Bosch FPC-500-2, FPC-500-4, FPC-500-8 Installation Manual

Conventional Fire Panel
FPC-500-2 / FPC-500-4 / FPC-500-8
en Installation Guide
1
Safety Instructions 6
2
System Overview 8
2.1 Operating Levels 12
3
Installation 13
3.1 Scope of Delivery 13
3.2 Installation 13
3.2.1 Inserting the Cable 13
3.2.2 Opening the Housing 14
3.2.3 Installing the Housing 15
3.2.4 Mains Supply 16
3.2.5 Batteries, 24 V Emergency Power Supply 17
3.2.6 Extensions 18
3.3 Wiring 19
3.3.1 Inputs 20
3.3.2 Zones 21
3.3.3 Aux power 23
3.3.4 Notification Appliances 24
3.3.5 Relay Outputs 25
3.3.6 Extensions 26
3.3.7 External power supply 26
3.4 Initial Start-Up 29
3.4.1 Setting the Language 29
3.4.2 Setting the Time and Date 29
4
System Configuration 31
4.1 System Configuration 34
4.1.1 Setting the Date/Time 34
4.1.2 Buzzer Beep 34
4.1.3 EOL Elements 35
4.1.4 Resetting Zones 35
4.1.5 Aux Power 37
4.1.6 Faults 37
4.1.7 Level Code 38
4.1.8 Test Log 39
Conventional Fire Panel Table of Contents | en 3
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
4.2 Configuring Delays 39
4.2.1 Deactivating Day Mode 40
4.2.2 Alarm Verification 40
4.2.3 Intermediate Alarm Storage 42
4.2.4 Delay for Mains Fault 44
4.3 Zone Configuration 44
4.4 Configuring Inputs 47
4.4.1 Input 1 48
4.4.2 Input 2 (FPC-500‑8 only) 49
4.5 Configuring Outputs 49
4.5.1 Notification Appliances 49
4.5.2 Alarm Relay 51
4.5.3 OC/Relay Extensions 52
4.6 Displaying the Configuration 53
4.7 Controlling Outputs 54
4.7.1 Notification appliance 1 54
4.7.2 Notification appliance 2 54
4.7.3 Alarm Relay 55
4.7.4 Fault Relay 55
4.7.5 OC/Relay Extension 55
4.7.6 Control all outputs 56
4.8 Resetting To Delivery State 56
5
Fault Diagnosis 58
6
Technical Data 59
6.1 Electrical Data 59
6.1.1 Communication parameters 61
6.2 Mechanical 62
6.3 Environmental Conditions 62
6.4 Information as per EN 54‑4, chapter 7.1 63
6.5 Options with requirements as per EN 54‑2:1997/A1:2006 64
7
Appendix 65
7.1 Brief Overview, Operating Level 1 and 2 65
7.2 Test menu 66
7.3 Brief Overview, Operating Level 3 67
7.4 Default Settings 74
4 en | Table of Contents Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
7.5 Event Memory 76
7.6 Test Memory Messages 78
Index 79
Conventional Fire Panel Table of Contents | en 5
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Safety Instructions
Danger!
The fire panel may only be operated with the housing closed
because of the danger of an electric shock.
Danger!
Only perform installation work when the panel has no voltage.
There is a danger of an electric shock.
!
Caution!
Installation may only be performed by authorized qualified
personnel in order to ensure that the system is not damaged
and operates properly.
Notice!
Note local regulations when connecting to 230 V power
supplies.
Notice!
Please observe the country-specific regulations and guidelines
during planning, installation and programming of the fire panel.
Notice!
In line with EN 54-13 (BOSEC certificate TCC 2 - 977), each
conventional line must be terminated with EOL modules for the
operation of fire detection systems.
The AUX power supply must also be terminated with EOL
modules when using four-wire detectors.
1
6 en | Safety Instructions Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Notice!
The fire panel has been designed for operation in closed rooms.
Please note the permissible environmental conditions in the
technical specifications.
Conventional Fire Panel Safety Instructions | en 7
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
System Overview
1
ESC
8 7 6 5 4 3 2
ACK
i
RESET
EVAC
1
2
3
4
5
6
7
8
P re-Alarm
F ault
System Fault
Earth Fault
Power Fault
NAC Fault / Disabled
Notification Appliance Silent
Day Mode
T est
D isable
Power
A LARM
4
3
1
2
1 LED display
2 LCD display with zone numbers
3 Zone keys and zone status LEDs
4 Operating panel
2
8 en | System Overview Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
FPC-500-2FPC-500-4FPC-500-
8
Inputs – Zones – Prog. inputs
2 1
4 1
8 2
Outputs – Prog. AUX (500 mA) – Alarm device, 500 mA
each
Relay
1 2 2
Extensions – Open collector (20 mA) – Relay (via OC)
no
1 x 4
2 x 4
LCD, 2 x 16 characters Yes
230
VAC
AUX
24 V DC
OC (0, 4, 8)
Z1
. . .
Z8
ALARM RLY
FAULT RLY
IN1
IN2
Conventional Fire Panel System Overview | en 9
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Conventional detectors
Conventional manual call point
Visual or audible notification appliances
Z1 ... Z8
Conventional zones 1 to 8 (max. 2 on FPC-500-2, max. 4 on FPC-500-4)
IN
Inputs (max. 1 on FPC‑500‑2 and FPC‑500‑4, max. 2 on FPC‑500‑8)
ALARM RLY
Alarm relay
FAULT RLY
Fault relay
OC
Transistor output for extension cards (0 on FPC‑500‑2, 4 on FPC‑500‑4, 8 on FPC‑500‑8)
AUX 24 VDC AUX power supply
Features
Alarm verification: The user is prompted to verify the alarm. – Intermediate alarm storage: an alarm triggered by an
automatic detector is reset automatically after 20 seconds (adjustable) by the panel. If there is an additional alarm within 10 minutes in this zone, the notification appliances are enabled. Otherwise the pre-alarm is reset automatically.
Dual-zone dependency on neighboring zones.
10 en | System Overview Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Dual-detector dependency for detectors in a zone. – Alarm counter for 999 alarms. – Event memory for 1000 entries. – Three operating levels, two of them protected with freely
selected code.
Up to 8 monitored detector zones depending on panel
version.
Up to 2 monitored inputs available depending on panel
version. – One alarm and one fault relay. – Up to 8 additional transistor or relay outputs, freely
programmable, depending on panel version. – Quick and easy programming using the keypad and LCD
display. – Easy operation for the end user. – Two monitored notification appliance outputs. – EN 54-13 (BOSEC certificate TCC 2 - 977) compliant system
by using EOL modules. – Power supply via power supply unit with thermal fuse. – Emergency power supply using batteries, up to 7.2 Ah,
reverse polarity protected. – Removable quick guide for the user on the panel.
Conventional Fire Panel
System Overview | en 11
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Operating Levels
This fire panel has three operating levels. You can only perform certain actions depending on operating level.
Level 1 Display information
Read out event memory – Display faults and deactivations – Perform display test
Level 2 Change language and time/date
Switch key tones on/off – Put zones in test mode and take zones out of
test mode
Switch off/on zones, notification appliances,
relay and transistor outputs – Trigger evacuations – Reset panel – Switch between day/night mode – All actions of level 1
Level 3 All settings for installing and programming the
system.
Code inputs are necessary for accessing level 2 and 3.
2.1
12 en | System Overview Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Installation
Scope of Delivery
The fire panel packaging contains the following components: – Fire panelFPC‑500‑2/FPC‑500‑4/FPC‑500‑8 – EOL resistors for zones and inputs – Battery cable set – Cable ties for strain relief on power supply feeder – Labeling strips for zones and LEDs – Quick Installation Guide – Quick Operation Guide – CD – Two plastic foam blocks for securing the batteries
Installation
Notice!
Install the fire panel in a location easily accessible to
emergency response teams (e.g. fire department).
