the bottom mounting holes.
6. Knock out the desired wire entrances on the
enclosure.
1 - Control panel location
2 - Mounting holes
3 - Retainer holes for standoffs
4 - Retainer holes for support posts
5 - Transformer
6 - Stud
7 - Ground wire
1
2
7
6
5
3
4
2
16
If using the knockouts located at the
bottom of the enclosure install batteries in
a separate enclosure.
1.5 Installing the FPD-7024
The control circuit board in the FPD-7024
is static sensitive. Touch ground before
1. Insert the three support posts in the enclosure’s
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
handling the control board. This discharges
any static electricity in your body. For
example, run the ground wire to the
enclosure before handling the control
circuit board. Continue touching the
enclosure while installing the control board.
retainer holes. Refer to Figure 3 above and
Figure 4 on page 17.
.
2. Press the 1/8 in. nylon standoffs
(P/N: F01U034705) into the retainer holes.
3. Slide the top of the control panel onto the
retainer tabs (the slots under the top of the
frame). When the control panel is in the retainer
tabs, it rests on the posts.
4. Secure the bottom of the circuit board by
inserting and tightening the screws at the two
bottom corners through the support posts and
the retainer holes Figure 4.
Connect the supplied ground wire between
the door and the enclosure using the
supplied nuts before the circuit board is
installed.
A second ground wire is provided for connecting
the AC power ground. Both grounds connect to the
stud in the enclosure to the left of the circuit board.
Refer to Figure 3 on page 16.
Figure 4: Standoff and Support Post Installation
3
4
5
1
2
=
6
1 - 1/8 in. nylon standoff
2 - Retainer holes
3 - Support post assembly
4 - Corner of circuit board
5 - Support post
6 - Retainer hole in enclosure
1.6 Installing Optional Equipment
Two expansion options connect directly to the
control panel, and are automatically detected and
supervised when the control panel is powered:
• FPD-7034 Four Point Expander
• D7039 Multiplex Expansion Module
When the control panel is powered after installing
one of these options, the control panel displays one
of the following windows:
4Z EXP DETECTED
PRESS ENTER KEY
FPD-7024 | Operation and Installation Guide | 1.0 Overview
MUX DETECTED
PRESS ENTER KEY
Press the [#/Enter] key to confirm the installation of
the device and automatically set it up for
supervision.
If the [#/Enter] key is not pressed during the powerup time-out period, the control panel resumes
operation using the last confirmed status of the
affected expander and displays an installation error
condition.
Expansion devices such as point expanders
and multiplex expanders are disabled if they
are removed from the control panel
configuration after installation. You cannot
disable supervision of these devices when
they are installed.
Refer to the installation instructions for these
expanders for additional information.
When the D7039 Multiplex Expansion
Module is first installed, the system displays
an EEPROM fault. Execute the default
procedure to synchronize the EEPROM on
the expansion module to the EEPROM in
the control panel. Remove power to the
control panel, then reapply power and reinstall option bus devices after the default
procedure.
Replacing a D7039 Multiplex Expansion
Module causes the loss of programming of
expansion points and PINs. Reprogram all
multiplex point and PINs if you replace the
D7039.
When the D7039 is first installed, or anytime the
control panel is powered with a D7039 that has no
points programmed, the system automatically starts
the multiplex auto-programming process:
AUTO PROGRAM?
:YES(1)/NO(0)
Pressing the [1] key starts auto-programming, and
pressing [0/Prog] allows the control panel to
continue normal startup. The menu automatically
closes with NO selected if no key is pressed after
several minutes. Refer to Section 5.9.4 Auto Program
on page 74 for detailed instructions on the autoprogramming mode.
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
17
FPD-7024 | Operation and Installation Guide | 2.0 Control Panel Terminal Connections
2.0 Control Panel Terminal Connections
Figure 5: FPD-7024 Control Panel Terminal Connections
Incorrect connections may result
in damage to the unit and personal injury.
Before servicing this equipment, remove all
-
power including the transformer, battery
and phone lines.
Shared cable is not recommended for
option bus, telephone or NAC wiring.
Typical Fire Wiring
Red
Brown
Typical 4-wire smoke
detector wiring.
