Bosch F.01U.505.983 Datasheet

Communications Systems | LBC 3086/41 Ceiling Loudspeaker
LBC 3086/41 Ceiling Loudspeaker
Suitable for speech and music reproduction
Flush-mounting in ceiling cavity
Easy to install
Simple power setting
Optional certified fire dome
Unobtrusive in virtually all interiors
Complies with international installation and safety
regulations
BS‑5839‑8, EN 54‑24 and EN 60849 compliant
Voice alarm loudspeakers are specifically designed for use in buildings where performance of systems for verbal evacuation announcements is governed by regulations. The LBC 3086/41 is designed for use in voice alarm systems and is compliant with British standard BS 5839-8.

Functions

The loudspeaker unit is a 6 W, dual-cone loudspeaker with an integrated circular metal grille. A 100 V matching transformer is mounted on the back. The appearance and neutral white RAL color have been selected to be unobtrusive in virtually all interiors.
The loudspeaker has built-in protection to ensure that, in the event of a fire, damage to the loudspeaker does not result in failure of the circuit to which it is connected. In this way, system integrity is maintained, ensuring loudspeakers in other areas can still be used to inform people of the situation. The loudspeaker has ceramic terminal blocks, thermal fuse and heat-resistant, high­temperature wiring. It can also be fitted with an optional fire-dome to increase protection of the cable termination.

Certifications and Approvals

All Bosch loudspeakers are designed to withstand operating at their rated power for 100 hours in accordance with IEC 268-5 Power Handling Capacity (PHC) standards. Bosch has also developed the Simulated Acoustical Feedback Exposure (SAFE) test to demonstrate that they can withstand two times their rated power for short durations. This ensures extra reliability under extreme conditions, leading to higher customer satisfaction, longer operating life, and much less chance of failure or performance deterioration.
Region Certification
Europe CE
Poland CNBOP
Safety acc. to EN 60065
Emergency acc. to BS 5839‑8 / EN 54‑24 / EN 60849
* Water and dust protection
* only in combination with the LBC 3081/02 Fire Dome
acc. to EN 60529‑IP32
www.boschsecurity.com
2 | LBC 3086/41 Ceiling Loudspeaker
90
3.54

Installation/Configuration Notes

Installation
The assembly is quickly installed into a hole in the ceiling cavity. A separate mounting ring, secured by three integral spring-loaded ceiling locking clamps (for ceilings and wall boards from 9 to 25 mm thick) holds it in place. The clamps are provided with protective rubbers to avoid damaging soft ceiling material. A circular template for marking a 196 mm (7.7 in) diameter hole is included with the loudspeaker. The loudspeaker unit is held in the mounting ring with a bayonet fitting.
Terminal Block
The unit has a three-way terminal block with screw connections suitable for loop-through wiring. Four primary taps are provided on the matching transformer to allow selection of nominal full-power, half-power, quarter-power or eighth power radiation (i.e. in 3 dB steps).
LBC 3081/02 Fire Dome Assembly
During a fire, the ceiling cavity in which loudspeakers are installed can allow flames to spread throughout a building. To prevent fire entering the caving via the loudspeaker, the ceiling loudspeaker can be fitted with a protective steel fire dome (LBC 3081/02).
Dimensions in mm (in)
LBC 3086/41 with LBC 3081/02 fire dome assembly
Circuit diagram
LBC 3086/41 with LBC 3081/02 fire dome assembly dimensions in mm (in)