Note permissible environmental conditions.
Install the fire panel at a height above the ground that permits convenient operation by the user and easy reading of the LCD display.
Inserting the Cable
Route the necessary cables for zones, inputs and outputs, as well as the power supply, etc., and carefully punch out the cable entries needed for this.
!
Warning!
Electrostatic discharge (ESD)! Electronic components could
become damaged. Ground yourself using a wrist strap or take
other suitable measures.
3
3.1
3.2
3.2.1
Conventional Fire Panel Installation | en 13
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Remove the PC board if necessary. This is secured in the housing with a grounding screw and snap-fit hook. For cable entry on the upper side of the housing, use the pre­formed round holes. For more stable insertion, M 20 x 1.5 screw joints (PG13.5) can be used. The cable entries on the rear are intended for direct cable entry of flush mounted cables.
Opening the Housing
Remove the cover of the fire panel. Loosen both screws on the underside of the housing, lift up the cover approx. 20° and remove it.
3.2.2
14 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Installing the Housing
Use the panel housing to draw drill holes at the desired location on the wall (arrows in figure below). As an option, you can use the mounting dimensions indicated on the back of the housing. Ensure that the housing is aligned horizontally and draw on the holes using the built-in spirit level in the upper left corner. The dimensions can be taken from the drilling jib on the rear of the housing. Drill the holes. Guide the cables routed under plaster through the punched out cable ducts on the rear of the housing into the housing. Mount the housing to the wall using screws. Make sure that cables are not pinched. Then guide the cables routed on plaster through the cable entries to the upper side of the housing.
3x
( 8 x 40 mm)
3x
6 x 50 mmPZ3
S8
3x
6 x 50 mmPZ3
8mm
PZ3
3x
( 8 x 40 mm)
3x
6 x 50 mmPZ3
S8
3x
6 x 50 mmPZ3
8mm
PZ3
3.2.3
Conventional Fire Panel Installation | en 15
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Mains Supply
The fire panel requires a 230 V mains supply for the power supply. Route the power supply so that the line does not cross or touch the signal line. Use the left M 20 x 1.5 screw joint (PG13.5) on the upper side of the panel for the 230 V mains supply.
Notice!
Note local regulations when connecting to 230 V power
supplies.
Wire up the 230 V power supply to the screw clamp provided on the power supply unit board. Use a cable tie to ensure strain relief of the power supply feeder in the housing above the power supply unit.
Danger!
Only perform installation work when the panel has no voltage.
There is a danger of an electric shock.
N L
230 VAC
50 - 60 Hz
3.2.4
16 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Batteries, 24 V Emergency Power Supply
You can use two 12 V batteries with maximum 7.2 Ah each in the housing as emergency power supply. The batteries are connected in series. If the mains power fails, they are used to ensure interruption-free power supply of the fire panel and the components fed by them.
Notice!
The fire panel can also only be started with the batteries if the
power supply is disconnected.
After you have placed the batteries in the housing, secure them using the plastic foam blocks provided. Position the plastic foam blocks in between the top of the batteries and the housing. There are different emergency current back-up times depending on the battery capacity used and the current consumption of the components connected to the panel. You can calculate this using the battery calculator included on the CD. After troubleshooting a mains fault and operating the fire panel via emergency current, the power supply unit switches back to mains operation automatically. The batteries are charged again automatically.
Notice!
Note the polarity of the batteries.
If the batteries are connected with the polarity reversed, the
thermal fuse on the main board of the fire panel reacts.
3.2.5
Conventional Fire Panel Installation | en 17
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
BAT
- +
Secure the batteries with the plastic foam blocks provided so that they cannot move.
Extensions
Notice!
Note that the maximum line resistance for transistor outputs is
22.5 Ohm.
The extensions are connected to the left side of the main board. Simply connect the board to the plugs. Make sure that the plug engages correctly.
3.2.6
18 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
There is a groove on the top of the extensions. Make sure that the board has been correctly installed.
Notice!
A maximum of two extensions can be connected:
FPC-500‑2: No extension can be connected
FPC-500‑4: One extension can be connected
FPC-500‑8: Two extensions can be connected
Wiring
External components such as zones, notification appliances, inputs, etc. are wired to screw terminals attached to the upper side of the board.
1 2 3 4 5
No.Meaning FPC‑500-2FPC‑500-4FPC‑500
-8
1 Inputs 1 1 2
2 Zones 2 4 8
3 Aux power supply 1
4 Notification appliance 2
5 Alarm and fault relay 1/1
3.3
Conventional Fire Panel Installation | en 19
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Notice!
The screw terminals are designed for a cable diameter of
0.8 mm and for cable cross sections of up to 1.5 mm2.
The fire panel is designed for unshielded cable. If you do use
shielded cable, only connect the cable shielding to the earth
bar on one side above the power supply unit.
Terminal resistances
The zones of the fire panels must be terminated. Use either resistors or in case of EN 54-13 (BOSEC certificate TCC 2 - 977) the EOL modules.
Notice!
Only use resistors with a maximum 1% tolerance.
The 3.9 kOhm resistors are supplied.
Inputs
+ -
IN1
820Ω ± 5%
3,9k
The fire panel offers two control inputs. You can assign different functions to these depending on programming (see Configuring Inputs, page 47). The connection terminals IN1 and IN2 are available.
Notice!
Note that the maximum line resistance for inputs is 22.5 ohm.
Use 820 Ohm ±5% resistors for the alarm resistance (not
included in scope of delivery).
3.3.1
20 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Notice!
Only use buttons (no locking element) if you have programmed
inputs as Drill/Evacuate, Silence, or Reset Panel.
Access levels as per EN 54‑2 must be observed.
Zones
Notice!
Do not connect the zone- with any power+ like for example:
AUX power, external power supply or batteries for emergency
power supply.
b+ a-|b+ a-
1-ZONE-2
3,9k
a-
b+
3,9k
b+ a-|b+ a-
1-ZONE-2
EOL
EOL
a-
b+
EN 54‑13 (BOSEC certificate TCC 2 - 977)
Each zone must be completed with a terminal element. You can either use a 3.9 kΩ ± 1% resistor or EOL modules for an EN 54-13 (BOSEC certificate TCC 2 - 977) compliant termination. Unused zones must also be terminated with a terminal element. Mixing different terminal elements is not allowed.
3.3.2
Conventional Fire Panel Installation | en 21
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Notice!
Note that the maximum line resistance for conventional zones is
22.5 Ohm.
The voltage of the zones is 20 VDC ±1 V.
The maximum current of the zones is 100 mA ±5 mA.
Notice!
Observe local regulations for the maximum number of detectors
in a zone.
When using the FLM-320-EOL4W Module, use the battery
calculator included on the CD.
Notice!
The last zone of the fire panel supports the use of 4-wire
detectors.
The fire panel does not support dual-detector dependency with
4-wire detectors.
Please use permissible external power supply units depending
on power consumption.
Notice!
Activating a manual call point in a zone programmed as "No
Delay" triggers an immediate alarm.
Notice!
Only use manual call points in zones which are programmed as
No Delay.
22 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Aux power
b+ a-|b+ a-
7-ZONE-8
3,9k
a-
b+
3,9k
+ -
AUX
+
-
4W
Non-EN54-13
b+ a-|b+ a-
7-ZONE-8
+ -
AUX
+
-
POWER CONV
Shield +U 0V b+ a-
R
V
P
FLM-320-EOL4W
EOL
4W
a-
b+
EN54-13 (BOSEC certificate TCC 2 - 977)
The fire panel allows you to use 4-wire (4W) elements on the last zone. These must be supplied with power by the auxiliary power supply or an external power source. Both the zone and the auxiliary power must be terminated by a terminal element. For EN 54-13 (BOSEC certificate TCC 2 - 977) compliant connection of 4‑wire elements, the AUX and zone lines must be routed in separate cables. You can either use a 3.9 kΩ ±1% resistor or EOL modules for EN 54-13 (BOSEC certificate TCC 2 - 977) compliant termination. Program the reset behavior of the auxiliary power as described in Aux Power, page 37.