SMK+
SMK-
1A+
1B+
1B-
1A-
SMK+
SMK-
1A+
1B+
1B-
1A-
Typi c al 2-wir e
smoke detector
wiring (supervised)
1A+
1B+
1B-
1A-
1A+
1B+
1B-
1A-
EOL
Resistor
CLASS A
STYLE D
CLASS B
STYLE B
CLASS A
STYLE D
CLASS B
STYLE B
NC
AC Power 2
NC
AC Power 1
For connection to
listed power limited
Class 2 or Class 3
sources only.
R2
HR2
HT2
T2
R1
RH1
TH1
T1
switched
unsupervised
Phone Line 2
(Supervised)
Phone Line 1
(Supervised)
unsupervised
unsupervised
unsupervised
Smoke Power: 24 V, 1.0 A max. (filtered)
Refer to Technogr a m P/ N: F0 1U010790
for compatible dev ices.
Contacts
rated at
5.0 A, 24 V
Relay 3
Relay 2
Relay 1
Earth Ground
Input Points 1-4:
(supervised) Points are intended for
connection of normally-open/
normally-closed alarm contacts.
They may also be used for compatible
two-wire s moke detectors.
All EOL resistors are 2.21 k Ω,
P/N: 25899 Bosch,UL listed.
Initiating devices are Class B, Style B
or Class A , Style D.
Two-Wire Compatibility Identifier “A”.
NC 3
COM3
NO 3
NC 2
COM2
NO2
NC 1
COM1
NO 1
SMK+
SMK-
4A+
4B+
4B4A-
3A+
3B+
3B3A-
2A+
2B+
2B2A-
1A+
1B+
1B1A-
COM
+12V
DATA
R B G Y OPTION BUS
Supervised, Class B,
Style 4, 500 mA , Max.
BATTERIES:
Black
Battery # 1
Yel low
(supervised)
All wiring except battery terminal and
primary AC power is power-limited.
Primary AC and battery wires must be
separated from other wires by at least
¼ in. (64 mm) and tied to prevent
movement.
-
)
(
+)
(
(-)
(
+)
Battery # 2
Black
White
Red
Battery # 1Battery # 2
unswitched
unsupervised
Aux. Power: 24 V, 1. 0 A max.
CLASS B
STYLE Y
(supervised)
CLASS A
STYLE Z
DX4020
(unfiltered)
EOL
Black
Red
Alarm
Silenced
Supervisory
Trouble
TEST WEEKLY
1
2
456
789
0
*
Back
Prog
History
AUX-
AUX+
A+
N
A
B+
C
B-
1
A-
A+
N
A
B+
C
B-
2
A-
BAT24V
BAT+
BOSCH
Silence
ACK
3
Reset
Drill
#
Disable
Enter
Test
NOTIFICATION APPLIANCE CIRCUIT:
+24 V while in alarm; ground while in standby.
NAC 1+
Ground while in alarm; supervisory voltage whil e in standby.
NAC 1-
NOTIFICATION APPLIANCE CIRCUIT:
+24 V while in alarm; ground while in standby.
NAC 2+
Ground while in alar m; supervisory voltage whi le in standby.
NAC 2-
BAT -
Requires two 1 2 V batteries, in series , for a combined voltage of
24 V. Charge current = 1.1 A, max.
BAT +
Use only indicating devices as listed on Technogram P/N: F01U010791.
Do not short terminals - explosion and burn haza r d.
Backup Batteries
18
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
FPD-7024 | Operation and Installation Guide | 2.0 Control Panel Terminal Connections
.
2.1 Power Supply Connections
Use wire nuts to connect the primary side of the
transformer (black and white wires) to the
unswitched 120 V, 60 Hz or (yellow and white
wires) to unswitched 240 V, 50 Hz circuit. Connect
the earth ground to the threaded ground stud on the
left side of the enclosure.
Figure 6: Connecting the Transformer to the FPD-7024 Circuit Board
AUX-
AUX+
A+
N
A
B+
C
B-
1
A-
A+
N
A
B+
C
B-
2
A-
BAT24V
BAT+
Yel lo w
Primary
White
Black
Connect the primary side of
the transformer black and
white wires to unswitched
120V, 60Hz or yellow and
white wires to 240V, 50 Hz
circuit using wire nuts.
Place a wire nut over the unused black or
yellow wire.
