Bosch FPD-7024 User Manual 2

Fire Alarm Control Panels
FPD-7024
en Installation and Operation Manual
Fire Alarm Control Panels Table of Contents | en 3

Table of contents

1
2
2.1 System overview 8
2.2.2 Off-board addressable points (with D7039 Multiplex Expansion Module) 9
2.2.4 Remote LCD Keypads 10
2.2.5 Remote LED Annunciators 10
2.2.6 D7032 - use with the D7030X 10
2.2.7 Communicator 12
2.2.8 Users 13
2.2.9 Lightning protection 13
2.2.10 Battery backup calculation 13
2.2.11 Required batteries for existing load 16
2.2.12 Compatible devices 17
2.3 Parts List 19
3
3.1 Smoke detector layout 20
3.1.1 General considerations 20
3.1.2 Family residences 20
3.2 Having and practicing an escape plan 21
4
4.1 Installation guide for UL Listed systems 22
4.1.1 FPD‑7024 UL Listings 22
4.1.2 Installation considerations 22
4.1.3 UL requirements 22
4.2 Installing the enclosure 25
4.3 Installing the FPD‑7024 26
4.4 Installing optional equipment 27
5
5.1 FACP terminal connection 29
5.2 Power supply connection 33
5.3 Option bus wiring requirements 34
6
6.1 Modes of Operation 36
6.1.1 Normal 36
6.1.2 Off-normal Displays 36
6.1.3 Acknowledge 36
6.1.4 Alarm 36
6.1.5 Supervisory 36
6.1.6 Trouble 37
6.1.7 Fire Silence/Reset 37
Notices 6
Overview 8
Fire Safety 20
Installation 22
Connection 29
System Operation 36
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
4 en | Table of Contents Fire Alarm Control Panels
6.2.1 Function keys 38
6.2.2 Selecting menu items 38
6.2.3 After a Main Menu item is selected 38
6.2.5 Entering data 38
6.2.7 Disable 38
6.2.9 Remote Programming 40
6.3 Keypads 40
6.3.1 Built-in keypad 40
6.3.2 FMR-7033 keypad 42
6.4 Testing 43
6.4.1 Walk test 43
6.4.2 Communicator test 43
6.4.3 Battery/NAC circuits test 44
6.4.4 Activate ouputs test 44
6.4.5 Zone input level test 44
6.4.6 Addressable point test (MUX test) 44
6.4.7 Sensitivity test 45
6.5 Point/Zone Mapping 45
6.6 Personal Identification Numbers (PINs) 47
6.7 Communicator Operation 47
7
Programming 49
7.1 Programming features 49
7.2 Point programming 50
7.3 Alpha programming 51
7.4 Format programming 53
7.5 Program menu tree 55
7.6 Shortcuts 56
7.7 Remote programming 57
8
Control Panel Programming 59
8.1 PROG TIME 59
8.1.1 Program time 59
8.1.2 Automatic test 59
8.1.3 Daylight saving time 60
8.2 SECURITY 60
8.2.1 Personal Identification Numbers (PINs) 61
8.2.2 Authority 61
8.3 PROG SYSTEM 62
8.3.1 Program timers 62
8.3.2 AC line synch 64
8.3.3 Option bus 64
8.3.4 PIN required 65
8.3.5 NAC silence mode 66
8.3.6 Remote programming 67
8.4 PROG INPUTS 67
8.4.1 Point number 67
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Table of Contents | en 5
8.5.1 Programming NACs 73
8.5.2 Programming relays 76
8.6.5 Communication Tries 85
8.6.6 Machine Bypass 85
8.6.7 ALT. COMM 85
8.7 PROG FORMATS 85
8.7.1 4/2 Zone Report 86
8.7.2 4/2 Report Codes 87
8.7.3 BFSK Report Codes 88
8.8 HISTORY DEFAULTS 88
8.8.1 Clear History 88
8.8.2 Default EE 89
8.8.3 Alternate 4/2 Codes 89
8.9 Program MUX 89
8.9.1 MUX Edit 90
8.9.2 MUX Program 90
8.9.3 MUX Bus Type 92
8.9.4 AUTO PROGRAM 93
8.9.5 Removing MUX Devices 96
9
10
Specifications 98
Appendices 99
10.1 Appendix A: Abbreviations on Control Panel Display 99
10.2 Appendix B: Control Panel Display Descriptions 100
10.3 Appendix C: Reporting Summary for Fire Communicator 102
10.4 Appendix D: Programming Defaults List 110
10.5 Appendix E: Phone Monitor Troubleshooting 118
10.5.1 COMM FLT/DATA LOST 118
10.5.2 Trouble Phone 119
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
6 en | Notices Fire Alarm Control Panels
1
1.1
1.2

Notices

FCC Compliance Notice

This equipment was tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instructions, might cause harmful interference to radio communications. There is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, that can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Re-orient or relocate the receiving antenna. – Increase the separation between the equipment and the receiver. – Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
Consult the dealer or an experienced radio or TV technician for help.

