This equipment was tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses, and can radiate radio frequency energy, and if not installed and used in accordance with
the instructions, might cause harmful interference to radio communications. There is no
guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, that can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
–Re-orient or relocate the receiving antenna.
–Increase the separation between the equipment and the receiver.
–Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
–Consult the dealer or an experienced radio or TV technician for help.
FCC Phone Connection to Users
This control panel complies with Part 68 of the FCC rules.
On the inside of the enclosure is a label that contains, among other information, the ringer
equivalence number (REN) for this equipment. You must, upon request, provide this
information to your local telephone company.
The REN is useful to determine the quantity of devices that can be connected to your
telephone line and still have all of those devices ring when your telephone number is called. In
most, but not all areas, the sum of the RENs of all devices connected to one line should not
exceed five. To ascertain the number of devices that you can connect to your line, contact
your local telephone company to determine the maximum REN for your local calling area.
This equipment can not be used on coin service provided by the telephone company. Do not
connect this control panel to party lines. If this equipment causes harm to the telephone
network, the telephone company might discontinue your service temporarily. If possible, they
will notify you in advance. But if advance notice isn’t practical, you will be notified as soon as
possible.
You will be informed of your right to file a complaint with the FCC. The telephone company
might make changes in its facilities, equipment, operations, or procedures that could affect
the proper functioning of your equipment. If they do, you will be notified in advance to give
you an opportunity to maintain uninterrupted telephone service.
If you experience trouble with this equipment, contact the manufacturer for information on
obtaining service or repairs.
The telephone company might ask that you disconnect this equipment from the network until
the problem is corrected or until you are sure that the equipment is not malfunctioning. The
manufacturer, not the user, must make the repairs to this equipment. To guard against
accidental disconnection, there is ample room to mount the telco jack inside of the control
panel cabinet.
The operation of this control panel might also be affected if events such as accidents or acts
of God cause an interruption in telephone service.
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
Fire Alarm Control PanelsNotices | en7
1.3
1.4
Industry Canada Notice
The Industry Canada label identifies certified equipment. This certification means that the
equipment meets certain telecommunications network protective, operational, and safety
requirements. Industry Canada does not guarantee the equipment will operate to the user’s
satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to
the facilities of the local telecommunications company. The equipment must also be installed
using an acceptable method of connection. The customer should be aware that compliance
with the above conditions might not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alterations made by the user to this
equipment, or equipment malfunctions, might give the telecommunications company cause to
request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the
power utility, telephone lines, and internal metallic water pipe system, if present, are
connected together. Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or electrician.
Trademarks
All hardware and software product names used in this document are likely to be registered
trademarks and must be treated accordingly.
Microsoft, Windows, and Windows NT are either registered trademarks or trademarks of
Microsoft Corporation in the United States and/or other countries.
CYCOLOY is a registered trademark of Sabic Plastic.
POLYLAC is a registered trademark of CHI MEI Industrial Corporation, LTD.
CleanMe is a trademark of GE Interlogix, Inc. in the United States and/or other countries.
The FPD‑7024 Fire Alarm Control Panel is a fully integrated hard-wire fire alarm system. It can
support four input points (expandable to 255 using D7039 Multiplex Expansion Module and
the FPC‑7034 Four-Point Expander) and 16 individual users (expandable to 100 with the
D7039). The control panel has a built-in LCD keypad. Up to four additional keypads can be
used to provide user interface with the system and programming access for the installer. The
FPD‑7024 also includes the following features:
–Built-in dual-line communicator
–Menu driven keypad programming
–Freely programmable alphanumeric/alphabetical display
–99 event history buffer
–16 user codes
–UL Listed, CSFM, MEA Approved
When the D7039 Multiplex Expansion Module is installed, these additional features are
available:
–247 additional addressable input points (255 total points)
–499 Non-volatile event history buffer
–100 user codes
For the location of the major items on the FPD‑7024 Control Board, see the following figure:
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
Fire Alarm Control PanelsOverview | en9
4 Zone input terminal strip10 NAC terminal strip
5 Option bus terminal strip11 Auxiliary power terminal strip
2.2
2.2.1
6 FPC-7034 point expander connector
pins
Components
On-board conventional points
All on-board points and points implemented with the FPC-7034 work with two- or four-wire
detectors. The system has an optional alarm verification feature.
