Intrusion Alarm Systems | DX4010V2 USB/Serial Interface Module
DX4010V2 USB/Serial Interface Module
www.boschsecurity.com
u RS-232/USB connectivity
u Enhanced direct connection for Remote
Programming Software (RPS)
u RJ-16 data bus
The DX4010V2 USB/Serial Interface Module creates a
local connection between compatible control panels
and approved applications. The module connects to
the control panel’s data bus which provides power and
data.
System overview
u Transparent enclosure
u Diagnostic light emitting diodes (LEDs)
1. A control panel’s option or SDI bus through the data
bus connector or terminal block connection.
2. A PC for RPS, BIS, or other third party applications
through an RS-232 or USB connection.
3. A serial printer or parallel printer with a converter
cable box (not shown) through the RS-232 connector
with a compatible control panel. Refer to
Compatibility Information for details.
Functions
RJ-16 Data Bus and RS-232/USB Connectivity
Use the RJ-16 data bus connector for a remote
programming connection. Use the DB9 DTE RS-232
connector to connect to approved RS‑232 devices. Use
a USB-A to USB-B cable to connect to a USB port.
Transparent enclosure
The diagnostic LEDs show through the transparent
enclosure, making troubleshooting easy and
convenient.
Diagnostic LEDs
There are four diagnostic LEDs that provide
information about the transmission and receipt of
data.
The DX4010V2 Serial Interface Module connects to:
Two Red LEDs Function
BUS RX Receiving data from control panel
2 | DX4010V2 USB/Serial Interface Module
BUS TX Transmitting data to control panel
Two Green LEDs Function
SER RX Receiving data from serial device
SER TX Transmitting data to serial device
DIP Switches
Use the external DIP switches to easily assign an
address to the DX4010V2 Serial Interface Module.
Certifications and approvals
This product is also designed to comply with the certifications and
standards listed here:
Region Certification
Australia C-Tick
United States FCC
Canada IC
Region Certification
Europe CE 2004/108/EC EMC Directive (EMC),
1006/95/EC Low-Voltage Directive
(LVD); 2011/65/EU Restriction of the
use of certain hazardous substances in
electrical and electronic equipment
[DX4010V2]
Installation/configuration notes
Compatibility Information
Applications and RS-232 Devices
SDI Bus Control Panels (version 6.0 or higher)
United States • All G Series control panels
• D7212, D7412, D9412
• D9112
Australia • D9412GV2-AU
Option Bus Control Panels
Europe • DS7400Xi (version 2.02 or higher)
• DS7220, DS7240, DS7240V2, and
DS7220V2
Australia • CC7240-AP
United States • D4412 and D6412
The DX4010V2 Serial Interface Module replaces the
following modules:
United States D9133 Serial
Interface Module
For use with BIS, PC9000, or
other third party applications
on SDI bus control panels.
D9133DC Serial
Interface Module
For use with RPS or other
third party applications on
SDI bus control panels.
United States,
Europe, and
China
D9533 RS-232
Serial Interface
Module
DX4010/
DX4010i RS-232
Serial Interface
For use with RPS, CMS
7000*, or printers on option
bus control panels
For use with RPS,
CMS 7000*, or printers on
option bus control panels.
Module
*CMS 7000 is available in China only.
United States RPS: Supported on all
compatible control panels.
PC9000: Supported on all the
following control panels:
D9412G, D7412G,
D7212G, D9112, D7412,
D7212.
Building Integration
Software (BIS):
Supported on the following
SDI bus control panels
(version 6.3 and higher):
All G Series control panels
including D9412GV2‑AU
Austrailia Building Integration
D9412GV2‑AU
Software (BIS):
China CMS 7000: Supported on DS7400Xi
Control Panels (option bus)
set at Mode 18 (version
3.09 or higher).
All Printers: Supported on option bus
control panels.
Technical specifications
Environmental Considerations
Operating Temperature: 0°C to +50°C
(+32°F to +122°F)
Relative Humidity: 5% to 85% at +30°C (+86°F)
non‑condensing
Power Requirements
Current (Maximum): 55 mA nominal, 60 mA with LED
Voltage (Operating): 8 VDC to 14 VDC
Ordering information
DX4010V2 USB/Serial Interface Module
Provides a local connection between compatible
control panels and approved applications.
Order number DX4010V2