FCC Phone Connection to Users

This control panel complies with Part 68 of the FCC rules. On the inside of the enclosure is a label that contains, among other information, the ringer equivalence number (REN) for this equipment. You must, upon request, provide this information to your local telephone company. The REN is useful to determine the quantity of devices that can be connected to your telephone line and still have all of those devices ring when your telephone number is called. In most, but not all areas, the sum of the RENs of all devices connected to one line should not exceed five. To ascertain the number of devices that you can connect to your line, contact your local telephone company to determine the maximum REN for your local calling area. This equipment can not be used on coin service provided by the telephone company. Do not connect this control panel to party lines. If this equipment causes harm to the telephone network, the telephone company might discontinue your service temporarily. If possible, they will notify you in advance. But if advance notice isn’t practical, you will be notified as soon as possible. You will be informed of your right to file a complaint with the FCC. The telephone company might make changes in its facilities, equipment, operations, or procedures that could affect the proper functioning of your equipment. If they do, you will be notified in advance to give you an opportunity to maintain uninterrupted telephone service. If you experience trouble with this equipment, contact the manufacturer for information on obtaining service or repairs. The telephone company might ask that you disconnect this equipment from the network until the problem is corrected or until you are sure that the equipment is not malfunctioning. The manufacturer, not the user, must make the repairs to this equipment. To guard against accidental disconnection, there is ample room to mount the telco jack inside of the control panel cabinet. The operation of this control panel might also be affected if events such as accidents or acts of God cause an interruption in telephone service.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Notices | en 7
1.3
1.4

Industry Canada Notice

The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational, and safety requirements. Industry Canada does not guarantee the equipment will operate to the user’s satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions might not prevent degradation of service in some situations. Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, might give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected together. Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician.

Trademarks

All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Microsoft, Windows, and Windows NT are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
CYCOLOY is a registered trademark of Sabic Plastic.
POLYLAC is a registered trademark of CHI MEI Industrial Corporation, LTD.
CleanMe is a trademark of GE Interlogix, Inc. in the United States and/or other countries.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
8 en | Overview Fire Alarm Control Panels
2
2.1

Overview

System overview

The FPD‑7024 Fire Alarm Control Panel is a fully integrated hard-wire fire alarm system. It can support four input points (expandable to 255 using D7039 Multiplex Expansion Module and the FPC‑7034 Four-Point Expander) and 16 individual users (expandable to 100 with the D7039). The control panel has a built-in LCD keypad. Up to four additional keypads can be used to provide user interface with the system and programming access for the installer. The FPD‑7024 also includes the following features: – Built-in dual-line communicator – Menu driven keypad programming – Freely programmable alphanumeric/alphabetical display – 99 event history buffer – 16 user codes – UL Listed, CSFM, MEA Approved When the D7039 Multiplex Expansion Module is installed, these additional features are available: – 247 additional addressable input points (255 total points) – 499 Non-volatile event history buffer – 100 user codes For the location of the major items on the FPD‑7024 Control Board, see the following figure:
Figure 2.1: FPD-7024 ControlBoard
1 TELCO terminal strip 7 Keypad
2 Relay terminal strip 8 D7039 MUX expansion module
connector pins
3 Smoke power terminal strip 9 LCD display
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Overview | en 9
4 Zone input terminal strip 10 NAC terminal strip
5 Option bus terminal strip 11 Auxiliary power terminal strip
2.2
2.2.1
6 FPC-7034 point expander connector
pins

Components

On-board conventional points

All on-board points and points implemented with the FPC-7034 work with two- or four-wire detectors. The system has an optional alarm verification feature.
Number of two-wire circuits Four circuits, expandable to eight using an
FPC-7034 Expander
Type of Circuit Class B, Style B and Class A, Style D as
needed)
EOL Resistor 2.21 kΩ (P/N: 25899 or F01U034504), UL
listed
Supervisory Existing 8 mA to 20 mA
Required Existing for Alarm 25 mA
Maximum Short Circuit Existing 45 mA
Maximum Line Resistance 150 Ω
Circuit Voltage Range 20.4 VDC to 28.2 VDC
2.2.2
Maximum Detectors per Point 20 detectors (two-wire)
Total Detector Standby Existing 3 mA maximum
Response Time
Dirty Detector Monitoring Implements Bosch Security Systems, Inc.
1
See , 24
Table 2.1: Two-wire circuits
All on-board points, and points activated with the FPC‑7034 Four Point Expander, are continuously monitored for detectors signaling a dirty condition using the Bosch Security Systems, Inc. Chamber Check and GE Interlogix, Inc. CleanMe protocols. To prevent nuisance reports, a two-minute delay occurs before a dirty detector is annunciated. A six-minute delay occurs after the detector restores from the dirty condition before the control panel restores the condition.
1
Either fast (500 ms) or programmable (from 1 second to 89 seconds)
Chamber Check and GE Interlogix, Inc. CleanMe protocol to monitor conventional loops for dirty detectors.