Number of two-wire circuitsFour circuits, expandable to eight using an
FPC-7034 Expander
Type of CircuitClass B, Style B and Class A, Style D as
needed)
EOL Resistor2.21 kΩ (P/N: 25899 or F01U034504), UL
listed
Supervisory Existing8 mA to 20 mA
Required Existing for Alarm25 mA
Maximum Short Circuit Existing45 mA
Maximum Line Resistance150 Ω
Circuit Voltage Range20.4 VDC to 28.2 VDC
2.2.2
Maximum Detectors per Point20 detectors (two-wire)
Total Detector Standby Existing3 mA maximum
Response Time
Dirty Detector MonitoringImplements Bosch Security Systems, Inc.
1
See , 24
Table 2.1: Two-wire circuits
All on-board points, and points activated with the FPC‑7034 Four Point Expander, are
continuously monitored for detectors signaling a dirty condition using the Bosch Security
Systems, Inc. Chamber Check and GE Interlogix, Inc. CleanMe protocols. To prevent nuisance
reports, a two-minute delay occurs before a dirty detector is annunciated. A six-minute delay
occurs after the detector restores from the dirty condition before the control panel restores
the condition.
1
Either fast (500 ms) or programmable (from
1 second to 89 seconds)
Chamber Check and GE Interlogix, Inc.
CleanMe protocol to monitor conventional
loops for dirty detectors.
–Each point is individually supervised for proper connection to the common bus (when
over ten points are troubled, up to ten troubles are shown per bus and the balance of the
troubles is indicated by a common bus failure message).
–Response time can be set to fast, or programmed from 1 to 89 seconds.
–Input points on the SLCs are implemented with a D7042 Eight Input Remote Module.
2.2.3
2.2.4
2.2.5
2.2.6
Enclosure Housing
The standard enclosure is 18 ga., cold-rolled steel, and measures 20.75 in. x 15 in. x 4.25 in.
(52.7 cm x 38.1 cm x 10.8 cm). A keyed lock is included, and the LEDs and LCD display are
visible through the door.
Remote LCD Keypads
Maximum number of keypads: Four FMR‑7033 LCD Fire Keypads.
For wiring Requirements, see Option bus wiring requirements, 34
Remote LED Annunciators
Maximum number of annunciators: Eight D7030 eight-zone LED Annunciators.
For wiring Requirements, see Option bus wiring requirements, 34
D7032 - use with the D7030X
When a D7032 Eight-Zone LED Annunciator Expander is connected to the D7030X, eight
additional LED zones appear. This allows the D7030X/D7032 combination to show 16 LED
zones. Up to eight D7030X/D7032 combinations can be connected to the FPD‑7024 Fire Alarm
Control Panel.
Notice!
Each D7030X processes 16 zones of information. If no D7032 is attached, only the lower eight
zones are shown.
Notice!
The column labeled “shown on D7030X” in the LED assignments table below applies regard-
less if an attachment of a D7032 to any D7030X is made.
For LED assignments when up to eight D7030X/D7032 combinations are used, see the
following table:
D7030Xzones
covered
11 to 161 to 89 to 16Combination with lowest option
217 to 3217 to 2425 to 32Combination with second lowest
333 to 4833 to 4041 to 48Combination with third lowest
shown on
D7030X
shown on
D7032 (if
attached)
comments
bus address (such as Address 1)
option bus address (such as
Address 2)
option bus address (such as
Address 3)
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
Fire Alarm Control Panels
Overview | en11
D7030Xzones
covered
shown on
D7030X
shown on
D7032 (if
comments
attached)
449 to 6449 to 5657 to 64Combination with fourth lowest
option bus address (such as
Address 4)
51 to 161 to 89 to 16Fifth combination repeats first
combination
617 to 3217 to 2425 to 32Sixth combination repeats second
combination
733 to 4833 to 4041 to 48Seventh combination repeats third
combination
849 to 6449 to 5657 to 64Eighth combination repeats fourth
combination
Table 2.2: LED assignments for LED Annunciators
For the LED display for Zones 49 to 64, see the following table.