Notice!
Note that the maximum line resistance for the auxiliary power is
22.5 Ohm.
3.3.3
Conventional Fire Panel Installation | en 23
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Notification Appliances
NAC1
A- B+
OUT IN
A- B+
NAC2
A- B+ A- B+
INOUT
Notice!
Each notification appliance output provides connected
notification appliances with a maximum current of 500 mA at
24 VDC. The permissible voltage range of the output is 21–
29 VDC.
Notice!
Note that the maximum line resistance for notification
appliances is 22.5 Ohm.
The fire panel offers you two notification appliance circuit lines that can be used to activate the audible notification appliances and visual notification appliances. When there is a fire alarm, the notification appliance circuit lines are activated depending on programming.
3.3.4
24 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Notice!
Connect the notification appliances to the terminals NAC1
and/or NAC2. This connection is EN 54‑13 (BOSEC certificate
TCC 2 - 977) compliant.
Relay Outputs
NO C NC ALARM
NO C NC FAULT
Notice!
The fault relay is activated in a normal state. It is opened in the
event of a fault.
The fire panel has two relay outputs. The relays work as potential-free change-over contacts. The alarm relay is activated by every fire alarm.
Notice!
A transmission device must be installed in the immediate
vicinity (without a space) of the FPC‑500‑x.
The connecting line between the fire panel and the
transmission device must not be exposed, as it is not
monitored.
Notice!
Both relay outputs "ALARM" and "FAULT" can switch a
maximum of 1 A @ 30 VDC each.
3.3.5
Conventional Fire Panel Installation | en 25
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Notice!
Note that the maximum line resistance for the relay outputs is
22.5 Ohm.
Extensions
The extension modules offer four connections activated by transistors or relay.
Notice!
The relay outputs can switch a maximum of 1 A @ 30 VDC each.
The transistor outputs switch a maximum of 20 mA @ 24 VDC
each. Inductive loads are not permitted.
External power supply
You can use the FPP-5000 as an external power source for the FPC-500 Fire Panel.
Notice!
Note that the FPP‑5000 housing must be installed in the direct
vicinity (without a space) of the FPC‑500‑x. The connecting line
between the FPP-5000 and the transmission device must not be
exposed, as it is not monitored.
FPC‑500‑2 and FPC‑500‑4
Wire the FPP-5000 as shown in FPC‑500‑2 and FPC‑500‑4, page
26.
Program input 1 to Ext PS Fault (see Input 1, page 48). The relay is not included in the scope of delivery.
3.3.6
3.3.7
26 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
N
O
Relais
24VDC/1A
N
C
C
FPP--5000
12 V 12 V
BCM-0000-B
+ - + - 24V 24V
MAIN BAT1 BAT2 FAULT
FAULT
AC
BAT
MAIN POWER
MAIN POWER
TROUBLE
TROUBLE
TROUBLE
BATTERY 1
BATTERY 2
+ - + - + - - - - +
Σ
1
2
24V
3k9
820
FPC‑500‑8
Wire the FPP-5000 as shown in FPC‑500‑8, page 27.
Conventional Fire Panel Installation | en 27
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Program input 1 to Ext PS Fault and input 2 to Ext Batt Fault (see Input 1, page 48). The relays are not included in the scope of delivery.
FPP--5000
12 V 12 V
BCM-0000-B
+ - + - 24V 24V
MAIN BAT1 BAT2 FAULT
FAULT
AC
BAT
MAIN POWER
MAIN POWER
TROUBLE
TROUBLE
TROUBLE
BATTERY 1
BATTERY 2
+ - + - + - - - - +
Σ
1 2
24V
NO
Relais
24VDC/1A
NC
C
NO
Relais
24VDC/1A
NC
C
3k9
820
3k9
820
28 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Initial Start-Up
As soon as the fire panel is connected to the power for the first time, an LED and buzzer test begins. This is completed the first time a key is pressed. In the initial start-up, you must make the following basic settings: – Set the language – Set the time and date
Setting the Language
To set the language, proceed as follows:
i
Use the arrow keys to set the desired language.
ACK
Confirm your selection in the menu with the ACK key.
Setting the Time and Date
Set the current time and date. The current time and date are important for functions such as – Event memory and – Automatic switching to night mode.
i
Use the arrow keys to set the current day.
ACK
Confirm your selection in the menu with the ACK key.
Repeat this procedure to set the correct values for the month, year and time.
3.4
3.4.1
3.4.2
Conventional Fire Panel Installation | en 29
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Notice!
Summer and winter time settings are not made automatically.
Make these settings manually.
If there is a total power failure, you must make the settings for
the date and time again.
30 en | Installation Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
System Configuration
To be able to perform the actions in operating level 3, you will need a code you can enter with the zone keys.
Notice!
The following codes are programmed in delivery status:
Operating level 2: 1234
Operating level 3: 3333
The basic settings can be found in Default Settings, page 74.
Calling up operating level 3
Press the "Code input" key. You will be prompted to enter a code.
C O D E /
Enter the code with zone keys 1 to 8.
You are in the programming menu of the system.
!
Caution!
In operating level 3, the fire panel is not operational. None of
the inputs and outputs are monitored.
Automatic exit of level 3
If you are in level 3 and no key has been pressed for 10 minutes, the system will exit level 3 automatically. One minute before exiting level 3, a pulse tone of the internal buzzer indicates the time. The time up to the automatic exit of level 3 is displayed in the LCD display.
4
Conventional Fire Panel System Configuration | en 31
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Exiting operating level 3
Notice!
When you exit operating level 3, the fire panel automatically
switches to night mode.
If you are in operating level 3, proceed as follows.
RESET
Press the RESET key. You exit operating level 3 when you are at the top level of the menu. The configuration is stored and the inputs and outputs are activated.
ACK
RESET
Press the ACK key to exit operating level 3. – If you do not want to exit operating level 3,
press the RESET key.
Menu
Operating level 3 of the fire panel offers you the following setting options: – 1-System Config 2-Delay Config 3-Zone Config 4-Input Config 5-Output Config 6-View Config 7-Output Control 8-Config Reset
Notice!
The structure and description of menus of operating levels 1
and 2 can be found in the operating instructions.
32 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Notice!
The menus are described in these instructions as follows:
A hyphen between the number and the menu description "-"
shows you that it is a menu item with a submenu.
An equals sign between the number and the menu description
"=" represents a set value.
A space between the number and the menu description " " is a
value that can be set.
Preset values are always shown in bold.
Operation
You have different options for navigating in the menu of the fire panel.
Using autoscrolling
ACK
The menus scroll automatically every 2.5 seconds to the next menu item. If you would like to select the menu item currently shown, simply confirm with the ACK key.
Navigating with the zone keys
8
1
...
In the menu, each menu item has a number from 1 to 8 preceding it. Use the zone keys to select the desired menu item in the menu. The desired menu item does not have to be shown in the display.
Navigating with the arrow keys
i
Use the arrow keys to navigate in the menu. Using the arrow keys stops autoscrolling in the menus.
ACK
Confirm your selection in the menu with the ACK key.
Conventional Fire Panel System Configuration | en 33
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Exiting submenus
RESET
ESC
In the menu and in the submenus, you can jump to a higher level or cancel the setting using the RESET (ESC) key. Hold the RESET (ESC) key down for 2 seconds to jump to the uppermost level.
System Configuration
In the System Config menu, you can specify basic settings for your fire panel.
Setting the Date/Time
1
Press zone key 1. This takes you to the System Config menu.
1
Press zone key 1. You can now set the date and time.
ACK
To save the currently displayed value, press the ACK key.
Repeat the steps to set the month, year, hour, and minute.