Power
Alarm
SupervisoryGnd Flt
213
456
789
0
Prog
Back
*
Enter
R2
HR2
HT2
T2
R1
RH1
TH1
T1
NC 3
COM3
NO 3
NC 2
COM2
NO2
NC 1
Trouble
Silenced
Drill
Acknowledge
Disable
Silence
Test
Reset
#
History
R B G Y OPTION BUS
COM1
NO 1
SMK+
SMK-
4A+
4B+
4B4A-
3A+
3B+
3B3A-
2A+
2B+
2B2A-
1A+
1B+
1B1A-
2.2 Option Bus Wiring Requirements
Use 18 AWG (1.2 mm) or larger wire to connect
option bus devices to the FACP. The total length of
wire connected to the option bus terminals must not
exceed 4,000 ft (1,219 m), regardless of the wire
gauge wire used.
Shared cable is not recommended for
option bus, addressable points bus,
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
telephone, or NAC wiring.
To comply with UL, do not share
supplementary devices with primary device
on the option bus.
Avoid shielded or twisted pair-wire except for
special applications where a reduced length of
wiring (approximately 50%) is acceptable for
tolerating a harsh electrical environment.
19
FPD-7024 | Operation and Installation Guide | 2.0 Control Panel Terminal Connections
The length of wire allowed between the control
panel and the last device on a wiring run depends
on the existing drawn on that wiring run. Reducing
the number of devices on a wiring run allows the
individual runs to be longer. Use the guidelines in
Table 10 on page 20 where devices are all of the
same type on a given wire run.
Table 10: Option Bus Wiring Guidelines
Device Model Number Wiring Run
Number
D7030 LED Annunciator 1 1000 ft (304 m) 175 mA
D7030X LED Annunciator 2 500 ft (152 m) 175 mA x 2 = 350 mA
D7030 LED Annunciator 4 250 ft (76 m) 175 mA x 4 = 700 mA
FMR-7033 Remote Keypad 1 2000 ft (608 m) 100 mA
FMR-7033 Remote Keypad 2 1000 ft (304 m) 100 mA x 2 = 200 mA
FMR-7033 Remote Keypad 4 500 ft (152 m) 100 mA x 4 = 400 mA
D7048/B Octal Driver
Module
D7035/B Octal Remote
Relay
FPP-RNAC-8A-4C 2 4000 ft (1219 m) < 50 mA each
DX4020 Network Interface
Module
1 500 ft (152 m) 330 mA
2 250 ft (76 m) 330 mA x 2 = 660 mA
1 750 ft (229 m) 280 mA
Maximum Allowed Cable Length to
Last Device (#18 Wire)
Existing Draw (for reference)
Where more than one type of device is installed on a given wiring run, add together the alarm existing drawn by
all the devices on the wiring run to determine the maximum allowed distance between the option bus terminals
on the control panel and the last device on the wire run (the device farthest from the control panel).
Add up the total alarm load for option bus devices on the wire run, and use Figure 7 to determine the maximum
allowed length for the run. For example, if the total load of option bus devices on a particular run is 400 mA, the
maximum length of the run can be up to 500 ft (152 m). No more than 4,000 ft (1,219 m) of wire can be
connected to the option bus terminals, even if the individual lengths of the runs are all within limit.
Figure 7 shows allowed lengths for18 AWG (1.2 mm). For16 AWG (1.5 mm) wire, cable lengths can be 1.5 times
longer. For14 AWG (1.8 mm) wire, cable lengths can be 2.5 times longer. The 4,000 ft (1,219 m) maximum
length of connected wire still applies.
20
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
.
Figure 7: Option Bus Cable Length vs Existing Draw
2500
2000
1500
1000
500
0
100300500
0
Current Draw (mA)
3.0 System Operation
3.1 Modes of Operation
There are four modes of system operation for the
FPD-7024: Alarm, Supervisory, Trouble, and
Normal.
3.1.1 Alarm
When an alarm occurs, the top line of the display
shows ALARM (XXX), where XXX indicates the
number of alarms. This display overrides any other
system display. The second line of the display gives
more instructions. When the group is entered by
pushing the [6/►] key, more details of the event
appear. The top line shows the number of alarms
and the point that is in alarm. The bottom line
alternates between the instructions and the
programmed description for the affected point. The
built-in sounder turns on with a steady tone, and
outputs programmed to activate with the existing
alarm condition(s) activate.
