Turning On (arming) your System using the DS7445/DS7445i
or DS7447/DS7447E Keypad
Normal Arming[PIN] + [On]
Perimeter Arming, no entry delay[PIN] + [No Entry] +
[Perimeter Only]
Perimeter Arming, with entry delay[PIN] + [Perimeter Only]
Maximum Security Arming [PIN] + [No Entry] + [On]
Custom Arming[PIN] + [#] [4]
Set Delayed Arming[PIN] + [#] [9] [9] and enter
number of hours from
current time to the desired
arming time.
Extend Automatic Arming[PIN] + [OFF] during pre-
arm time
Force ArmingEnter an arming
command followed by
[Bypass]
Zone Bypass[PIN] + [Bypass] followed
by the Zone number.
[PIN] +[Bypass] [*] to clear
ALL Bypasses.
Armed
Status
Power
Fire
TEST WEEKLY
On
123
456
789
*
0
#
Off
Perimeter
Only
No
Entry
Bypass
System
Reset
DS7447/DS7447E
Commands for other System Features
Chime Mode[PIN] + [#] [7]
System Walk T est[PIN] + [#] [8] [1]
Read Event History[PIN] + [#] [8] [9]
Battery Test[PIN] + [System Reset]
Communicator Test[PIN] + [#] [8] [2]
Fire Reset[PIN] + [System Reset]
Remote Program Dial-out[PIN] + [#][8] [3]
Remote Program Answer[PIN] + [#] [8] [6]
Battery/Sounder Test[PIN] + [#] [8] [5]
Error Display[PIN] + [#] [8] [7]
Error Display Reset[PIN] + [System Reset]
Fire Walk Test[PIN] + [#] [9] [1]
To Silence a Fire Trouble/Alarm[PIN] + [Off]
To Clear a Fire Trouble Display[PIN] + [System Reset]
Access Control
Enter your [Access Control PIN] followed by [Off]
Turning Off (disarming) your System
Enter your [PIN] followed by [Off]
NOTE:For additional information on operating this system, consult the DS7400Xi (Ver. 4+) User ’s Guide (P/N: 43851) and section 7
The standard enclosure is manufactured from 20 Guage (1.0 mm),
cold-rolled steel, and measures 12.5 by 14.5 by 3 inch (31.8 by
36.8 by 7.6 cm) (HxWxD). A keyed lock is included, and this enclosure
has provision for an optional tamper switch (required for
commercial burglary applications) for monitoring the door.
1.2Storage and Operating Temperature
• Temperature: +32°F to +120°F (0°C to +49°C)
NOTE:Fire Systems installed under NFPA-72 or UL Listed Fire
Systems require the use of 18 AWG or larger wire.
1.7Communicator
Will report to two phone numbers with full single, double and backup reporting. Communicates in SIA (110 or 300 baud), 3/1, 3/1 Ext.,
3/1 with Parity, 3/1 Ext. with Parity, 4/1, 4/2, BFSK, Contact ID, and
Pager formats.
FCC Registration Number is ESVUSA-75333-AL-E
The ringer equivalence is 0.1B
Commercial Fire CSFM Listing Number is 7165-1062:113
Residential Fire CSFM Listing Number is 7167-1062:114
1.3Power
NOTE:The total current output capacity for all auxiliary devices,
including keypads and smoke detectors = 1.5 A standby,
2.5 A alarm. The following ratings are maximum values.
The total combined output cannot exceed the maximum
load current.
• Input power:18 VAC, 50 VA, 50 Hz./60 Hz.
• Auxiliary power:12 VDC, 1.0 A max.
• UL Listed Alarm Power Output:12 VDC, 1.75 A max.
• Auxiliary power voltage range:12 V special application
• Control panel current draw:175 mA, Standby
250 mA, Alarm
1.4Outputs
• Alarm Output:12 VDC, 1.75 A output. Can be programmed
for steady or pulsed output.
• Programmable Solid state current sink (1.0 A max.). Shorts to
Aux. negative when activated. Connect device
Output 1*
• Programmable Solid state voltage source (500 mA max.). Can
Output 2*
* = Current draw should be subtracted from either maximum
auxiliary or maximum alarm current draw.
** = Not investigated to the requirements of UL294.
to Aux. power positive. Can be used for alarm,
arming state, or access control.** This output
is generally programmable.
be used for alarm, arming state, or access
control.** This output is generally
programmable. For use with such compatible
devices as the Listed DS250 with a 4-wire
base.
1.5Zones
• 8 on-board zones. Up to 248 total zones with expansion modules.
• Zone Response Time: 300 ms.
1.8Partitions
The system has the capacity for 8 independent partitions. One
partition may be a common area.
1.9Users
The DS7400Xi Ver 4+ system allows up to 200 individual users.
Each user will have his own PIN number (the 4- or 6-digit code
entered at the keypads) and his own authority level (to determine
which functions he may perform).
1.10Lightning Protection
MOVs and spark gaps provide protection from lightning surges
and static discharges.
NOTE:Do not use twisted-pair or shielded cable. Do not share
cable with the keypad lines.
• #22 AWG (0.8 mm). Up to 2000 feet (610 m) per system.
• #18 AWG (1.0 mm). Up to 5000 feet (1525 m) per system.
1.13.1 Multiplex Zone Loop Wiring
• Maximum wire length not to exceed 500 feet (150m) regardless
of the wire gauge.
1.14Option Bus Wiring Requirements
• Maximum wire length 1000 feet (305 m) per home-run.
1.15Max. Load Currents
Max. Load CurrentsStandbyAlarm
UL Installa tions1.5 A2.5 A
Maximum Current By Outpu t:
Not to excee d the maximum load currents listed above in Standby or Alarm
Aux. Power & Keyp ad (Combine d)1.0 A1.0 A
Option Power1.0 A1.0 A
Bell OutputX1.75 A
Programmable Output 2500 mA500 mA
Loop Power +500 mA500 mA
1.16Backup Battery Calculation
• The following table is used to calculate the standby battery
capacity required by NFPA when using the DS7400Xi:
Device
Quantity
Standby Current
per Device
Total Standby
Current
(Quantity x Standby
Current per Devic e)
Alarm Current
per Device
Total Alarm
Current
(Quantity x Alarm
Current per Devic e)
DS7400Xi (4+) Control Panel 1 175 mA 175 mA 250 mA 250 mA
DS7416i Advanced Radio Communications Module 127 mA 127 mA
DS7412 - RS232 Serial Interface Module 35 mA max. 35 mA max.
DS7420i -Dual Phone Line/Bell Supervision Module 20 mA 140 mA
DS7430 – Multiplex Expansion Module 65 mA 65 mA
DS7432 – 8-Input Remote Module 10 mA 10 mA
DS7433 – 8-Input Direct Module 65 mA 80 mA*
DS7436 – Dual Multiplex Expansion Module 130 mA 130 mA
DS7445/DS7445i Keypad 75 mA 75 mA
DS7447/ DS7447E Keypad 100 mA 100 mA
DS7448 Keypad 80 mA 100 mA
DS7450, DS7452, DS7455 Contact Points
DS7457 – Single Zone Multiplex Input Module
350 μA
350 μA
350 μA
350 μA
DS7460 – Dual Zone Module 1 mA 1 mA
DS7465 – Input/Output Module 1 mA 1 mA
DS7480 – Bell Supervision Module 7 mA 50 mA
DS7481 – Single Phone Line Monitor 20 mA 20 mA
DS7488 – Octal Relay Module** 10 mA + 40 mA** 10 mA + 40 mA**
DS7489 – Solid State Output Module 10 mA 750 mA max.***
MX280 Series Multiplex Smoke Detectors
MX540 (DS7473) PIR D etector
500 μA
800 μA
560 μA
800 μA
MX835 TriTech® PIR/Microwave Detector 6 mA 35 mA
MX775 (DS7470) PIR D etector
MX794 (DS7474) PIR D etector
MX934 (DS7471) PIR D etector
MX938 (DS7472) PIR D etector
200 μA
800 μA
200 μA
200 μA
200 μA
800 μA
200 μA
200 μA
MX950 (DS7476) TriTech® PIR/Microwave Detector 6 mA 35 mA
RF3222 Wireless Receivers 30 mA 30 mA
2-Wire Smoke Detectors
4-Wire Smoke Detectors
Bells, Horns, etc.
Other Sensors
Other
Grand Total
Grand Total
* = Add 15 mA for each additional zone in alarm.
** = When calculating Standby and Alarm Current for the Octal Relay Module, use 10 mA plus 40 mA for each activated relay.
*** = Maximum current draw if using the DS7400Xi Panel power supply. Total of all outputs cannot exceed 750 mA.
1.17Standby Current Load
• Battery Ah - (20% Storage + 0.375 Ah Alarm)
• The following table is the derated battery divided by hours minus the control standby (175 mA):
• DS7412: RS232 Serial Interface module.
The DS7412 module allows the panel to send event
information, in an ASCII format, directly to a serial
printer or computer. In addition, the interface allows
the direct connection of a computer to the panel for
programming via the WDSRP programming software.
• Current Draw= 25 mA; 35 mA with LEDs on.
• DS7416i: Advanced Radio Communications Module provides
a means of communicating alarm and supervision
signals using the Motient radio network. This can
be a replacement for, or a complement to, the
standard digital communicator.
• Current draw = 127 mA Standby and Alarm.
• DS7420i: Dual Phone Line/Bell Supervision Module (1 per
system).
The DS7420i allows the control to be used in NFPA
72 installations. It provides two supervised 12.0 VDC
signaling outputs, one Class A (Style D) input zone,
and dual phone line transmission and supervision.
• Current Draw = 20 mA Standby; 140 mA Alarm.
• DS7430: Multiplex Expansion Module (1 per system).
The DS7430 provides a two-wire multiplex bus for
the connection of additional remote zones. It also
supplies up to 200 mA for 4-wire multiplex devices
such as the DS7432.
• Current Draw = 65 mA, Standby; 65 mA, Alarm.
• DS7432: 8-Input Remote Module (up to 30 per system.
Requires a DS7430 or DS7436 Multiplex Expansion
Module).
The DS7432 provides a means of monitoring
conventional Normally Open or Normally Closed
contacts. It reports their status to the control panel
as multiplex addresses. It occupies eight multiplex
zones on the system and can monitor up to eight
separate loops. It will support 4-wire smoke
detectors.
• Current Draw = 10 mA; Standby. 10 mA, Alarm.
• DS7433: 8-Input Direct Module (1 per system. Can not be used
with the DS7430 or DS7436 Multiplex Expansion
Modules).
The DS7433 provides a means of expanding the
system to include eight additional hard-wired zones.
Each zone can support up to twenty 2-wire smoke
detectors (can also support 4-wire smoke detectors).
• Current Draw = 65 mA, Standby; 80 mA, Alarm.
Add 15 mA for each additional zone in alarm.
• DS7436: Multiplex Expansion Module. (1 per system.)
The DS7436 provides two two-wire multiplex buses
for the connection of up to 120 remote points. It
also supplies 200 mA per bus.
• Current Draw = 130 mA, Standby or Alarm.
• DS7445/DS7445i: Control Station. (15 Keypads max. per
system). The DS7445/DS7445i is an LED keypad
which has LEDs representing the first 8 zones of
the system. It displays information on various
control panel functions. A built in sounder is used
as an interior warning device and to annunciate
keystroke entries.
• Current Draw = 75 mA, Standby; 75 mA, Alarm.
• DS7447/DS7447E: Control Station. (15 Keypads max. per
system)
The DS7447/DS7447E is an Alpha-Numeric LCD
keypad. It displays information on various control
panel functions. A built-in sounder is used as an
interior warning device and to annunciate keystroke
entries.
• Current Draw = 100 mA, Standby; 100 mA, Alarm.
• Keypad Access Output: The DS7447/DS7447E
Alpha Keypad will provide a ten (10) second access
relay output if equipped with the optional K800 Relay.
The relay will energize at the keypad if the user has a
master, unlimited, general, or access PIN. The output
will change only if the user has access to the partition
assigned to the keypad. See the DS7445/DS7447
Keypad Installation Instructions (P/N: 22235) or the
DS7445/DS7445i/DS7447E Installation Instructions
(P/N: 4998138630) for wiring information.
• DS7448: Control Station. (15 Keypads max. per system)
The DS7448 is a four-wire LCD annunciator
keypad. It has a Silence key and a Reset key used
for controlling annunciator and control panel
operation, a Keylock Switch that can be used to
lock out the annunciator to prevent unwanted
silencing or resetting of the control panel, and a
two-line, 16-character Display capable of showing
all messages normally displayed on a DS7447/
DS7447E keypad.
• Current Draw = 80 mA, Standby; 100 mA, Alarm
• DS7450: Flush Mount Single Multiplex Contact Point (requires
a DS7430 Multiplex Expansion Module).
The DS7450 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 μA, Standby; 350 μA, Alarm.
• DS7452: Surface Mount Single Multiplex Contact Point (requires
a DS7430 Multiplex Expansion Module).
The DS7452 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 μA, Standby; 350 μA, Alarm.
• DS7455:Surface Mount Single Multiplex Contact Point
(requires a DS7430 Multiplex Expansion Module).
The DS7455 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 µA, Standby; 350 µA, Alarm.
• DS7457: Single Zone Multiplex Input Module (requires a
DS7430 Multiplex Expansion Module).
The DS7457 provides a means of monitoring
conventionally Normally Open or Normally Closed
contacts. It reports their status to the control panel as
multiplex addresses. It occupies one multiplex zone
on the system and can monitor one loop. It also
includes a tamper loop.
• DS7460: Dual Zone Module (up to 60 per system. Requires a
DS7430 Multiplex Expansion Module).
The DS7460 provides a means of monitoring
conventional Normally Open or Normally Closed
contacts. It reports their status to the control panel as
multiplex addresses. It occupies two multiplex zones
on the system and can monitor up to two separate
loops.
• Current Draw = 1 mA, Standby; 1 mA, Alarm.
• DS7465: Input/Output Module (up to 60 per system. Requires
a DS7430 Multiplex Expansion Module).
The DS7465 provides a Form “C” relay that may be
programmed to activate on system events, and an
input loop to monitor conventional Normally Open or
Normally Closed contacts. It reports their status to
the control panel as multiplex addresses.
• Current Draw = 1 mA Standby; 1 mA with relay
energized.
• Occupies 2 zones.
• DS7480: Bell Supervision Module (1 per system).
The DS7480 provides a means of monitoring bells. It
provides a supervised (polarity reversing) output relay
to activate the bell. It also provides a Form “C” Bell
Fault Output to be connected to the control panel.
• Current Draw = 7 mA @ 12 VDC, Standby; 50 mA
@ 12 VDC, Alarm.
• DS7481: Single Phone Line Monitor (1 per system).
The DS7481 provides a means of monitoring a single
phone line for fault conditions. When a fault is
detected, the DS7481 automatically closes its
Normally Open relay contacts to provide a means of
signaling the fault.
• Current Draw = 20 mA, Standby; 20 mA, Alarm.
• DS7488: Octal Relay Module (2 per system).
The DS7488 provides 8 Form “C” relay outputs for
addition to the system. The outputs are fully
programmable and can be activated by system
events. Each output operates individually of the other
7 outputs for complete flexibility.
• Current Draw = 10 mA + 40 mA for each relay
when energized.
• DS7489: Solid State Output Module (2 per system).
The DS7489 is a Solid State Octal Driver Module that
provides 8 open collector transistor outputs. The
outputs are fully programmable and can be activated
by system events. Each output operates individually
of the other 7 outputs for complete flexibility. The
DS7489 Module has not been investigated by
Underwriters Laboratories, Inc.
• Current Draw = 10mA.
• Outputs: Provides a current sink (the output shorts
to common (-) when activated). The maximum
current draw for all 8 outputs combined cannot
exceed 750 mA.
• DS9484:The DS9484 is a Remote Notification Appliance
Circuit (NAC) Power Supply designed to add four
additional NACs (NFPA 72 Class B, Style Y) to a
Fire Alarm Control Panel (FACP). When connected
to the Options Bus of the DS7400Xi, it can provide
intelligent control of its individual outputs. It
supplies 6 A of NAC power through four circuits to
drive horn strobe loads. It is UL Listed as a fire
accessory for use in Commercial fire applications
and as a continuous-load power supply for auxiliary
devices.
• Current Draw = 150 mA, Standby; 6 A maximum,
Alarm
• MX280:Multiplexed Photoelectric Smoke Detector (up to 120
detectors may be used per system. Requires a
DS7430 and occupies one multiplex zone). Detects
smoke and automatically determines the detector’s
sensitivity using the Detection Systems “Chamber
Check” feature.
• Current Draw = 500 μA, Standby; 560 μA, Alarm.
• MX280TH: Multiplexed Photoelectric Smoke Detector with a
135°F heat sensor (up to 120 detectors may be used
per system. Requires a DS7430 and occupies one
multiplex zone). Detects smoke and is equiped with
a 135°F heat sensor for high temperature alarms.
The Detection Systems “Chamber Check” feature
automatically determines the detector’s sensitivity.
• Current Draw = 500 μA, Standby; 560 μA, Alarm.
• MX280THL: Multiplexed Photoelectric Smoke Detector with a
135°F heat sensor and a 45°F freeze alarm (up to 60
detectors may be used per system. Requires a
DS7430 and occupies two multiplex zones). Detects
smoke and is equiped with a 135°F heat sensor for
high temperature alarms and a 45°F sensor for freeze
alarms. Freeze alarms are reported separately from
smoke and high temperature alarms. The Detection
Systems “Chamber Check” feature automatically
determines the detector’s sensitivity.
• Current Draw = 500 μA, Standby; 560 μA, Alarm.
• MX540:Multiplexed Passive Infrared (PIR) Intrusion Detector
(DS7473) with a standard range of 40 by 50 feet (12
by 15 meters). Requires a DS7430 and occupies
one multiplex zone.
• Current Draw = 200 μA, Standby; 2 mA, Alarm.
• MX835 TriTech Microwave/PIR Intrusion Detector with “Pet
Avoidance” technology and a standard range of 35 by
35 feet (10.7m by 10.7 m). Requires a DS7430 and
occupies one multiplex zone.
• Current Draw = 6 mA, Standby; 35 mA in “Trouble”
and Walk Test mode.
• MX775 Multiplex Passive Infrared (PIR) Intrusion Detector with
(DS7470) a standard range of 50 by 50 feet (15 m by
15 m). Requires a DS7430 and occupies one multiplex
zone.
• MX794 The MX794 is a Long Range Multiplex PIR intrusion
(DS7474) Detector with Self-test. The standard ranges
are 80 ft. by 50 ft. (24.0 m by 15.0 m) and 200 ft. by 10 ft.
(61.0 m by 3.1 m). Requires a DS7430 and occupies
one multiplex zone.
• Current Draw = 800 μA, Standby; 2 mA, Alarm.
• MX934 Multiplex Passive Infrared (PIR) intrusion detector with
(DS7471) a standard range of 35 by 35 feet (10.7 m by
10.7 m). Requires a DS7430 and occupies one multiplex
zone.
• Current Draw = 200 μA, Standby; 2 mA in Walk
Test mode.
• MX938 360° Ceiling Mount Multiplex PIR Intrusion Detector
(DS7472) with a 60 foot (18.3 m) diameter range.
Requires a DS7430 and occupies one multiplex zone.
• Current Draw = 200 μA, Standby; 2.5 mA in Walk
Test mode.