Buzzer Beep
1
Press zone key 1. This takes you to the System Config menu.
2
Press zone key 2. This takes you to the Keypad Tone submenu.
2
1
...
Press zone keys 1 or 2: – 1=On (default setting) – 2 Off
4.1
4.1.1
4.1.2
34 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
EOL Elements
You can use EOL Devices to specify whether you want to use resistors or EOL modules for zone termination.
1
Press zone key 1. This takes you to the System Config menu.
3
Press zone key 3. This takes you to the EOL Devices submenu.
3
1
...
Press zone keys 1 to 3: – 1=Resistor (default setting, not EN 54‑13
compliant) – 2 Only 2W Module 3 With 4W Module
1 2 3 4 5 6 7 8
CS TH: mA
If you select With 4W Module, you must specify the threshold for the creeping short-circuit. You can calculate this using the battery calculator included on the CD.
Resetting Zones
In this menu, you can specify the delay times for resetting zones. You can specify how long the zones can be disconnected from the power and how long the stabilization time of the detector should last. This setting is used for the zone test, restarting the fire panel and intermediate alarm storage.
4.1.3
4.1.4
Conventional Fire Panel System Configuration | en 35
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Cut For
1
Press zone key 1. This takes you to the System Config menu.
4
Press zone key 4. This takes you to the Zone Reset submenu.
1
Press zone key 1. This takes you to the Cut For submenu.
5
1
...
Press zone keys 1 to 5. – 1 1s – 2=5s (default setting) – 3 10s – 4 15s – 5 20s
Stabilize for
1
Press zone key 1. This takes you to the System Config menu.
4
Press zone key 4. This takes you to the Zone Reset submenu.
2
Press zone key 2. This takes you to the Stabilize For submenu.
5
1
...
Press zone keys 1 to 5. – 1 1s – 2=5s (default setting) – 3 10s – 4 15s – 5 20s
36 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Aux Power
The With Zone setting relates to the last zone of the fire panel. If the last zone is reset after a pre-alarm or alarm, the AUX power supply is reset simultaneously. The With Panel setting also resets the power supply each time the fire panel is reset. If you select Never, the auxiliary power supply is never reset.
1
Press zone key 1. This takes you to the System Config menu.
5
Press zone key 5. This takes you to the Aux Power submenu.
3
1
...
Press zone keys 1 to 3. – 1=With Zone (default setting) – 2 With Panel 3 Never
Faults
The Faults setting specifies whether faults on the fire panel are to be displayed until the fire panel is manually reset.
Notice!
This setting does not apply to system faults.
System faults can only be reset manually.
4.1.5
4.1.6
Conventional Fire Panel System Configuration | en 37
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
1
Press zone key 1. This takes you to the System Config menu.
6
Press zone key 6. This takes you to the Faults submenu.
2
1
...
Press zone key 1 or 2. – 1=Latching (default setting) – 2 Non Latching
Level Code
In the Level Code menu, you can specify new codes for operating levels 2 and 3. The new code must be 4 characters long and is displayed during entry.
Notice!
The following codes are programmed in delivery status:
Operating level 2: 1234
Operating level 3: 3333
1
Press zone key 1. This takes you to the System Config menu.
7
Press zone key 7. This takes you to the Code submenu.
2
1
...
1- Level 2 Code 2- Level 3 Code
1 2 3 4 5 6 7 8
Level 2 Code Set to: ____
You are prompted to enter the new code.
4.1.7
38 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
1 2 3 4 5 6 7 8
Level 2 Code Confirm: ____
You then have to confirm the new code by entering it again. The procedure for changing the code for operating level 3 is exactly the same.
Notice!
If you have forgotten your code, contact your Bosch partner.
Test Log
You can decide whether or not the fire panel creates a Test History.
1
Press zone key 1. This takes you to the System Config menu.
8
Press zone key 8. This takes you to the Test History submenu.
2
1
...
Use zone keys 1 or 2. – 1=Log Enabled (default setting) – 2 Log Disabled
Configuring Delays
In the Delay Config menu, you can program different delay times for different zone programs, outputs and fault types.
2
Press zone key 2. This takes you to the Delay Config menu.
4.1.8
4.2
Conventional Fire Panel System Configuration | en 39
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Deactivating Day Mode
Specify whether you want day mode (zones with alarm verification start a verification time in the event of an alarm) to be exited manually by the user or automatically at a defined time. You can program the time in this submenu.
Notice!
Day mode must always be started manually; it is not possible to
configure an automatic start.
2
Press zone key 2. This takes you to the Delay Config menu.
1
Press zone key 1. This takes you to the Day Mode Off submenu.
2
1
...
Use zone keys 1 or 2. – 1=Manual (default setting) – 2 Automatic
If you set Day Mode Off to Automatic, you must program the changeover time from day to night mode.
1 2 3 4 5 6 7 8
Off Time: :17:00 Confirm with
Set the time with the arrow keys and confirm using the ACK key.
Alarm Verification
Notice!
This setting only applies to zones that are programmed as alarm
verification.
Note that the delay settings are only effective in day mode. In
night mode, the alarm is triggered immediately.
4.2.1
4.2.2
40 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
In the Alarm Verific menu, you set the times within which the user must confirm a triggered alarm (ACK Within). The Invest Time submenu specifies the time available to the user to enter the alarm triggering area before the notification appliance is activated. You can also use NAC 1 to specify whether: – Alert switches NAC 1 on immediately in the event of an
alarm. NAC 1 is then switched off during the verification time and switched on again after the verification time.
With Evacuate, NAC 1 is switched off during the delay time
and only activated during the actual alarm.
Time setting for alarm acknowledgement
2
Press zone key 2. This takes you to the Delay Config menu.
2
Press zone key 2. This takes you to the Alarm Verific submenu.
1
Press zone key 1. This takes you to the ACK Within submenu.
4
1
...
Use the zone keys to set the respective delay. – 1 30 s 2= 60 s (default setting) – 3 90 s 4 120s
Time setting for verification time
2
Press zone key 2. This takes you to the Delay Config menu.
2
Press zone key 2. This takes you to the Alarm Verific submenu.
Conventional Fire Panel System Configuration | en 41
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
2
Press zone key 2. This takes you to the Invest Time submenu.
8
1
...
Use the zone keys to set the respective delay. – 1 1 min (default setting) – 2 2 min – 3 3 min – 4 4 min – 5 5 min – 6 6 min – 7 7 min – 8 8 min
Notification appliance 1
2
Press zone key 2. This takes you to the Delay Config menu.
2
Press zone key 2. This takes you to the Alarm Verific submenu.
3
Press zone key 3. This takes you to the NAC 1 submenu.
2
1
...
Press zone key 1 or 2. – 1 Alert 2=Evacuate (default setting)
Intermediate Alarm Storage
Intermediate alarm storage is an automatic procedure designed to rule out false alarms as far as possible. The entire procedure lasts up to 60 seconds: – Ten seconds after a fire is detected, the zone is reset
(setting Reset After).
The zone is reset for x seconds (setting Cut For, Cut For ,
page 36).
4.2.3
42 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
There is an x second stabilization phase for the elements in
the zone (setting Stabilize For, Stabilize for, page 36).
!
Caution!
Detectors of the FCP-320 series must not be used with
intermediate alarm storage because the detector calculates a
new standby value after the reset. This can generate an
increased alarm threshold. If there is a fire, this can thus delay
the trigger of an alarm.
Before using automatic fire detectors, find out from the
manufacturer whether they can be used for intermediate alarm
storage.
In this menu you can change the pre-set time values indicated above.
Reset after
2
Press zone key 2. This takes you to the Delay Config menu.
3
Press zone key 3. This takes you to the Int Alarm Stor submenu.
1
Press zone key 1. This takes you to the Reset After submenu.
4
1
...
