Communications Systems | PLN 24CH12 24 V and PRS 48CH12 48 V Battery Chargers
PLN 24CH12 24 V and PRS 48CH12 48 V
Battery Chargers
www.boschsecurity.com
u 12 A battery charger
u 6x 40 A, 3x 5 A outputs
u 150 A back up current
u Fully supervised, EN 54 4 certified
u Under voltage and over voltage protection
The PLN 24CH12 and PRS 48CH12 Battery Chargers are designed for public address and emergency sound systems, to assure that the system batteries are always charged. Rack mountable, the unit charges lead acid batteries and simultaneously provides 24 V or 48 V for system components that use 24 V or 48 V exclusively. These chargers are fully compliant and certified to EN 54 4. The battery chargers are premium quality, intelligent, microprocessor controlled devices.
Functions
Performance
The maximum charger current is 12 A for charging the battery. The maximum battery capacity, according to EN 54 4, is therefore 225 Ah, minimum size is 86 Ah. The maximum output of the back up power system is 150 A.
The charger has an input voltage range of 195 V to 264 V, and a power factor corrector. The charger features automatic shutoff when the battery voltage is too low, to prevent battery damage. It also features over voltage protection, protection against wrong battery polarity and short circuit protection. The
outputs are protected by fuses. The power supply takes a resistance measurement of the battery including connections every 4 hours.
The charger comes with a temperature sensor that is used to adjust the charging voltages.
The charger has additional 24 V or 48 V (depending on model) auxiliary outputs, to supply power to equipment that needs 24 V or 48 V as primary power. The current capacity of these outputs is 5 A per output.
The charger has relay outputs to signal a mains fault, battery fault and charger output voltage fault.
Controls and indicators
•Mains status LED
•Battery status LED
•Output voltage fault LED
2 | PLN 24CH12 24 V and PRS 48CH12 48 V Battery Chargers
Interconnections
•6 main outputs for the system, each with their own fuse
•3 auxiliary outputs for peripherals, system components that always use 24/48 V with a lower current need
•Fault relays
•Battery connection
Certifications and approvals
Safety |
|
acc. to EN 60950 1 |
|
|
|
EMC |
|
EN 61000 6 1 |
|
|
EN 61000 6 2 |
|
|
EN 61000 6 3 |
|
|
EN 61000 6 4 |
|
|
EN 55022 class B |
|
|
|
Evacuation |
|
acc. to EN 54 4 |
|
|
EN 12101 10 class A, part 10: power |
|
|
supplies. |
|
|
CE CPD: |
|
|
PLN 24CH12: 0333 CPD 075381 1 |
|
|
PRS 48CH12: 0333 CPD 075383 1 |
|
|
|
Immunity |
|
acc. to EN 55130 1/2 |
|
|
|
Emission |
|
acc. to EN 55103 4 |
|
|
|
|
|
|
Region |
Certification |
|
|
|
|
Europe |
CPD |
|
|
|
|
Installation/configuration notes
•6 main outputs, 40 A (32 A GG fuse) per output.
•3 auxiliary outputs, 5 A (5 AT fuse) per output.
•The maximum total back up current is 150 A (9 outputs).
•The maximum charger output current to the battery and outputs combined is 12 A.
Parts included
Quantity Component
1PLN 24CH12 24 V Battery Charger or PRS 48CH12 48 V Battery Charger
1Mains plug
1Installation and User Instructions
1Temperature sensor with cable
Technical specifications
Electrical
Mains power supply
Voltage |
195 to 264 VAC, 50 to 60Hz |
|
|
Input current |
2 A |
(PLN 24CH12) |
|
|
|
Input current |
4 A |
(PRS 48CH12) |
|
|
|
Power consumption |
380 W maximum |
(PLN 24CH12) |
|
|
|
Power consumption |
760 W maximum |
(PRS 48CH12) |
|
|
|
Performance |
|
(PLN 24CH12) |
|
|
|
Voltage min. |
21.6 VDC (auto shutdown) |
|
|
Voltage max. |
28.5 VDC |
|
|
Performance |
|
(PRS 48CH12) |
|
|
|
Voltage min. |
43.2 VDC (auto shutdown) |
|
|
Voltage max. |
56.9 VDC |
|
|
Performance |
|
(PLN 24CH12 and |
|
PRS 48CH12) |
|
|
|
Max. charge current |
12 A |
|
|
Max. system current (Ib) |
150 A |
|
|
Main outputs (6 x) |
|
|
|
Voltage |
24 or 48 VDC (battery voltage) |
|
|
Current |
40 A |
|
|
Auxiliary outputs (3 x) |
|
|
|
Voltage |
24 or 48 VDC (battery voltage) |
|
|
Current |
5 A |
|
|
Fault outputs (3 x) |
|
|
|
Rating |
24 V/1 A, 120VAC/500 mA voltage free |
|
|
Contacts |
Normally energized (failsafe) |
|
|
Mechanical |
|
|
|
Dimensions (H x W x D) |
88 x 430 x 260 mm |
|
(19" wide, 2U high) |
|
|
Input connections |
Screw terminal |
(connect to battery) |
|
|
|
Output connections |
10 x pluggable screw connector |
(connect to system) |
|
|
|
Weight |
Approx. 6 kg |
|
|