Communications Systems | LBB 442x/xx Power Amplifiers
LBB 442x/xx Power Amplifiers
There are four types of power amplifier units in the Praesideo product range. These differ in the number of amplifier channels per frame: one, two, four, or eight. The overall power rating is 500 watts for all of the amplifiers.
The power amplifiers can be set to 100 V, 70 V and 50 V output tappings. They have short-to-ground and shortcircuit detection functions, and can generate their own pilot tone for supervision purposes.
The power amplifiers receive input signals over the network. They also have two auxiliary audio inputs (four for LBB 4428/00) for local audio. Their eight control inputs are freely programmable for system actions, and priorities can be assigned to these inputs. Each control input has the ability to monitor the attached line for open and short-circuits. Control outputs are freely programmable for faults and call related actions.
The 2 x 16-character display and the rotary control enable local status enquiries. The display shows the VU-meter reading, when the audio monitoring mode is active. Audio can be monitored by headphone.
1, 2, 4, or 8 audio outputs (selection from 100 / 70 / 50 V outputs)
Audio processing and delay for each amplifier channel
Amplifier supervision and spare amplifier switching
Loudspeaker line and loudspeaker supervision (LBB 4428/00 only line supervision)
Eight control inputs and 1, 2, 4 or 8 control outputs
Supervision of line attached to control inputs
Automatic volume control
Two audio inputs (4 audio inputs for LBB 4428/00)
Redundant network connection
The units are self-monitoring and continually report their status to the network controller. They support both single branch and redundant loop cabling. The amplifiers have a changeover facility for spare power amplifier switching. Changeover relays are included with the units. The amplifiers have a 48 V DC back-up supply input.
The digital audio processing can handle three parametric equalization sections and two shelving equalization sections per channel with configurable audio delay.
Controls and indicators
•2 x 16-character LCD for status display
•Rotary/push control button
•Mains switch
Interconnections
•Mains input
•Battery backup input
•Two system network connections
•Two mic/line inputs (four for LBB 4428/00)
•100 V, 70 V or 50 V outputs (for each amplifier channel)
•50 V output
•Eight programmable control inputs
•Control output (for each amplifier channel)
•Headphone output
•Spare amplifier connection (for each amplifier channel)
www.boschsecurity.com
2 | LBB 442x/xx Power Amplifiers
Region |
Certification |
|
Europe |
CE |
CE |
|
|
Traction |
|
TUEV- |
TUV Certificate IEC60849 |
|
SUED |
|
|
GL |
GL-SOLAS |
Safety |
acc. to IEC 60065-98 |
Rear view of LBB 4421/10 Power Amplifier 1 x 500 W |
|
Immunity |
acc. to EN 55103 2 |
/ EN 50130 4 |
|
Emissions |
acc. to EN 55103-1 |
/ FCC-47part 15B |
|
EVAC (TÜV certified) |
acc. to IEC 60849 |
|
|
|
9 |
1 |
|
|
10 |
2 |
6 |
3 |
11 |
|
7 |
|
12 |
|
8 |
1 Audio inputs, 2 x or 4 x
2Control inputs
3Plastic optical fiber network
4 Loudspeaker outputs, 1 x, 2 x, 4 x, 8 x
5Spare amplifier input
6 Control outputs, 1 x, 2 x, 4 x, 8 x
7Mains input
8 48 V backup supply
9Display and control
10Network processor and DSP
11Network redundancy switching
12Power supply
4
5Rear view of LBB 4422/10 Power Amplifier 2 x 250 W
Rear view of LBB 4424/10 Power Amplifier 4 x 125 W
Rear view of LBB 4428/00 Power Amplifier 8 x 60 W