Use the zone keys to set the respective delay. – 1 1 s – 2 5 s – 3= 10 s (default setting) – 4 15s – 5 20 s
Conventional Fire Panel System Configuration | en 43
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Display total delay
2
Press zone key 2. This takes you to the Delay Config menu.
3
Press zone key 3. This takes you to the Int Alarm Stor submenu.
2
Press zone key 2. This takes you to the Total Delay submenu.
The total delay is displayed.
Delay for Mains Fault
The Power Fault menu option enables you to specify the delay after which an error message indicating a power supply failure (mains or battery) is to be displayed. If the fault is resolved before the time set here, it is no longer displayed.
2
Press zone key 2. This takes you to the Delay Config menu.
4
Press zone key 4. This takes you to the Power Fault submenu.
5
1
...
Use the zone keys to set the respective delay. – 1=No Delay (default setting) – 2 1 min – 3 5 min – 4 10 min – 5 15 min
Zone Configuration
In the Zone Config menu, you can program the individual zones of the fire panel. Depending on the panel, you can set 2, 4 or 8 zones. The following zone types are available:
4.2.4
4.3
44 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
No delay (No Delay)
A zone programmed as No Delay triggers an alarm immediately. If you are using manual call points, they must be set as No
Delay.
Notice!
Only use manual call points in zones which are programmed as
No Delay.
Int Alarm StorIntermediate alarm storage
A zone triggers an alarm. This is evaluated by the fire panel as a pre-alarm and is not displayed. The zone is reset automatically. If it triggers an alarm again, the panel switches immediately to alarm. If a second alarm is not triggered, the fire panel reverts to its normal state after 10 minutes.
Alarm verification (Alarm Verific)
Notice!
Note that the delay is only effective in day mode. In night mode,
the alarm is triggered immediately.
Notice!
If the fire panel automatically switches to night mode during an
ongoing verification time, an alarm is triggered immediately.
Notice!
If during the verification time in one zone an alarm is triggered
in another zone, which is programmed as alarm verification, an
alarm is triggered immediately.
If a zone programmed as alarm verification detects an alarm, it triggers an alarm, which is delayed.
Conventional Fire Panel System Configuration | en 45
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
The LCD display prompts you to verify the alarm. You must confirm the alarm within a pre-defined time using the ACK key. After this pre-defined time the verification time begins. Within this time you must investigate the alarm triggering area and, if necessary, trigger an alarm. During the verification time, the panel can be reset without triggering an alarm. After the verification time has expired, the panel goes into the alarm state.
Dual-detector dependency (2-Det Depend)
!
Caution!
Detectors with connected remote displays must not be used
with the dual-detector dependency.
Dual-detector dependency only works with detectors that use
an alarm resistance of 820 ohm +/- 5% or 910 ohm +/- 5%.
Otherwise, in the event of a fire, proper functioning of the fire
panel cannot be guaranteed.
Notice!
The fire panel does not support dual-detector dependency with
4-wire detectors.
The zone must contain more than one detector. If one of the detectors in the zone triggers, this is evaluated as a pre-alarm. If an additional detector in the same zone is activated, an alarm is triggered. The panel automatically attempts to reset the pre­alarm every 10 minutes. However, this is not possible if a detector remains active. This procedure is repeated until no more detectors are active and the panel returns to its normal state, or until a second detector becomes active, thus elevating the pre-alarm to an alarm.
Dual-zone dependency (2-Zone Depend)
Applies to adjacent zones, for example zones 1 and 2. If a zone detects an alarm, this is evaluated as a pre-alarm. An alarm is only triggered when the second zone detects an alarm.
46 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Possible zone dependencies: – FPC‑500-2: 1&2 – FPC‑500‑4: 1&2, 3&4 – FPC‑500‑8: 1&2, 3&4, 5&6, 7&8 If you set a zone to dual-zone dependency, the other associated zone is also changed automatically.
Zones 1 to 8
3
Press zone key 3. This takes you to the Zone Config menu.
1
Press zone key 1. This takes you to the zone 1 submenu.
6
1
...
Use the zone keys to program the zone. – 1=No Delay (default setting) – 2 Int Alarm Stor 3 Alarm Verific 4 2-Det Depend 5 2-Zone Depend
Zones 2 to 8 are pre-programmed in the same way as zone 1. You can change the settings as with zone 1.
Notice!
Zones 3 and 4 are only available on the FPC‑500‑4 and
FPC‑500‑8 panels. Zones 5–8 are only available on the
FPC‑500‑8.
Configuring Inputs
In the Input Config menu, you can program the behavior of the inputs.
4.4
Conventional Fire Panel System Configuration | en 47
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Notice!
Only use buttons (no locking element) if you have programmed
inputs as Drill/Evacuate, Silence, or Reset Panel.
Access levels as per EN 54‑2 must be observed.
Notice!
Depending on the panel, there is one input on the FPC‑500‑2
and FPC‑500‑4, and two inputs on the FPC‑500‑8.
4
Press zone key 4. This takes you to the Input Config menu.
Input 1
4
Press zone key 4. This takes you to the Input Config menu.
1
Press zone key 1. This takes you to the Input 1 submenu.
7
1
...
Use the zone keys to set the programming for input
1. – 1= Not Used (default setting) – 2 Drill/Evacuate 3 Silence 4 Level 2 5 Reset Panel 6 Ext PS Fault 7 Ext Batt Fault
Notice!
You do not have to confirm the input functions on the panel.
Thus use a key switch if possible to activate inputs.
4.4.1
48 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Input 2 (FPC-500‑8 only)
4
Press zone key 4. This takes you to the Input Config menu.
2
Press zone key 2. This takes you to the Input 2 submenu.
Additional settings correspond to those for Input 1.
Configuring Outputs
In the Output Config menu, you can program the behavior of the individual fire panel outputs.
Notification Appliances
In the NAC submenu, you specify the behavior of the notification appliances. You can use NAC Zones to assign the notification appliances to particular zones. Reactive NAC specifies whether silenced notification appliances are reactivated by a new alarm in another zone. You can use NAC in test to specify whether the notification appliances are activated for 15 seconds when a zone test is performed.
!
Caution!
When assigning the zones to notification appliances, make sure
that each zone of the fire panel is assigned to at least one
notification appliance.
Zones not assigned do not trigger any alarm signaling via the
notification appliance if there is a fire.
4.4.2
4.5
4.5.1
Conventional Fire Panel System Configuration | en 49
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Notification appliance 1 zone assignment
5
Press zone key 5. This takes you to the Output Config menu.
1
Press zone key 1. This takes you to the NAC submenu.
1
Press zone key 1. This takes you to the NAC Zones submenu.
8
1
...
Use the zone keys to select the corresponding zones whose alarm you want to activate notification appliance 1. You can select multiple zones. If you press the zone key again, the selection is cancelled.
ACK
Confirm your selection.
Notification appliance 2 zone assignment
See "Notification appliance 1 zone assignment", Notification appliance 1 zone assignment, page 50.
Reactivating notification appliances
5
Press zone key 5. This takes you to the Output Config menu.
1
Press zone key 1. This takes you to the NAC submenu.
3
Press zone key 3. This takes you to the Reactive NAC submenu.
2
1
...
Press zone keys 1 or 2. 1=By Other Zone (default setting) 2 No Reactivate
50 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Notification appliance behavior in zone test
5
Press zone key 5. This takes you to the Output Config menu.
1
Press zone key 1. This takes you to the NAC submenu.
4
Press zone key 4. This takes you to the NAC in test submenu.
2
1
...
Press zone keys 1 or 2. 1 Activation 2=No Activation (default setting)
Alarm Relay
In the Alarm Relay submenu, you can specify the properties of the alarm relay. These include the Silencable and Drillable settings. You can use Silencable to specify whether the relay can be silenced manually. Drillable specifies whether the alarm relay is also activated during a manual alarm (Drill/Evac).