• MX950 Multiplex TriTech Microwave/PIR Intrusion Detector
(DS7476) with motion monitor and antimask features
and with a standard range of 50 by 50 feet (15 m by
15 m). Requires a DS7430 and occupies one multiplex zone.
• Current Draw = 6 mA, Standby; 35 mA in “Trouble”
and Walk Test mode.
• RF3222:120-zone Wireless Receiver. (up to two receivers
per system. Requires use of a DS7430 or DS7436
Multiplex Expansion Module.)
See the DS7400Xi (4+) Wireless Reference Guide(P/N: 44575) for more information.
• Current Draw = 30 mA
The control/communicator is also available in three package formats. The packages include the following:
• DS7400XiF: DS7400Xi in large red enclosure manufactured
from 18 Guage (1.2 mm), cold-rolled steel,
measuring 15.0 by 20.75 by 4.25 inch (38.1 by 52.7
by 10.8 cm) (HxWxD).
The DS7400Xi control/communicator and the enclosure are
shipped together. The control, however, still needs to be installed
into the enclosure. Hardware for mounting the enclosure to a wall,
and the control to the enclosure is located in its own hardware
pack.
2.1Install the Enclosure
• Use the enclosure as a template and mark the top mounting
holes on the mounting surface.
• Pre-start the mounting screws for these two holes. Slide the
enclosure onto these mounting screws so that the screws move
up into the thinner section of the holes. Tighten the screws.
• Screw in the remaining two screws in either set of bottom
mounting holes.
• Knock out the desired wire entrances on the enclosure.
2.2Install the Control/Communicator
The control is static sensitive. Make sure you touch
earth ground before handling the control. This will
discharge any static electricity in your body. Example:
Run the ground wire to the enclosure before handling
the control. Then keep holding the ground wire while
installing the control.
• Insert the three support posts into the control retainer holes as
shown in the diagram.
• Slide the top of the control into the retainer tabs (the slots under
the top frame).
• Once in the retainer tabs, the control will rest on the three support
posts.
• Secure the bottom of the enclosure by screwing the bottom three
holes through the support posts and through to the control
retainer holes.
Once the control is installed, be sure to connect its
ground wire to the top hinge of the enclosure (the
unpainted tab).
When installing a UL Listed system, refer to Section 1 1.0, InstallationGuide for UL Listed Systems.
he Battery Terminals and Wires are NOT Power Lim ited.
A ¼ in. (6.4 m m) spacing must be maintained between
he battery terminals, battery wiring and all other wiring. Battery wirin g m ay not share the same conduit, conduit
ittings or conduit knock-outs with other wiring.
Option or
Keypad Wires
¼ in. (6.4 mm) Minimum
Battery Wir es
Output or
Zone Wires
To ensure proper spacing
secure wires using
Tie-Wraps or similar device s
Before servicing, remove all power
including the transformer, battery and
phone line. A complete functional test
WARNING
CAUTION
1
2
3
4
5
6
7
8
R
B
G
Y
is required after any programming.
Incorrect connections may
result in damage to the unit.
System is Power Limited except for
battery t erm inals. All wiring entering
this enclosure must be power limited.
A/C Power Indica tion LED
EARTH GROUND:
a good earth ground such as a cold water
pipe and also connected to the cabinet cover,
using the supplied wire jumper.
A/C INPUT: Use U. L. listed, 18 VAC 50
A
VA, class 2 transformer. Model TR-1850
requires 50/60 Hz. unswitched dedicated
C
outlet - do not share.
ALARM O UTPUT:
–
Provides 12 VDC, spec ial application, up to
1.75 A for powering bells, siren drivers, etc.
A
Function programmed in address 2734.
Must be connected to
–+AUXILIARY POWER:
Provides 12 VDC, spec ial application, up to
1.0 A for powering detectors.
O
OPTION BUS:
P
Used for options such as the DS7416i
T
I
Communications Module, the DS7420i Dual
O
Phone Line Module, etc.
N
Also for keypads #11 - #15.
For Commercial Fire Mode: Option Bus wiring
should be in conduit if run ouside the
enclosure.
KEYPAD BUS*:
Up to 15 keypads**
may be used. Can be
“home-run” or
“daisy-chained.”
PHONE LIN E:
TTHRHR
RBGYGBSR
TYPICAL BURGLAR AND FIRE WIRING
Loop +Zone
Input
Z–L+
NO
NC
Typical burglar
alarm loop wiring
Loop +Zone
Input
Z–L+
Typical 2-wire
smoke detector
wiring
(for a list of
compatible 2-wire
smoke detectors,
see Technical Service
Note P/N 27685)
Zone
or PO2
Input
Z–L+
inout
inout
Super v is io n Re la y
(e.g. Detec tio n Sys tems’
Typical 4-wire smoke
detector wiring.
For example:
Detection Systems’
DS250 in an MB4W base.
++
Power
Alarm
++
Power
Alarm
End-of-Line
EOL200)
–
Aux. Power (—)
(terminal 5 or 7)
–
–
Loop +
An appropriate two pole disconnect device must be installed
by qualified service personnel, as part of the building installation.
CAUTION
Danger of explosion if battery is incorrectly replaced.
Replace with the same or equivalent type
CAUTION
recommended by th e manufacturer.
Dispose of used batteries according to the
manufacturer's instructions.
PROGRAMMABLE OUTPUTS:
PO1 shorts to aux. power negative when activ ated, PO1 can sink up to 1.0 A.
PO1 function programmed in address 2735.
PO2 supplies 12 V and up to 500 mA when activated.
PO2 function programmed in address 2736.
ZONES 1-8:Zones 1-8 are intended for connection of Normally
Open or Normally Closed alarm contacts. They may also be used
for compatible 2-wire smoke detectors. These zones require a
2.21kΩ resistor (P/N 25899) at the end of the loop. Power is
momentarily removed from L+ after a [PIN] + [System Reset] or
during a fire verification.
Zone 1-8 assignments are programmed in address 0031-0038.
PO1 PO2
1–
L+
2–3–5–6–7–8–4–
L+L+L+
91011213141516
Keypad
(#1 - #10)
Keypad
(#1 - #10)
* = Maximum wire length each: 1000 ft. (305 m).
Maximum wire length total in system: 6000 ft. (1830 m) when using
#22 AWG (0.8 mm) or #18 AWG (1.0 mm) cable.
** = Keypads #1 - #10 connect to the Keypad Bus and keypads #11 - #15
connect to the Option Bus.
NOTE
17 18192021 2223 2425 2627 282930
Shared cable is not recommended for keypad,
multiplex, options bus, telephone, or siren wiring.
Keypads #11 - #15 must be connected to
the Options Bus. Keypads #1 - #10 must
be connected to the Keypad Bus .
Armed
Statu s
Power
Fire
Armed
Statu s
Power
Fire
Armed
Statu s
Power
Fire
Armed
Statu s
Power
Fire
1 23
456
789
0
*
1 23
456
789
0
*
1 23
456
789
0
*
1 23
456
789
0
*
On
Off
Perimeter
Only
No
Entry
Bypass
#
System
Reset
On
Off
Perimeter
Only
No
Entry
Bypass
#
System
Reset
On
Off
Perimeter
Only
No
Entry
Bypass
#
System
Reset
On
Off
Perimeter
Only
No
Entry
Bypass
#
System
Reset
DS7447/DS7447E and DS7445/DS7445i
Keypads
Armed
Status
Power
Fire
Armed
Armed
Status
Status
Power
Power
Fire
Fire
Armed
Armed
Status
StatusPower
Power
Fire
Fire
Armed
Armed
Status
Status
Power
Power
Fire
Fire
1 23
456
789
*
Perimeter
Peri meter
Supervisory
Supervisory
Bell Silenced
Bell Silenced
Trouble
Trouble
1 23
123
456
456
789
789
*
*
Peri meter
Perimeter
Supervisory
SupervisoryBell Silenced
Bell Silenced
Trouble
Trouble
1 23
123
456
456
789
789
*
*
Perimeter
Peri meter
Supervisory
Supervisory
Bell Silenced
Bell Silenced
Trouble
Trouble
123
1 23
456
456
789
789
*
*
0
12345678
1234567 8
910111213
TEST WEEKLY
0
0
1234567 8
12345678
910111213141516
TEST WEEKLY
0
0
12345678
1234567 8
12 1314 15 16
91011
TEST WEEKLY
0
0
On
Off
Perim eter
Only
No
Entry
Bypas s
#
Syst em
Reset
®
14 1516
On
On
Off
Off
Perimeter
Perim eter
Only
Only
No
No
Entry
Entry
Bypass
Bypass
#
#
System
Syst e m
Reset
Reset
®
On
On
Off
Off
Perim eter
Perimeter
Only
Only
No
No
Entry
Entry
Bypass
Bypass
#
#
Syst e m
System
Reset
Reset
®
On
On
Off
Off
Perimeter
Perim eter
Only
Only
No
No
Entry
Entry
Bypass
Bypass
#
#
System
Syst e m
Reset
Reset
Note :
R
B
G
Y
DS7430
+–+–
Power Bus
DS7400Xi
1
R
2
B
Option
Bus
3
G
4
Y
5
+
Battery
–
6
–
7
+
Bell Output
–
8
–
9
Auxiliary
+
Output
10
–
DS7420i Dual Phone
Line/Be ll Supervision
RTRT TTRRTRTR
–+––
++
1 121 314 1516 1718 1920 2122 2324 2526 2728
Module
DS7488 Octal
Relay Board
BatteryBattery
Ensure at least 1/4" separation
between battery wires and all
other cabling.
+–+
–
12345678
POWER BUS
+–+
–
12345678
POWER BUS
+–+
–
1234567 8
POWER BUS
+–+–
1234567 8
POWER BUS
DS7432 8-Input
Remote Modules
Dry contact inputs
1234
2G
5
+
1
-
BUS
+
123
NO
NC
C
47kΩ
EOL
DS7450/ 52 Se ri es Co nt act s , DS74 60 In pu t Mod ule
DS7465 Input/Output Modules, MX540, MX775,
MX794, MX835, MX934, MX938, and MX950 mo tio
detectors and MX280 Series Smoke Detectors
RF3222 120-Zone
Wireless Receivers
Wireless Senso rs
• Up to 15 keypads may be used. Keypads #1 - #10 connect to the Keypad Bus and keypads #11 - #15
connect to the Option Bus. One keypad must be designated as keypad #1 and connect ed to the Keyp ad
Bus. See th e DS7447/DS7447E, D S7445/DS7445i, and D S7448 Installati on I nstructions for f ur t her details.
• A DS7420i (Dual Phone Line/Bell Supervision Module) may be connected to the Control Panel, and
placed within the enclosure. Connect to the Options Bus of the control panel. See the DS7420i Installation
Instructions for further details.
• Up to 2 DS7488s (Octal Relay Modules) may be connected to the Control Panel, and placed within the
enclosure. Connect to the Options Bus of the Control Panel. This provides an additional 8 Form “C”
relay outputs for the Control Panel. See the DS7488 Installation Instruct ions for further detai ls .
• A DS7430 or a DS7436 (Multiplex Expansion Module) may be connected to the control panel via the
expansion port. This will allow for th e connection of additional zones via the Options Bus. See t he D S7430
or DS7436 Installation Instructions fo r furthe r details.
• Up to 30 DS74 32s (8-Input Remote Modules) may be connected to the DS 7430 or DS7436. Connect to the
Power and Bus Terminals of the Multiplex Expansion Module. This allows for a means of addressing up to
240 input loops of conventional contacts t o the Control Panel. See the DS7432 Instal lat ion Instruct ion s for
further details.
• Up to 2 RF3222 (120-Zone Wireless Receivers) may be connected to the DS7430 or DS7436. Connect to
the Power and Bus terminals of the Multiplex Expansion Module. This allows for the monitoring of wireless
detectors.
• A DS7416i Advanced Radio Co mmunications Module may be connected to the Control Panel via the Options
Bus. This allows for connection to a radio network.
• Up to 248 zones are available for the connecti on of Sing le, Multiple , Input/ Ou tput, and Multiplex devices.
Up to 112 wireless zones (137-248) are also available.
Name Contact Person
Address Voice Phone Number
Panel Phone Number
City, State, Zip Panel Answers P hone Armed Disarmed
AC Voltage VAC Battery Voltage VDC AUX Current A
Battery Standby Ah Bell Current A
Control Panel
Transformer
Telephone Jack
Telephone On Same Line as P a nel
Earth Ground Co nne ct ion
Alarm Sounder (s)
Type * Zone/Output Partition & Location
Function #
Zone # 1
Zn Funct. 1
Example
Zone Location and Notes
* = SZ: Single Zone Input
MZ: Multiple Zone Input
IO: DS7465
(see section 10.3)
2, KitchenSZ
Type * Zone/Outpu t Partition & Location
Function #
Zone # 1
Zone # 2
Zone # 3
Zone # 4
Zone # 5
Zone # 6
Zone # 7
Zone # 8
Zone # 9
Zone # 10
Zone # 11
Zone # 12
Zone # 13
Zone # 14
Type * Zone/Output Partition & Locatio
Function #
Zone # 31
Zone # 32
Zone # 33
Zone # 34
Zone # 35
Zone # 36
Zone # 37
Zone # 38
Zone # 39
Zone # 40
Zone # 41
Zone # 42
Zone # 43
Zone # 44
Zone # 15
Zone # 16
Zone # 17
Zone # 18
Zone # 19
Zone # 20
Zone # 21
Zone # 22
Zone # 23
Zone # 24
Zone # 25
Zone # 26
Zone # 27
Zone # 28
Zone # 29
Zone # 30
• Normal Arming - [PIN] + [On]: If programmed, arms the entire
system while allowing entry delays for entry/exit zones.
• Perimeter Instant Arming - [PIN] + [No Entry] [Perimeter Only]: If
programmed, arms only the perimeter of the system and does
not allow entry delays for entry/exit zones.
• Perimeter Arming - [PIN] + [Perimeter Only]: If programmed,
arms only the perimeter of the system while allowing entry delays
for entry/exit zones.
• Custom Arming - [PIN] + [#] [4]: If programmed, allows custom
arming of the system and bypasses the zone functions specified
in data addresses 2725-2728.
• Maximum Security Arming - [PIN] + [No Entry] [On]: If
programmed, arms the entire system and does not allow an
entry delay for entry/exit zones.
• General Authority by Partition
A general (level 2) authority can be programmed to have armonly authority; arm and bypass authority; arm and disarm
authority; or arm, disarm, and bypass authority by partition. This
is done at addresses 3421-3424.
- Arm-only access by partition allows someone with a General
Authority to arm zones in a partition he can not disarm.
- This level can still be used to arm, disarm, and bypass zones
in the other partitions that it has access to.
• Closing Ring-Back: If programmed, the keypad sounders and
Bell will activate for 2 seconds after the system is armed and the
closing report is successfully sent. This requires Closing RingBack and Closing Report to be programmed.
- If a closing report is not programmed, the control will test for a
dial tone when the system is armed. If the test passes, the
system will arm normally. If the test fails, the system will arm,
but will indicate a trouble condition.
- The DS7447/DS7447E keypad will display “Communication
Err” after [#] [8] [7] is entered.
• Siren on Comm. Fail for Silent Zone: If programmed, a silent
zone will sound the alarm outputs if the zone is in an alarm
condition and the system fails to communicate with the central
station.
• Restore when Sounders Silence: If programmed, a zone sends
a restoral report and is ready to activate again only after the
burglary bell cut-off time expires or the bells are silenced.
- The zone can alarm multiple times per armed period.
• Restore when Zone Restores: If programmed, a zone sends a
restoral report and is ready to activate again as soon as it
physically restores.
- This zone can alarm multiple times per armed period.
• Restore when System Disarms: If programmed, a zone sends
a restoral report when the system is disarmed.
- It can only alarm once per armed period.
• Allow Swinger Shunts: If programmed, a zone can only alarm
or trouble up to three times per armed period. After the third
alarm or trouble, the zone will be bypassed and a bypass report
will be sent.
NOTE: Swinger Shunts are not allowed on UL Certificated
Installations.
6.2Zone Function Programming
• Zone Function
A Zone Function is the description of how a particular zone will
behave (e.g. steady alarm output, bypassing allowed, alarm on
short, trouble on open, perimeter instant).
- There are many possible zone functions. Up to 30 different
zone functions are allowed per control.
- Zone functions may be custom made as needed.
- Each zone must be programmed as a specific zone function.
Any number and combination of zones may be programmed
as particular zone functions.
- Program zone functions at addresses 0001-0030.
• Invisible Alarms : This is a zone programmed not to have an
alarm output or an alarm display at any keypad when activated.
An alarm signal will be sent, but the DS7447/DS7447E keypad
display will read “Not Ready” while this zone is violated.
- Invisible Alarm zones are recommended for holdup alarms.
• Silent Alarms: This is a zone programmed to activate the visual
display at the keypad, but not audible signals.
- If this zone is also an entry zone, an entry tone will sound when
this zone is activated.
• Bypassing Allowed: This is a zone programmed to allow
bypassing (shunting). This is done using the bypass command
or the force-arming sequence.
• Alarm on Short: This is a zone programmed to activate an
alarm when its loop is shorted.
• Alarm on Open : This is a zone programmed to activate an
alarm when its loop is opened.
• Trouble on Open: This is a zone programmed to activate a
trouble when its loop is opened and the system is disarmed.
- If the system is armed, this zone will activate an alarm if shorted
or opened.
- For 24-hour zones, regardless of the arming state of the panel,
this always remains as a Trouble on Open.
• Trouble on Short: This is a zone programmed to activate a
trouble when its loop is shorted and the system is disarmed.
- If the system is armed, this zone will activate an alarm if shorted
or opened.
- For 24-hour zones, regardless of the arming state of the panel,
this always remains as a Trouble on Short.
• Interior Delayed : This is a zone programmed to be ignored
during the entry/exit delay period. If it is violated when the system
is armed, it will activate a delay for the programmed entry delay
time. The keypad pre-alert sounders will activate and the system
may be disarmed during this delay period. If the system is not
disarmed during this delay period, this zone will activate an alarm.
This zone is bypassed by Perimeter Instant or Perimeter Armed.
• Perimeter Instant : This is a zone programmed to activate an
alarm even during the entry/exit delay period.
• 24-Hour: This is a zone programmed to activate when its loop is
faulted, even if the system is disarmed.
• Entry/Exit Delay #1: This is a zone programmed to be ignored
during the entry/exit delay period.
- If it is violated while the system is armed, it will activate a delay
for the amount of time programmed for entry delay time #1
(address 4028). The keypad pre-alert sounders will activate
and the system may be disarmed during this delay period.
- If the system is not disarmed during the entry period, this zone
• Entry/Exit Delay #2: This is a zone programmed to behave
identical to the Entry/Exit Delay #1 zone function except that it
uses entry delay time #2 (address 4029).
NOTE:If both entry delays have been activated, the control will
use the shorter entry delay.
• Entry/Exit Delay Cancel Zone Functions
Entry/Exit Delay Cancel 1 and Entry/Exit Delay Cancel 2 Zone
Functions cause the exit delay to expire as soon as the premises
is vacated.
- If a zone is programmed as an Entry/Exit Delay Cancel zone,
and it is activated during the exit delay , the exit delay will expire
as soon as the zone has been restored.
• Interior Entry/Exit Follower: This is a zone programmed to be
ignored during an entry/exit delay and then become an interior
instant zone.
- If this zone is violated while the system is armed and no entry/
exit zones have been violated, it will activate an alarm.
- If this zone is violated after an entry/exit delay zone is violated,
it will follow that entry/exit delay time.