Off-board addressable points (with D7039 Multiplex Expansion Module)

The D7039 Multiplex Expansion Module adds: – Two Class B, Style 4 or one Class A, Style 6 Signaling Line Circuits (SLCs)
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
i
i
10 en | Overview Fire Alarm Control Panels
Each point is individually supervised for proper connection to the common bus (when
over ten points are troubled, up to ten troubles are shown per bus and the balance of the
troubles is indicated by a common bus failure message). – Response time can be set to fast, or programmed from 1 to 89 seconds. – Input points on the SLCs are implemented with a D7042 Eight Input Remote Module.
2.2.3
2.2.4
2.2.5
2.2.6

Enclosure Housing

The standard enclosure is 18 ga., cold-rolled steel, and measures 20.75 in. x 15 in. x 4.25 in. (52.7 cm x 38.1 cm x 10.8 cm). A keyed lock is included, and the LEDs and LCD display are visible through the door.

Remote LCD Keypads

Maximum number of keypads: Four FMR‑7033 LCD Fire Keypads. For wiring Requirements, see Option bus wiring requirements, 34

Remote LED Annunciators

Maximum number of annunciators: Eight D7030 eight-zone LED Annunciators. For wiring Requirements, see Option bus wiring requirements, 34

D7032 - use with the D7030X

When a D7032 Eight-Zone LED Annunciator Expander is connected to the D7030X, eight additional LED zones appear. This allows the D7030X/D7032 combination to show 16 LED zones. Up to eight D7030X/D7032 combinations can be connected to the FPD‑7024 Fire Alarm Control Panel.
Notice!
Each D7030X processes 16 zones of information. If no D7032 is attached, only the lower eight
zones are shown.
Notice!
The column labeled “shown on D7030X” in the LED assignments table below applies regard-
less if an attachment of a D7032 to any D7030X is made.
For LED assignments when up to eight D7030X/D7032 combinations are used, see the following table:
D7030X zones
covered
1 1 to 16 1 to 8 9 to 16 Combination with lowest option
2 17 to 32 17 to 24 25 to 32 Combination with second lowest
3 33 to 48 33 to 40 41 to 48 Combination with third lowest
shown on D7030X
shown on D7032 (if attached)
comments
bus address (such as Address 1)
option bus address (such as Address 2)
option bus address (such as Address 3)
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels
Overview | en 11
D7030X zones
covered
shown on D7030X
shown on D7032 (if
comments
attached)
4 49 to 64 49 to 56 57 to 64 Combination with fourth lowest
option bus address (such as Address 4)
5 1 to 16 1 to 8 9 to 16 Fifth combination repeats first
combination
6 17 to 32 17 to 24 25 to 32 Sixth combination repeats second
combination
7 33 to 48 33 to 40 41 to 48 Seventh combination repeats third
combination
8 49 to 64 49 to 56 57 to 64 Eighth combination repeats fourth
combination
Table 2.2: LED assignments for LED Annunciators
For the LED display for Zones 49 to 64, see the following table.
LED
Zone Description
1 49 User defined
2 50 User defined
3 (reserved)
4 52 General fire alarm monitor waterflow (non-silencable)
5 53 General fire alarm monitor (silencable)
6 (reserved)
7 55 General Supervisory (silencable)
8 56 General Waterflow (silencable)
9 (reserved)
10 58 General supervisory alarm (non-silencable)
11 (reserved)
12 (reserved)
13 61 General waterflow alarm (non-silencable)
14 (reserved)
15 63 General alarm monitor waterflow (non-silencable)
16 (reserved)
Table 2.3: LED display for Zones 49 to 64
See also
D7032 - use with the D7030X, 10
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
i
i
12 en | Overview Fire Alarm Control Panels
2.2.7

Communicator

The communicator can report to two phone numbers or IP addresses with full single, double, and back-up reporting. Communicates in SIA, Modem IIIa2, Contact ID, BFSK, and 3/1 and 4/2 Tone burst formats (available communication formats depend on phone or IP connection).
Notice!
The communicator must be enabled and configured to operate. The communicator and phone
line monitors are disabled in the default factory configuration.
Phone Line and Phone Number/IP Selection: To ensure the delivery of critical reports, the fire panel has two phone lines and two phone numbers or IP addresses that can be used for reporting. Reports can be directed to one or both of two phone numbers or IP addresses using the Report Steering feature in the control panel programming. Note that Account Number 1 is used with Phone Number/IP 1, and Account Number 2 is used with Phone Number/IP 2. Except for test reports, the control panel automatically selects the phone line or IP address to use. If the report is not successful after two attempts on Line 1, the control panel automatically switches and uses Phone Line 2. One exception is when test reports (manual or automatic) are sent. Test reports are sent every 4 hours to 28 days. Each time a test report is sent, the control panel alternates phone lines. This happens even if the monitor says the line is bad. If the user sends two manual test reports, both phone lines can be tested. The first report uses one line, and the second uses the other line. During normal operation, the automatic test uses a different line each day. Because the control panel automatically selects which line to use, both phone lines must use the same dialing sequences for sending reports. For example, a line that requires a 9 to be dialed for an outside line cannot be paired with a line that does not require a 9. For more information on report steering, see Report Steering, 83.
Notice!
PBX lines and ground start lines do not comply with NFPA requirements for digital communi-
cation.
While the control panel is idle, the FACP monitors the primary and alternate telephone lines by monitoring the line for trouble. The FACP monitors each line every 12 seconds. When a trouble still exists after three samples (36 seconds), the FACP sends a trouble report and activates the yellow trouble LED and trouble relay.
Danger!
If the central station receives the automatic test report only every other day, this indicates
that one phone line at the protected premises is inoperative.
Correct this condition immediately, because other critical reports can be delayed when the
communicator is trying to send the test signal through the inoperative phone line (once each
48 hours).
Supplemental Reporting: While two independent phone lines are required for UL864 Central Station service, the FACP can be configured with one phone line if the control panel is used only for supplemental reporting on a local, remote station or auxiliary system. To install the control panel with only one phone line, connect a jumper from T1 to T2 and a jumper from R1 to R2. These jumper connections are shown in the following figure:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
i
Fire Alarm Control Panels Overview | en 13
Figure 2.2: Supplemental Reporting
1 Jumper from R1 to R2 3 House phone
2 Jumper from T1 to T2 4 TELCO line
2.2.8
2.2.9
2.2.10