Alarm relay can be muted
5
Press zone key 5. This takes you to the Output Config menu.
2
Press zone key 2. This takes you to the Alarm Relay submenu.
1
Press zone key 1. This takes you to the Silencable submenu.
2
1
...
Press zone keys 1 or 2. 1 Silencable 2=Not Silencable (default setting)
4.5.2
Conventional Fire Panel System Configuration | en 51
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Alarm relay follows manual alarm
5
Press zone key 5. This takes you to the Output Config menu.
2
Press zone key 2. This takes you to the Alarm Relay submenu.
2
Press zone key 2. This takes you to the Drillable submenu.
2
1
...
Press zone keys 1 or 2. 1 Drillable 2= Not Drillable (default setting)
OC/Relay Extensions
In the OC/Relay Ext menu, you can individually set the properties of all OC/Relay outputs. The possible settings for the
OC/Relay outputs 2 to 8 correspond to those for the first OC/ Relay . The following settings are possible:
Zone = Alarm: The output is activated if the zone triggers
an alarm. Here zone 1 is assigned to output 1, etc.
Zone Normal: If the zone is not in a normal state, the
output is activated. Assignment: zone 1 to output 1 etc.
Sum Alarm: When the fire panel is in an alarm state, this
output is activated regardless of the zone.
Sum PreAlarm: When the fire panel is in a pre-alarm state,
this output is activated regardless of the zone. – Sum Fault: This output is activated if there is a fault. – Sum Disable: If a fire panel element is disabled, this output
is activated (zones, notification appliances, relays). – Sum Test: This output is activated if a zone in the fire panel
is in test mode. – Not Used: The output is not used.
4.5.3
52 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
5
Press zone key 5. This takes you to the Output Config menu.
3
Press zone key 3. This takes you to the OC/Relay Ext submenu.
1
Press zone key 1 to choose Open Collector 1.
8
1
...
Use the zone keys to make the corresponding setting. – 1=Zone = Alarm (default setting) – 2 Zone Normal 3 Sum Alarm 4 Sum PreAlarm 5 Sum Fault 6 Sum Disable 7 Sum Test 8 Not Used
The procedure for OC/Relay 2 to 8 is the same.
Displaying the Configuration
In the View Config menu, you can display the programming of the fire panel.
6
Press zone key 6. This takes you to the View Config menu.
i
Use arrow keys to scroll more quickly through the displayed programming. Hold the arrow key down to scroll through the menu in increments of 10 steps.
RESET
To exit the display, press the ESC key.
4.6
Conventional Fire Panel System Configuration | en 53
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Controlling Outputs
In the Output Control menu you can activate and deactivate the individual outputs for test purposes. When you exit operating level 3, all activations of the outputs are reset to the normal state again.
Notification appliance 1
7
Press zone key 7. This takes you to the Output Control menu.
1
Press zone key 1. This takes you to the NAC 1 submenu.
ACK
RESET
Press the ACK key.
Notification appliance 1 is activated.
Press the RESET key.
Notification appliance 1 is deactivated.
Notification appliance 2
7
Press zone key 7. This takes you to the Output Control menu.
2
Press zone key 2. This takes you to the NAC 2 submenu.
ACK
RESET
Press the ACK key.
Notification appliance 2 is activated.
Press the RESET key.
Notification appliance 2 is deactivated.
4.7
4.7.1
4.7.2
54 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Alarm Relay
7
Press zone key 7. This takes you to the Output Control menu.
3
Press zone key 3. This takes you to the Alarm Relay submenu.
ACK
RESET
Press the ACK key.
The alarm relay is activated.
Press the RESET key.
The alarm relay is deactivated.
Fault Relay
7
Press zone key 7. This takes you to the Output Control menu.
4
Press zone key 4. This takes you to the Fault Relay submenu.
ACK
RESET
Press the ACK key.
The fault relay is activated.
Press the RESET key.
The fault relay is deactivated.
OC/Relay Extension
7
Press zone key 7. This takes you to the Output Control menu.
5
Press zone key 5. This takes you to the OC/Relay Ext submenu.
4.7.3
4.7.4
4.7.5
Conventional Fire Panel System Configuration | en 55
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
1
Press zone key 1. This takes you to the OC/Relay 1 submenu.
ACK
RESET
Press the ACK key.
The OC/Relay 1 output is activated.
Press the RESET key.
The OC/Relay 1 output is deactivated.
Continue in the same way for the Open Collector outputs 2 to 8.
Control all outputs
7
Press zone key 7. This takes you to the Output Control menu.
6
Press zone key 6. This takes you to the All submenu.
ACK
RESET
Press the ACK key.
All outputs are activated.
Press the RESET key.
All outputs are deactivated.
Resetting To Delivery State
You can use Config Reset to reset the programming of the fire panel to the default values set when delivered.
Notice!
Resetting the fire panel deletes all of your changes to the
programming. The panel is reset to the default programming,
see Default Settings, page 74.
4.7.6
4.8
56 en | System Configuration Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
8
Press zone key 8. This takes you to the Config Reset menu.
ACK
RESET
Press the ACK key.
The fire panel is reset to the delivery state.
Press the RESET key.
You exit the menu without making changes.
Conventional Fire Panel System Configuration | en 57
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Fault Diagnosis
Thermal fuse, power supply unit monitoring
The integrated power supply unit is equipped with a thermal fuse. If there is an overload this will switch off the power supply. After the fuse cools off, it will switch the power on again. There is a green LED on the power supply unit. This flashes when there is an error in the power supply unit.
Thermal fuse, battery monitoring
There is a thermal fuse on the motherboard that monitors the battery current and protects against reverse polarity. When the fuse cools off, the battery current is switched on again.
Updating the panel software (firmware) via USB
You can update the panel software using the USB port on the lower left side of the main board. To do this, connect the USB port to your computer and install the programming software supplied on the CD. Follow the on-screen instructions.