- This zone is bypassed by Perimeter Instant or Perimeter
arming.
• Interior Home/Away: This is a zone programmed to become an
interior instant zone if the system is armed and an entry/exit
delay zone is violated during the exit delay time.
- If the system is armed and an entry/exit delay zone is not
violated, this zone will be bypassed.
- This zone is bypassed by Perimeter Instant or Perimeter
arming.
• Interior Instant: This is a zone programmed to activate an alarm
even during the entry/exit delay periods.
- It is bypassed by Perimeter Instant or Perimeter arming.
• Day Monitor: This is a zone programmed to be a perimeter
instant zone when the system is armed.
- When the system is disarmed, any violation of this zone will
activate the keypad sounders which will sound continuously
until a disarm command sequence is entered.
- The alarm outputs for this zone will not activate and there will
be no report for this zone when the system is disarmed.
• Keyswitch Input: This is a zone programmed to allow the system
to be armed or disarmed using a Normally Open momentary
keyswitch.
- Outputs for keyswitch LEDs and sounders are available using
the programmable outputs or the Octal relay outputs.
- An output is needed for each LED and sounder.
- A keyswitch will only control the partition that these zones are
assigned to unless programmed as a master, then it will
control all at once. See Program Address 0001, Data Digit 1.
- Keyswitches and keypads may be used in the same partition,
if desired.
• Fire Zone: This is a zone programmed to activate if the system
is armed or disarmed.
- It can be silenced (not reset) by entering a valid [PIN] + [Off].
- The display will indicate a Fire Alarm for this zone on all
keypads in every partition.
- A fire reset command must be entered after silencing the
alarm to re-enable this zone.
- If this zone is programmed for trouble and the loop opens, the
DS7447/DS7447E keypad will display “Fire Trouble” for this
zone and the keypad sounders will beep once every ten
seconds.
- If the system is a combination fire and burglar alarm, the fire
alarm has priority over the burglar alarm.
• Fire Zone with V erification: This zone is identical to a Fire Zone
except that after the first alarm, it will perform a fire reset and
then wait up to two minutes for a second alarm.
- If a second alarm occurs within this two minute period, the
system will indicate a fire alarm.
- If there is no second alarm within this two minute period, the
control panel will reset back to its normal condition.
NOTE:Use of this control’s alarm verification feature is not per-
mitted for applications in the state of California.
• Water Flow Zone: This is a zone programmed to operate like a
Fire Zone, but is specifically intended for water flow switches.
- An optional retard timer can be programmed to compensate
for changes in water pressure. If the timer is used, the water
flow zone must be activated for the complete time period; an
alarm will be initiated at the end of the timer period.
- The maximum combined water flow delay of the control panel
and the device must not exceed two minutes.
NOTE:Any zone can be a water flow zone, but only zones 1
through 4 may be programmed as delayed water flow
zones.
• Supervisory Zone: This is a zone programmed to accommodate
shut-off valves.
- It will indicate a supervisory condition at the keypads when
activated.
6.3Zone Programming
• Zone
A Zone is an input to the DS7400Xi Control/Communicator.
- There are 8 hardwired zones on the main circuit board.
- Additional zones may be added by using the DS7433 (8 zone
expansion module), the DS7430 (multiplex loop module), and/
or other modules.
• Single Zone Input : This is an individual zone such as the onboard zones and multiplex contact zones.
• Multiple Zone Input : This is a zone connected to one of the 8Input Modules (DS7432 or DS7433) or to a Dual Zone Module
(DS7460).
- The inputs are programmed separately (see the separate
Programming Addresses Worksheet, P/N: 29802).
- When using the Dual Zone Module (DS7460), loop A is always
programmed as an odd numbered program address (ending
in 1, 3, 5, 7, or 9). Loop B is the even numbered program
address that follows loop A.
• DS7465: This is the input zone or the output relay on a DS7465.
The odd numbered zone is programmed for the input zone
function and the even numbered zone is programmed for the
output function.
• Multiplex Smoke: This is a multiplexed input zone (zones 9-
248) that is used with a MX280 series smoke detector. This zone
must have a Zone Function of Fire Zone and Trouble on Open
applied to the multiplex smoke zone.
• Multiplex Smoke with Low Temperature: This zone is used
with the MX280 series smoke detectors with a low temperature
alarm. Making this selection requires the programming of two
zones as follows:
- Smoke alarm. This must be the odd numbered zone of the
zone pair required for these devices. The zone must be
programmed with a zone function that is set for Fire Zone and
Trouble on Open.
- Low Temperature Alarm. This must be the even numbered
zone of the zone pair required for these devices. This zone
must be programmed with a zone function that is set as
Supervisory and Trouble on Open.
6.4Output Programming
• Latch on Any Zone Alarm: This is an output programmed to
activate upon any zone alarm (including invisible zones) and will
latch until the system has been disarmed.
- If this output is programmed to respond only to a fire zone, it
will remain latched until the fire reset command is performed.
• ON during Entry Pre-Alert: This is an output programmed to
activate when an entry/exit zone is violated while the system is
armed.
- It will remain activated until the system is disarmed, or until
the entry delay time has expired.
• ON for 10 seconds after [PIN] + [System Reset] is entered: This
is an output programmed to activate for 10 seconds after the fire
reset command is entered at the keypad or if a Fire Zone with
Verification activates.
- This output is intended to be used to power 4-wire smoke
detectors or any other device that requires a power interruption
to reset an alarm condition.
NOTE:When Programmable Output 2 is programmed this way,
it will normally supply auxiliary power and will turn OFF for
10 seconds when the fire reset command is entered.
• ON when System is Armed: This is an output programmed to
activate when the system is armed.
- It will remain activated until the system is disarmed.
• Ground Start: This is an output programmed to activate for 3
seconds when the phone line is seized. It is intended for use
with ground start phone systems that require a momentary short
to ground to obtain a dial tone.
- Connect a separate 12 VDC, DPDT relay.
- Connect both relay contact commons to ground, and connect
the Normally Open of each contact to terminal positions 13
and 16 (one to terminal 13, the other to 16) of the DS7400Xi.
- This output follows all partitions regardless of how data digit 2
of the output programming address is programmed.
- Not intended for UL Listed systems. Not for use with phone
line monitors.
• System Status (ready to arm): This is an output programmed
to follow the Status LED of the keypad.
- It will activate when the system is ready to arm with no zones
violated.
• Zone Alarm: This is an output programmed to activate when a
zone is in an alarm condition.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens.
- This will not activate from Silent or Invisible Zones.
• Zone Alarm Delayed by 20 sec.: This is an output programmed
to wait 20 seconds after a zone enters an alarm condition to
activate.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens, but
provides a delay to allow the user to silence the system before
it activates.
• Output Functions
Output Functions can be programmed to follow system events
or to follow one or two specific zones in a “cross-matrix” fashion
(see Input/Output Cross-Matrixing).
- These Output Functions can be programmed to control Octal
Relay outputs or Multiplex Bus outputs.
- Output Functions are programmed in addresses 2772-2843.
• Input/Output Cross Matrixing
Input/Output Cross Matrixing allows Output Functions to follow
the status of specific input zones (zones 1 through 248 only).
- Outputs can be programmed to follow any combination of one
or two zones, open or closed, with the system armed or disarmed.
- If programmed to latch, the output will latch until a valid PIN is
entered at the keypad.
• Keypad Sounder Output: This is an output programmed to follow
the keypad sounder.
- It activates during the entry pre-alert and during any day monitor
alarm. It does not follow momentary keypad beeps such as
keystrokes, chimes, etc.
• Access Output : This is an output programmed to activate for
10 seconds when an access control PIN is entered at the keypad.
- Not UL Listed for Access Control (UL294).
• Panic/Duress Output : All outputs, including the three on-board
outputs, the Octal Relays, and the Output Functions, support a
Panic/Duress function. This output will follow Duress activations,
Keypad Emergency Keys B and C, and Invisible and Silent Zone
alarms. It will only be reset by a user acknowledgement and will
not reset after the burglary bell time-out occurs. Duress activations will latch until acknowledged by a user.
• Multiplex Bus Outputs
The DS7400Xi supports up to 60 DS7465 Input/Output Modules.
- These modules are connected to the multiplex bus and provide
one input loop and one Form “C” output relay.
- The input loop operates the same as all other multiplex inputs.
- The output loop can be programmed to follow Output
Functions.
- Multiplex Bus outputs can be bypassed using the bypass
function. If an output zone is bypassed while it is ON, it will turn
OFF. The bypass will not be removed when the system is
armed and then disarmed; it must be cancelled by entering
the bypass command again or by cancelling all bypasses.
NOTE:DS7465 Module outputs will not pulse, even if programmed
to do so.
• Octal Relay Modules (DS7488)
The DS7400Xi can support two Octal Relay Modules.
- Each relay can be programmed to follow system-wide events
or Output Functions as described above.
• Solid State Output Modules (DS7489)
The DS7400Xi can support two Solid State Output Modules.
- Each output can be programmed to follow system-wide events
or Output Functions as described above.
6.5Partition Control Programming
• Partition Control Programming: Up to eight partitions may be
used. They are assigned (program address 3420) in order.
- For example: When using only one partition, it is partition one.
When using three partitions, they are partitions one, two, and
three.
- Partitioning allows the system to act as up to 8 different
systems.
- Zones, keypads, outputs, and other items may be assigned to
particular partitions.
- Access to partitions may be through each partition’s keypad
or through a Master keypad (see the User’s Guide P/N: 43851for more details).
• Common Area: Partition 1 can be programmed as a common
area, that is, common to other partitions. This allows it to be
used in an installation with one common entry area such as a
foyer or vestibule.
- When Partition 1 is programmed as a common area, it will
only arm when all the partitions it is common to are armed.
- The common area will disarm when any of the partitions it is
common to are disarmed - only if the user has access to the
common area.
- When using a common area, a Master keypad should be used
and assigned to the common area (see keypad assignment
programming).
Key.
- If programmed, the key will activate a supplementary or an auxiliary
type alarm when pressed for 2 seconds.
- It may be programmed for a silent, steady, or pulsed alarm.
• Panic Key: The emergency key (key C) at the bottom right of the
keypad entry area is the Panic Key.
- If programmed, the key will activate a panic alarm when
pressed for 2 seconds; nothing will display at the keypad to
indicate an alarm.
- It may be programmed for a silent, steady, or pulsed alarm.
NOTE:The Special Emergency Key and the Panic Key will gen-
erate the alarm sounders only in the partition of the keypad that activated that Key.
6.8Custom Arming Programming
• Custom Arming - [PIN ] + [#] [4]: If programmed, the [PIN] + [#]
+ [4] command sequence may be used to custom arm the system
by arming only certain zone functions.
- For example: All interior zones plus some perimeter zones
may be bypassed while leaving some of the perimeter armed.
6.6Keypad Assignment Programming
• Keypad Assignment: The keypad type and the partition it is
assigned to must be programmed.
- Each program address (3131-3138) programs the keypad
type for two keypads. For example: for address 3131, data
digit 1 is for keypad 1, data digit 2 is for keypad 2.
- Each program address (3139-3146) programs the partition
assignment for two keypads. For example: for address 3139,
data digit 1is for the partition assignment of keypad 1, data
digit 2 is for the partition assignment of keypad 2.
- Users must have access to the partition the keypad is assigned
to in order to use the keypad.
• Master Keypad Programming : A Master keypad can be used
to access all the partitions.
- It will display the arm/disarm status of all the partitions and
can be used to individually control each partition (see section
7.6).
- A Master keypad can be assigned to any of the partitions.
- Any number of the 15 allowable keypads can be a Master
keypad.
- When using the common area, it is suggested that a Master
keypad be used and that it is assigned to the common area.
6.7Emergency Key Programming
NOTE:Do not label these keys if they are unprogrammed. Only
the “A” key may be programmed and labeled as the Fire
key. These keys are not intended to substitute for Listed
manual pull boxes.
• Fire Key: The emergency key (key A) at the bottom left of the
keypad entry area is the Fire Key. If programmed, the key will
activate a fire alarm when pressed for 2 seconds.
- It may be programmed for a steady or pulsed alarm.
NOTE:The Fire Key will generate the fire alarm sounders in the
partition that activated the Fire Key. Any other partitions in
use will only have their keypad sounders activated. All
keypad displays will be the same.
• Special Emergency Key: The emergency key (key B) at the
bottom center of the keypad entry area is the Special Emergency
6.9Force Arming
• Force Arming: If programmed, allows violated zones to be force
armed. When force arming, the user must enter the usual arming
command followed by the [Bypass] key. This automatically
bypasses zones that are violated and programmed as
bypassable.
- Fire zones, supervisory zones, keyswitch zones, waterflow
zones, and non-bypassable zones can not be force armed.
- Not available in UL Listed systems.
- See Program Address 2732.
6.10Ground Fault Detect Programming
• Ground Fault: If programmed, this function will allow the system
to detect ground faults. This function is required for fire panels
and will be forced on when the panel is in the commercial fire
mode.
- See Program Address 2732.
6.11Commercial Fire Mode Programming
NOTE:In a system that includes both fire alarm and burglar alarm
devices, the system must produce distinct sounds for fire
and burglar alarm conditions either by using different indicating appliances or by using distinct cadences for the
same appliance.
• Commercial Fire Mode : When in Commercial Fire Mode, the
control panel will perform some functions (e.g. communications)
differently to conform with commercial fire regulations.
- See Commercial Fire Mode Programming, program address
2733.
• Water Flow Zone Delay: This is the amount of time a water flow
zone must be violated before the control panel will initiate an
alarm.
- The delay is necessary to accommodate normal changes in
water pressure.
- If the water flow initiating device incorporates its own time
delay, do not program the control panel unit to exceed 120
seconds combined time delay.
• Pulsing Fire Zone: This is a zone programmed to output a pulse
for a fire alarm in the normal manner (one second ON, one second
OFF).
• California March Time: This is a zone programmed to output a
pulse for a fire alarm in the California Time cadence (ten 1/2
second pulses, followed by one second of quiet time).
• T emporal: This is a zone programmed to output a pulse for a
fire alarm in the Temporal cadence (three 1/2 second pulses,
followed by one second of quiet time).
• Single Keypad Use: The keypad should be used on the keypad
bus and be mounted to the front of the control enclosure OR if
within the same room as the control equipment with the wire run
in conduit (or equivalently protected against mechanical injury)
within 20 ft. (6.1 m) of the control equipment.
- This keypad should be assigned as address 1.
• Multiple Keypad Use: One keypad only must be used on the
option bus, at any address from 11 - 14, and must meet the
following requirements:
- The keypad must be mounted to the front of the control
enclosure OR mounted within the same room as the control
equipment and the wire is run in conduit (or equivalently
protected against mechanical injury) within 20 ft. (6.1 m) of the
control equipment.
- All other keypads should be connected to the keypad bus and
may be placed as needed (within the noted wiring limitations
in the installation manual).
- One keypad must be assigned as address 1.
6.12Open/Close Report Control Programming
• Open and Close Reports: If programmed, these reports are
sent when the system is armed or disarmed. They may be sent
independently for the opening and closing of each partition, or
the first partition to open and the last partition to close may send
the reports.
• Send T rouble at Close for Bypassed Zones: If programmed, a
trouble report will be sent for each zone bypassed when the
system is armed.
• Alternate between both Phone Numbers: If programmed, open
and close reports will be sent to phone number one first. If phone
number one does not pick-up, the control panel will alternate to
phone number two. If phone number two does not pick-up, the
control panel will alternate back to phone number one. It will
alternate between both phone numbers until successful.
6.13Report Programming
• Reports: For pulse formats, reports are programmed by entering data in the reporting and extended digits. The report will
send the data programmed for each event. For SIA and Contact
ID, the report formats are fixed and may be activated by placing a
1 in the reporting digit.
- To disable a report, enter a 0 in the reporting digit.
- To send the Man No. along with Open and Close reports,
program an "F" (enter [*] [5] at the keypad) in the extended
digit.
• Keypad Fire Alarm: This report is sent when a fire alarm has
been activated by the “A” emergency key.
• Keypad Fire Restoral: This report is sent when a keypad fire
alarm has been restored using the [System Reset] command.
• Keypad Emergency Alarm: This report is sent when an
emergency alarm has been activated using the “B” emergency key.
• Keypad Panic: This report is sent when an emergency alarm has
been activated using the “C” emergency key.
• Keypad T amper: For keypads fitted with a wall tamper switch, this
report is sent when the keypad is removed from the wall.
• Keypad Tamper Restoral: For keypads fitted with a wall tamper
switch, this report is sent when the keypad is properly replaced
on the wall after experiencing a tamper condition.
• Zone Function Alarm: An alarm report is sent when a zone
alarm occurs. Alarm reports are enabled by zone function. Program this report for any zone functions you wish to send an
alarm report about. For local zones (no reports), do not program
an alarm report. The zone number will automatically be sent for
this report in SIA or Contact ID format.
• Zone Function Restoral: This report is sent when the zone alarm
and trouble conditions are cleared. The zone number will automatically be sent for this report in SIA or Contact ID format.
• Zone Function Trouble: This report is sent when a zone trouble
condition occurs. This can be an open circuit, if the zone is programmed for “trouble on open”, a multiplex tamper switch being
activated, or a multiplex zone not communicating with the control
panel. The zone number will automatically be sent for this report
in SIA or Contact ID format.
• Zone Function Bypass: This report is sent when a zone is bypassed. (Note: Fire zones can never be bypassed.) Zone bypass reports for non-24 hour zones are sent with the closing
report. Bypass reports for 24 hour zones are sent when the zone
is bypassed. If a zone is force armed, the bypass report is sent
with the partial close report. If a 24 hour or non-24 hour zone is
custom armed, the bypass report is sent with the partial close
report.
• Zone Function Bypass Restoral: This report is sent when the
zone bypass is cleared. For non-24 hour zones the bypass restoral is sent with the open report. Bypass restoral reports for 24
hour zones are sent when the zone is manually restored. The
bypass restoral report for a zone that was force armed is sent
when the zone is restored. If a 24 hour or non-24 hour zone was
custom armed, the bypass restoral is sent with the open report.
• Open: This report is sent when the system has been disarmed.
In SIA or Contact ID formats, the user number for the person who
disarmed the system will be sent with this report. To send the
user number along with an Open report in other formats, program
the extended digit of the report as *5. In Contact ID format, the
partition number will also be sent along with this report. The
Open report will only be sent if a Close report was sent previously.
• Close: This report is sent when the system has been armed. In
SIA or Contact ID formats, the user number for the person who
armed the system will be sent with this report. To send the user
number along with a Close report in other formats, program the
extended digit of the report as *5. In Contact ID format, the partition
number will also be sent along with this report.
• Duress: This report is sent when the system is disarmed using
a duress code. The user number is not sent with this report.
• Partial Close: This report is sent when the system is armed
partially, or force armed.
• First Open After Alarm : This report is sent when the system is
disarmed after an alarm has occurred.
• Low Battery: This report is sent when a low battery condition
occurs.
• Battery Restoral: This report is sent when a low battery condition
restores.
• AC Fail: This report is sent when an AC failure condition occurs.
This report may be delayed in address 4034.
• A/C Failure Report Delay
The A/C power loss report can be programmed to delay for up to
254 minutes (see address 4034). (The same delay would also
apply to the A/C restoral report.)
- If another report is sent during this delay period, the A/C fail
report will be sent along with this report.
- If the A/C power restores during this delay period, the A/C loss
report will not be sent.
- Programming address 4034 as FF causes the report to be
sent at a random interval of at least 15 minutes, but no more
than 2 hours after the A/C failure occurs.