Users

The system allows up to 16 individual users, or up to 100 users when the D7039 is installed. A personal identification number (PIN, the four-digit code entered at the keypads) and an authority level to determine which functions can be performed can be assigned to each user. For PINs, see Personal identification numbers (PINs), 47.

Lightning protection

Notice!
This system is intended for installation entirely within one building.
Metal-oxide varistors (MOVs) and spark gaps provide protection from lightning surges and static discharges.

Battery backup calculation

To calculate the standby battery capacity required by NFPA when using the FPD‑7024, see the two following tables:
Device Quantity Standby
existing/device
FPD‑7024 Control Panel
1 200 mA 200 mA 380 mA 380 mA
Total standby
Alarm existing/ device
Total alarm
FPC‑7034 Four‑Point Expander
D7035/B Octal
1
Relay
D7048/B Octal Driver Module
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
44 mA 156 mA
8 mA + 30 mA 2 8 mA + 30 mA 2
10 mA 10 mA
14 en | Overview Fire Alarm Control Panels
Device Quantity Standby
existing/device
FMR‑7036
80 mA 100 mA Annunciator Keypad
D7030X
27 mA 132 mA Eight‑Point LED Annunciator
D7030X‑S2
1
35 mA 175 mA Eight‑Point LED Annunciator
D7030X‑S8
35 mA 175 mA Eight-Point LED Annunciator
D7032 Eight‑
1 mA 90 mA Point LED Annunciator Expander
FMR‑7033 Keypad
1
80 mA 100 mA
Total standby
Alarm existing/ device
Total alarm
D7039 MUX Expansion Module
D7042/B Addressable Eight Point Input
D7050 MUX Photoelectric Smoke Detector
D7050TH MUX Photoelectric Smoke Detector
FMM-7045 MUX Pull Station
D7044 MUX Single Input Fire
D7044M MUX Mini Contact Module
150 mA 150 mA
18 mA 18 mA
0.50 mA 0.56 mA
0.50 mA 0.56 mA
0.55 mA 0.55 mA
0.55 mA 0.55 mA
0.55 mA 0.55 mA
D7052 MUX Dual
0.55 mA 0.55 mA
Input Fire
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
i
Fire Alarm Control Panels Overview | en 15
Device Quantity Standby
existing/device
D7053 MUX I/ O
0.70 mA 0.70 mA
Total standby
Alarm existing/ device
Total alarm
Module Fire
Smoke Detectors
Bells, Horns, and so on
Other Sensors
Other
Grand Total
Standby Existing
1
The 24 VDC existing requirements for the D7030X, FMR-7033 and D7035 are shown at 75%
Grand Total Alarm Existing
of the 12 VDC level shown on the specification sheets for these models. The FPD-7024 regulates 24 VDC power from the battery to 12 VDC for these accessories.
2
Add 30 mA for each relay activated
Table 2.4: Standby battery capacity calculations
The units shown in the following table are Amp hours (Ah), and the calculations include a 20% derating factor.
Grand Total Standby Existing (in amps)
Total Hours of Standby Required
CS
HS
(usually 24 or 60):
Total Standby Capacity (multiply CS x HS) TS= CS x HS
Grand Total Alarm Existing (in amps) CA
Total Hours of Alarm Time Required
HA
(usually 0.083 o 0.25):
Total Standby Capacity (multiply CA x HA) TA= CA x HA
Total Capacity Required (add TA + TS): TC = TA + TS
Required Capacity with 20% Derating
C = TC x 1.2
(TC x 1.2)
Table 2.5: Required battery size calculation
Notice!
The required battery size to support the system can be calculated using the tables for Stand-
by load battery size, 16 and Alarm load battery size, 16.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
16 en | Overview Fire Alarm Control Panels
2.2.11