LED
ZoneDescription
149User defined
250User defined
3(reserved)
452General fire alarm monitor waterflow (non-silencable)
The communicator can report to two phone numbers or IP addresses with full single, double,
and back-up reporting. Communicates in SIA, Modem IIIa2, Contact ID, BFSK, and 3/1 and 4/2
Tone burst formats (available communication formats depend on phone or IP connection).
Notice!
The communicator must be enabled and configured to operate. The communicator and phone
line monitors are disabled in the default factory configuration.
Phone Line and Phone Number/IP Selection: To ensure the delivery of critical reports, the fire
panel has two phone lines and two phone numbers or IP addresses that can be used for
reporting. Reports can be directed to one or both of two phone numbers or IP addresses
using the Report Steering feature in the control panel programming. Note that Account
Number 1 is used with Phone Number/IP 1, and Account Number 2 is used with Phone
Number/IP 2. Except for test reports, the control panel automatically selects the phone line or
IP address to use. If the report is not successful after two attempts on Line 1, the control
panel automatically switches and uses Phone Line 2. One exception is when test reports
(manual or automatic) are sent. Test reports are sent every 4 hours to 28 days. Each time a
test report is sent, the control panel alternates phone lines. This happens even if the monitor
says the line is bad. If the user sends two manual test reports, both phone lines can be tested.
The first report uses one line, and the second uses the other line. During normal operation,
the automatic test uses a different line each day. Because the control panel automatically
selects which line to use, both phone lines must use the same dialing sequences for sending
reports. For example, a line that requires a 9 to be dialed for an outside line cannot be paired
with a line that does not require a 9.
For more information on report steering, see Report Steering, 83.
Notice!
PBX lines and ground start lines do not comply with NFPA requirements for digital communi-
cation.
While the control panel is idle, the FACP monitors the primary and alternate telephone lines by
monitoring the line for trouble. The FACP monitors each line every 12 seconds. When a trouble
still exists after three samples (36 seconds), the FACP sends a trouble report and activates
the yellow trouble LED and trouble relay.
Danger!
If the central station receives the automatic test report only every other day, this indicates
that one phone line at the protected premises is inoperative.
Correct this condition immediately, because other critical reports can be delayed when the
communicator is trying to send the test signal through the inoperative phone line (once each
48 hours).
Supplemental Reporting: While two independent phone lines are required for UL864 Central
Station service, the FACP can be configured with one phone line if the control panel is used
only for supplemental reporting on a local, remote station or auxiliary system.
To install the control panel with only one phone line, connect a jumper from T1 to T2 and a
jumper from R1 to R2. These jumper connections are shown in the following figure:
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
i
Fire Alarm Control PanelsOverview | en13
Figure 2.2: Supplemental Reporting
1 Jumper from R1 to R23 House phone
2 Jumper from T1 to T24 TELCO line
2.2.8
2.2.9
2.2.10
Users
The system allows up to 16 individual users, or up to 100 users when the D7039 is installed. A
personal identification number (PIN, the four-digit code entered at the keypads) and an
authority level to determine which functions can be performed can be assigned to each user.
For PINs, see Personal identification numbers (PINs), 47.
Lightning protection
Notice!
This system is intended for installation entirely within one building.
Metal-oxide varistors (MOVs) and spark gaps provide protection from lightning surges and
static discharges.
Battery backup calculation
To calculate the standby battery capacity required by NFPA when using the FPD‑7024, see the
two following tables:
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
i
Fire Alarm Control PanelsOverview | en15
DeviceQuantity Standby
existing/device
D7053 MUX I/ O
0.70 mA0.70 mA
Total
standby
Alarm existing/
device
Total alarm
Module Fire
Smoke Detectors
Bells, Horns, and
so on
Other Sensors
Other
Grand Total
Standby Existing
1
The 24 VDC existing requirements for the D7030X, FMR-7033 and D7035 are shown at 75%
Grand Total
Alarm Existing
of the 12 VDC level shown on the specification sheets for these models. The FPD-7024
regulates 24 VDC power from the battery to 12 VDC for these accessories.