• AC Restoral: This report is sent when an AC failure condition
restores.
• Communicator Test/System Normal : This report is sent at the
24-hour check-in time if there is not a control trouble, an active
fire alarm that has not been acknowledged, a fire trouble, or a
supervisory condition. Note: To send a Communicator Test
even if one of these conditions exists, program the Communicator
Test/System Off Normal.
• Remote Program Successful: This report is sent after a Remote
Program session, if the session was terminated properly.
• Remote Program Unsuccessful: This report is sent after a
Remote Program session, if some error has occurred or the
session did not terminate properly.
• Local Program Successful: This report is sent when local
programmer’s mode is exited and there is no error associated
with the programming.
• Local Program Unsuccessful: This report is sent when local
programmer’s mode is exited and there has been some error
associated with the programming.
• System Trouble: This report is sent when a control trouble
condition occurs.
• System Trouble Restoral: This report is sent when all system
trouble conditions restore.
• Communicator Test/System Off Normal : This report is sent at
the 24-hour check-in time if there is a control trouble, an active
fire alarm that has not been acknowledged, a fire trouble, or a
supervisory condition.
• Exit Error: This report is sent if an exit error occurs. An exit error
occurs when an entry/exit zone is still violated at the end of the
exit delay. If this happens, the entry delay will begin and any
output programmed to activate an alarm will energize. If the
system is not disarmed before the entry delay expires, an alarm
report for the effected zone will be sent and the Exit Error report
will be sent. If this report is not programmed, the control will not
sound the exit error warning.
• Recent Closing: This report is sent, along with any alarm reports,
when there is an alarm within the first five minutes after the
system has been armed.
• System Walk Test: This report is sent when a system test has
been started ([#] [8] [1] key sequence). Zone reports are sent
during a system test.
• System Walk Test Restoral: This report is sent when the system
test has been completed or has timed-out.
• Fire Walk Test: This report is sent when a Fire Walk Test has
been started ([#] [9] [1] key sequence). Zone reports are not sent
during a Fire Walk Test.
• Fire Walk Test Restoral: This report is sent when the Fire Walk
Test has been completed or has timed-out.
• Mux. Smoke Low Temperature Report: This supervisory report
is sent when a MX280 Series smoke detector with a low
temperature feature detects a temperature of 45°F (7.5°C) or
less for a period of 30 minutes or more.
• Mux. Smoke Low Temperature Restoral: This report is sent
when a MX280 Series smoke detector with a low temperature
alarm determines that the temperature has risen above 45°F
(7.5°C).
• Dirty Chamber Report: This report is sent when a MX280 Series
smoke detector fails to pass the “Chamber Check®” sensitivity
test.
• Dirty Chamber Restoral : This report is sent when a MX280
Series smoke detector has been returned to normal operation
after service.
6.14Phone Number General Control
Programming
• Enable Remote Programmer Callback : If programmed, when
the remote programmer tries to initiate a session with the panel,
the panel will hang up and call the remote programmer phone
number.
- Ensures the correct remote programmer is initiating the call.
• Dial Pulse on all Phone Numbers: If programmed, the panel will
dial phone number 1, 2, and the remote programmer phone
number 3 using the pulse format.
• Dial Tone on all Phone Numbers: If programmed, the panel will
dial phone number 1, 2, and the remote programmer phone
number 3 using the tone format.
6.15Phone Answering Programming
• Answering Machine Bypass : This feature allows the panel to
answer incoming calls when answering machines are used. If
the line rings, stops ringing, then rings again within one minute,
the panel will seize the phone line on the first ring.
• Phone Answering Programming: The panel can be
programmed to answer the phone after a selected number of
rings for remote programming access. It can also be
programmed to answer the phone after a different number of
rings when in armed or disarmed states.
- This can be used to call the panel location and determine its
This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy
and if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and the receiver.
• Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for
help.
6.17FCC Phone Connection Notice To Users
This control complies with Part 68 of the FCC rules.
On the inside of the enclosure is a label that contains, among
other information, the FCC Registration Number and the Ringer
Equivalence Number (REN) for this equipment. You must, upon
request, provide this information to your local telephone company.
The REN is useful to determine the quantity of devices that may be
connected to your telephone line and still have all of those devices
ring when your telephone number is called. In most, but not all
areas, the sum of the REN's of all devices connected to one line
should not exceed five (5.0). To be certain of the number of devices
that you may connect to your line, you may want to contact your
local telephone company to determine the maximum REN for your
local calling area.
This equipment may not be used on coin service provided by the
telephone company. This control should not be connected to party
lines.
Should this equipment cause harm to the telephone network, the
telephone company may discontinue your service temporarily. If
possible, they will notify you in advance. But if advanced notice isn’t
practical, you will be notified as soon as possible. You will be
informed of your right to file a complaint with the FCC. The telephone
company may make changes in its facilities, equipment,
operations, or procedures that could affect the proper functioning
of your equipment.
If they do, you will be notified in advance to give you an opportunity
to maintain uninterrupted telephone service.
If you experience trouble with this equipment, please contact the
manufacturer for information on obtaining service or repairs.
The telephone company may ask that you disconnect this
equipment from the network until the problem has been corrected
or until you are sure that the equipment is not malfunctioning. The
repairs to this equipment must be made by the manufacturer and
not the user.
To guard against accidental disconnection, there is ample room to
mount the Telco jack to the inside of the Control cabinet.
The operation of this Control may also be affected if events such
as accidents or acts of God cause an interruption in telephone
service.
6.18Canadian Dept. of Communications
General Installation Requirements: Notice: The Canadian
Department of Communications label identifies certified
equipment. This certification means that the equipment meets
certain telecommunications network, protective, operational, and
safety requirements. The Department does not guarantee the
equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is
permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be
installed using an acceptable method of connection. In some
cases, the company’s inside wiring associated with a single line
individual service may be extended by means of a certified connector
assembly (telephone extension cord). The customer should be
aware that compliance with the above conditions may not prevent
degradation of service in some situations.
Repairs to certified equipment should be made by an authorized
Canadian maintenance facility designated by the supplier. Any
repairs or alterations made by the user to this equipment, or
equipment malfunctions, may give the telecommunications
company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical
ground connections of the power utility , telephone lines, and internal
metallic water pipe system, if present, are connected together.
This precaution may be particularly important in rural areas.
Users should not attempt to make such connections
themselves, but should contact the appropriate
electric inspection authority, or electrician, as
appropriate.
Terminal Requirements: The Load Number (LN) assigned to
each terminal device denotes the percentage of the total load to be
connected to a telephone loop which is used by the device, to
prevent overloading. The termination on a loop may consist of any
combination of devices subject only to the requirement that the
total of the Load Numbers of all the devices does not exceed 100.
The Load Number of the DS7400Xi is 2.
RFI Requirements: This Class A digital apparatus meets all
requirements of the Canadian Interference-Causing Equipment
Regulations. [Cet appareil numerique de la classe A respecte
toutes les exigences du Reglement sur le material broilleur du
Canada.]
6.19For Installations in New Zealand
Two-wire Connection:
The operation of this equipment on the same line as telephones
or other equipment with audible warning devices or automatic ring
detectors will give rise to bell tinkle or noise and may cause false
tripping of the ring detector. Should such problems occur, the user
is not to contact Telecom Faults Service.
For additional information on operating this system, consult the DS7400Xi (Ver. 4+) User’s Guide (P/N: 43851) and the front cover of this
Reference Guide.
7.1Emergency Procedures
7.1.1 Identifying Alarm Sounds
Your alarm system may be programmed for a steady alarm sound
or a pulsed alarm sound. It is important to learn the difference
between a fire alarm sound and an intrusion alarm sound before
you are confronted with an actual emergency.
7.1.2 Silencing Alarms
All alarms can be silenced with any PIN that has disarm privileges.
Entering your [PIN]+ [Off] will silence the alarm and turn off (disarm)
the control.
7.1.3 A Cautionary Note
How you respond to an alarm will depend, mostly, on the type and
time of the alarm. You should seek the advice of your installing
company as they install your system, not later (e.g. after an alarm)
to develop a response plan.
7.1.4 Use Common Sense
Above all else, common sense should prevail. If there is any threat
or hint of danger to yourself or others on the premises, such as in
the event of a fire alarm, everyone should be instructed to leave the
premises immediately. Do not enter the premises unless
accompanied by the appropriate Emergency Services’ personnel,
or after they have given the OK to enter.
7.1.5 Caution When Entering a Building
If the bells and sirens are on and/or the red Armed Light is flashing
with the DS7447/DS7447E display reading “Zone Alarm” or the
DS7445/DS7445i having its zone LEDs flashing, then the keypad
is signaling that an alarm has occurred. The keypad will also issue
a pulsed tone during the entry delay instead of the usual steady
tone.
If the alarm has not been previously investigated, do not enter the
building unless accompanied by the appropriate Emergency
Services’ personnel.
7.1.6 Fire Alarms
Fire Alarms are silenced using the same procedure as intrusion
alarms: a [PIN] (with disarm privileges) plus the [Off] key.
The Fire Alarm system is not reset until alarms at smoke detectors
are cleared by using the [System Reset] command. The Fire Alarm
system will not be functional until this procedure has been followed.
See the “Fire Reset” section, 7.2.
7.2Fire Reset/Fire Trouble
7.2.1 Fire Reset
During a fire alarm, exit the premises immediately. When you have
determined there is no fire, you may silence the bells/sirens before
you initiate the [System Reset] command: [PIN] + [System Reset].
Before the [System Reset] command is used, determine which
smoke detector has alarmed so the monitoring company may
verify its operation.
NOTE:To use the System Reset command sequence, your PIN
must have disarm privileges. The System Reset command will perform a fire reset, a battery test, and will clear
all system troubles.
NOTE:If the System Reset command has not been performed
after 24 hours of the Fire Alarm, the keypad will sound
and it will display “Fire Alarm Not Reset.” If the sounders
have been silenced and the system has been reset properly, this warning will not occur.
7.2.2 Fire Trouble
A Fire Trouble message with a zone number signifies a problem
with the fire system, such as a break in the wiring that monitors
smoke detectors. A Fire Trouble message with no zone number
indicates a ground fault if the unit is in the commercial fire mode.
A Fire Trouble will be indicated by a short beep from the keypad
sounders every 10 seconds. The DS7447/DS7447E will display
“Fire Trouble” followed by the zones in a trouble condition. The
DS7445/DS7445i will turn the Fire and Trouble Lights on steady
and will light the corresponding zone LEDs.
Notify your installing company immediately if the Fire Trouble
message is displayed.
The Fire Trouble beep can be silenced with any [PIN] plus the [Off]
key. After problems have been remedied, a [PIN] plus the [Off] key
should again be entered to clear the “Fire Trouble” display.
7.2.3 Dirty Smoke
A Dirty Smoke display , followed by a zone number and accomp anied
by a beep every ten seconds indicates that the smoke detector for
that zone requires cleaning or replacement. The smoke detector
will also give a Dirty indication by flashing its LED once per second.
The Dirty Smoke beep can be silenced by any [PIN] plus the [Off]
key .
Notify your installing company immediately if the Dirty Smoke
message is displayed.
7.3Emergency Keypad Alarms
The Emergency Alarm Keys [A], [B], and [C] may generate Fire,
Special Emergency, and Panic Alarms if programmed by the
installer.
Ask your installing company to explain the function of these
keys.
When using the Emergency Keys, they must be pressed for two seconds to generate an alarm.
NOTE:If the Emergency Alarm Keys are to be used, they should be labeled to signify their functions.
The A key should be labeled as the Fire key. This is the only key that may be designated as the Fire key.
The B key should be labeled as the Special Emergency key.
The C key should be labeled as the Panic key.
Use the Disarming Command Sequence to cancel or silence these alarms.
7.4Fire
Safety
No fire detection device or system should be considered 100% foolproof.
This fire alarm system can provide early warning of a developing
fire. Such a system, however, does not ensure protection against
property damage or loss of life resulting from a fire. Any fire alarm
system may fail to warn for any number of reasons (e.g. smoke not
reaching a detector that is behind a closed door).
When considering detectors for residential applications, refer to
NFPA Standard 72, “The National Fire Alarm Code.” This standard
is available at a nominal cost from: The National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269.
7.4.1 If Installed in Family Residences
Adherence to the NFPA Standard 72 can lead to reasonable fire
safety when the following items are practiced:
• Minimize hazards: Avoid the three traditional fire killers: smoking
in bed, leaving children home alone, and cleaning with
flammable liquids.
• Providing a fire warning system: Most fire deaths occur in the
home, the majority, during sleeping hours. The minimum level
of protection requires smoke detectors to be installed outside of
each separate sleeping area and on each additional story of the
dwelling.
For added early warning protection, it is recommended that
detectors be installed in all separated areas including the
basement, bedrooms, dining room, utility room, furnace room,
and hallways.
7.4.2 Having and Practicing an Escape Plan
A fire warning may be wasted unless the family has planned in
advance for a rapid and safe exit from the building.
• Draw a floor plan of the entire house showing two exits from
each bedroom and two from the house. Since stairwells and
hallways may be blocked during a fire, the plan should provide
exits from bedroom windows.
Make copies of the plan and practice it with all family members.
• Pre-arrange a meeting place outside and away from the
residence. Once out of the building, all occupants should
immediately go to the pre-selected location to be accounted for.
• Provide a barricade between family members and fire, smoke,
and toxic gases (e.g. close all bedroom doors before retiring).
• Children should be instructed on opening their bedroom
windows and exiting safely from the building. If exiting is not
possible, they should be taught to stay at the open window and
shout for help until it arrives.
• In the event of a fire alarm after retiring, wake the children by
shouting to them from behind your closed door. Tell them to
keep their bedroom doors closed.
• If the top of your bedroom door is uncomfortably hot, do not open
it. There is most likely fire, intolerable heat, or smoke on the
other side. Shout to all family members to keep their bedroom
doors closed and to exit the building via alternate routes.
• If the top of the door is not uncomfortably hot, brace the bottom of
the door with your foot, and the top with one hand, then open the
door about one inch. Be prepared to slam the door shut if there
is any pressure against the door or if any hot air rushes in.
• If there is no evidence of excessive heat or pressure, leave the
room and close the door behind you. Shout appropriate
instructions to all family members and immediately leave the
building via the pre-planned routes. If heavy smoke is present,
drop to your hands and knees, or crawl to remain below the
smoke level.
7.4.3 Installation Considerations
Proper location of detection devices is one of the most critical
factors in a fire alarm system.
• Smoke detectors should not be installed in “dead air” spaces or
close to ventilating or air conditioning outlets because smoke
may be circulated away from the detector. Locations near air
inlets should be favored.
• Avoid areas subject to normal smoke concentrations such as
kitchens, garages, or near fireplaces.
• Do not install smoke detectors where normal area temperatures are above 100° F (38° C) or below 32° F (0° C).
• Areas of high humidity and dust concentrations should be avoided.
• The edge of ceiling mounted detectors should be no closer than
4 inches (10 cm) from any wall.
• Place the top edge of wall mounted detectors between 4 and 12
inches (10 to 30 cm) from the ceiling.
7.5Personal Identification Numbers
7.5.1 General Information
A PIN (Personal Identification Number) is the 4- or 6-digit code
users must enter at the keypad to gain access to the system. Your
system has the capability to assign up to 200 PINs, each four or six
digits long. A PIN may be assigned to each User Number.
PINs should never be programmed with common sequences
such as 1 2 3 4, 1 1 1 1, or 2 4 6 8 because they are easily
violated.
A User Number is the number that identifies each person using
the system. There are 200 possible User Numbers available for
use (001 through 200).
Each User Number can have only one PIN assigned to it.
Attempting to assign the same PIN to multiple User Numbers will
result in the three-beep error tone, and the entry will not be made.
User Number 001 is designated as a Master code. It can be used
to add, delete, or change other PINs. It will always have access to
all partitions regardless of how it is programmed.
User Number 001 is shipped from the factory with the PIN of 1 2 3
4. If your system has been reprogrammed for 6-digit PINs, the PIN
for User Number 001 will be 123456. This PIN should be changed
to one of your personal preference and must be programmed
as a Master code.
A Master code is one of the available authority levels which can be
assigned to a user to determine which functions that user will be
able to perform. The available authority levels are:
0 = Master:Can enter all commands, add or change PINs
in assigned partitions, change the time and
date, bypass, arm, disarm, perform system
tests, system reset and view history. User
Number 001 must have the Master authority
level. Any or all PINs can behave as a Master
code.
1 = Unlimited:Can enter all commands, bypass, arm,
disarm, system reset and perform system
tests. It can not change PINs.
2 = General:Can bypass, arm and disarm. It can not change
PINs, system reset, enter [#] [7] or any of the
[#] [8] functions.
3 = Arm Only:Can arm the system with [PIN] + [ON] arming
sequence only. It can not perform any other
functions, including disarming.
4 = Temporary:Valid only for a specified time (the PIN will
disappear upon expiration date). It can arm
and disarm the system, but can not perform
any other functions. If this is done from a
Master keypad, you must be in Single Partition
Mode. If access is assigned to more than one
partition, you must enter a Temporary PIN
expiration date for all assigned partitions (see
Changing the Expiration Date for Temporary
PINs).
5 = Duress:When the system is disarmed using the duress
code, a silent report is sent to your monitoring
service. The Duress code is intended to be
used when the user is forced to disarm the
system.
6 = Access Code: When a PIN with an Access Code is entered,
any output programmed for Access Output (i.e.
door strikes) will pulse on for 10 seconds
(works when the system is armed or
disarmed).
7.5.2 Programming PINs
PINs can only be added, changed, or removed in Master
Programming Mode, so they are not programmable from an RF
(wireless) keypad.
You should write down your entries before you enter the Master
Code Programming Mode and have them with you as you begin
programming. Make your entries promptly. If a long delay occurs in
your entries, the 3-beep error tone occurs and exits you from the
programming mode.
It is recommended that all PIN programming procedures be
performed at a DS7447/DS7447E keypad since this keypad will
provided visual prompts throughout the programming sequence.
No visual clues will be given from a D7445/DS7445i keypad. When
the programming sequence is successfully completed, both the
DS7447/DS7447E and DS7445/DS7445i keypads will signal the
seccessful completion with a long beep.
NOTE:User Number 001 can not be disabled in this manner.
A
a
d
8
A
a
d
8
7.6The Master Keypad
7.6.1 General Information
Your system may include a Master keypad. A Master keypad is a
DS7447/DS7447E keypad programmed to give a user access to
all the partitions the user has access to, not just the partition in
which the Master keypad is located. This is different from a
Standard keypad in that Standard keypads only give access to the
single partition in which they are located. Commands entered at
the Master keypad will affect all the partitions to which the user has
access. If this is not desirable, the Master keypad can also be
used to control each partition individually; this is called Single
Partition Mode. Single Partition Mode allows a user to control any
or all of the partitions the user has access to on an individual (oneby-one) basis (see section 7.6.3 for more information on Single
Partition Mode).
NOTE:In order to use the Master keypad, your PIN must be
assigned to the partition in which the Master keypad is
located.
7.6.2 Master Keypad Displays
Master keypad displays will differ slightly from Standard keypads.
The Master keypad display will scroll the Status of each partition,
followed by the partition number. For example, if all partitions are
armed, the Master keypad will scroll through the following displays:
rmed
rea 1
Armed
area 2
Armed
area 3
Armed
area 4
Armed
area 5
Armed
area 6
Armed
area 7
If only partitions 1, 2, 3, 4, 6, and 8 are armed, the Master keypad
will scroll through the following displays:
rmed
rea 1
Armed
area 2
Armed
area 3
Armed
area 4
Ready to Arm
area 5
Armed
area 6
Ready to Arm
area 7
Displays for partitions that are Not Ready will display in the same
manner.
