Bosch DS7457I, DS7457IF Specsheet

Intrusion Alarm Systems | DS7457i Series Single‑zone Input Modules
DS7457i Series Single‑zone Input Modules
www.boschsecurity.com
u Power-limited and supervised input zones
u Compact enough to fit within most back boxes and
enclosures
The DS7457i Series Single‑zone Input Modules includes the DS7457i, the DS7457i-CHI, and the DS7457iF. Each model has a supervised input zone for connecting normally-open (NO) or normally-closed (NC) contacts. The DS7457i Series supervises the contacts using 47 kΩ end-of-line(EOL) resistors. Each model operates with compatible multiplex expansion modules and occupies one multiplex zone address on the system. The DS7457i and the DS7457i-CHI are designed for intrusion applications while the DS7457iF is designed for fire applications.
Certifications and approvals
Region Certification
Europe CE 2004/108/EC EMC Directive (EMC),
2006/95/EC Low-Voltage Directive (LVD)
Belgium INCERT B-509-0005 (DS7457i only)
USA UL DS7457i and DS7457iF: AMCX: Central
Station Alarm Units (UL1610, UL1635), AOTX: Local Alarm Units (UL464, UL609), APAW: Police Station Alarm Units (UL365, UL464)
Region Certification
UL DS7457iF only: NBSX: Household Bur-
glar Alarm System Units (UL1023), UOXX: Control Unit Accessories, System (UL864, 9th edition), UTOU: Control Units and Accessories - Household Sys­tem Type (UL985)
CSFM DS7457iF: 7165-1615: 0113 FIRE
ALARM CONTROL UNIT (COMMERCIAL)
CSFM 7165-1615:0119
CSFM 7167-1615:0239
Installation/configuration notes
Compatibility Information
Control Panels D9412GV3, D7412GV3, and D7212GV3
Control Panels
D9412GV2, D7412GV2, and D7212GV2
Control Panels
D9412G , D7412G, and D7212G Control
Panels
D9412, D7412, and D7212 Control Panels
DS7400Xi Control Panel
2 | DS7457i Series Single‑zone Input Modules
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2013 | Data subject to change without notice 2541132811 | en, V4, 01. Oct 2013
Multiplex Modules D8125MUX Multiplex Bus Interface
DS7430 Multiplex Expansion Module
DS7436 Multiplex Expansion Module
The DS7457i Series Modules require a multiplex expansion module to connect to the control panels.
Wiring Considerations
Maximum Impedance: 4.05 Ω at +20°C (+68°F) nominal
Distance (approximate) Size
76 m 0.65 mm
193 m 1.02 mm
250 ft 22 AWG
600 ft 18 AWG
Refer to the intended control panel’s installation guide for multiplex wiring requirements. The recommended wiring to the control panel is quad (four-wire) cable. Do not use shielded or twisted pair cable.
Notice
If used in fire applications, 18 AWG wire is required.
Ordering information
DS7457i Single‑zone Input Module
Connects normally‑open (NO) or normally‑closed (NC) contacts, and supervises the contacts using 47 kΩ end-of-line(EOL) resistors. Designed for intrusion applications.
Order number DS7457i
DS7457iF Single‑zone Input Module
Connects normally‑open (NO) or normally‑closed (NC) contacts, and supervises the contacts using 47 kΩ end-of-line(EOL) resistors. Designed for fire applications.
Order number DS7457iF
Parts included
Quantity Component
1 Single-zone input module
1 Literature pack
Technical specifications
Circuit Parameters
Initiating Circuit Type (DS7457iF): Class B (Style A)
Signaling Line Circuit Type: Class B (Style 4)
Environmental Considerations
Temperature (Operating): 0°C to +49°C (+32°F to +120°F)
Power Requirements
Current Draw: 0.5 mA maximum
Voltage (Operating): 8 VDC peak (minimum)
Loading...