2
Add 30 mA for each relay activated
Table 2.4: Standby battery capacity calculations
The units shown in the following table are Amp hours (Ah), and the calculations include a 20%
derating factor.
Grand Total Standby Existing (in amps)
Total Hours of Standby Required
CS
HS
(usually 24 or 60):
Total Standby Capacity (multiply CS x HS)TS= CS x HS
Grand Total Alarm Existing (in amps)CA
Total Hours of Alarm Time Required
HA
(usually 0.083 o 0.25):
Total Standby Capacity (multiply CA x HA)TA= CA x HA
Total Capacity Required (add TA + TS):TC = TA + TS
Required Capacity with 20% Derating
C = TC x 1.2
(TC x 1.2)
Table 2.5: Required battery size calculation
Notice!
The required battery size to support the system can be calculated using the tables for Stand-
by load battery size, 16 and Alarm load battery size, 16.
Use the following procedure to determine the battery requirements for your system:
–Estimate the size of the battery required to support the standby load using the following
table:
Standby load battery
size chart
Grand Total Standby
Existing
100 to 200 mA5.811.514.4
201 to 300 mA8.617.321.6
301 to 400 mA11.523.028.8
401 to 500 mA14.428.836.0
501 to 600 mA17.334.6X
601 to 700 mA20.2XX
701 to 800 mA23.0XX
801 to 900 mA25.9XX
901 to 1000 mA28.8XX
Capacityr required
for 24 hours
Capacity required for
48 hours
Capacity required for
60 hours
1001 to 1100 mA31.7XX
Table 2.6: Standby load battery size (Ah)
–Estimate the size of the battery required to support the alarm load using the following
table:
Alarm load
battery size
chart
Grand Total
Capacity
required for
5 minutes
Capacity
required for
10 minutes
Capacity
required for
15 minutes
Capacity
required for
30 minutes
Capacity
required for
45 minutes
Alarm Existing
250 to
0.10.10.20.30.5
500 mA
501 to
0.10.20.30.60.9
999 mA
1.0 to 1.5 A0.20.30.50.91.4
1.6 to 2.0 A0.20.40.61.21.8
2.1 to 2.5 A0.30.50.81.52.3
2.6 to 3.0 A0.30.60.91.82.7
3.1 to 3.5 A0.40.71.12.13.2
3.6 to 4.0 A0.40.81.22.43.6
Table 2.7: Alarm load battery size (Ah)
–Add the results together for the total battery size.
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
Fire Alarm Control PanelsOverview | en17
–Select the next larger standard battery for the system.
If the results show a requirement for a battery over 40 Ah, reduce the existing load or add an
external regulated fire protective signaling power supply.
2.2.12
Compatible devices
DeviceFunction
D7030 Eight Point LED
Annunciator
D7030X Eight Point LED
Annunciator
D7030X‑S2 Eight Point LED
Annunciator
D7030X‑S8 Eight Point LED
Annunciator
D7032 Eight Point LED
Annunciator Expander
FMR‑7033 Alphanumeric LCD
Keypad
Identifies the location of a fire alarm for up to eight zones
allowed per system.
Identifies the location of a fire alarm for up to eight zones
allowed per system.
An eight zone LED annunciator, of which two zones are
reserved for supervisory functions. It has Power and
Trouble LEDs plus eight zone LEDs that can be labeled
individually.
An eight-zone LED annunciator, of which all eight zones are
reserved for supervisory functions. It has Power and
Trouble LEDs plus eight-zone LEDs that can be labeled
individually.
Attaches to a D7030X and identifies the location of a fire
alarm for eight additional zones.
The FMR‑7033 LCD Keypad combines remote annunciator
and controller functions for the FPD‑7024. Up to four
keypads can be connected.
FPC‑7034 Four Point ExpanderAllows the FPD‑7024 Control Panel to support four
additional loops. The FPC‑7034 plugs into the control panel
and provides four Class B, Style 4 loops that are identical
in characteristics to the loops on the control panel. One
FPC‑7034 is allowed per system.