The chart at the bottom of this page will help you understand what
each LED function of the Master keypad represents.
7.6.3 Single Partition Mode
Single Partition Mode is used to control partitions on a “one at a
time/one by one” basis from the Master keypad.
To enter the Single Partition Mode, enter your [PIN], then press the
[#] key twice. This will call up the first partition you have access to.
Enter the command sequence you wish for this partition. You do
not need to use your PIN again. To move on to the next partition you
have access to, press the [#] key twice.
T o exit the Single Partition Mode, hold the [*] key down for 2 seconds.
The system will also automatically drop out of Single Partition
Mode after 40 seconds without a keypad entry.
Example of accessing Single Partition Mode
• Enter your [PIN], followed by the [#] key twice: [1] [2] [3] [4] [#] [#].
Arme
area
Arme
area
• The first partition you have access to will be displayed: “Ready
to Arm. Cafeteria.”
• Complete the command sequence (in this case arming) you
wish for this partition: [#] [On].
• Move to the next partition you have access to by pressing the [#]
key twice: [#] [#].
• The next partition you have access to will be displayed: “Ready
to Arm. Office.”
• Complete the command sequence you wish for this partition.
• After you have completed all the command sequences for the
partitions you have access to, exit Single Partition Mode by
pressing the [*] key for two seconds.
7.6.4 Arming from the Master Keypad
To arm all the Partitions to which you have access:
• [PIN] + any Arming Command Sequence. This will arm all the
partitions to which you have access even if they are already
armed.
To arm only some of the Partitions to which you have access:
• [PIN] + [#] + [#]. This puts you into Single Partition Mode.
• The first partition to which you have access is displayed: “Ready
to Arm. Cafeteria.”
• Enter the Arming Command Sequence you want for this partition.
• [#] + [#] opens the next partition to which you have access.
• The next partition to which you have access is displayed: “Ready
to Arm. Office.”
• Enter the Arming Command Sequence you want for this partition.
• After arming any or all partitions to which you have access, you
may exit Single Partition Mode by holding the [*] key for at least
two seconds. The system will also drop out of Single Partition
Mode after 40 seconds without a keypad entry.
7.6.5 Disarming from the Master Keypad
To disarm all the Partitions to which you have access:
• [PIN] + [Off]. This will disarm all the partitions to which you have
access even if they are already disarmed.
To disarm only some of the Partitions to which you have access:
• [PIN] + [#] + [#]. This puts you into Single Partition Mode.
• The first partition to which you have access is displayed: “Armed.
Cafeteria.”
• If you wish to disarm this partition, enter [Off]. If not, go to the next
step.
• [#] + [#] opens the next partition to which you have access.
• The next partition to which you have access is displayed: “Armed.
Office.”
• If you wish to disarm this partition, enter [Off]. If not, go to the next
step.
• After disarming any or all partitions to which you have access,
you may exit Single Partition Mode by holding the [*] key for at
LEDOffFlashingOn
Armed
(red)
Status
(green)
Power
(green)
All partitions are disarmed.One or more partitions are armed, or
an alarm ha s occurred.
Not ready to arm (if the Armed LED is
One or more zones are bypassed.All partitions are ready to arm.
On, all partitions are armed).
The Control Panel has lost all power;
no AC or b attery.
Control Panel problems exist.
See Err or Di s pla ys.
All Partitions are armed, and no
alarms have occurred.
Normal Operation.
The Control Panel is running on AC
power with no problems,
Fire
There are no fire alarms.A fire zone is in alarm.A fire trouble condition exists.
least two seconds. The system will also drop out of Single Par-
]
[#] [8] [7] will display [#] [8] [9] will
display
RAM Fault System Fault 01
ROM Fault System Fault 02
EEPROM Fault System Fault 03
Ground Fault System Fault 04
2Ph/Bell Fault = loss of communication to
DS7420i
System Fault 10
Line 1 Fault = DS7420I phone line 1 fault System Fault 11
Line 2 Fault = DS7420I phone line 2 fault System Fault 12
Bell Fault = DS7420i bell circuit fault System Fault 13
Aux. Relay Fault = DS7420I auxiliary relay
fault
System Fault 14
Oct. Relay Fault = loss of communication to
DS7488
System Fault 20
Reserved for older panels System Fault 50
AR IB Queue Full = modem buffer full System Fault 51
AR Host Down = network data switch down System Fault 52
AR Unreg. Modem = modem not registered System Fault 53
AR Power Fail = power source below
defined threshold
System Fault 54
AR Network Lost = loss of network System Fault 55
AR Modem HW Err = modem hardware
error
System Fault 56
AR Modem SW Err = modem software
error
System Fault 57
AR Opt. Bus Err = loss of communications
to ARDIS module
System Fault 58
AR Corrupt MSG = message error System Fault 59
tition Mode after 40 seconds without a keypad entry.
Error Displays can only be read when the control is disarmed.
Some Control Panel Errors, such as battery trouble and any RF
troubles, will cause the keypad sounders to beep every 10 seconds.
The keypad sounders may be silenced for 4 hours by entering:
The sounders will continue to resound until the problem is fixed.
To Clear a display, enter:
NOTE:System faults may be read from any keypad because they
There is an E rror Message. To
display the message, enter [PIN] + [#
[8] [7].
There is a po we r fa i lu r e, and t h e
panel is operating on backup battery
power.
If the system has just been through a
power failure, wait at least two hours
for the battery to rechar g e, the enter
[PIN] + [System Reset] to perform a
battery test,
The communicator failed to
communicate with the Central
Station.
Internal error in the control circuitry or
optional circuitry. See System Faults.
One of the keypads is not responding
to the Control Panel.
One of the keypad housings has
been op ened.
The multiplex bus is defe c tive or has
been shorted.
The auxiliary power has been
shorted.
One of the zones is not responding to
the Control Panel. This may also be
displ ayed during power -u p; i f so,
ignore it.
Indicates a problem with an RF
(wireless) zone.
One of the multiplex smoke detectors
has failed the sensitivity test and may
require cleaning or replacement. The
keypad beep may be cleared by
entering [PIN] + [Off].
[PIN] + [Off].
[PIN] + [System Reset].
Clear the Error Display only on the advice of your
installing company or if you are certain the problem
has been remedied.
are system-wide. All other Error Displays are limited to
the partition the standard keypad is in. If you are on a
Master keypad, you may read Error Displays one partition
at a time.
7.7.3 Event History
The History Buffer stores the last 400 events in memory. The
DS7447/DS7447E can display all of these events. If this test is
performed from a Master keypad, it must be in Single Partition
Mode. The DS7445/DS7445i will only display those zones (1-8)
that have alarmed since the last Event History Readback. The
RF3341 cannot display history events.
To readback the Event History Buffer:
• Press [PIN] + [#] [8] [9]. On a DS7447/DS7447E keypad, the last
event to take place will be displayed. On a DS7445/DS7445i
keypad, the zone LEDs for any zones that have alarmed since
the last Event History Readback in that partition will flash.
• Scroll through the events using the [9], [6], and [#] keys as follows:
To begin scrolling back through the events, press the [#] key. The
[#] key will scroll you back through the history line by line. The [9]
key will scroll you back in reverse chronological order by event. A
[6] will scroll you back up through the events (toward the most
recent) by event.
Each event consists of two or three lines or display screens. The
first line/screen will be the event title and user. The second line/
screen will be the date of the event or the change being made. If
there is a third line/screen, it will be the date of the change.
NOTE:When performing this from a Master keypad, each partition
will display its own history.
• T o exit the Event History Mode, press the [*] key or wait 20 seconds
and the keypad will exit automatically.
7.8Testing Your System
7.8.1 Zone (System Walk) T est
The Zone Test is used to confirm that detectors will report alarms
to the keypad. A Zone Test works on all zones, except 24-hour
zones and fire zones. While the keypad is in a Zone Test, no control
panel alarms will activate an alarm, except 24-hour zone alarms
and fire alarms; these will override the Zone Test function.
To initiate a Communicator Test:
• Press [PIN] + [#] [8] [2]. A long beep will sound. A “Test” report is
sent to the monitoring service. If the test fails, the keypad sounder
will sound continuously. To silence the sounder, press [System
Reset].
NOTE:This test may take several minutes to complete because
the control panel will try ten attempts.
To perform a Zone Test:
• Press [PIN] + [#] [8] [1].
- The DS7445/DS7445i zone LEDs of any untested zones will
flash.
- The DS7447/DS7447E displays “Test Zone” followed by the
zone number of any zones that have not been tested.
• Pick any untested zone and manually cause a detector to alarm
using a method specified in the detector’s Installation
Instructions.
- The DS7445/DS7445i zone LED for the zone currently being
tested willturn on steady.
- The DS7447/DS7447E displays “Now Testing” followed by
the zone number of the zone that is currently being tested.
• Clear the alarm condition from the detector using a method
specified in the detector’s Installation Instructions, and trigger
an alarm on the next detector in that zone. Continue until all
detector’s in that zone have been tested.
- As each zone is tested, its DS7445/DS7445i zone LED turns
off.
- As each zone is tested, the DS7447/DS7447E display returns
to “Test Zone” and indicates the remaining untested zones.
• Test each zone.
• Exit the Zone Test using [PIN] + [#].
7.8.2 Battery Tests
You may perform a test of the battery and the local sounder or just
test the battery. If these tests are performed from a Master keypad,
it must be in Single Partition Mode. System Tests are not available
from RF (wireless) keypads.
To initiate a Local Battery / Sounder Test:
• Press [PIN] + [#] [8] [5]. All keypad LEDs will turn on. The keypad
sounder and all alarm sounding devices will operate for two
seconds. If the test fails, the control panel will indicate a control
problem. See Error Displays on page 30.
NOTE: If power in your building has been off recently, wait two
hours for the battery to recharge and then try again.
7.8.4 Fire Walk Test
This test is used to confirm that Smoke detectors will report alarms
to the keypads. The Fire Walk Test tests all fire zones, including
verified fire and waterflow.
At the start of the Fire Walk Test a Fire Walk Test report, if
programmed, is sent to the central station. Fire alarm reports are
not sent to the central station during the Fire Walk Test. A Fire Walk
Test restoral is sent upon completion of the Fire Walk Test.
The Fire Walk Test is enabled for 20 minutes once it is started. The
test time is extended to 20 minutes every time another zone is
tested.
When a fire zone is tested, any output programmed to follow that
zone will activate for 5 seconds.
To perform a Fire Walk Test:
• Press [PIN] + [#] [9] [1].
- The DS7445/DS7445i zone LEDs of any untested zones will
flash.
- The DS7447/DS7447E displays “Fire Test” followed by the
zone number of any zones that have not been tested.
• Pick any untested zone and manually cause a detector to alarm
using a method specified in the detector’s Installation
Instructions.
- The DS7445/DS7445i zone LED for the zone currently being
tested will turn on steady.
- The DS7447/DS7447E displays “Fire Testing” followed by
the zone number of the zone that is currently being tested.
• Clear the alarm condition from the detector using a method
specified in the detector’s Installation Instructions, and trigger
an alarm on the next detector in that zone. Continue until all
detector’s in that zone have been tested.
- As each zone is tested, its DS7445/DS7445i zone LED turns
off.
- As each zone is tested, the DS7447/DS7447E display returns
to “Fire Test” and indicates the remaining untested zones. *
• Test each zone as instructed by your installing company.
• Exit the Zone Test using [PIN] + [#].
To initiate a Battery Test:
• Press [PIN] + [System Reset]. The control panel will perform a
battery test. The control panel will report a Low Battery or a Low
Battery Restoral if necessary.
NOTE:A Fire Walk Test will prevent the system from sending any
Fire Reports during the test.
7.8.3 Communicator Test
This test is available only if the system transmits alarms and system
information to a monitoring service, and has been programmed by
the security installing company to permit communicator tests. This
test can be performed from a Master Keypad. The account code for
partition #1 will be used. System Tests are not available from RF
(wireless) keypads.
To enter the Programmer’s Mode, enter the Programmer ’s Code followed by [#] [0]. Shorting the program pads (see section 2.0 for
location) on the control panel will also activate Programmer’s Mode.
NOTE:The factory set default Programmer’s Code is [9] [8] [7] [6]. If the system has been reprogrammed for 6-digit PINs, the default
Programmer’s Code will be [9] [8] [7] [6] [5] [4].
8.2Reading Back a Program Address
Once you are in the programmer’s mode, to read back the value of a Program Address, enter that Program Address followed by [#]. Each
data digit is displayed one data digit at a time. To view the second data digit, enter the # button again.
The display will look like this:
8.3Entering a Value in a Program Address
To enter a value in the Program Address, enter the Program Address, then enter the value for each Data Digit, then enter [#] to save it and
move on to the next Program Address. Entering data digit 1 will increment you to the next data digit.
The display will show the Program Address and will display the value of each Data Digit after you enter it. The data will be programmed
(saved) when you press the [#] key. The control panel will automatically increment to the next program address.
• If you wish to program that next address, enter the necessary information.
• If you wish to read back the value of that address, press the [#] key.
• If you wish to program a different address, press the [*] key two times and enter the program address you wish to program.
If you make a mistake at any time, press the [*] key two times (before pressing the [#] key). This will clear the display , allowing you to enter
the program address you wish to work with.
8.4HEX values
Some Data Digit values will be higher than 9. These values must be programmed by pressing the [*] key followed by some other
number. These values will display as HEX characters (A - F) when entered. Example: entering *0 at the keypad will display an A.
The HEX character values are as follows:
*0 = A*1 = B*2 = C*3 = D*4 = E*5 = F
8.5Defaults
The DS7400Xi is shipped from the factory as a working, pre-programmed control. Many of the programming addresses may already be
set to the values you need. The default values are shown in
If the value you would like is in
In the example, a “0” is the default value:
If the default value is not shown in
, you don’t need to re-program this address.
, it will be shown in a separate table.
.
8.6Setting the Control to the Factory Default
Only enter [0] [1] [#] in Program Address 4058 when you are completely sure you want to erase all installer programming. Entering [0] [1] [#] in Program Address 4058 will immediately reset the control to the factory default. Any
programming already done by the installer will be erased. This action cannot be reversed.
To set the control’s programming values back to the default, enter the programming mode, then enter [4][0][5][8][0] [1] [#].
8.7Exiting the Programmer ’s Mode
To exit the Programmer ’s Mode, press the [*] key for a minimum of 2 seconds. If no keypad entries are made for 4 minutes, the control
will automatically exit you from the Programmer’s Mode.
The Programming Reference Guide makes use of three types of charts. Each is described below.
If the chart looks like this, a combination of features is available to be programmed for that particular address.
10.1General Control Programing: Program Address (0000)
General Control programming defines the system-wide general operating parameters. See Glossary (section 6.1) for further details.
Normal Arming Custom Arming Perimeter Instant Arming Perimeter Arming Maximum Security Arming Closing Ring Back Siren on Communication Fail Restore Swinger Shunts
= For installations in North America, select 60 Hz. operation.
*0 - *5 are Hex values. They will display as A - F at the keypads.
Select Options
Restore zone when Sounders Silence
Restore zone when Zone Restores
Restore zone when System is Disarmed
0Select Options1 234567
89 *0 *1 *2 *3 *4 *5
Enter D D as a:
012
4
3
5
678
Allow Swinger Shun ts. Send Bypass Reports
Allow Swinger Shunts. No B ypass Repo rts
** = • Normal Arming = [PIN] + [On]: If programmed, Normal Arming arms the entire system while allowing entry delays for entry/
exit zones.
• Perimeter Instant Arming = [PIN] + [No Entry] + [Perimeter Only]: If programmed, Perimeter Instant Arming arms only the
perimeter of the system and does not allow entry delays for entry/exit zones.
• Perimeter Arming = [PIN] + [Perimeter Only]: If programmed, Perimeter Arming arms only the perimeter of the system
while allowing entry delays for entry/exit zones.
• Custom Arming = [PIN] + [#] [4]: If programmed, Custom Arming allows custom arming of the system and bypasses the
zone functions specified in data addresses 2725-2728.
• Maximum Security Arming = [PIN] + [No Entry] + [On]: If programmed, Maximum Security Arming arms the entire system
and does not allow entry delays for entry/exit zones.
Programming a Zone is a four step process. These steps must be performed, in order, to program a zone.
• Step 1 is programming Zone Functions (what the zone will do in alarm),
• Step 2 is assigning a Zone Function to the zone.
• Step 3 is assigning a Zone T ype to the zone.
• Step 4 is assigning the zone to a partition.
Step 1: Programming the Zone Functions
10.2Zone Function Programming: Program Addresses (0001-0030)
A Zone Function is the description of how a zone will behave. Up to 30 different Zone Functions may
be programmed. Y ou may use the default values (which are already programmed into the panel) and
skip this step, or change the defaults, or add new Zone Functions. See section 6.2 for further
details.
Select Options
Invisible Alarm
Silent Alarm
Steady Alarm Output
Pulsing Alarm Output
Alarm on Short
Alarm on Open
Trouble on Open**
Trouble on Short
*2 - *5 are Hex values. They will display as C - F at the keypads.
** = Only when disarmed. When armed, this becomes Alarm on Open or Short for
non-24-hour zones.
not be programmed for Trouble on Open.
2 = Steady alarm output, alarm on short and open.
3 = Entry/exit delay 1.
2 = Steady alarm output, alarm on short and open.
4 = Entry/exit delay 2.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
5 = Interior entry/exit follower.
2 = S teady alarm output, alarm on short and open.
6 = Interior home/away.
2 = S teady alarm output, alarm on short and open.
7 = Interior Instant.
2 = Steady alarm output, alarm on short and open.
2 = 24-hour.
7 = Pulsing alarm output, alarm on short, trouble on open.
*0 = Fire zone with verifica tion.
2 = S teady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = S teady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = S teady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = S teady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = S teady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = S teady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = S teady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Inst ant.
Default Values
Interior Delay ed
Perimeter Instant
24-Hour
Entry/Exit Delay #1
Entry/Exit Delay #2
Interior En try/Exit Follower
Interior Home/Away
Interior Insta nt
Day Monitor
Keyswitch (See note below)
Fire Zone with verification
Fire Zone w/out verification
Waterflow
Supervisory
Entry/Exit Delay Cancel 1
Entry/Exit Delay Cancel 2
Note:
If digit 2 = 9 (keyswi tch), use
this chart for digit 1.
Single Par tition-No Force A rm
Single Partition-Can Force Arm
All Partitions-No Force Arm
An open loop will always produce
a steady alarm response.
In this step, a Zone function is assigned to the Zone.
10.3Zone Programming: Program Addresses (0031-0278)
In Zone Programming, each zone is defined according to its input (single or multiple zone input, or a DS7465) and its Zone Function
(1-30) or Output Function (1-24). The DS7465’s relay is the only device that will follow the output functions; its input loop will follow a zone
function. All single and multiple zone inputs will follow a zone function. See section 6.3 for further details.
Data Digit
1
he DS7465 occupies tw o zones. The odd numbered
one of the zone pair is the input zone. The even
umbered zone of the zone pair is the output relay.
he output follows an output function.