Required batteries for existing load

Use the following procedure to determine the battery requirements for your system: – Estimate the size of the battery required to support the standby load using the following
table:
Standby load battery size chart
Grand Total Standby Existing
100 to 200 mA 5.8 11.5 14.4
201 to 300 mA 8.6 17.3 21.6
301 to 400 mA 11.5 23.0 28.8
401 to 500 mA 14.4 28.8 36.0
501 to 600 mA 17.3 34.6 X
601 to 700 mA 20.2 X X
701 to 800 mA 23.0 X X
801 to 900 mA 25.9 X X
901 to 1000 mA 28.8 X X
Capacityr required for 24 hours
Capacity required for 48 hours
Capacity required for 60 hours
1001 to 1100 mA 31.7 X X
Table 2.6: Standby load battery size (Ah)
Estimate the size of the battery required to support the alarm load using the following
table:
Alarm load battery size chart
Grand Total
Capacity required for 5 minutes
Capacity required for 10 minutes
Capacity required for 15 minutes
Capacity required for 30 minutes
Capacity required for 45 minutes
Alarm Existing
250 to
0.1 0.1 0.2 0.3 0.5
500 mA
501 to
0.1 0.2 0.3 0.6 0.9
999 mA
1.0 to 1.5 A 0.2 0.3 0.5 0.9 1.4
1.6 to 2.0 A 0.2 0.4 0.6 1.2 1.8
2.1 to 2.5 A 0.3 0.5 0.8 1.5 2.3
2.6 to 3.0 A 0.3 0.6 0.9 1.8 2.7
3.1 to 3.5 A 0.4 0.7 1.1 2.1 3.2
3.6 to 4.0 A 0.4 0.8 1.2 2.4 3.6
Table 2.7: Alarm load battery size (Ah)
Add the results together for the total battery size.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Overview | en 17
Select the next larger standard battery for the system. If the results show a requirement for a battery over 40 Ah, reduce the existing load or add an external regulated fire protective signaling power supply.
2.2.12

Compatible devices

Device Function
D7030 Eight Point LED Annunciator
D7030X Eight Point LED Annunciator
D7030X‑S2 Eight Point LED Annunciator
D7030X‑S8 Eight Point LED Annunciator
D7032 Eight Point LED Annunciator Expander
FMR‑7033 Alphanumeric LCD Keypad
Identifies the location of a fire alarm for up to eight zones allowed per system.
Identifies the location of a fire alarm for up to eight zones allowed per system.
An eight zone LED annunciator, of which two zones are reserved for supervisory functions. It has Power and Trouble LEDs plus eight zone LEDs that can be labeled individually.
An eight-zone LED annunciator, of which all eight zones are reserved for supervisory functions. It has Power and Trouble LEDs plus eight-zone LEDs that can be labeled individually.
Attaches to a D7030X and identifies the location of a fire alarm for eight additional zones.
The FMR‑7033 LCD Keypad combines remote annunciator and controller functions for the FPD‑7024. Up to four keypads can be connected.
FPC‑7034 Four Point Expander Allows the FPD‑7024 Control Panel to support four
additional loops. The FPC‑7034 plugs into the control panel and provides four Class B, Style 4 loops that are identical in characteristics to the loops on the control panel. One FPC‑7034 is allowed per system.
D7035/B Octal Relay Module Provides eight Form C relay outputs for addition to the
system. The outputs are programmable and can be activated by system events. Each output operates independently of the other seven outputs for complete flexibility. The D7035 connects to the option bus; up to two are allowed per system. The D7035B comes installed on a mounting skirt. For required enclosure modification, see also the D7035 Installation Guide.
FMR‑7036 Fire Annunciator Keypad
FPP‑RNAC‑8A‑4C Remote NAC Power Supply
Establishes the location of a fire alarm.
Adds four NFPA 72 Class B, Style Y Notification Appliance Circuits through the option bus and is supervised by the control panel. The FPP‑RNAC‑8A‑4C connects to the option bus of the FPD‑7024 control panel and up to four are allowed per system.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
18 en | Overview Fire Alarm Control Panels
Device Function
D7039 Multiplex Expansion Module
Provides either 2 two-wire (Class B, Style 4) multiplex buses or 1 four-wire (Class A, Style 6) multiplex bus. In Class A mode, up to 120 addressable points can be added. In Class B Mode, up to 247 addressable points can be added. The D7039 connects directly to the control panel. One is allowed per system.
D7042/B Eight‑Input Remote Module
Provides eight Class B, Style 4 input points. Connect up to 15 modules to MUX Bus A, and 15 on MUX Bus B. The D7042 is powered by 12 VDC supplied by the option bus power terminals, in addition to the two‑wire data connection. The D7042 can not be used on a signal line circuit (SLC) configured for Class A, Style 6 operation.
D7048/B Octal Driver Module Provides eight open‑collector transistor outputs for
addition to the FPD‑7024 Fire Alarm Control panels. It connects to the control panels through the option bus.
FMM-7045 MUX Pull Station UL Listed fire alarm initiating device.
D7044 MUX Single Input Module
Connects a normally‑open contact device to the multiplex bus of the FPD‑7024 with a supervised local loop. The D7044 draws operating power from the FPD‑7024.
D7044M MUX Mini Contact Module
Connects a contact device to the multiplex bus of the FPD‑7024 with a supervised input loop. The D7044 draws operating power from the FPD‑7024.
D7052 MUX Dual Input Fire Connects to the multiplex bus of the FPD‑ 7024 and
provides two supervised input zones for connecting conventional normally-open inputs. The D7052 draws operating power from the FPD‑7024.
D7053 MUX I/O Module Fire Connects to the multiplex bus of the FPD‑7024 and
implements a supervised local loop, and a Form C relay output. Up to 20 modules can be connected to each MUX bus. The D7053 draws operating power from the FPD‑7024.
D7050/TH MUX Smoke Detector The D7050/TH is a photo-electric smoke detector with a
heat option. It connects to the multiplex bus of the FPD‑7024. The D7050 draws operating power from the FPD‑7024.
DX4020 / B420 models The Conettix DX4020 and B420 models are communication
devices that manages secure, two-way IP communications over Ethernet networks.
ITS‑DX4020‑G The ITS-DX4020-G enables two-way IP or dialed
communications over a commercial GPRS/GSM network. Typical applications are event reporting to a central monitoring station and remote access to Bosch control panels.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Overview | en 19
Table 2.8: Compatible devices
Install D7042 modules only at addresses:
9 17 25 33 41 49 57 65
73 81 89 97 105 113 121 129
137 145 153 161 169 177 185 193
201 209 217 225 233 241
Do not install D7052 and D7053 modules at these addresses:
16 24 32 40 48 56 64 72
80 88 96 104 112 120 128 136
144 152 160 168 176 184 192 200
208 216 224 232 240 248 255
Table 2.9: Address restrictions for the D7042, D7052, and D7053
2.3

