12 en | Programming
Automatic Fire Detectors LSN improved
version
F.01U.003.448 | 8.0 | 2011.10 Operation Guide Bosch Sicherheitssysteme GmbH
4.2 FAP-DOT420 / FAP-OT 420
4.3 FAP-DO420 / FAP-O 420 / FAP-O 420-KKW
NOTICE! The default setting of the FAP-DOT 420 and FAP-OT 420 detector types in RPS and
WinPara is "Office (day mode)". For a description of this setting, see the below table.
Selectable installation locations in the
programming software (WinPara and
FSP-5000-RPS)
Detector Type Sensitivity
Thermomax
(T
max
)
Optical
(O)
Office (after hours) O, T
max
, T
diff
High (A2) High
Office (smoker)/waiting room/restaurant/
meeting room
O, T
max
, T
diff
High (A2) Low
Office (day mode)
= default setting
O, T
max
, T
diff
Low (B) Medium
EDP room O, T
max
, T
diff
High (A2) High
Production location O, T
max
, T
diff
Low (B) Low
Garage
– FAP-OT 420
– FAP-DOT420
T
max
, T
diff
T
max
, T
diff
High (A2)
High (A2)
-
Low
High storage warehouse without vehicle traffic
with combustion engine
O, T
max
, T
diff
Low (B) High
Conference hall/waiting room/fairground O, T
max
, T
diff
High (A2) Low
Kitchen/casino/restaurant during active operation T
max
Low (B) -
Warehouse with vehicle traffic O, T
max
, T
diff
Low (B) Low
Rate of rise only (optical sensor off)** T
max
, T
diff
High (A2) -
Optical only (thermal sensor off)** O - Low
Fixed temperature heat only (optical sensor off)** T
max
High (A2) -
Schools/kindergarten O, T
max
, T
diff
High (A2) Medium
Theatre/concert hall O, T
max
, T
diff
High (A2) Medium
O = optical sensor (dual-optical in FAP-DOT420 detectors)
T
max
= thermal maximum unit
T
diff
= thermal differential unit
** FSP-5000-RPS only
For details on installation height, see Section 4.4 FAH-T 420/FAH-T 420-KKW, page 13
NOTICE!
The FAP-DOT420 detector is not supported by the WinPara programming software.
NOTICE! The default setting of the FAP-DO 420 and FAP-O 420 detector types in RPS and
WinPara is "Medium". For a list of possible installation locations and corresponding sensitivity
settings, see the below table.