5
58 en | Fault Diagnosis Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Technical Data
FPC-500‑2FPC-500‑4FPC-500
-8
Zones 2 4 8
Max. number of detectors in accordance with EN 54‑2
64 128 256
Max. number of detectors per zone in accordance with EN 54‑2
32
Max. number of extensions 0 1 2
Prog. inputs 1 2
AUX output 1
Alarm device output 2
Relay 2
Electrical Data
FPC-500‑2FPC-500‑4FPC-500
-8
Power supply voltage 230 VAC +10%/-15%, 50–
60 Hz
Current consumption 275 mA 312 mA 375 mA
AC power consumption 80 W
Operating voltage 21.4 VDC to 29 VDC
I
min
70 mA
I
max, a
0.7 A
I
max, b
2.3 A
6
6.1
Conventional Fire Panel Technical Data | en 59
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
FPC-500‑2FPC-500‑4FPC-500
-8
Zones – Voltage – Max. output current – Max. line resistance
20 VDC ±1VDC 100 mA ±5 mA
22.5 Ohm
AUX – Voltage – Max. output current – Max. line resistance – Fuse
21 VDC to 29 VDC 500 mA ±10%
22.5 Ohm
0.75 A @ 60 V
Notification appliance outputs – Voltage – Max. output current – Max. line resistance – Fuse
21 VDC to 29 VDC 500 mA ±10% per output
22.5 Ohm
0.75 A @ 60 V
Relay outputs – Breaking capacity – Max. line resistance
1 A @ 30 VDC
22.5 Ohm
Transistor outputs – Breaking capacity – Max. line resistance
No inductive loads 20 mA @ 24 VDC
22.5 Ohm
Recommended cable type Unshielded cable, 0.8-mm
cable diameter, cable cross section up to 1.5 mm
2
Batteries – Max. inner resistance – Max. current consumption – Fuse
800 mOhm
2.3 A 5 A @ 60 V
End-point voltage 21.4 V
60 en | Technical Data Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Communication parameters
FPC-500‑2FPC-500‑4FPC-500
-8
Notification appliances
Standby – A­– B+ Alarm state – A­– B+
10 V to 15 V 0 V to 0.5 V
0 V to 1 V 21 V to 29 V
Inputs
Alarm resistor 820 ohm ±5%
EOL Resistor 3900 ohm ±1%
Zones (with resistance combination)
Alarm resistor 820 ohm ±5%
910 ohm ±5% No 2-Det Depend: 680 ohm ±5%
EOL Resistor 3900 ohm ±1%
Zones (with EOL modules)
Alarm resistor 820 ohm ±5%
910 ohm ±5% No 2-Det Depend: 680 ohm ±5%
6.1.1
Conventional Fire Panel Technical Data | en 61
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Mechanical
FPC-500‑2FPC-500‑4FPC-500
-8
Dimensions (H x W x D) 351 x 351 x 90 mm
Weight 2200 g, without batteries
Housing material – Front – Back
ABS+PC ABS-FR
Housing color – Front – Back
RAL 9003 (Signal White) PANTONE 10 C (Cool Grey)
Environmental Conditions
FPC-500‑2FPC-500‑4FPC-500
-8
Protection category according to EN 60529
IP 30
Protection class as per EN 60950
II
EMC interference immunity, emissions
EN 61000-6-3
EMC interference immunity EN 50130-4
Vibrations EN 60068-2-6
Permitted operating temperature
0 °C to +40 °C
Permitted storage temperature -10 °C to +55 °C (14 °F to 131
°F)
Relative humidity Max. 95% non-condensing
6.2
6.3
62 en | Technical Data Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Information as per EN 54‑4, chapter 7.1
a) This is a power supply unit that is installed in the FPC‑500 Fire Panel. It provides power to the device and the connected peripherals and is used to charge the two connectable batteries. b) Technical data
1) Recommended power output
61 W
2) Power supply 230 VAC +10%/-15%, 50–60 Hz
Operating voltage 26 VDC to 29 VDC
3) Communication parameters
None
4) Fuse values 3.15 A/250 V
5) Batteries 2 x 7.0–7.2 Ah (max.) lead gel battery
6) Max. current
consumption
2.3 A
7) Max. battery inner
resistance
800 mOhm
8) I
min
70 mA
I
max, a
0.7 A
I
max, b
2.3 A
9) Cable parameters
Battery Cable enclosed
Board power supply Wired ex works
230-V power supply 1.5-mm2 standard cable
6.4
Conventional Fire Panel Technical Data | en 63
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
c) The power supply unit is a component of the FPC‑500 Fire Panel and is supplied preinstalled. No additional installation instructions are necessary.
1) Please refer to the information on environmental conditions in this document.
2) The power supply unit is supplied preinstalled – assembly instructions are not required.
3) For connection instructions, please refer to the FPC‑500 installation instructions. d) The power supply unit is a component of the FPC‑500 Fire Panel – there are no additional operating instructions.e) The power supply unit is a component of the FPC‑500 Fire Panel – no operation is required.f) Have maintenance and installation work carried out regularly by trained, qualified personnel. Bosch Sicherheitssysteme GmbH recommends carrying out a functional and visual check at least once a year. Replace the batteries on a regular basis. Please observe the appropriate requirements stipulated by the local authorities etc.
Options with requirements as per EN 54‑2:1997/A1:2006
The FPC‑500 provides the following options with requirements under EN 54‑2:1997/A1:2006 – Alarm counter – Test status – Output for activation of fire alarm devices – Transmission delay – Dependency of fire detection status on more than one
alarm signal – Type A dependency – Type B dependency
6.5
64 en | Technical Data Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Appendix
Brief Overview, Operating Level 1 and 2
Submenu
1 2 3
Menu operating level 1 and 2
i
1 Current
Events
1 Faults - -
2 Disablements - -
3 Test - -
4 PreAlarm - -
2 History 1 Event History - -
2 Test History - -
3 Alarm Counter - - - -
4 System Info 1 SW Release - -
2 Operation Days - -
Menu operating level 2 – code required
i
5 View Config - - - -
6 System Config 1 Date/Time - -
2 Keypad Tone 1 On
2 Off
3 Language 1 1-A - L
2 2-M - Z
7
7.1
Conventional Fire Panel Appendix | en 65
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Test menu
Submenu
1 2 3
Test menu
1 Test MMI - - - -
2 Test Zones 1 Zone 1 - -
2 Zone 2 - -
3 Zone 3 - -
4 Zone 4 - -
5 Zone 5 - -
6 Zone 6 - -
7 Zone 7 - -
8 Zone 8 - -
3 Dis/Enable 1 Zones 1 Zone 1
2 Zone 2
3 Zone 3
4 Zone 4
5 Zone 5
6 Zone 6
7 Zone 7
8 Zone 8
2 NAC ACK =YES ESC=No
3 Relays ACK =YES ESC=No
4 All ACK =YES ESC=No
7.2
66 en | Appendix Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Brief Overview, Operating Level 3
Submenu
1 2 3
1 - System Config
1 1 Date/Time
2 Keypad Tone 1 On - -
2 Off - -
3 EOL Devices 1 Resistor - -
2 Only 2W Module - -
3 With 4W Module - -
4 Zone Reset 1 Cut For 1 1 s
2 5 s
3 10 s
4 15 s
5 20 s
2 Stabilize For 1 1 s
2 5 s
3 10 s
4 15 s
5 20 s
5 Aux Power 1 With Zone - -
2 With Panel - -
3 Never - -
6 Faults 1 Latching - -
7.3
Conventional Fire Panel Appendix | en 67
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Submenu
1 2 3
2 Non Latching - -
7 Code 1 Level Code 2 - -
2 Level Code 3 - -
8 Test History 1 Log Enabled - -
2 Log Disabled - -
Submenu
1 2 3
2 - Delay Config
2 1 Day Mode Off 1 Manual - -
2 Automatic Off Time: : 17:00
2 Alarm Verific 1 ACK Within 1 30 s
2 60 s
3 90 s
4 120 s
2 Invest Time 1 1 min Delay
2 2 min Delay
3 3 min Delay
4 4 min Delay
5 5 min Delay
6 6 min Delay
7 7 min Delay
8 8 min Delay
68 en | Appendix Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Submenu
1 2 3
3 NAC 1 1 Alert
2 Evacuate
3 Int Alarm Stor 1 Reset After 1 1 s
2 5 s
3 10 s
4 15 s
5 20 s
2 Total Delay - -
4 Power Fault 1 No Delay - -
2 1 min Delay - -
3 5 min Delay - -
4 10 min Delay - -
5 15 min Delay - -
Submenu
1 2 3
3 - Zone Config
3 1 Zone 1 1 No Delay - -
2 Int Alarm Stor - -
3 Alarm Verific - -
4 2-Det Depend - -
5 2-Zone Depend - -
2 Zone 2 1 No Delay - -
Conventional Fire Panel Appendix | en 69
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Submenu
1 2 3
3 Zone 3 No Delay (FPC‑500‑4 /-8)
4 Zone 4 No Delay (FPC‑500‑4 /-8)
5 Zone 5 No Delay (FPC‑500‑8)
6 Zone 6 No Delay (FPC‑500‑8)
7 Zone 7 No Delay (FPC‑500‑8)
8 Zone 8 No Delay (FPC‑500‑8)
4 - Input Config
4 1 Input 1 1 Not Used - -
2 Drill/Evacuate - -
3 Silence - -
4 Level 2 - -
5 Reset Panel - -
6 Ext PS Fault - -
7 Ext Batt Fault - -
2 Input 2 See Input 1 (FPC‑500‑8)
Submenu
1 2 3
5 - Output Config
5 1 NAC 1 NAC Zones 1 - -
2 NAC Zones 2 - -
3 Reactive NAC 1 By Other Zone
2 No Reactivate
70 en | Appendix Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Submenu
1 2 3
4 NAC in test 1 Activation
2 No Activation
2 Alarm Relay 1 Silencable 1 Silencable
2 Not Silencable
2 Drillable 1 Drillable
2 Not Drillable
3 OC/Relay Ext 1 OC/Relay 1 1 Zone = Alarm
2 Zone Normal
3 Sum Alarm
4 Sum PreAlarm
5 Sum Fault
6 Sum Disable
7 Sum Test
8 Not Used
2 OC/Relay See OC/Relay 1
3 OC/Relay See OC/Relay 1
4 OC/Relay See OC/Relay 1
5 OC/Relay See OC/Relay 1
6 OC/Relay See OC/Relay 1
7 OC/Relay See OC/Relay 1
8 OC/Relay See OC/Relay 1
6 - View Config
Conventional Fire Panel Appendix | en 71
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Submenu
1 2 3
7 - Output Control
7 1 NAC 1 ACK =On ESC=Off - -
2 NAC 2 ACK =On ESC=Off - -
3 Alarm Relay ACK =On ESC=Off - -
4 Fault Relay ACK =On ESC=Off - -
5 OC/Relay Ext 1 OC/Relay 1 ACK =On ESC=Off
2 OC/Relay 2 ACK =On ESC=Off
3 OC/Relay 3 ACK =On ESC=Off
4 OC/Relay 4 ACK =On ESC=Off
5 OC/Relay 5 ACK =On ESC=Off
6 OC/Relay 6 ACK =On ESC=Off
7 OC/Relay 7 ACK =On ESC=Off
8 OC/Relay 8 ACK =On ESC=Off
6 All ACK =On ESC=Off - -
8 - Config Reset
Navigation in the menu
i
Press the arrow key to scroll up in the menu.