When the control panel is not scanning the inputs,
as during smoke power reset, alarm verification
delay, or on-site programming, the trouble LED
flashes to indicate this condition.
200
400
3.1.2 Supervisory
When a Supervisory condition occurs,
Supervisory (XXX), XXX indicates the number
of supervisory conditions. The second line of the
display gives more instructions. When the group is
entered by pushing the [6/►] key, more details of the
event appear. The bottom line alternates between
the instructions and the programmed description for
the affected point. The built-in sounder beeps.
Outputs programmed to activate with the existing
condition(s) then activate.
3.1.3 Trouble
When a trouble condition occurs (such as cut wiring
for a point or AC power fails), the sounder beeps
every 10 seconds. The Trouble LED lights and the
LCD shows TROUBLE (XXX). When the [6/►] key
is pressed the group is entered and more detail
appears. The system can diagnose and show a
variety of trouble conditions, including those
affecting the input points, NAC circuits, power,
battery, system grounding, and internal operations
of the fire control panel. Notify your installing
company immediately if the system trouble message
appears.
Press the [Silence] key to silence the system trouble
beep.
3.1.4 Acknowledge
When the control panel is off-normal, the control
panel’s piezo (buzzer) can be silenced without
silencing the NACs or resetting the control panel.
Press the [ACK] button on the local or remote
keypad to silence only the piezo.
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
21
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
3.1.5 Fire Silence/Reset
During a fire alarm, exit from the premises
immediately. Do not enter the premises
unless accompanied by the appropriate
emergency services' personnel, or until they
have given the OK to enter.
When it is determined that there is no fire, you can
silence the horns or bells to allow more investigation
of the devices that initiated the alarm, or you can
reset the system to return it to normal operation.
Before using the [Reset] key, determine
which smoke detector sounded the alarm
so that the monitoring company can check
that the system is operating correctly. If the
control panel is being used as an
addressable control panel, use the [History]
key to determine which address is in alarm.
If the system is configured to allow alarm silencing,
the [Silence] key turns off the horns or bells, but
does not reset the alarm status and does not return
the activated input to normal service. Detectors that
were activated stay in alarm and can be checked
(usually by observing an LED on the device) to see
which detector caused the alarm. When the
detectors causing the alarm are identified, reset the
system to return it to normal service.
The [Reset] key clears the system alarm status, and
briefly turns off power to the detectors to reset them.
This command is required after any fire alarm
affecting a point programmed for latching operation
(which is the normal configuration). This operation
is also required to reset a Class A, Style 6 multiplex
(SLC) wiring fault troubles.
The software uses a system supervisor function that
automatically supervises the system software for
proper operation. If the system fails, a CPU FAULT
message appears, and the nature of the failure can
be optionally recorded in the history buffer. To
enable history buffer recording for CPU faults,
program Output Zone D of onboard Relay 2 to
Zone 51 (unused). The history buffer message, if
enabled, shows CPUFLTxxx, where xxx is an error
code. If the display shows CPU FAULT, contact
Bosch Security Systems, Inc. Technical Support and
report the history buffer code along with a
description of the operations that caused the fault.
Unusual conditions during programming and
debugging operations can result in a CPUFLT
message in the history buffer. If, this occurs when
the control panel is in service, report it to Technical
Service.
3.1.6 Off-Normal Displays
Control panel alarms and problems are indicated by
one of the messages shown in Table 11 on the top
line of the display. Contact your installing company
if problems persist.
Table 11: Off-Normal Displays
Off-Normal Display Description
FIRE ALARM (XXX) One or more fire or waterflow points are in alarm.
SUPERVISORY (XXX) One or more supervisory conditions exist.
TROUBLE (XXX)
3.1.7 Normal
When the system operates normally, it shows
SYSTEM NORMAL on the top line of the display, the
Power LED lights steadily, and no other LEDs are lit.
The bottom line indicates the existing date
MM/DD/YY and time HH:MM. If the system is
programmed to require a PIN, the second line of the
LCD screen shows ENTER PIN.
A trouble condition exists (AC power failure, phone line trouble, and so on.).