D7035/B Octal Relay ModuleProvides eight Form C relay outputs for addition to the
system. The outputs are programmable and can be
activated by system events. Each output operates
independently of the other seven outputs for complete
flexibility. The D7035 connects to the option bus; up to
two are allowed per system. The D7035B comes installed
on a mounting skirt.
For required enclosure modification, see also the D7035
Installation Guide.
FMR‑7036 Fire Annunciator
Keypad
FPP‑RNAC‑8A‑4C Remote NAC
Power Supply
Establishes the location of a fire alarm.
Adds four NFPA 72 Class B, Style Y Notification Appliance
Circuits through the option bus and is supervised by the
control panel. The FPP‑RNAC‑8A‑4C connects to the option
bus of the FPD‑7024 control panel and up to four are
allowed per system.
Provides either 2 two-wire (Class B, Style 4) multiplex
buses or 1 four-wire (Class A, Style 6) multiplex bus. In
Class A mode, up to 120 addressable points can be added.
In Class B Mode, up to 247 addressable points can be
added. The D7039 connects directly to the control panel.
One is allowed per system.
D7042/B Eight‑Input Remote
Module
Provides eight Class B, Style 4 input points. Connect up to
15 modules to MUX Bus A, and 15 on MUX Bus B. The
D7042 is powered by 12 VDC supplied by the option bus
power terminals, in addition to the two‑wire data
connection. The D7042 can not be used on a signal line
circuit (SLC) configured for Class A, Style 6 operation.
D7048/B Octal Driver ModuleProvides eight open‑collector transistor outputs for
addition to the FPD‑7024 Fire Alarm Control panels. It
connects to the control panels through the option bus.
FMM-7045 MUX Pull StationUL Listed fire alarm initiating device.
D7044 MUX Single Input
Module
Connects a normally‑open contact device to the multiplex
bus of the FPD‑7024 with a supervised local loop. The
D7044 draws operating power from the FPD‑7024.
D7044M MUX Mini Contact
Module
Connects a contact device to the multiplex bus of the
FPD‑7024 with a supervised input loop. The D7044 draws
operating power from the FPD‑7024.
D7052 MUX Dual Input FireConnects to the multiplex bus of the FPD‑ 7024 and
provides two supervised input zones for connecting
conventional normally-open inputs. The D7052 draws
operating power from the FPD‑7024.
D7053 MUX I/O Module FireConnects to the multiplex bus of the FPD‑7024 and
implements a supervised local loop, and a Form C relay
output. Up to 20 modules can be connected to each MUX
bus. The D7053 draws operating power from the
FPD‑7024.
D7050/TH MUX Smoke Detector The D7050/TH is a photo-electric smoke detector with a
heat option. It connects to the multiplex bus of the
FPD‑7024. The D7050 draws operating power from the
FPD‑7024.
DX4020 / B420 modelsThe Conettix DX4020 and B420 models are communication
devices that manages secure, two-way IP communications
over Ethernet networks.
ITS‑DX4020‑GThe ITS-DX4020-G enables two-way IP or dialed
communications over a commercial GPRS/GSM network.
Typical applications are event reporting to a central
monitoring station and remote access to Bosch control
panels.
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
Fire Alarm Control PanelsOverview | en19
Table 2.8: Compatible devices
Install D7042 modules only at addresses:
917253341495765
73818997105113121129
137145153161169177185193
201209217225233241
Do not install D7052 and D7053 modules at these addresses:
1624324048566472
808896104112120128136
144152160168176184192200
208216224232240248255
Table 2.9: Address restrictions for the D7042, D7052, and D7053
2.3
Parts List
The FPD‑7024 comes with:
–One FPD-7024 Control/Communicator in static-resistant bag
–One enclosure with transformer
–One hardware pack containing the hardware necessary for installing the control panel in
the enclosure
–One enclosure lock, washer, and keys
–Six end-of-line (EOL) resistors
No fire detection device or system is 100% foolproof.
This fire alarm system can provide early warning of a developing fire. Such a system, however,
does not ensure protection against property damage or loss of life resulting from a fire. Any
fire alarm system can fail to warn for any number of reasons (such as smoke not reaching a
detector that is behind a closed door).
Notice!
This system must be regularly tested (when installed, when modified, and at least annually
thereafter) to ensure continued performance.