10.4Zone Programming: Zone Type Program Addresses (0415-0538)
In Zone Programming, each zone is defined according to its Input (single or multiple zone input, or a DS7465) and its Zone Function
or Output function (1-24). The DS7465’s relay is the only device that will follow the output functions; its input loop will follow a zone
function. All single and multiple zone inputs will follow a zone function. See section 6.3 for further details.
Select OptionDD
(zones 1-8 on the control, multiplex contacts,
(any zone that is on a DS7432, DS7433, or DS7460)
(the input zone or the output relay on a DS7465)
IMPORTANT
MX280, MX280TH Multiplex Smoke Detectors
MX280THL Multiplex Smoke Detectors
The MX280THL occupies two zones. The odd
numbered zone of the zone pair is the smoke
detector. Th e even numbered zone of the zone
MPORTANT
Single Zone Input
sensors, or a DS7457)
Multiple Zone Input
DS7465 Connectio ns
The D7465 occupies two zones. The odd
numbered zone of the zone pair is the input
zone. The even numbered zone of the zone
with Low Temperature Alarm
pair is the output relay.
pair is the Low Temperatu r e Alarm.
Keyfob
DDSelect Option
Data Digit
(zones 1-8 on the control, multiplex contacts,
0
1
2
If Data Digit 1 is 2
Data Digit 2 MUST be 2
3
4
If Data Digit 1 is 4
Data Digit 2 MUST be 4
12
0
1
(any zone that is on a DS7432, DS7433, or D S7460)
2
(the input zone or the output relay on a DS7465)
The D7465 occu p ies t w o zo nes. The odd
numbered zone of the zone pair i s the input
zone. The even numbered zone of t he zone
MX280, MX280TH Multiplex Smoke Detectors
3
MX280THL Multiplex Smoke Detectors
4
The MX280THL occupies two zones. The odd
numbered zone of the zone pair is the smoke
detector. The even number ed zone of the zone
pair is the Low Temperatur e Alarm.
5
Singl e Zone Input
sensors, or a DS7457)
Multiple Zone Input
DS7465 Connections
pair is the output relay.
with Low Temperature Alarm
Keyfob
IMPORTANT
IMPORTAN
5
ZonesAddressZonesAddressAddressAddressZonesZones
Zones 1 & 2
Zones 3 & 4
Zones 5 & 6
Zones 7 & 8
Zones 9 & 10
Zones 11 & 12
Zones 13 & 14
Zones 15 & 16
Zones 17 & 18
Zones 19 & 20
Zones 21 & 22
Zones 23 & 24
Zones 25 & 26
Zones 27 & 28
Zones 29 & 30
Zones 31 & 32
Zones 33 & 34
Zones 35 & 36
Zones 37 & 38
Zones 39 & 40
Zones 41 & 42
Zones 43 & 44
Zones 45 & 46
Zones 47 & 48
Zones 49 & 50
Zones 51 & 52
Zones 53 & 54
Zones 55 & 56
Zones 57 & 58
Zones 59 & 60
Zones 61 & 62
Zones 63 & 64
Zones 65 & 66
Zones 67 & 68
Zones 69 & 70
Zones 71 & 72
Zones 73 & 74
Zones 75 & 76
Zones 77 & 78
Zones 79 & 80
Zones 81 & 82
Zones 83 & 84
Zones 85 & 86
Zones 87 & 88
Zones 89 & 90
Zones 91 & 92
Zones 93 & 94
Zones 95 & 96
Zones 97 & 98
Zones 99 & 100
Zones 101 & 102
Zones 103 & 104
Zones 105 & 106
Zones 107 & 108
Zones 109 & 110
Zones 111 & 112
Zones 113 & 114
Zones 115 & 116
Zones 117 & 118
Zones 119 & 120
Zones 121 & 122
Zones 123 & 124
Zones 125 & 126
Zones 127 & 128
Zones 129 & 130
Zones 131 & 132
Zones 133 & 134
Zones 135 & 136
Zones 137 & 138
Zones 139 & 140
Zones 141 & 142
Zones 143 & 144
Zones 145 & 146
Zones 147& 148
Zones 149 & 150
Zones 151 & 152
Zones 153 & 154
Zones 155 & 156
Zones 157 & 158
Zones 159 & 160
Zones 161 & 162
Zones 163 & 164
Zones 165 & 166
Zones 167 & 168
Zones 169 & 170
Zones 171 & 172
Zones 173 & 174
Zones 175 & 176
Zones 177 & 178
Zones 179 & 180
Zones 181 & 182
Zones 183 & 184
Zones 185 & 186
Zones 187 & 188
Zones 189 & 190
Zones 191 & 192
Zones 193 & 194
Zones 195 & 196
Zones 197 & 198
Zones 199 & 200
Zones 201 & 202
Zones 203 & 204
Zones 205 & 206
Zones 207 & 208
Zones 209 & 210
Zones 211 & 212
Zones 213 & 214
Zones 215 & 216
Zones 217 & 218
Zones 219 & 220
Zones 221 & 222
Zones 223 & 224
Zones 225 & 226
Zones 227 & 228
Zones 229 & 230
Zones 231 & 232
Zones 233 & 234
Zones 235 & 236
Zones 237 & 238
Zones 239 & 240
Zones 241 & 242
Zones 243 & 244
Zones 245 & 246
Zones 247 & 248
10.5Zone Partition Assignment: Program Addresses (0287-0410)
In Zone Partition Assignment, each zone is assigned to a partition. By default, all zones are assigned to partition 1.
The partition assignment for odd numbered zones is programmed in the first data digit of these addresses. The partition assignment
for even numbered zones is programmed in the second data digit of these addresses.
For example, to assign zone 1 to partition 1 and zone 2 to partition 2, program address 0287 as 01.
ZonesAddressZonesAddressAddressAddressZonesZones
Zones 1 & 2
Zones 3 & 4
Zones 5 & 6
Zones 7 & 8
Zones 9 & 10
Zones 11 & 12
Zones 13 & 14
Zones 15 & 16
Zones 17 & 18
Zones 19 & 20
Zones 21 & 22
Zones 23 & 24
Zones 25 & 26
Zones 27 & 28
Zones 29 & 30
Zones 31 & 32
Zones 33 & 34
Zones 35 & 36
Zones 37 & 38
Zones 39 & 40
Zones 41 & 42
Zones 43 & 44
Zones 45 & 46
Zones 47 & 48
Zones 49 & 50
Zones 51 & 52
Zones 53 & 54
Zones 55 & 56
Zones 57 & 58
Zones 59 & 60
Zones 61 & 62
Zones 63 & 64
Zones 65 & 66
Zones 67 & 68
Zones 69 & 70
Zones 71 & 72
Zones 73 & 74
Zones 75 & 76
Zones 77 & 78
Zones 79 & 80
Zones 81 & 82
Zones 83 & 84
Zones 85 & 86
Zones 87 & 88
Zones 89 & 90
Zones 91 & 92
Zones 93 & 94
Zones 95 & 96
Zones 97 & 98
Zones 99 & 100
Zones 101 & 102
Zones 103 & 104
Zones 105 & 106
Zones 107 & 108
Zones 109 & 110
Zones 111 & 112
Zones 113 & 114
Zones 115 & 116
Zones 117 & 118
Zones 119 & 120
Zones 121 & 122
Zones 123 & 124
Zones 125 & 126
Zones 127 & 128
Zone s 129 & 130
Zone s 131 & 132
Zone s 133 & 134
Zone s 135 & 136
Zone s 137 & 138
Zone s 139 & 140
Zone s 141 & 142
Zone s 143 & 144
Zone s 145 & 146
Zones 147& 148
Zone s 149 & 150
Zone s 151 & 152
Zone s 153 & 154
Zone s 155 & 156
Zone s 157 & 158
Zone s 159 & 160
Zone s 161 & 162
Zone s 163 & 164
Zone s 165 & 166
Zone s 167 & 168
Zone s 169 & 170
Zone s 171 & 172
Zone s 173 & 174
Zone s 175 & 176
Zone s 177 & 178
Zone s 179 & 180
Zone s 181 & 182
Zone s 183 & 184
Zone s 185 & 186
Zone s 187 & 188
Zone s 189 & 190
Zone s 191 & 192
Zones 193 & 194
Zones 195 & 196
Zones 197 & 198
Zones 199 & 200
Zones 201 & 202
Zones 203 & 204
Zones 205 & 206
Zones 207 & 208
Zones 209 & 210
Zone s 211 & 212
Zones 213 & 214
Zones 215 & 216
Zones 217 & 218
Zones 219 & 220
Zones 221 & 222
Zones 223 & 224
Zones 225 & 226
Zones 227 & 228
Zones 229 & 230
Zones 231 & 232
Zones 233 & 234
Zones 235 & 236
Zones 237 & 238
Zones 239 & 240
Zones 241 & 242
Zones 243 & 244
Zones 245 & 246
Zones 247 & 248
10.6Zone Bypass Programming: Program Addresses (2721-2724)
it
it
Zone Bypass programming determines which zone functions can be bypassed. Zone functions that can not be bypassed can not be
force armed either. Fire zones can never be manually bypassed, but can be force armed. The Default of [0] or [8] means those zones can
be bypassed.
P A 2721
Note: This programming item does not affect Custom Arming Programming (PA 2725-2778) or
Swinger Shunt Bypasses (see programming for Program Address 0000).
Data Dig
12
Enter the Data Digit as a:
Select Options
Zone Function 1 Can Be Bypassed
Zone Function 2 Can Be Bypassed
Zone Function 3 Can Be Bypassed
Zone Function 4 Can Be Bypassed
*0 - *5 are Hex values. They will di spl ay as A - F at the keypads.
Select Options
Zone Function 5 Can Be Bypassed
Zone Function 6 Can Be Bypassed
Zone Function 7 Can Be Bypassed
Zone Function 8 Can Be Bypassed
*0 - *5 are Hex values. They w ill di spl ay as A - F at th e keypads.
123456789 *0 *1 *2 *3
0
Enter the Data Digit as a:
123456709 *0 *1 *2 *3 *4 *5
8
*4
*5
P A 2722
Data Dig
12
Select Options
Zone Function 9 Can Be Bypassed
Zone Function 10 Can Be Bypassed
Zone Function 11 Can Be Bypassed
Zone Function 12 Can Be Bypassed
*0 - *5 are Hex values. They wi l l display as A - F at the keypads.
Enter the Data Digit as a:
0
123456789 *0 *1 *2 *3 *4 *5
Enter the Data Digit as a:
Select Options
Zone Function 13 Can Be Bypassed
Zone Function 14 Can Be Bypassed
Zone Function 15 Can Be Bypassed
Zone Function 16 Can Be Bypassed
*0 - *5 are Hex values. They will display as A - F at the keypads.
10.7Output Programming: Program Addresses (2734, 2735, 2736)
t
Output programming defines the event, partition, and type of alarm (burglary or fire) that will trigger each of the three physical outputs on
the control panel.
See section 3.0 for the location of the physical outputs on the control panel.
See Glossary (section 6.4) for further details.
Data Digit
Pro grammable Output 1 will
be ON for 10 seconds after
pressing [System Reset].
Pro grammable Output 2 will
be OFF for 10 seconds after
pressing [System Reset].
3
Options
Disabled
Armed Full
Armed Partial
Armed Any
** = This incl udes invisible zones. See glossary for further details.
*** = See section 6.4 for description of th is option.
OutputAddressDefault
Alarm
Prog rammable Output 1
Prog rammable Output 2
DD
0
1
2
3
Select Option
Latch on ANY Zone Alarm**
ON during Entry Pre-Alert/E xit Warning
ON for 10 sec. after pressing [System Reset]
ON when system is Armed
Ground Sta rt
System Status (ready to arm)
Zone Alar m
Zone Alar m d elayed by 20 sec.
Keypad Sounder Output
Access Output (10 sec. pulse)
Keyfob
10.8Output Partition Assignment: Program Addresses (2737-2738)
it
In Output Partition Assignment, each On-board output is assigned to a partition. By default, outputs are assigned to all partitions.
PA 2737PA 2738
Data Digit
12
Data Dig
12
Select OptionDD
OutputAddressDefault
Alarm
Programmable Output 1
Programmable Output 2
2737-DD1
2737-DD2
2738-DD1
8
8
8
Belongs to Partition 2
Belongs to Partition 3
Belongs to Partition 4
Belongs to Partition 5
Belongs to Partition 6
Belongs to Partition 7
Belongs to Partition 8
Follows all Partitions
0Belongs to Partition 1
1
2
3
4
5
6
7
8
Keyfob Chirp
Options
Chirp Disabled
Bell Output
P01
P02
DD
0
1
2
3
10.9Partition Control Programming: Program Address (3420)
Partition Control programming defines the number of partitions in use and the common area (common area can only be partition 1).
10.11 Keypad Assignment Programming: Program Addresses (3131-3138)
K
Keypad Assignment Programming is where you assign the keypad type and the partition to which it belongs.
See Glossary (section 6.6) for further details.
Each keypad must have its own Bus address. This must also be selected on the keypad via its address pins. See DS7445/
DS7447 Installation Guide (P/N: 22235). One keypad must be selected as keypad 1.
Defaults:The default, if using only one keypad, is an Alpha keypad belonging to partition one.
Program Address 3131
Data D igit 1 Data Dig it 2
Program Address 3132
Data Digit 1 Data Digit 2
Program Addr es s 3133
Data Digit 1 Data Digit 2
Program Address 3134
Data Digit 1 Data Digit 2
eypad 1*
default = 1
Program Address 3135
Data D igit 1 Data Dig it 2
Keypad 9
default = 0
* = When in Commercial Fire Mode, certain keypads must have specific assignments (see section
6.11).
** = Keypads 11-15 are connected to the Option Bus. If the DS7412 is connected to the Option Bus (at
keypad address 13 or 14), keypad 13 or 14 is unavailable. Similarly, if the DS7420i is connected to the
Option Bus at keypad address 15, keypad 15 is unavailable; and if the DS7488 is connected to the
Option Bus at keypad address 11-15, the corresponding keypad(s) is (are) unavailable.
Keypad 2
default = 0
Keypad 10
default = 0
Select Options
Disabled
Alpha (LCD) Keypad
LED Keypad
Master Keypad
*** = If only using one partition, do not program keypads as Master Keypads.
Only program for a Master Keypad if you need to view multiple partitions from a
single keypad.
***
Keypad 3
default = 0
Program Address 3136
Data Digit 1 Data Digit 2
Keypad 11**
default = 0
Keypad 4
default = 0
**** *
Keypad 12**
default = 0
0123
Keypad 5
default = 0
Program Addr es s 3137
Data Digit 1 Data Digit 2
Keyp ad 13**
default = 0
Data Digit
12
Keypad 6
default = 0
Keypad 14**
default = 0
Select Options
LCD Backlight Always On
LCD Backlight Off Until Keypress
Backlight selection af fect s all L CD keyp ads
Keypad 7
default = 0
Program Address 3138
Data Digit 1 Data Digit 2
Keypad 15**
default = 0
Keypad 8
default = 0
01
10.12 Keypad Partition Assignment: Program Addresses (3139-3146)
10.13 Emergency Key Programming: Program Addresses (3147-3148)
it
M
P A 3147
Emergency Key and Panic Key programming disables or activates these keys (the A, B, and C keys) located on the keypads and/or
keyfobs.
It also determines a silent, pulsed, or steady alarm.
See Glossary (section 6.7) for further details.
Data Dig
Select OptionDD
12
Fire Key
A
Fire Key Disabled
Fire Key = Disabled
Fire Key = Steady Alarm
0
1
2
Fire Key = Pulsed Alarm3
May be forced to a different value when in
Commercial Fire Mode. See section 10.16.3.
Emergency Key
Special Emergency Key Disabled
Special Emergency Key = Silent Alarm
Specia l Emerg ency Key = S tea dy Alarm
B
Specia l Emerg ency Key = Pulsed Alarm3
P A 3148
Panic Key
Data Digit
12
C
Select OptionDD
Panic Key Disabled
Panic Key = Silent A lar m
Panic Key = Steady Alarm
Panic Key = Pulsed Alarm3
ay be forced to a different value when in Comm ercial Fire Mode . See sect io n 10.16 .3.
0
1
2
Data Digit 2
must be 0
0
0
Select OptionDD
0
1
2
Armed
Perimeter
Supervisory
Status
Bell Silence d
Power
Trouble
Fire
12345678
910
123
456
789
*
11 12 13 14
TEST WEEKLY
0
15 16
#
ABC
On
Off
Perim eter
Bypass
System
Only
No
Entry
Reset
10.14 Custom Arming Programming: Program Addresses (2725-2728)
10.15 Force Arming and Ground Fault Detect Programming: Program Address (2732)
Force Arming programming defines how many zones may be Force Armed using an Arming sequence followed by the [Bypass] key.
With this entry, all violated zones (up the programmed limit) will automatically be Force Armed (bypassed). Ground Fault Detect
programming determines whether or not the control will detect a ground fault condition.
See Glossary (sections 6.9 and 6.10) for further details.
Note: This limit does not apply when arming with
a keyswitch programmed with force arming enabled.
10.16 Commercial Fire Mode Programming: Program Address (2733)
This section describes how to define the parameters for the Commercial Fire Mode.
See Glossary (section 6.11) for further details.
When programming Fire zones, it is recommended that they be zone functions 12 and 13 (see sections 10.2, 10.4 and 10.16.3).
10.16.1 When Central Station Commercial Fire Mode is chosen, address 4021 (DS7420i: Dual Phone Line/Bell Supervision Mod-
ule Output Programming), will be forced to a value of 5.
10.16.2 When Local Commercial Fire Mode is chosen, address 4021 (DS7420i: Dual Phone Line/Bell Supervision Module Output
Programming),will be forced to a value of 3, 4, or 5. (Turns the Bell Monitor feature ON and the Alarm Output on Line Fault feature
OFF)
10.16.3 Regardless of which Commercial Fire Mode is chosen, the following parameters will be forced when exiting local
programmer’s mode:
• Zone Function 12, address 0012, will be a 7 *0. (Alarm on Short, Trouble on Open, Pulsing Fire with verification)
• Zone Function 13, address 0013, will be a 7 *1. (Alarm on Short, Trouble on Open, Pulsing Fire without verification)
• Zone Function 14, address 0014, will be a 7 *2. (Alarm on Short, Trouble on Open, Pulsing Water Flow)
• Zone Function 15, address 0015, will be a 7 *3. (Alarm on Short, Trouble on Open, Pulsing Supervisory)
• Zone Bypass address 2722 will not allow zone functions 12 - 15 to be bypassed.
• Emergency Key, address 3147, data digit 1, will become a 3 if programmed previously as a 2. Data digit 2 will become a 2 if
programmed previously as a 3.
• Panic Key, address 3148, data digit 1, will become a 2 if programmed previously as a 3.
• Fire Bell Cutoff, address 4032: If less than 5, set to 5, otherwise untouched.
• The AC Fail Report delay will be random between 6-12 hours regardless of the delay time programmed in 4034. Also, the AC Fail
Report will not be sent as a “tag-along.”
10.16.4 In Central Station Commercial Fire Mode, the following communication parameters will be forced:
Report Codes: If 0, the following defaults will be set, otherwise they will be unchanged.
• Phone Control (address 3156): If 0, set to 6 1, 4/2 @ 18/23, 10pps, otherwise untouched.
• Test Report (address 4026): Set to 8, call out every day.
10.17 Open/Close Report Control Programming: Program Address (3149)
it
it
See Glossary (section 6.12) for further details.