3.2 Basic System Use
3.2.1 Function Keys
A keypad that does not require a PIN number shows
(under normal conditions) SYSTEM NORMAL on the
top line, and existing date and time on the bottom
line. On a keypad that does require a PIN number,
enter the PIN number first. This enables the function
keys.
3.2.2 Selecting Menu Items
Depending on which level in the system, (menu,
sub-menu, sub-sub-menu), you can select an item
three different ways:
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
22
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
.
1. In the main menu, TEST, HISTORY, DISABLE,
and DRILL each have an exclusive key on the
keypad. To select one of these menu items,
press the corresponding key. For example, to
3.2.6 Drill
The drill command activates all NACs and no relays.
It creates a history log entry and as an option can be
reported to the central station.
select TEST, press the [TEST] button.
2. The [PROG] and [ENTER] keys are not
exclusive, but shared with other characters. The
character sharing the corresponding key appears
in the second line following a forward slash (\).
To select one of these items, press the
corresponding key. For example, the [PROG]
key is also 0.
3. The key corresponding to a sub-menu item
might appear in the second line preceding a
dash. Press the corresponding key to select that
item. For example, press [1] to select PROG
TIMES.
3.2.7 Disable
Use the disable command to disable input points,
outputs, or the dialer. When any device is disabled,
the system shows this condition on the LCD and on
the system trouble LED. The Disable All Inputs
operation takes several seconds to perform, during
which time the system display remains fixed.
3.2.8 History
If a system without a D7039 Multiplex
Expansion Module loses all power (AC and
standby battery), all history events are
cleared.
While a menu is active, you do not need to wait for
the desired menu item to appear before making your
selection. You can select any item on the existing
menu rotation at any time.
3.2.3 After a Main Menu Item is Selected
When a main menu item is selected, the keypad
might prompt you to enter your PIN. If so, enter the
number (factory default is 9876) and press the
[#/Enter] key (or press the key labeled with the
desired command directly). The display automatically
retrieves the sub-menu display.
3.2.4 Returning to an Earlier Screen
To return to a previous screen at any time, press the
[*/Back] key. To return to the SYSTEM NORMAL
display, press the [*/Back] repeatedly until you reach
SYSTEM NORMAL. When you reach SYSTEM
NORMAL, you cannot go any farther.
3.2.5 Entering Data
When a sub-menu item asks you to enter data, enter
the data and press the [#/Enter] key. If data already
exists at a particular location, you can either accept
that data or enter new data.
When you press the [#/Enter] key to enter the data,
the display returns you to the previous sub-menu
display.
The HISTORY option is a chronological list of
system events that occurred. Press the [History] key
to HISTORY select from the Main Menu (SYSTEM NORMAL display).
On an FPD-7024 FACP with a D7039 Multiplex
Expansion Module, up to 499 History events are
supported.
On an FPD-7024 FACP without a D7039 Multiplex
Expansion Module, up to 99 History events are
supported.
After you press the [History] key, the most recent
system event appears on the top line of the LCD with
the time and date below it.
Example: (Assume you pressed the [History] key at
the Main Menu):
While the first event shows, the bottom line toggles
every four seconds between the time and date that
the event occurred.
To return to a previous screen in the history buffer,
press [2/▲].To scroll to the next event record, press
[8/▼]. The abbreviations shown in Table 12 on page
8 are used in history events.
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
23
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
Table 12: History Event Abbreviations
Abbreviation Meaning Abbreviation Meaning
ALRM Alarm OFFNORM Off Normal at Test
ARST Alarm Restore PH1 Phone Line 1
AUTOTST Auto Test PH2 Phone Line 2
BATT:LOW Battery Low RSTR Restore
BAT:RSTR Battery Restore S Supervisory
CPUFLT Internal Error SMK:FLT Smoke Power Fault
DRILL:BEG Drill Begin SYSRESET System Reset
DRILL:OVR Drill Over SYSRST System Restore
DRST Dirty Restore SYSTRB System Trouble
DRTY Dirty SYS:WDOG Automatic CPU Reset
(Watchdog)
DSBL Disable TRBL Trouble
EE2 EEPROM TRST Trouble Restore
ENBL Enable TST:BEG Test Begin
F Fire TST:OVR Test Over
MANULTST Manual Test W Waterflow
Refer to Appendix C on page 87 for additional history log ID information.
24
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
.