When considering detectors for residential applications, refer to NFPA Standard 72, The
National Fire Alarm Code. This standard is available at a nominal cost from: The National Fire
Protection Association, Batterymarch Park, Quincy, MA 02269.
Smoke detector layout
General considerations
Proper location of detection devices is one of the most critical factors in a fire alarm system.
Smoke detectors should not be installed in dead air spaces or close to ventilating or air
conditioning outlets because smoke can be circulated away from the detector. Locations near
air inlets are favored.
Avoid areas subject to normal smoke concentrations such as kitchens, garages, or near
fireplaces.
Do not install smoke detectors where normal area temperatures are above +100°F (+38°C) or
below +32°F (0°C).
Avoid areas of high humidity and dust concentrations.
Place the edge of ceiling mounted detectors no closer than 4 in. (10 cm) from any wall.
Place the top edge of wall-mounted detectors between 4 in. and 12 in. (10 cm and 30 cm)
from the ceiling.
For exact mounting information, refer to the instructions provided with the smoke detectors.
3.1.2
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
Family residences
Providing a Fire Warning System: Most fire deaths occur in the home, especially during
sleeping hours. The minimum level of protection requires smoke detectors to be installed
outside of each separate sleeping area and on each additional story of the dwelling.
Notice!
For added early warning protection, install detectors in all separate areas including the base-
ment, bedrooms, dining room, utility room, furnace room, and hallways.
For residential smoke detector locations, see the following figure:
Fire Alarm Control PanelsFire Safety | en21
Figure 3.1: Smoke detector locations in residential settings
1 Bedroom5 Basement
2 Hall6 Recreation room
3 Living room7 Kitchen
4 Dining room* Smoke detector
3.2
Having and practicing an escape plan
A fire warning can be wasted unless the personnel planned in advance for a rapid and safe exit
from the building.
Draw a floor plan of the entire building showing two exits from each sleeping area and two
from the building. Since stairwells and hallways can be blocked during a fire, provide exits
from sleeping area windows. Make copies of the plan and practice it with all personnel.
Arrange a meeting place outside and away from the building. Once out of the building, all
occupants should immediately go to the pre-selected location to be accounted for.
Provide a barricade between personnel and fire, smoke, and toxic gases (such as closing all
sleeping area doors before retiring).
Instruct children on opening their bedroom windows and exiting safely from the building. If
exiting is not possible, teach them to stay at the open window and shout for help until it
arrives.
If a fire alarm occurs after retiring, wake the children by shouting to them from behind your
closed door. Tell them to keep their bedroom doors closed.
If the top of your bedroom door is uncomfortably hot, do not open it. There is most likely fire,
intolerable heat, or smoke on the other side. Shout to all family members to keep their
bedroom doors closed and to exit the building by alternate routes.
If the top of the door is not uncomfortably hot, brace the bottom of the door with your foot,
and the top with one hand, then open the door about one inch. Be prepared to slam the door
shut if there is any pressure against the door or if any hot air rushes in.
If there is no evidence of excessive heat or pressure, leave the room and close the door
behind you. Shout appropriate instructions to all family members and immediately leave the
building by the planned routes. If heavy smoke is present, drop to your hands and knees, or
crawl to remain below the smoke level.
The FPD‑7024 is UL Listed for the following:
–Commercial Fire Alarm (UL Standard UL864)
–Type Service: Auxiliary, Local, Central Station, and Remote Station
–Type Initiating: Automatic, Manual, Sprinkler Supervisory, and Waterflow
Install the control panel according to NFPA 72 for Commercial Fire installations.
Installation considerations
Failure to install and program the control panel according to the requirements in this section
voids the listing mark of Underwriters Laboratories.
–The standby battery capacity is 40 Ah at 24 VDC.
–The total nominal existing must not exceed 1.25 A in standby or 4 A when in alarm.
–The control panel must be mounted indoors and within the protected area.
–Grounding must be according to article 250 of the NEC (NFPA 70).
–Points must be connected to UL Listed, compatible devices.
–The ground wire provided with the enclosure must be connected between the door and
the enclosure using the supplied nuts.
–Do not program the ground start feature.