Data Dig
12
Enter the Data Digit as a:
4Select Options0 12356 789
Do not report opens or closes
Report opens and close s in Partition 1
Report opens and close s in Partition 2
Report opens and close s in Partition 3
Report opens and close s in Partition 4
Report opens and close s in Partition 5
Report opens and close s in Partition 6
Report opens and close s in Partition 7
Report opens and close s in Partition 8
Report first Partition to open and last Partition to close**
** = When using t his option, all partitions should have the same account code.
Send Closing and
Bypass reports at close
Send Closing and
Bypass reports after
exit delay
Data Dig
12
0
1
0
10.18 Open/Close & Zone Report Control Programming: Program Address (3151)
This section allows you to decide which phone number will send open and close reports, zone alarm, zone restoral, and zone trouble
reports.
10.19 Report Control Programming: Program Address (3152)
This section allows you to decide which phone number will send reports other than open/close reports and zone reports.
Data Digit
Select OptionDD
Altern ate between both Phone Numbers
Report to P hone Number 1
Report to Phone Number 2
Report to Phone Number 1 and 2
10.22 General Authority Programming: Program Address (3421-3424)
This allows for a user with a General Authority level to Arm, Disarm and Bypass specified zones.
See Glossary (section 6.1) for further details.
Program Address 3421
Data Digit 1 Data Digit 2
Program Address 3423
Data Digit 1 Data Digit 2
Partition 1Partition 2
Partition 5Partition 6
Select OptionDD
General Code can Arm, Disarm, and Bypass
General Code can Arm and Bypass
General Code can Arm and Disarm
General Code can Arm
0
1
Program Address 3422
Data Digit 1 Data Digit 2
Program Address 3424
Data Digit 1 Data Digit 2
2
3
Partition 3Partition 4
Partition 7Partition 8
10.23 Arming Warning Programming: Program Addresses (3425-3428)
Arming Warning programming defines whether the keypad will be audible during the exit delay and auto arm period. If programmed, the
keypad sounder will activate once every 5 seconds during the exit delay. At 10 seconds and 5 seconds remaining, the keypad sounder
will activate 3 times. During auto arming, a pre-arming period will begin 15 minutes before the system arms automatically. The keypad
sounders will pulse five times every minute. During the last five minutes before arming, these sounders will be on steady.
10.24 DS7412 RS232 Interface Control Programming: Program Address (4019)
it
DS7412 RS232 Interface Control
Programming allows you to enable or disable
the DS7412 and to select which history events
are sent to the printer as they occur. Selecting
“No Events” will cause the history to be printed
only on command.
T o print the History Buffer st arting from the most
recent event, enter the Master Code followed
by [#] [0] [8]. T o stop printing, enter Master Code
[#] [0] [8] again.
10.25 DS7412 RS232 Interface Configuration Programming: Program Address (4020)
DS7412 RS232 Interface Configuration Programming allows you to configure the DS7412 for your printer. Most printers will operate
using the default values for the DS7412. Some printers may operate more efficiently using optional program values.
Consult the operating guide provided with your printer to be sure that its configuration matches
the one programmed here.
NOTE:If using the WDSRP Direct Connection
option for programming, Address 4019
must be set for 1 0. Address 4020 must
be set for 2 5.
10.26 RS232 Carriage Return/Line Feed Control: Program Address (4027)
The RS232 Carriage Return/Line Feed (CR/LF) Control allows you to choose between sending carriage returns/line feeds or spaces to the DS7412 module. This is only used when Program Address 4019 Data Digit #2 is programmed with the numbers 1 through
10.27 Report Programming: Program Addresses (3207-3419)
• To send the User number along with open, close, or partial close reports: place an ‘F’ (*5) in the extended digit.
• To disable a report (meaning that nothing will be sent), place a ‘0’ in the reporting digit.
• When using SIA or Contact ID format, place a ‘1’ in the reporting digit of each report you wish to enable. It is not necessary to program
the extended digit.
• For suggested values for 4/2, BFSK and Pager format, see section 12.1-12.3. For SIA and Contact ID, the values sent are listed in
sections 13.1 and 13.2. For other formats, consult your central station.
• HEX values: Some Data Digit values are higher than 9. These values are programmed by pressing the [*] key followed by another
number. These values will display as HEX characters when entered. The HEX character values are as follows:
Select OptionDDDDDDSelect OptionSelect OptionSelect Op tion
0
Use Phone
Use Either
Try Phone First
Use Both
1 27 *1 *5
Select Options
Enter the DD as a:
3
Use Phone
Use Either
Try Phone First
Use Both
1 27 *1 *5
Select Options
Enter the DD as a:
3
Data Digit
12
Second digit: Zone Alarm, Zone Restoral,
and Zone Trouble Reports.
Phone/DS7416i report routing and Phone First count (3154)
First Digit: System Reports.
Use DS7416i
Use DS7416i
Use DS7416i
10.28 Phone/DS7416i Routing Control: Program Addresses (3153-3154)
If address 3155 is programmed to “Try DS7416i first”, the following addresses can be used to control report routing. If address 3155
is set to “Send alarms via both DS7416i and digital”, this will force alarms to go to the phone even if the Phone/DS7416i report
routing for alarms does not specify phone usage.
Phone/DS7416i report routing (3153).
First digit: Open and Close Reports.
Second digit: Phone First count. Number of attempts before trying the DS7416i:
This value is used to control the number of attempts made on the phone line before switching to the DS7416i. This value is only
referenced if the “Use Phone”, “Use DS7416i”, and “Try Phone First” options are all selected. If the value is less than or equal
to 2, or more than 5, two attempts will be made on the phone before trying the DS7416i if the Phone First option is selected.
10.29 Account Code Programming: Program Addresses (3429-3459)
Account Code programming defines the number transmitted to the central station that identifies this panel. It also identifies which
partition is reporting from this panel.
1.Account Codes are programmed from left to right. If programming a 3 digit Account Code, the fourth digit of the address must be “0.”
For example: If the Account Code is 121, program 1210 in the programming address.
2.If you wish to send a zero “0,” enter it as *0 (this does not apply to the added zero in a three digit Account Code).
For example: If the Account Code is 101, program 1*010 in the programming address. If the Account Code is 3050, program 3*05*0
in the programming address.
When using the Pager Dialing Format (selected in Addresses 3156 and 3157), you may insert a delay time after the phone number is
dialed and before the reports are sent to the pager system. This delay can be used to allow for greeting and instruction messages in the
pager system. This delay will not affect any other report formats.
Pager Delay Time
Address 4038
Data Digit
1
2
0 to 99 seconds
Default = 10 seconds
10.34 Programmer ’s and Master Code Programming: Program Addresses (7589-7592)
Programmer’s Code programming defines what the Programmer’s Code will be. This code is used to enter the programming mode
from the keypads.
Although the DS7400Xi (Ver. 4+) Control/Communicator is shipped with 6-digit codes preprogrammed, it is also shipped
with a 4-digit PIN length default. The default codes for the Programmer’s Code and the Master Code will be 4-digits (9876
and 1234 respectively) unless you have reprogrammed for a 6-digit PIN length.
Program Address 7589
Data Digit
1234
98
Programmer’s Code
Enter as 6 digits.
It can not be the same
as any PIN number.
The Default for the Pro grammer’s Code = 987654
Master Code programming defines what the Master Code will be. This code is the highest authority level for a PIN.
If the Master Code is lost, this address may be used to program a new one.
Otherwise, the Master Code Programming Mode should be used to create PINs
that have a Master Code authority level.
76
56
5
Master Code for User Number 001 has its
authority fixed at level 0. It will always have
access to all partitions.
NOTE:User Numbers 002 through 200
must be programmed from the
Master Code Programming
Mode.
10.35 PIN Length Programming: Program Address (3478)
PIN Length Programming defines the length of the PINs that are assigned to each user.
PINS can be programmed to be 4 or 6 digits in length.
10.36.1 Follow Action: Program Addresses (2740-2771)
To program an Octal Relay Module for Follow Action, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 1 for Follow Action.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired function.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.
The Octal Relay Module is the DS7488. See section 1.18 and 6.4 for further details.
NOTE:If a DS9484 is used, it replaces the DS7488 and takes up outputs 1-4 of the Octal Relay Module. Outputs 5-8 of the Octal Relay
Module are unavailable. If two DS9484 power supplies are used, one replaces Octal Relay Module 1 and the other replaces
Octal Relay Module 2.
For Octal Relay Partition Assignment, see section 10.36.5.
ON during Entry Pre-Alert
ON for 10 sec. after pressing [System Reset]
ON for Any Armed state
Ground Start
System Status (Rea dy to Arm)
Zone Alarm
Zone Alarm delayed by 20 seconds
Keypad Sounder Output
Access Output (10 sec. pulse)
Future Selection
Pani c/D uress Outp ut***0*1
ON when System is Partial
DD
0 0Latch ON after Zone Alarm**
0 1
0 2
0 3
0 4
0 5
0 6
0 7
0 8
0 9
0*0
0*2
0*3ON when System is Full y Armed
** = This includes invisible zones. See glossary for further details
*** = See section 6.4 for description of this option.
10.36.2 Follow System Wide Event: Program Addresses (2740-2771)
To program an Octal Relay Module for Follow System Wide Event, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 2 for Follow System Wide Event.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired function.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.
For Octal Relay Partition Assignment, see section 10.36.5.
10.36.3 Follow Function: Program Addresses (2740-2771)
T o program an Oct al Relay Module for Follow Output Function, follow the steps below .
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 3 for Follow Function.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired function.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.
For Octal Relay Partition Assignment, see section 10.36.5.
10.36.4 Follow Zone: Program Addresses (2740-2771)
To program an Octal Relay Module for Follow Zone, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 4 for Follow Zone.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired zone.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.
Activate:
Disabled
When zone is shorted
When Zone is opened
When panel i s Arm ed
When pan el is not Arm ed
Latch when activated**
Program Address A
Data Digit
12
4
SELECT OPTION DD 2
102 3 4 5
** = This applies only to the DS7465 outputs.
DS7488 outputs will not l atch when this is selected.
10.37 Output Function Programming: Program Addresses (2772-2843)
Output programming allows you to have the Outputs follow status events by partition or system-wide, or follow zone outputs in an Input/
Output Cross Matrix. See the Programming Addresses Worksheet (P/N: 43850) for a description of each address. See Glossary
(section 6.4) for further details.
DDSelect Option
Latch ON after Zone A larm
ON during Entry Pre- Al ert
ON when system is armed
Zone alarm
Zone Alarm delayed by 20 sec.
Keypad Soun der output
Access output (10 sec. pulse)
Keyfob output
Panic/Duress output**
Follow System Status Even t
Follow a single zone
Follow two zones-When EITHER zone changes state
Follow two zones-When BOTH zones change state
Data Digit
12
*2
Select Option
AC Power Failure
Low Battery
Communication Failure
Syst em Fault**
Keypad Supervision Fault
Multiplex Bus Fault
*0 - *2 are Hex values. They will display as A - C at the keypads.
The Dual Phone Line/Bell Supervision Module is the DS7420i. See section 1.18 for further details.
When in Central Station or Local Commercial Fire Mode, this address will be forced to specific values (see sections 10.16.1 and
10.39 Call-Out Timer Programming: Program Addresses (4022-4025)
This section allows you to define the Hour and Minute for the Communicator Test Report and Remote Programmer Call-Out.
The default time for the Communicator Test Report to be sent and for the control to call the Remote Programmer is Midnight.
10.40 Test Report and Remote Programmer Call-Out Programming: Program Address (4026)
This section allows you to define the Day and Frequency for the Communicator Test Report and the Remote Programmer Call-Out.
If this address is not programmed, the Communicator Test Report will not be sent and the control will not call the Remote Programmer.
10.41 Alpha Description Programming: Program Addresses (0545-2720, 5001-6920)
Alpha Description Programming allows up to 16 characters to be programmed for the description of each partition or zone (e.g. “J. Hill’s
Office”). If a description is less than 16 characters, leave the remaining address(es) blank. Once programmed, the descriptions will be
displayed on the alpha keypads.
The following chart lists the Program Addresses used to program Alpha-Numeric characters for each partition or zone:
See Section 10.41.1 for an Alpha Description Programming worksheet for Partitions 1 through 8 and Zones 1 through 8.
See the Programming Addresses Worksheet (P/N: 43850) for a complete Alpha Programming Worksheet
(covering addresses 0545 through 6920).
Words are created one character at a time. Each character uses two data digits.
The data digit values for these characters are shown below:
10.42 Phone Number Programming: Program Addresses (3159, 3175, 3191)
0
0
0
10.42.1 Phone Number 1 Programming: Program Address (3159)
123456789101112131415161718192
21222324252 6272829303132
10.42.2 Phone Number 2 Programming: Program Address (3175)
123456789101112131415161718192
212223242526272829 303132
10.42.3 Phone Number 3 Programming: Program Address (3191)
123456789101112131415161718192
212223242526272829 303132
Notes:
To dial the “*” character, enter *1 (The “*” character is sent as “1” “1” when pulse dialing).
To dial the “#” character, enter *2 (The “#” character is only valid when tone dialing).
To input a three second delay, enter *3.
To wait for the dial tone, enter *4 in the first digit.
To disable a Phone Number, enter *5 in the first digit.
(*1 - *5 are Hex values. They will display as B - F at the keypads.)
Recommendation: The phone line that the control panel is connected to should not have a Call Waiting feature. If it must have call
waiting, program the code to disable call waiting and add a three second delay before the phone number. This will prevent incom ing
calls from interrupting a communication. For example: call waiting can be disabled in many areas by dialing *70 before the phone
number for tone dial and 1170 for pulse dial.
• Commercial Fire Alarm (Type Service: Local, Central Station, Remote Station; Type Initiating: Automatic, Manual, Sprinkler
Supervisory, and Waterflow), UL Standard UL864
• Household Burglary Alarm, UL Standard UL1023
• Police Station Connection Grades AA and A, UL Standard UL365
• Central Station Burglary Alarm Grades AA, A, B, and C; UL Standard UL1610
• Proprietary Alarm Units Grades A and AA, UL Standard UL1076
The control panel should be installed in accordance with UL Standard UL681, Installation and Classification of Mercantile and Bank
Burglar Alarm Systems, or UL Standard UL1641, Installation and Classification of Residential Burglar Alarm Systems. It should also be
installed in accordance with NFPA 72 for Household and Commercial Fire installations.
11.1.1UL System Configurations
The following table shows the DS7400Xi system configuration for the various types of fire and burglar alarm service for which the
product is UL Listed.
CSF-D = Central Station Fire w/ DA CT (Digital Alarm Communications Transmitter/dialer)
CSF-D/RF = Cent ral Sta tion F i re w/ DACT and Radio (DS7416i)
LF = Local Fire
CSB-A = Central Station Burglary, grades AA and A
PP-AA = Proprietary grade AA
CSB-B/C = Central Station Burglary, grad es B and C
PP-A = Proprietary grade A
LB-A = Loca l B u rglary , grade A
PSCB-D-A = Pol ice Station Connected Burglary w/DACT, grade A
PSCB-RF-A = P olice Station Connected Burglary w/Radio (DS7416i), grades AA and A
HF/B = Household (residential) F ire and Burglary
R
1
1
R
n/a
R
0
0
0
2
0
n/a
n/a
0
n/a
n/a
n/a
n/a
n/a
n/a
n/a
R
R
0
0
0
3
0
0
R
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
n/a
0
R
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
n/a
0
R
R
n/a
R
n/a
n/a
n/a
0
0
0
3
0
n/a
n/a
0
R
Configuration Codes
R
= Required
0
= Optional
n/a
= Not Applicable
1
= Standard or attack enc l osure may be
used.
2
= Either enclosur e m ay be used. Device
must be mounted to the enclosure cover,
or within 20 ft. w/wiring in conduit.
3
= Either enclosur e m ay be used.
4
= Either the DS7420i or the DS7481
must be used to monitor the phone line
input to the control unit.
• Failure to install and program the control in accordance with the
requirements in this section voids the listing mark of Underwriters
Laboratories, Inc.
• The maximum standby battery capacity is 35 Ah @ 12 VDC.
• The total nominal standby current must not exceed 1.5 A nor 2.5
A when in alarm.
• The control must be mounted indoors and within the protected
area.
• Enclosure tamper switches (if used) must be connected to a 24hour zone.
• Grounding must be in accordance with article 250 of the NEC
(NFPA 70).
• At least one UL Listed keypad with zone display must be
connected.
• Zones must be connected to UL Listed, compatible devices.
• 50 Hz. AC input cannot be used in UL Listed Requirements.
• The ground wire provided with the enclosure must be connected
to the “Earth GND” connection on the control and the enclosure
tab.
• The keypad panic alarm output must follow the corresponding
zone function’s programming (e.g. fire = pulsing [or steady if not
a combination], burglary = steady). In all cases, the special
emergency keys must be silent.
• The ground start feature shall not be programmed.
11.3Programming the DS7400Xi
When used in UL Listed Requirements, the control must conform
to certain programming requirements. The following is a list of the
required program entries and required accessories for specific
UL Listed Requirements.
11.3.1Household Fire Alarm Using Digital Alarm
Communicator Transmitter With Local Bell
The control must be installed in accordance with NFPA 72.
Required Accessories:
• At least one Detection Systems, Inc. Model DS250 Series smoke
detector with an MB Series base, DS280 Series, MX280 Series,
or another Listed compatible smoke detector.
• At least one DS7480 Bell Supervision Module.
• One Wheelock 46T-G10-12 bell or 34T-12 horn (will provide
85db for UL985 and NFPA 72 requirements; other Listed
compatible devices with a voltage range of 10.2 to 14.0 V may be
used) is required and must be installed inside the protected
area.
• The standard control enclosure can be used.
• At least one DS7447/DS7447E or DS7445/DS7445i Keypad must
be used.
• Four-wire detectors must be used with Listed power supervision
devices. A compatible Listed 4-wire detector is the Detection
Systems, Inc. DS250 in an MB4W base. A compatible Listed
EOL relay is the Detection Systems, Inc. EOL200.
• All zones must be used with the EOL resistor (P/N 25899),
provided.
1.Report Programming:
• Fire Zone Report must be programmed.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.
2.Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 4 minutes.
3.Zone Function Programming:
• For household fire inst allations only, the output signal may be
pulsed or steady. For a combination system, see the selection
below on alarm output programming.
4.Alarm Output Programming:
• Program Address 2734 must be programmed as: Data Digit 1=
6, Data Digit 2= 3.
5.General Control Programming:
• Program Address 2732 must be programmed as: Data Digit 1=
0, Data Digit 2= 0.
11.3.2Grade A Household Burglary Alarm Using Digital
Alarm Communicator Transmitter With Local
Bell
The control must be installed in accordance with UL Standard
UL1641.
Required Accessories:
• At least one Wheelock 46T-G10-12 bell or 34T-12 horn (other
Listed compatible devices with a voltage range of 10.2 to 14.0 V
may be used) is required for this application.
• The standard DS7400 enclosure can be used.
1.Report Programming:
• Burglar Zone Reports must be programmed for those zones
used.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.
2.Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 4 minutes.
• Entry Delay Timer (Program Addresses 4028 and 4029) must
be programmed for not longer than 60 seconds.
• Exit Delay Timer (Program Address 4030) must be programmed
for not longer than 45 seconds.
3.General Control Programming:
• Program Address 0000, Data Digit 2 must be programmed for
NO Swinger Shunts (enter 0, 1, or 2).
• Program Address 2732 must be programmed as: Data Digit 1=
0, Data Digit 2= 0.
4.Alarm Output Programming:
• Program Address 2734 must be programmed as: Data Digit 1=
6, Data Digit 2= 3.