3.3 Keypads
3.3.1 Built-in Keypad
The keypad built into the control/communicator is an alphanumeric LCD keypad. It has a two-line by 16character display to provide information on various control panel functions. Usually, the first line shows the offnormal condition, while the second line describes specific details that might be relevant to the existing system
status. A built-in sounder annunciates keystroke entries and acts as a warning device.
Figure 8: Built in Keypad
1
Power
3
Alarm
SupervisoryGnd Flt
14
Trouble
Silenced
4
FF01U002311
213
456
6
7
789
0
Prog
Back
*
#
Enter
Drill
Disable
Test
History
Acknowledge
Silence
Reset
13
16
12
11
8
1. Green Power LED - is on when the AC power is
present, and flashes when the unit is operating from
battery power.
2. Yellow Trouble LED - lights when the system detects a
problem with wiring or internal circuitry. The Trouble
LED flashes while programming mode is active and
whenever inputs are not active, such as during smoke
power reset or alarm verification.
3. Red Alarm LED - lights when the system registers an
alarm and was not reset.
4. Yellow Silenced LED - lights when the user manually
silences an alarm or trouble condition, turns off when
the condition that was silenced is corrected.
5. [Disable] key - used to disable or re-enable inputs,
NACs or relays (outputs), and the dialer.
6. [Test] key - used to select one of seven special test
modes (refer to Section 3.4 Testing on page 26).
7. [*/Back] key - used during programming to exit from
menus or to exit from the programming mode entirely.
8. [0/Prog] key – for selecting the programming mode.
9. [#/Enter] key - to accept data when in the
programming mode.
10. [History] key - to view system events.
11. [Reset] key - briefly (programmable from 1 to 16
seconds) turns off power to the detectors to reset
them and clears any off-normal conditions.
12. [Silence] key - quiets the bell or sirens for an alarm
or trouble condition, if the system is so configured.
13. [Drill] key – used to activate the NACs manually. It
creates a history log entry and as an option reports
to the central station.
14. Yellow Supervisory LED - lights whenever the
system registers a supervisory condition.
15. Yellow GND Fault LED - lights whenever the
system detects a ground fault condition.
16. [Acknowledge] key to silence local keypad
sounders and to view off-normal conditions.
For abbreviations on the keypad and control panel, refer to Appendix A on page 85.
5
9
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
25
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
3.3.2 FMR-7033 Keypad
The FMR-7033 Keypad is an alphanumeric LCD
keypad. Up to four of these keypads can be
mounted apart from the main control panel to
provide additional locations for system status and
control. The LCD display and keys operate
identically to those of the built-in keypad on the
control panel (refer to Appendix A on page 85).
Figure 9: FMR-7033 Keypad
1
Alarm
Silenced
Supervisory
Trouble
Back
1
4
7
*
1 -LEDs
2 –Keypad Display
3 -Keys
3.4 Testing
Select any of seven special test modes using the [Test]
key on the built-in and FMR-7033 keypads.
3.4.1 Walk Test
The Walk Test allows a technician to alarm each
point manually to ensure that detectors connected to
a point send an Alarm report to the control panel.
While in this mode, the LCD shows the system test
status and the trouble sounder sounds every 10 sec.
Outputs programmed for general alarm or fire alarm
output, or outputs mapped to points using zones
activate during this test as points are alarmed and
restored:
When selecting this mode, three options are given for
activation of outputs:
SHORT ACTIVE: 1 second activation
LONG ACTIVE: 5 second activation
NO ACTIVE: outputs do not activate
BOSCH
2
TEST WEEKLY
2
5
8
0
Prog
History
3
6
#
Enter
9
As each point is alarmed, the outputs activate once (if
selected) and power is reset. As each point is
activated, alarms and restorals are logged in the
control panel’s history log. When the point returns to
standby, the outputs activate twice. The control panel
attempts to reset points ten times to restore them.
Points remaining alarmed when exiting from the walk
test mode cause an immediate alarm.
3.4.2 Communicator Test
The communicator sends a test report. While
communication is in progress, the Power LED
flashes. When the communication succeeds, a long
keypad beep sounds, the Power LED returns to
normal, and the display returns to normal.
Silence
3
ACK
Reset
Drill
Disable
Tes t
26
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
.
This test is available only if your system
sends alarms and system information to a
monitoring service, and was programmed
by the security installing company to permit
communicator tests.
