Bosch F.01U.214.760 Datasheet

Bosch F.01U.214.760 Datasheet

Communications Systems | PLN 24CH12 24 V and PRS 48CH12 48 V Battery Chargers

PLN 24CH12 24 V and PRS 48CH12 48 V

Battery Chargers

www.boschsecurity.com

u 12 A battery charger

u 6x 40 A, 3x 5 A outputs

u 150 A back up current

u Fully supervised, EN 54 4 certified

u Under voltage and over voltage protection

The PLN 24CH12 and PRS 48CH12 Battery Chargers are designed for public address and emergency sound systems, to assure that the system batteries are always charged. Rack mountable, the unit charges lead acid batteries and simultaneously provides 24 V or 48 V for system components that use 24 V or 48 V exclusively. These chargers are fully compliant and certified to EN 54 4. The battery chargers are premium quality, intelligent, microprocessor controlled devices.

Functions

Performance

The maximum charger current is 12 A for charging the battery. The maximum battery capacity, according to EN 54 4, is therefore 225 Ah, minimum size is 86 Ah. The maximum output of the back up power system is 150 A.

The charger has an input voltage range of 195 V to 264 V, and a power factor corrector. The charger features automatic shutoff when the battery voltage is too low, to prevent battery damage. It also features over voltage protection, protection against wrong battery polarity and short circuit protection. The

outputs are protected by fuses. The power supply takes a resistance measurement of the battery including connections every 4 hours.

The charger comes with a temperature sensor that is used to adjust the charging voltages.

The charger has additional 24 V or 48 V (depending on model) auxiliary outputs, to supply power to equipment that needs 24 V or 48 V as primary power. The current capacity of these outputs is 5 A per output.

The charger has relay outputs to signal a mains fault, battery fault and charger output voltage fault.

Controls and indicators

Mains status LED

Battery status LED

Output voltage fault LED

2 | PLN 24CH12 24 V and PRS 48CH12 48 V Battery Chargers

Interconnections

6 main outputs for the system, each with their own fuse

3 auxiliary outputs for peripherals, system components that always use 24/48 V with a lower current need

Fault relays

Battery connection

Certifications and approvals

Safety

 

acc. to EN 60950 1

 

 

 

EMC

 

EN 61000 6 1

 

 

EN 61000 6 2

 

 

EN 61000 6 3

 

 

EN 61000 6 4

 

 

EN 55022 class B

 

 

 

Evacuation

 

acc. to EN 54 4

 

 

EN 12101 10 class A, part 10: power

 

 

supplies.

 

 

CE CPD:

 

 

PLN 24CH12: 0333 CPD 075381 1

 

 

PRS 48CH12: 0333 CPD 075383 1

 

 

 

Immunity

 

acc. to EN 55130 1/2

 

 

 

Emission

 

acc. to EN 55103 4

 

 

 

 

 

Region

Certification

 

 

Europe

CPD

 

 

 

Installation/configuration notes

6 main outputs, 40 A (32 A GG fuse) per output.

3 auxiliary outputs, 5 A (5 AT fuse) per output.

The maximum total back up current is 150 A (9 outputs).

The maximum charger output current to the battery and outputs combined is 12 A.

Parts included

Quantity Component

1PLN 24CH12 24 V Battery Charger or PRS 48CH12 48 V Battery Charger

1Mains plug

1Installation and User Instructions

1Temperature sensor with cable

Technical specifications

Electrical

Mains power supply

Voltage

195 to 264 VAC, 50 to 60Hz

 

 

Input current

2 A

(PLN 24CH12)

 

 

 

Input current

4 A

(PRS 48CH12)

 

 

 

Power consumption

380 W maximum

(PLN 24CH12)

 

 

 

Power consumption

760 W maximum

(PRS 48CH12)

 

 

 

Performance

 

(PLN 24CH12)

 

 

 

Voltage min.

21.6 VDC (auto shutdown)

 

 

Voltage max.

28.5 VDC

 

 

Performance

 

(PRS 48CH12)

 

 

 

Voltage min.

43.2 VDC (auto shutdown)

 

 

Voltage max.

56.9 VDC

 

 

Performance

 

(PLN 24CH12 and

 

PRS 48CH12)

 

 

 

Max. charge current

12 A

 

 

Max. system current (Ib)

150 A

 

 

Main outputs (6 x)

 

 

 

Voltage

24 or 48 VDC (battery voltage)

 

 

Current

40 A

 

 

Auxiliary outputs (3 x)

 

 

 

Voltage

24 or 48 VDC (battery voltage)

 

 

Current

5 A

 

 

Fault outputs (3 x)

 

 

 

Rating

24 V/1 A, 120VAC/500 mA voltage free

 

 

Contacts

Normally energized (failsafe)

 

 

Mechanical

 

 

 

Dimensions (H x W x D)

88 x 430 x 260 mm

 

(19" wide, 2U high)

 

 

Input connections

Screw terminal

(connect to battery)

 

 

 

Output connections

10 x pluggable screw connector

(connect to system)

 

 

 

Weight

Approx. 6 kg

 

 