Parts List

The FPD‑7024 comes with: – One FPD-7024 Control/Communicator in static-resistant bag – One enclosure with transformer – One hardware pack containing the hardware necessary for installing the control panel in
the enclosure – One enclosure lock, washer, and keys – Six end-of-line (EOL) resistors
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
i
i
20 en | Fire Safety Fire Alarm Control Panels
3
3.1
3.1.1

Fire Safety

Danger!
No fire detection device or system is 100% foolproof.
This fire alarm system can provide early warning of a developing fire. Such a system, however, does not ensure protection against property damage or loss of life resulting from a fire. Any fire alarm system can fail to warn for any number of reasons (such as smoke not reaching a detector that is behind a closed door).
Notice!
This system must be regularly tested (when installed, when modified, and at least annually
thereafter) to ensure continued performance.
When considering detectors for residential applications, refer to NFPA Standard 72, The National Fire Alarm Code. This standard is available at a nominal cost from: The National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.

Smoke detector layout

General considerations

Proper location of detection devices is one of the most critical factors in a fire alarm system. Smoke detectors should not be installed in dead air spaces or close to ventilating or air conditioning outlets because smoke can be circulated away from the detector. Locations near air inlets are favored. Avoid areas subject to normal smoke concentrations such as kitchens, garages, or near fireplaces. Do not install smoke detectors where normal area temperatures are above +100°F (+38°C) or below +32°F (0°C). Avoid areas of high humidity and dust concentrations. Place the edge of ceiling mounted detectors no closer than 4 in. (10 cm) from any wall. Place the top edge of wall-mounted detectors between 4 in. and 12 in. (10 cm and 30 cm) from the ceiling. For exact mounting information, refer to the instructions provided with the smoke detectors.
3.1.2
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.

Family residences

Providing a Fire Warning System: Most fire deaths occur in the home, especially during
sleeping hours. The minimum level of protection requires smoke detectors to be installed outside of each separate sleeping area and on each additional story of the dwelling.
Notice!
For added early warning protection, install detectors in all separate areas including the base-
ment, bedrooms, dining room, utility room, furnace room, and hallways.
For residential smoke detector locations, see the following figure:
Fire Alarm Control Panels Fire Safety | en 21
Figure 3.1: Smoke detector locations in residential settings
1 Bedroom 5 Basement
2 Hall 6 Recreation room
3 Living room 7 Kitchen
4 Dining room * Smoke detector
3.2

Having and practicing an escape plan

A fire warning can be wasted unless the personnel planned in advance for a rapid and safe exit from the building. Draw a floor plan of the entire building showing two exits from each sleeping area and two from the building. Since stairwells and hallways can be blocked during a fire, provide exits from sleeping area windows. Make copies of the plan and practice it with all personnel. Arrange a meeting place outside and away from the building. Once out of the building, all occupants should immediately go to the pre-selected location to be accounted for. Provide a barricade between personnel and fire, smoke, and toxic gases (such as closing all sleeping area doors before retiring). Instruct children on opening their bedroom windows and exiting safely from the building. If exiting is not possible, teach them to stay at the open window and shout for help until it arrives. If a fire alarm occurs after retiring, wake the children by shouting to them from behind your closed door. Tell them to keep their bedroom doors closed. If the top of your bedroom door is uncomfortably hot, do not open it. There is most likely fire, intolerable heat, or smoke on the other side. Shout to all family members to keep their bedroom doors closed and to exit the building by alternate routes. If the top of the door is not uncomfortably hot, brace the bottom of the door with your foot, and the top with one hand, then open the door about one inch. Be prepared to slam the door shut if there is any pressure against the door or if any hot air rushes in. If there is no evidence of excessive heat or pressure, leave the room and close the door behind you. Shout appropriate instructions to all family members and immediately leave the building by the planned routes. If heavy smoke is present, drop to your hands and knees, or crawl to remain below the smoke level.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
i
22 en | Installation Fire Alarm Control Panels
4
4.1
4.1.1
4.1.2

Installation

Installation guide for UL Listed systems

FPD‑7024 UL Listings

The FPD‑7024 is UL Listed for the following: – Commercial Fire Alarm (UL Standard UL864)
Type Service: Auxiliary, Local, Central Station, and Remote Station – Type Initiating: Automatic, Manual, Sprinkler Supervisory, and Waterflow
Install the control panel according to NFPA 72 for Commercial Fire installations.