–Select Phone Monitoring if the digital alarm communicator transmitter (DACT) feature is
used.
4.1.3
UL requirements
Notice!
The system must be tested after installation and after any re-programming, including pro-
gramming performed by downloading.
When used in UL Listed installations, the control panel must conform to certain programming
requirements. For a list of the required program entries specific UL Listed installations, see
the Programming features for UL864 table, 49.
Commercial Fire Alarm (Central Station [DACT] and Local)
Required Accessories
–At least one Bosch Security Systems, Inc. Model F220‑P Smoke Detector with an F220
Family Base; or another UL Listed compatible smoke detector.
–At least one Horn Strobe or Bell (provides 85 dB for UL985 and NFPA 72 requirements;
other UL Listed compatible devices listed for regulated 24 V can be used) is required for
this application and must be installed inside the protected area.
–Four-wire detectors must be used with UL Listed power supervision devices. A
compatible UL Listed four-wire detector is the Bosch Security Systems, Inc. F220‑P in an
F220‑B6 Family Base. A compatible UL Listed relay is the Bosch Security Systems, Inc.
D275.
–All points must be used with the resistor provided.
Report Programming
–Program non-supervisory and supervisory reports for those points used.
–Program trouble reports.
–Set AC Failure Report Delay for a delay of 1 hour to 3 hours.
–Set automatic test report frequency to occur at least every 24 hours.
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
Fire Alarm Control Panels
Installation | en23
Timer Programming
–Program Auto Silence Time for not less than five minutes, or to “0” to disable auto-silence
operation.
Point Programming
–For fire points: open = trouble, latching.
Alarm Output Programming
–Program notification appliance circuits to activate from the appropriate input points.
Communications Programming
–If used for Central Station Service, select a communication format compatible with the
central station. Enable monitoring of both phone lines.
UL Listed Accessory Devices
D132B Multi-use Reversing Relay Module
The D132B is a multi-purpose, fully configurable, smoke power-reversing module for activating
detectors with local annunciation. The D132B operates both two-wire and four-wire circuits
and also works with Class A or Class B initiating circuits. An alarm latch connection is
provided to allow an initiating loop to be held in alarm after the detector loop power is
reversed to activate any sounders. The D132B does not affect compatibility between the FACP
and detectors, or the FACP and Notification Appliance Circuits (NACs).
See also the D132B Installation Guide for detailed installation instructions for the D132B
module. One of the installation options shown in the D132B Installation Guide is also shown in
the following figure:
Figure 4.1: Wiring the D132B smoke power reversing module
1 Power limited and supervised7 12/24 VDC
2 Optional alarm latch8 24 V reversing detectors
3 Loop9 2.2 kΩ EOL (power limited and
supervised)
4 Class A10 Not used
5 Latch11 24 V NACs
6 NAC
D185 Reverse Polarity Module
The D185 Reverse Polarity Module is a UL Listed module that connects the control panel with
either a single set or a pair of leased telephone company (TELCO) lines in NFPA 72 remote
station applications. It relays system alarm status information from the control panel to a
monitoring station. The D185 operates with either 12 VDC or 24 VDC supply.
For typical wiring of the D185 module, see the following figure:
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
Fire Alarm Control PanelsInstallation | en25
Figure 4.2: Wiring the D185
The module can signal alarm, trouble, and supervisory conditions. The Wiring the D185 figure,
24 shows the module being used to signal alarm and trouble conditions only. With a third relay
(available from the eight-relay expansion module) and an additional leased line, supervisory
conditions can also be signaled.
In the example in the Wiring the D185 figure, Relay 1 must be programmed to operate on
Alarm (Zone 63) and Relay 2 must be programmed to operate on Trouble (Zone 62). Program
Input 4 to operate as a Supervisory point. Any alarm causes the voltage to the monitoring
station to be interrupted. Placing the D185 in test mode causes a SUPERVISORY TROUBLE.
See also the D185 Installation Manual.
4.2
Installing the enclosure
To install the enclosure, follow these instructions:
1.Using the enclosure as a template, mark the top mounting holes on the mounting surface.
2.Start the mounting screws (not supplied) for these two holes.