Terminating the communicator test function
(with the [*/Back] key) resets the
communicator and discards all unsent
reports. When an off-normal condition
occurs during a Communicator test, the test
automatically resets, clearing all reports, so
the off-normal conditions are sent normally.
3.4.3 Call for Remote Programming
Phone Numbers 1 and 3 must be programmed, along
with Account Code 1. The control panel calls Phone
Number 3 and attempts to connect for downloading.
If the control panel is already using the phone line, it
sounds the three-beep error tone. This function
requires an access code with programming authority
(Level 1).
3.4.4 Test Battery/NAC Circuits
If a power failure occurs, your control panel has a
built-in battery that continues to power the system for
several hours. The control panel automatically
recharges the battery when power is restored. In this
test mode, the system operates the local NAC circuits
and tests the battery for two seconds. The test results
are shown at the end of the test, and are not reported
to the central station. Pressing the [*/Back] key or the
[#/Enter] key returns the display to standby mode, or
the unit times out after three minutes.
3.4.5 Answer for Remote Programming
The control panel immediately seizes the phone line
to answer a remote programming call. While
programming is underway, the Trouble LED flashes.
This also allows on-site PC downloading. If the
control panel already uses the phone line for a report
communication, it sounds the three-beep error tone.
This function requires an access code with
programming authority (Level 1).
3.4.6 Manually Activate Outputs
This test turns a selected output on and off manually.
3.4.7 Read Zone Input Levels
This test shows the status of a selected on-board
point. The loop existing through the point is shown.
Normal loops show 11 to 15 mA. Loops in alarm
show over 25 mA, and loops in trouble show less
than 6 mA.
3.4.8 Addressable Point Test (MUX Test)
This test allows activation of the special test mode for
addressable (multiplex) devices. This applies only if
the optional D7039 Addressable Point Bus Expander
module is installed.
When this test mode is selected, the system asks
which bus to test, 1 or 2. Select 1 to test points 9 to
128 and select 2 to test points 129 to 255. The system
presents 5 options:
•List Devices: Shows the point numbers of all
devices on the selected bus. Some devices (such
as a dual point module) can use two or more
points
•Show Holes: Lists locations on the bus that have
no assigned device. This can help to find
programming errors or identify an available
address for a new device.
•Show Extras: The system scans the bus to
identify devices that are present on the bus, but
are not programmed into the system. Scanning
the bus takes about 60 sec to scan the bus.
Restoring the bus after scanning also takes about
60 sec. The system cannot identify devices above
Address 128 on Bus 1, or below Address 129 on
Bus 2. If you know that a device is connected to
the system but cannot find it, ensure that it is
connected to the correct bus: 9 to 128 for Bus 1,
129 to 255 for Bus 2.
•Show Missing: Lists devices programmed into
the system but not present on the bus are listed.
Unless a device was programmed into the system
(such as using MUX EDIT), it is not considered
missing.
•Show Status: After you select a device and press
[#/Enter], this test shows detailed status
information for the selected device. Eight
conditions (not all status conditions apply to or
are supported by all devices) are shown. See the
display shown below (which updates
automatically every five seconds). For this option,
you can view the status of any MUX device
regardless of which bus you selected to test when
test mode was entered.
XxLxRxDxMxTxFxAx
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
27
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
x is either 0 or 1 depending on whether the
condition is false or true (0=false and 1=true).
The letters indicate the condition:
X: Reserved for future use.
L: Commanded relay state - this is how the output
relay should be set.
R: Actual relay state - this is how the output relay is
actually set.
D: Detector dirty - the detector is excessively
3.5 Point/Zone Mapping
The control panel supports a flexible system to map
input points to output points. The system defaults so
that all NAC outputs are activated by a fire alarm. By
programming output zones, you can create almost
any output activation scheme, such as “floor above
and floor below” activation or conditional elevator
recall.
Input points:Smoke detectors, pull stations, and so
sensitive.
M: Missing device - the device cannot be found on
Zone:A group of input points (Zones 1 to 50
the loop. Unless a device was programmed into
the system (such as using MUX EDIT), it is not
considered missing.
F: Loop fault - the loop from a contact input device
is open, or the device is faulted.
A: Loop alarm - the point is in alarm.
Pressing [*/Back] ends the display for any of these
modes.