Press the arrow key to scroll down in the menu.
ACK
Press the ACK key to confirm your selection.
72 en | Appendix Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
RESET
ESC
Press the ESC key to exit the selection without making a change or to jump up a menu level.
RESET
ESC
Hold the ESC key down for 2 seconds to jump to the uppermost menu level.
8
1
...
In the menu, each menu item has a number from 1 to 8 preceding it. Use the zone keys to select the desired menu item in the menu.
Conventional Fire Panel Appendix | en 73
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Default Settings
Menu item Default setting
1 System Config
2 Keypad Tone On
3 EOL Devices Resistor
4 Zone Reset
1 Cut For 5 s
2 Stabilize For 5 s
5 Aux Power With Zone
6 Faults Latching
8 Test History Log Enabled
2 Delay Config
1 Day Mode Off Manual
2 Alarm Verific
1 ACK Within 60 s
2 Invest Time 1 min
3 NAC 1 Evacuate
3 Int Alarm Stor
1 Reset After 10 s
4 Power Fault No Delay
3 Zone Config
1 Zone 1 No Delay
...
4 Input Config
7.4
74 en | Appendix Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Menu item Default setting
1 Input 1 Not Used
...
5 Output Config
1 NAC
1 NAC Zones All zones
2 NAC Zones All zones
3 Reactive NAC By Other Zone
4 NAC in test No Activation
2 Alarm Relay
1 Silencable Not Silencable
2 Drillable Not Drillable
3 OC/Relay Ext
1 OC/Relay 1 Zone = Alarm
Conventional Fire Panel
Appendix | en 75
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Event Memory
Message Meaning
Drill/Evacuate A manual alarm has been triggered on the
panel.
Zone Alarm Zone # has triggered an alarm.
Zone PreAlarm Zone # has triggered a pre-alarm.
Zone Open Zone # is interrupted.
Zone Short Zone # has a short-circuit.
Zone Normal Zone # is in the normal state. (Fault or alarm
eliminated)
Zone Disabled Zone # was enabled.
Zone Enabled Zone # was enabled.
Input Open Input # interrupted.
Input Short Input # short-circuit.
Input Normal Input # normal.
Aux Power Short
Short-circuit in the AUX power supply
Aux Power Normal
Error in the AUX power supply eliminated.
NAC Open Notification appliance #, line interrupted
NAC Short Notification appliance #, short-circuit on line.
NAC Normal Notification appliance # normal. (Fault was
eliminated)
NAC Enabled Notification appliances re-enabled.
NAC Disabled Notification appliances disabled.
7.5
76 en | Appendix Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Message Meaning
Relays Enabled Relays re-enabled.
Relays Disabled Relays disabled.
Battery Fault Fault in the battery power supply.
Battery Restore Battery power supply was restored.
Mains Fault Fault in the 230 V power supply.
Mains Restore 230 V power supply was restored.
Ext PS Fault Fault in external power supply unit.
Ext PS Normal Fault in external power supply unit resolved.
Ext BATT Fault Fault in external battery.
Ext BATT Normal
Fault in external battery resolved.
Sys Load Fault Current consumption of panel and all
connected peripherals is above 3.5 A.
Sys Load Normal
Current consumption is back in permitted range.
System Fault System fault
Panel boot-up Panel has been restarted.
Reset Panel Panel has been reset.
Night Mode Panel has switched to night mode.
Day Mode Panel has switched to day mode.
Earth Fault Grounding fault.
Earth Normal Fault in grounding resolved.
Level Enter Operating level # entered.
Level Exit Operating level # exited.
Conventional Fire Panel Appendix | en 77
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
Message Meaning
Silenced An alarm has been silenced.
Unsilenced A silenced alarm has been reactivated.
Test Memory Messages
Message Meaning
Zone Start Zone # set to test mode.
Zone Test Zone # successfully tested.
Zone End Zone # test mode exited.
7.6
78 en | Appendix Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Index
A
Access model, 12 Alarm relay
Programming, 51
AUX;Reset settings, 37
B
Buzzer beep
Setting, 34
C
Cable entries, 13 Code
Change;Password:Change, 38 Code;Password, 31 Confirmation time
Setting, 41
D
Date/Time
Setting, 34 Default settings, 74 Delay
Power supply fault;Power
supply:Fault delay, 44
Delay settings, 39
E
Emergency power
supply;Batteries, 17 Extensions, 18
F
Fault handling;Store faults, 37
H
Housing
Installing, 15 Open, 14
I
Input, 20
Programming a function, 48 Installation location, 13 Intermediate alarm storage
Setting, 42 Invest time
Setting, 41
M
Mains supply, 16
N
Navigating
Arrow keys, 33 Navigation, 72
Zone keys, 33, 73 Notification appliance, 24
Assignment to zones, 50
Behavior in zone test, 51
Specifying reactivation, 50
Conventional Fire Panel Index | en 79
Bosch Sicherheitssysteme GmbH 2014.06 | 7.0 | F.01U.172.980
O
Operating level 3
Automatic exit, 31 Calling up, 31
Exiting, 32 Operation, 33 Outputs
Activation for testing, 54
Programming, 49
Programming;Transistor
outputs:Programming;Relay outputs:Programming, 52
P
Programming
Resetting to delivery state, 56
R
Relay outputs;Alarm relay;Fault
relay, 25
S
Screw terminals, 19 Submenus
Exiting, 34
T
Terminal resistance;Terminal
element;EOL module;End-Of-
Line module, 20, 21 Test log
Setting, 39
Z
Zone reset
Disconnection duration, 36 Setting times, 35 Stabilization time, 36
Zone termination
Setting, 35
Zone types, 44
dual-detector
dependency;dual-detector dependency, 46
Dual-zone dependency;dual-
zone dependency, 46
Intermediate alarm
storage;Intermediate alarm storage, 45
Manual alarm
verification;Manual alarm verification, 45
No delay;No delay, 45
Zones
Specify zone type, 47
80 en | Index Conventional Fire Panel
2014.06 | 7.0 | F.01U.172.980 Bosch Sicherheitssysteme GmbH
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5 85630 Grasbrunn Germany
www.boschsecurity.com
© Bosch Sicherheitssysteme GmbH, 2014
Loading...