3.Slide the enclosure onto these screws so that the screws rest on the thinner section of
5.Install and tighten the remaining two screws in the bottom mounting holes.
6.Knock out the desired wire entrances on the enclosure.
For mounting hole locations, see the following figure:
Figure 4.3: Enclosure iInstallation
1 Control panel location5 Transformer
2 Mounting holes6 Stud
3 Retainer holes for standoffs7 Ground wire
4 Retainer holes for support posts
Notice!
If using the knockouts located at the bottom of the enclosure, install batteries in a separate
enclosure.
4.3
Installing the FPD‑7024
Danger!
The control circuit board in the FPD-7024 is static sensitive.
To avoid damage to sensitive components, touch ground before handling the control board.
This discharges any static electricity in your body. For example, run the ground wire to the en-
closure before handling the control circuit board. Continue touching the enclosure while in-
stalling the control board.
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
!
Fire Alarm Control PanelsInstallation | en27
Warning!
Before the circuit board is installed, connect the supplied ground wires between the door and
the enclosure and from the transformer to the enclosure using the supplied nuts. Both
grounds connect to the stud in the enclosure to the left of the circuit board.
For installation illustrations, see the figures for Enclosue installation, 26 and for Standoff and
support post installation, 27.
1.Insert the three support posts in the enclosure’s retainer holes.
2.Press the 1/8 in. nylon standoffs (P/N: F01U034705) into the retainer holes.
3.Slide the top of the control panel onto the retainer tabs (the slots under the top of the
frame). When the control panel is in the retainer tabs, it rests on the posts.
4.Secure the bottom of the circuit board by inserting and tightening the screws at the two
bottom corners through the support posts and the retainer holes.
For installing standoffs and support posts, see the following figure:
Figure 4.4: Standoff and support post installation
1 1/8 in. nylon standoff4 Corner of circuit board
2 Retainer holes5 Support post
3 Support post assembly6 Retainer hole in enclosure
4.4
Installing optional equipment
Two expansion options connect directly to the control panel, and are automatically detected
and supervised when the control panel is powered:
–FPC-7034 Four Point Expander
–D7039 Multiplex Expansion Module
When the control panel is powered after installing one of these options, the control panel
displays one of the following windows:
4Z EXP DETECTED
PRESS BACK KEY
MUX DETECTED
PRESS BACK KEY
Press the [*/BACK] key to confirm the installation of the device and automatically set it up for
supervision.
If the [*/BACK] key is not pressed during the power-up time-out period, the control panel
resumes operation using the last confirmed status of the affected expander and displays an
installation error condition.
Warning!
Expansion devices such as point expanders and multiplex expanders are disabled if they are
removed from the control panel configuration after installation. You cannot disable supervi-
sion of these devices when they are installed.
For additional information, see the installation instructions for the specific expanders.
Notice!
EEPROM fault at first installation
When the D7039 Multiplex Expansion Module is first installed, the system displays an EE-
PROM fault. Execute the default procedure to synchronize the EEPROM on the expansion
module to the EEPROM in the control panel. Remove power to the control panel, then reapply
power and re-install option bus devices after the default procedure.
Notice!
Loss of programming
Replacing a D7039 Multiplex Expansion Module causes the loss of programming of expansion
points and PINs. Reprogram all multiplex point and PINs if you replace the D7039.
When the D7039 is first installed, or anytime the control panel is powered with a D7039 that
has no points programmed, the system automatically starts the multiplex auto-programming
process:
AUTO PROGRAM?
_______:YES(1) NO(0)
Pressing the [1] key starts auto-programming, and pressing [0/Prog] allows the control panel
to continue normal startup. The menu automatically closes with NO selected if no key is
pressed after several minutes.
For detailed instructions on the auto-programming mode, see Auto Program, 93.
2012.08 | 04 | F01U008458Installation and Operation ManualBosch Security System, Inc.
!
i
Fire Alarm Control PanelsConnection | en29
5
5.1
Connection
FACP terminal connection
Danger!
Incorrect connections may result in damage to the unit and personal injury.
Warning!
Before servicing this equipment, remove all power including the transformer, battery and
phone lines.
Notice!
Shared cable is not recommended for option bus, telephone or NAC wiring.