Examples: X0L0R0D0M0T0F0A0 (relay off, not
dirty, not missing, no tamper, no fault and no alarm).
3.4.9 Sensitivity Test
Tests the mux smoke detectors to determine if they
are within their normal range of sensitivity. Press
[Test] then [9].
Inputs activate zones, and zones activate outputs.
Zones 1 to 50 are available for the installer to
program. Each input can activate one zone; however,
any number of inputs can be mapped to the same
zone.
Zones above 50 are automatically activated by inputs.
For example, any input that is configured as a
waterflow type activates Zone 61 when it is alarmed.
Any output driven by Zone 61 activates when any
waterflow type point is alarmed.
Refer to Figure 10 to show how inputs control zones
and zones control outputs.
on.
are configurable, 52 to 63 are activated
automatically).
such as bells, strobes, and relays.
28
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
.
Figure 10: Mapping, Inputs, Zones, and Outputs
Input Point 1 is assigned to Zone 1, mapped to NAC Point 1.
Input Point 2 is assigned to Zone 2, mapped to NACs 1 and 2.
Input Point 3 is assigned to Zone 2, mapped to NACs 1 and 2.
Input Point 4 is assigned to Zone 2, mapped to NACs 1 and 2.
Input Point 5 is assigned to Zone 3, mapped to NAC 2, LR 1 and RR 1.
LR:
Local relay
RR:
Remote relay
General Alarm Zone 63 drives LR 2.
Up to 64 zones can be assigned. The installer can assign Zones 1 to 50. Zones 51 to 63 are hard-coded to preassigned conditions. Refer to Table 13.
Table 13: Pre-Assigned Zones
Zone Pre-Assigned Condition
51 Reserved for future use.
52 General Fire Alarm, Waterflow (non-silenceable). Same as Zone 53, but remains active even while system is silenced.
53 General Fire Alarm (silenceable). Active when a fire alarm condition is present; does not activate for waterflow.
54 Activates for approximately 7 sec before dialing, to initiate dial tone on a ground start phone system.
55 General Supervisory (silenceable)
56 General Waterflow (silenceable)
57 Communication Trouble. Active when the dialer fails to communicate; remains active until communication through the
58 General Supervisory Alarm (non-silenceable). Active when any supervisory alarm condition is present.
59 Alarm Verification. Active while alarm verification is in progress. This starts with the first detection of an alarm to be
60 No AC. Active when AC power fails.
61 General Waterflow (Non-silenceable). Active when any waterflow alarm is present.
62 General Trouble. Active while any system trouble is present, not active in test and programming modes.
63 General Alarm, Waterflow (non-silenceable). Active while any alarm, including supervisory, is present. Remains active
digital communicator is restored.
verified and clears in two minutes, or when system is reset.
even while system is silenced.
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
29
FPD-7024 | Operation and Installation Guide | 3.0 System Operation
3.6 Personal Identification Numbers
The personal identification number (PIN) is the four
digit code users enter at the keypad to gain access to
the system. A PIN can be assigned to each User
Number. The User Number identifies each person
using the system. There are 16 possible User
Numbers (00 to 15). User codes 00 to 99 are
available with the installation of a D7039 Multiple
Expansion Module. The Authority Level assigned to
each User Number determines which functions each
user can perform.
Your system can have up to 100 different PINs, each
four digits long. There is one PIN for each User
Number. Attempting to assign the same PIN to
multiple User Numbers results in the three-beep
error tone, and the change is not made.
Table 14: PIN Authority Levels
PIN Authority Level Allowed Operations
Maximum (1) All control panel operations, including programming, and disable
Medium (2) System test modes, fire drill, reset, silence, view history
Minimum (3) Silence, view history
None (0) None
User Number 00 is designated as a Programmer’s
Code. It can be used to silence alarms, reset, disable,
and program the unit.
User Number 00 is shipped from the factory with
the sequence of 9876. Change this code to one of
your personal preference. It is automatically
assigned the highest authority. Never program PINs
with common sequences such as 1111, 1234, or
2468 because they are easily violated.
Authority levels are assigned to PINs to determine
which functions each user can perform. Table 14
describes the four authority levels.
30
Bosch Security Systems, Inc. | 9/08 | F01U008458-01
Loading...
+ 72 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.