Installation considerations

Failure to install and program the control panel according to the requirements in this section voids the listing mark of Underwriters Laboratories. – The standby battery capacity is 40 Ah at 24 VDC. – The total nominal existing must not exceed 1.25 A in standby or 4 A when in alarm. – The control panel must be mounted indoors and within the protected area. – Grounding must be according to article 250 of the NEC (NFPA 70). – Points must be connected to UL Listed, compatible devices. – The ground wire provided with the enclosure must be connected between the door and
the enclosure using the supplied nuts. – Do not program the ground start feature. – Select Phone Monitoring if the digital alarm communicator transmitter (DACT) feature is
used.
4.1.3

UL requirements

Notice!
The system must be tested after installation and after any re-programming, including pro-
gramming performed by downloading.
When used in UL Listed installations, the control panel must conform to certain programming requirements. For a list of the required program entries specific UL Listed installations, see the Programming features for UL864 table, 49.
Commercial Fire Alarm (Central Station [DACT] and Local) Required Accessories
At least one Bosch Security Systems, Inc. Model F220‑P Smoke Detector with an F220
Family Base; or another UL Listed compatible smoke detector. – At least one Horn Strobe or Bell (provides 85 dB for UL985 and NFPA 72 requirements;
other UL Listed compatible devices listed for regulated 24 V can be used) is required for
this application and must be installed inside the protected area. – Four-wire detectors must be used with UL Listed power supervision devices. A
compatible UL Listed four-wire detector is the Bosch Security Systems, Inc. F220‑P in an
F220‑B6 Family Base. A compatible UL Listed relay is the Bosch Security Systems, Inc.
D275. – All points must be used with the resistor provided.
Report Programming
Program non-supervisory and supervisory reports for those points used. – Program trouble reports. – Set AC Failure Report Delay for a delay of 1 hour to 3 hours. – Set automatic test report frequency to occur at least every 24 hours.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels
Installation | en 23
Timer Programming
Program Auto Silence Time for not less than five minutes, or to “0” to disable auto-silence
operation.
Point Programming
For fire points: open = trouble, latching.
Alarm Output Programming
Program notification appliance circuits to activate from the appropriate input points.
Communications Programming
If used for Central Station Service, select a communication format compatible with the
central station. Enable monitoring of both phone lines.
UL Listed Accessory Devices D132B Multi-use Reversing Relay Module
The D132B is a multi-purpose, fully configurable, smoke power-reversing module for activating detectors with local annunciation. The D132B operates both two-wire and four-wire circuits and also works with Class A or Class B initiating circuits. An alarm latch connection is provided to allow an initiating loop to be held in alarm after the detector loop power is reversed to activate any sounders. The D132B does not affect compatibility between the FACP and detectors, or the FACP and Notification Appliance Circuits (NACs). See also the D132B Installation Guide for detailed installation instructions for the D132B module. One of the installation options shown in the D132B Installation Guide is also shown in the following figure:
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
24 en | Installation Fire Alarm Control Panels
Figure 4.1: Wiring the D132B smoke power reversing module
1 Power limited and supervised 7 12/24 VDC
2 Optional alarm latch 8 24 V reversing detectors
3 Loop 9 2.2 kΩ EOL (power limited and
supervised)
4 Class A 10 Not used
5 Latch 11 24 V NACs
6 NAC
D185 Reverse Polarity Module
The D185 Reverse Polarity Module is a UL Listed module that connects the control panel with either a single set or a pair of leased telephone company (TELCO) lines in NFPA 72 remote station applications. It relays system alarm status information from the control panel to a monitoring station. The D185 operates with either 12 VDC or 24 VDC supply. For typical wiring of the D185 module, see the following figure:
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Fire Alarm Control Panels Installation | en 25
Figure 4.2: Wiring the D185
The module can signal alarm, trouble, and supervisory conditions. The Wiring the D185 figure, 24 shows the module being used to signal alarm and trouble conditions only. With a third relay
(available from the eight-relay expansion module) and an additional leased line, supervisory conditions can also be signaled. In the example in the Wiring the D185 figure, Relay 1 must be programmed to operate on Alarm (Zone 63) and Relay 2 must be programmed to operate on Trouble (Zone 62). Program Input 4 to operate as a Supervisory point. Any alarm causes the voltage to the monitoring station to be interrupted. Placing the D185 in test mode causes a SUPERVISORY TROUBLE. See also the D185 Installation Manual.
4.2

Installing the enclosure

To install the enclosure, follow these instructions:
1. Using the enclosure as a template, mark the top mounting holes on the mounting surface.
2. Start the mounting screws (not supplied) for these two holes.
3. Slide the enclosure onto these screws so that the screws rest on the thinner section of
4. Tighten the screws.
1 D185 module 5 Fire control panel
2 To monitoring station bk black
3 D275 bu blue
4 2.2 kΩ EOL ye yellow
the holes.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
i
26 en | Installation Fire Alarm Control Panels
5. Install and tighten the remaining two screws in the bottom mounting holes.
6. Knock out the desired wire entrances on the enclosure. For mounting hole locations, see the following figure:
Figure 4.3: Enclosure iInstallation
1 Control panel location 5 Transformer
2 Mounting holes 6 Stud
3 Retainer holes for standoffs 7 Ground wire
4 Retainer holes for support posts
Notice!
If using the knockouts located at the bottom of the enclosure, install batteries in a separate
enclosure.
4.3

Installing the FPD‑7024

Danger!
The control circuit board in the FPD-7024 is static sensitive.
To avoid damage to sensitive components, touch ground before handling the control board.
This discharges any static electricity in your body. For example, run the ground wire to the en-
closure before handling the control circuit board. Continue touching the enclosure while in-
stalling the control board.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
!
Fire Alarm Control Panels Installation | en 27
Warning!
Before the circuit board is installed, connect the supplied ground wires between the door and
the enclosure and from the transformer to the enclosure using the supplied nuts. Both
grounds connect to the stud in the enclosure to the left of the circuit board.
For installation illustrations, see the figures for Enclosue installation, 26 and for Standoff and support post installation, 27.
1. Insert the three support posts in the enclosure’s retainer holes.
2. Press the 1/8 in. nylon standoffs (P/N: F01U034705) into the retainer holes.
3. Slide the top of the control panel onto the retainer tabs (the slots under the top of the frame). When the control panel is in the retainer tabs, it rests on the posts.
4. Secure the bottom of the circuit board by inserting and tightening the screws at the two bottom corners through the support posts and the retainer holes.
For installing standoffs and support posts, see the following figure:
Figure 4.4: Standoff and support post installation
1 1/8 in. nylon standoff 4 Corner of circuit board
2 Retainer holes 5 Support post
3 Support post assembly 6 Retainer hole in enclosure
4.4

Installing optional equipment

Two expansion options connect directly to the control panel, and are automatically detected and supervised when the control panel is powered: – FPC-7034 Four Point Expander – D7039 Multiplex Expansion Module When the control panel is powered after installing one of these options, the control panel displays one of the following windows:
4Z EXP DETECTED
PRESS BACK KEY
MUX DETECTED
PRESS BACK KEY
Press the [*/BACK] key to confirm the installation of the device and automatically set it up for supervision.
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
!
i
i
28 en | Installation Fire Alarm Control Panels
If the [*/BACK] key is not pressed during the power-up time-out period, the control panel resumes operation using the last confirmed status of the affected expander and displays an installation error condition.
Warning!
Expansion devices such as point expanders and multiplex expanders are disabled if they are
removed from the control panel configuration after installation. You cannot disable supervi-
sion of these devices when they are installed.
For additional information, see the installation instructions for the specific expanders.
Notice!
EEPROM fault at first installation
When the D7039 Multiplex Expansion Module is first installed, the system displays an EE-
PROM fault. Execute the default procedure to synchronize the EEPROM on the expansion
module to the EEPROM in the control panel. Remove power to the control panel, then reapply
power and re-install option bus devices after the default procedure.
Notice!
Loss of programming
Replacing a D7039 Multiplex Expansion Module causes the loss of programming of expansion
points and PINs. Reprogram all multiplex point and PINs if you replace the D7039.
When the D7039 is first installed, or anytime the control panel is powered with a D7039 that has no points programmed, the system automatically starts the multiplex auto-programming process:
AUTO PROGRAM?
_______:YES(1) NO(0)
Pressing the [1] key starts auto-programming, and pressing [0/Prog] allows the control panel to continue normal startup. The menu automatically closes with NO selected if no key is pressed after several minutes. For detailed instructions on the auto-programming mode, see Auto Program, 93.
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
!
i
Fire Alarm Control Panels Connection | en 29
5
5.1

Connection

FACP terminal connection

Danger!
Incorrect connections may result in damage to the unit and personal injury.
Warning!
Before servicing this equipment, remove all power including the transformer, battery and
phone lines.
Notice!
Shared cable is not recommended for option bus, telephone or NAC wiring.
Figure 5.1: Typical 2-wire smoke detector wirin (supervised)g
1 Class A, Style D 3 EOL resistor
2 Class B, Style B
Figure 5.2: Typical 4-wire smoke detector wiring
1 Class A, Style D 4 EOL resistor
2 Class B, Style B 5 Smoke detector
3 EOL relay
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458
i
30 en | Connection Fire Alarm Control Panels
Notice!
All wiring except battery terminal and primary AC power is power-limited. Primary AC and bat-
tery wires must be separated from other wires by at least ¼ in. (64 mm) and tied to prevent
movement.
Figure 5.3: Transformer
RD red
BN brown
supervised:
YE yellow
WH white
BK black
Figure 5.4: Input Points
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.
Loading...
+ 92 hidden pages