• Program Address 2737 must be programmed as: Data Digit 1=
8.
In a system that includes both fire alarm and burglar alarm
devices, the system must produce distinct sounds for fire
and burglar alarm conditions either by using different
indicating appliances or by using distinct cadences for
the same appliance.
Applies to the following grades only:
Local BurglaryGrade A using Digital Alarm Communicator
Alarm Police StationGrades AA and A using DACT and DS7416i
Connection -
Central StationGrades AA and A using DACT and DS7416i
Burglary Alarm -
The controls must be installed in accordance with UL Standards
UL681 and UL609 for all grades of service.
1.Report Programming:
• Burglar Zone Reports must be programmed for those zones
used.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.
• Open Report (Program Address 3331) must be programmed.
• Close Report (Program Address 3332) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 3340 and 3347)
must be programmed.
2.General Control Programming:
• The control must not be programmed for auto disarm.
• Must be programmed for no swinger shunts and closing ringback.
(Program Address 0000 data digit 2, enter 0, 1, or 2).
• Program Address 2732 must be programmed as: Data Digit 1=
0, Data Digit 2= 0.
3.Zone Function Programming:
• The Burglar alarm signal (whether pulsed or steady) must be
different from the Fire alarm signal.
4.Alarm Output Programming:
• Program Address 2734 must be programmed as: Data Digit 1=
6, Data Digit 2 = 3.
• Program Address 2737 must be programmed as: Data Digit 1=
8.
11.4.1Local Burglary Alarm
A. Grade A Installations using Digital Alarm Communicator
Transmitter with local bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
• An Ademco Model AB-12 bell/housing ( see section 11.6).
1.Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4029) must
be programmed for not longer than 60 seconds.
11.4.2Police Station Connection
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.
Transmitter (DACT)
Communications module.
Grade A using DACT and local Bell.
Communications module.
Grade B using DACT and local bell.
Grade C using Digital Alarm Communicator
Transmitter only.
• An DS7416i (or DataTAC) interface module.
• The DS7416i module and antenna should be mounted within
the protected area.
• The Detection Systems’ model DS7481 Phone Line Monitor.
1.Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
B .Grade A Installations Using Digital Alarm Communicator
Transmitter With Local Bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see section 11.6).
1.Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
11.4.3Central Station Burglary Alarm and Proprietary
A. Central Station Burglary Grades AA and A and Proprietary
Grade AA Installations Using an DS7416i Interface Module
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.
• An DS7416i (or DataTAC) interface module.
• The DS7416i module and antenna should be mounted within
the protected area.
• The Detection Systems’ model DS7481 Phone Line Monitor.
• The Ademco Model AB-12 bell/housing (see section 11.6).
1.Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
B. Grade B Installations Using Digital Alarm Communicator
Transmitter With Local Bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see section 11.6).
1.Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
C. Central Station Burglary Grade C and Proprietary Grade A
Installations Using Digital Alarm Communicator Transmitter only
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
1.Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
• For Local Commercial Fire Alarm: A Listed notification appliance
such as a Wheelock 46T-G10-12 bell or 34T-12 horn.
• If not using the phone line supervision, it must be disabled.
• AE-TR16 Transformer Housing.
• At least one DS7447/DS7447E must be used and assigned as
keypad 1. If only one is used, it may be connected to the keypad
bus if the keypad is mounted to the front of the box or within the
same room as the control equipment and the wire is run in
conduit (or equivalently protected against mechanical injury)
within 20 ft. (6.1 m) of the control equipment. If multiple
keypads are used,
bus and assigned as keypad 11-14 and meet the same
requirements as in single keypad use.
• 50 Hz. operation and ground start are automatically forced to the
disabled state when central station fire mode is selected.
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones
used.
• Fire Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.
one keypad only must be used on the options
• Open Report (Program Address 3331) must be programmed.
• Close Report (Program Address 3332) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 3340 and 3347)
must be programmed.
2.Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 5 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
3.General Control Programming:
• Must be programmed for no swinger shunts (Program Address
0000 data digit 2, enter 0, 1, or 2).
• Program Address 2732 must be programmed as: Data Digit
1=0, Data Digit 2= 0.
4.Commercial Fire Mode Programming:
• Local (Program Address 2733, data digit 1, enter as a 1 through
6).
• Central Station (Program Address 2733, data digit 1, enter as a
7 through *2).
• The keypad panic functions are not intended to be a substitute
for Listed manual pull boxes.
11.6Wiring and Programming Information for Installations Using the Ademco AB-12 Bell/Housing
AdemcoAB-12 Bell/Housing
To control Earth Ground
Terminal 1
Alternate EOL ( if not
EOL
To control Loop Positive
Terminal 29 (+)
To control Zone 8 Input
Terminal 30 (8-)
o control Alarm Output –
Terminal 5 (-)
o control Alarm Output +
Terminal 6 (A)
Bell Tampers
BELL
using a Fire c ard)
Ω
27 k
Detection Systems’
P/N 28300
Inner Bell Box Lining
Outer Bell Box
1) Disconnect the wire jumper from terminal 4 to the inner housing of the Bell Box (prevents a ground fault condition).
2) Connect wiring between the control and Bell Box as shown above. To use the AB-12 Bell/Housing, cut the jumper wire “JP1” on the
control. The EOL used in the AB-12 Bell/Housing must be 27 kΩ.
3) Program Zone 8 as a 24-hour zone by programming it to follow zone function 7. (Program address 0038 = 07).
4) Do not change the default programming of zone function 7. (Program address 0007 should be 22).
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
l
L
A
S
K
S
F
L
D
12.14/2 Format
Suggested Values
Report
Address Value
one Function 1
one Function 2
one Function 3
one Function 4
one Function 5
one Function 6
one Function 7
one Function 8
one Function 9
one Function 10
one Function 11
one Function 12
one Function 13
one Function 14
one Function 15
one Function 16
one Function 17
one Function 18
one Function 19
one Function 20
one Function 21
one Function 22
one Function 23
one Function 24
one Function 25
one Function 26
one Function 27
one Function 28
one Function 29
one Function 30
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
l
L
A
S
K
S
F
L
D
Suggested Values
Report
AddressValue
one Function 1
one Function 2
one Function 3
one Function 4
one Function 5
one Function 6
one Function 7
one Function 8
one Function 9
one Function 10
one Function 11
one Function 12
one Function 13
one Function 14
one Function 15
one Function 16
one Function 17
one Function 18
one Function 19
one Function 20
one Function 21
one Function 22
one Function 23
one Function 24
one Function 25
one Function 26
one Function 27
one Function 28
one Function 29
one Function 30
This is a 2 pulse per second (PPS) 0/2 (no account code/2 report event digits) format intended for manual reception, i.e. the panel will
call a phone number where a person is expected to answer. After a call is made, the panel will start sending the first report. If the report
was a “Communication Test” and Program Address 3340 had a value of 12 the person answering the phone would hear 1 pulse
followed by a 1 second delay, then 2 pulses followed by a 3 second delay. This sequence will repeat for 60 seconds per call. After the
60 seconds the panel will hang up and call again if any reports still remain to be sent.
A way to expedite this report process would be to provide an acknowledge to the panel that the report was heard and understood by the
receiving party. When an acknowledge is provided, the panel will start sending the next report or hang up if no reports remain. To provide
an acknowledge, press the 1 key of the telephone keypad during the 3 second delay of the report transmission. This “Acknowledge
Feature” is an enhancement that will allow the panel to send all reports in one call. If the call is not acknowledged a communication
failure is sent after all dial attempts are made.
Programming the first data digit as zero will disable the report. Values 1-9 and A-F are acceptable. A zero in the second data digit will
send ten pulses.
12.4Pager Format
The Pager format allows the control panel to dial a digital pager and leave a numeric message which includes an account ID and report
type. The telephone number is dialed when a report is available. At the completion of the telephone dialing, a time delay equal to 10
seconds occurs. This delay allows time to connect with the pager service, while skipping over any voice announcement. When the delay
has ended, the numeric message is sent. This message includes the account number followed by up to 5 reports. If a delay time greater
than 10 seconds is required, see Programming Address 4038 to adjust the delay time. In addition, increments of 3 seconds can be
added by programming the “*3” character (3 second delay) at the end of the phone number in address 3159 or 3175.
For example, if you call pager number 123-4567 and it takes 20 seconds after you finished dialing before you are allowed to enter the
message, the following digits should be programmed in address 3159: 1 2 3 4 5 6 7 *3 *3 *3 *3. This will give you an overall delay of
22 seconds.
NOTE:For Pager Format, it is not advisable to use the HEX character values (*0 = A, *1 = B, *2 = C, *3 = D, *4 = E, *5 = F) in the report
programming addresses 3207 through 3419. These characters could cause unpredictable results when sent to a pager
system that only expects numeric characters between 0-9. This is the reason that this format will not allow an associated user
number with an open and close report.
The following are recommended programming values for addresses 3207 through 3419 when using the Pager format.
NOTE:The Pager format is an open-loop format which has no acknowledge tone. There is no indication at the control panel that the
signal has been sent. Therefore, the Pager format is not recommended as the primary communication method.
Refer to the worksheet on the next page for Reports with Restorals. The values for each report can be determined by the
user in conjunction with the installer. Again, the digit “0” (zero) should not be used as the reporting (first) digit as it will affect
other reports in the system. Examples have been provided for possible reporting values, but the values can be set to the
user’s preferences.
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
l
L
A
S
K
S
F
L
D
Suggested Values
Report
AddressValue
one Fu nction 1
one Fu nction 2
one Fu nction 3
one Fu nction 4
one Fu nction 5
one Fu nction 6
one Fu nction 7
one Fu nction 8
one Fu nction 9
one Fu nction 10
one Fu nction 11
one Fu nction 12
one Fu nction 13
one Fu nction 14
one Fu nction 15
one Fu nction 16
one Fu nction 17
one Fu nction 18
one Fu nction 19
one Fu nction 20
one Fu nction 21
one Fu nction 22
one Fu nction 23
one Fu nction 24
one Fu nction 25
one Fu nction 26
one Fu nction 27
one Fu nction 28
one Fu nction 29
one Fu nction 30
Before installing a multiplex device, its address and other
information must be programmed into the control panel. (To disable
or remove a multiplex point, set the program address for 00 [see
Section 10.4]).
- The control will then take a few seconds to check the multiplex
connection to confirm nothing is connected to it. The display
will show the following:
If using a DS7436 Multiplex Expansion Module,
programming must be done using bus “A.”
Perform the following:
• Program the control panel.
- Refer to sections 10.2-10.5, Zone Programming.
These sections allow you to define the Multiplex Zone’s
address (zone number), its type (single or multiple zone input
device, a DS7465, a Multiplex Smoke or a Multiplex Smoke
with a Low Temperature Alarm), which zone or output function
it will follow (1-24) and its partition (1-8).
For example:Program zone 9 to be a single zone input device
(MX950 ) that follows zone function 1 and is in
partition 1.
Procedure: Enter the programmer’s mode.
Enter address 0039.
Enter the data digits as [0] and [1] followed by the
[#] button.
Enter address 0291.
Enter the data digits as [0] and [0] followed by the
[#] button.
Exit the programmer’s mode.
• Program the BusLoc® feature.
At this point, you must decide whether or not to use the BusLoc
feature.
BusLoc® is a proprietary method of tying the multiplex zones to
the control panel to prevent the system from being taken over.
Using BusLoc® will program an invisible identification code into
the multiplex zones.
NOTE:If using the DS7432 8-Input Remote Module or the DS7433
8-Input Direct Module, the BusLoc
®
feature can not be
used.
- If you choose to use the BusLoc® feature, program a 5-digit
code at programming address 9999.
It is very important to save this code under lock and key. If
you need to replace the control panel, you will have to program
it with the same BusLoc® code as the previous panel or the
multiplex devices will not match codes with the new control
panel.
For example: Program the BusLoc® code to be 54321.
Procedure: Enter the programmer’s mode.
Enter address 9999.
Enter the data digits as [5], [4], [3], [2], and [1]
followed by the [#] button.
Exit the programmer’s mode.
- The display will then call-up the first zone you have preprogrammed to be a multiplex zone. To access a different
zone, press the [Reset/*] key, then enter the three digit value of
the zone you want. The display will show the following:
Before you do anything else, reconnect the multiplex device (that
coincides with the displayed zone) to the multiplex bus of the
DS7430.
For DS7465s and Multiple Input devices, pressing the [#] button
now will program these devices to the control panel. Remember,
these devices take up two addresses. When address 009 (for
example) is a DS7465, pressing the [#] button now will program
both addresses 009 and 010.
For Single Input devices, press the [#] button to continue
programming. The display asks whether you are programming a
sensor or a contact; it will show the following:
If you are programming a sensor, press the [4] button to program
®
these devices to the control panel. If you are programming a contact,
press the [6] button to program these devices to the control panel.
- If the device is successfully programmed, the keypad will
sound a single beep and increment to the next zone (if there is
one) pre-programmed as a multiplex zone.
Disconnect the device you just programmed and
connect the next device (that belongs to the displayed
zone) to the multiplex bus of the DS7430 and press
the [#] button. Continue programming.
24-hour zones will alarm when you exit the
programmer’s mode. Alarm reports for these zones
will be sent if they have been programmed. If you do
not want these reports sent, disconnect power from
the system now by unplugging the transformer and
removing the red battery lead. Do not reconnect power
until all zones have been installed and connected to
the multiplex bus.
- If no other zones have been pre-programmed, the display will
show the following:
Once the pre-programming is done, you are ready to program the
multiplex devices. Perform the following:
• Disconnect all multiplex devices from the DS7430.
• Program the multiplex devices through the control panel. Perform the following:
- Enter the programmer’s mode.
- Enter the multiplex programming mode.
- You may now exit the Zone Programmer ’s mode by pressing
the [*/Reset] button for 2 seconds. This brings you back to the
Programmer’s Mode. To exit the Programmer ’s Mode, press
the [*/Reset] button for 2 seconds.
- If the zone is unsuccessfully programmed, the keypad will
sound a three-beep error tone.
Do this by entering [9] [9] [9] [5] followed by the [#] button.
Entry Error: Please Re-enter will
display on keypad. A three beep error
tone will sound continuously.
a) Two or more keypads share the same
b) The DS7430 or DS7433 is installed in
address.
the wrong pins.
a) Install keypad jumper properly in back of
keypads.
b) Be sure the DS7430 or DS7433 is installed
properly.
Keypad displays Not Programmed,See Instal Guide, sounder is on and
the keypad does not operate.
Keypad displays Ready to arm,partition 1 when using only one
partition.
Keypad displays System Fault,
sounder is on, and the keypad does
not operate.
a) The keypad not addressed properly.
b) The keypad is not programmed
properly.
c) Keypads 11-15 are not properly
configured.
The keypad is programmed as a Master
keypad.
a) Keypad wiring error.
b) Keypad(s) assigned to wrong or non-
existent partition.
c) The microprocessor isn’t running.
a) Install the keypad jumper properly in the back of
the keypad.
b) Check keypad programming addresses 3131-
3138.
c) Check keypad addresses 11-15. System will
only see keypads on the options bus.
Master keypads can only be used on multi-partition
systems. Program the keypad as a standard
keypad.
a) Check wiring.
b) Assign the keypad(s) to correct partition. If none
of the keypads are correctly assigned, re-enable
keypad 1 by shorting the program contacts in
the lower right corner of the main panel board.
This will force program mode and assign
keypad 1 as alpha, non-master to partition 1.
c) Disconnect battery and any aux. power load. If
the microprocessor has shut down, aux. power
will read approx. 11.5 VDC. If the EEProm chip
has been field-replaced, power down AC and
battery, and check for bent or mis-inserted pins;
Otherwise, replace the panel.
Keypad alpha display is locked up,
but the keys still function.
Can’t read back history with # 89
input.
In history, the Read-back for the A, B,
and C keys shows:
A = Fire
B = Emergency
C = Panic
But, the Central Station
transmissions display B as Silent
Panic and C as Audible Panic.
a) Entering from Master keypad.
b) Not using a PIN with test authority.
Formats display information regarding the
B and C keys differently.
In Contact ID: A = Fire
B = Silent Panic
C = Audible Panic
In SIA: A = Fire
B = Emergency
C = Panic
a) Entering from a Master keypad.
b) Not using a PIN with test authority.
Enter the program mode at the keypad and input
the correct sequence to re-enable it as an alpha
keypad. Care must be taken, since there will be no
visual feedback to verify programming until the
keypad is properly enabled.
a) First enter Single Partition Mode.
b) Use a PIN with test authority.
Discrepancy exists in the definition of these keys in
the two formats. Whatever the keys are
programmed for in the panel, that is what will be
sent.
a) Zone test is not available from a Master keypad.
b) Use a PIN with test authority.
Keypad Problems (Continued)
SymptomProbable CausePossible Solution
Chime Mode (#7) does not work
when a zone is faulted.
a) Not activating for interior zones.
a) Chime mode only activates for perimeter zones
- Chime mode must be programmed. Also, if
the perimeter zone has trouble enabled (trouble
on open), the chime won’t work if that zone is
opening.
Some functions won’t work on a
Master keypad.
15.2Reporting Problems
SymptomProbable CausePossible Solution
Won’t send open or close reports.
Reports for partitions 2-8 are being
sent with partition 1’s reporting ID.
Not getting AC power fail reports.
b) The keypad is not assigned to the same
partition as the zone being activated.
Some functions require you to enter single
partition mode when using a Master
keypad.
Not programmed correctly.Check addresses: 3331, 3332, 3334, and 3333.
The account codes for 2-8 are not programmed or are not programmed correctly.
a) AC power fail messages are sent only
with other reports, such as low battery.
b) Check AC report offset (3338). If 00, AC
report will work like above, if another
number, AC report will be delayed.
b) Chime mode will only activate the sounder on
keypads that are assigned to the same partition
as the zone.
The following commands require that you are in
Single Partition Mode when entering from a Master
keypad:
• History read-back
• Chime mode
• Checking zone status
• Checking zone trouble status (after #87 - Master
keypad will show only partition name)
• Bypassing zones
Check addresses: 3429-3459.
a) Try forcing another report to send when AC is
not present.
b) Wait until the delay times out or set to a lower
number if desired.
Panel never transmits history to
WDSRP.
The communicator test report is not
being sent.
a) Not programmed to send history.
b) Time and date not set.
a) Report not programmed properly.
b) There was a control problem at the time
the report should have been sent. If this
is the case, the communicator test
report will not be sent. Instead, the
control will send the “System Off
Normal” report.
a) Check programming.
b) Verify that the time in the panel is set.
a) Check programming addresses 4022, 4023,
4026, and 3340.
b) Program “System Off Normal” report in address
3347.
15.3Zone Problems
SymptomProbable CausePossible Solution
Fire Alarm displays on keypad but
no zone numbers are displayed.
Every other zone displays Not Ready .Zone Programming is incorrect.Program as a multiple zone input for DS7432 or
In Commercial Fire Mode, fire alarms must
be silenced before the zone number will
display.
Enter a valid disarm PIN and press #, then enter a
valid disarm PIN and press # again to display the
zones.
DS7460, a single zone input for contacts and
sensors, or program as a DS7465.
Zone Problems (Continued)
SymptomProbable CausePossible Solution
Zones 9 and above show Not Ready,
Zone Trouble.
Never disconnect the
power when in the
programming mode.
Always disconnect the
Multiplex Bus or have the
DS7430 or DS7436 in
the disable
programming mode
when powering up or
down.
a) The multiplex expansion module is not
installed properly.
b) Multiplex wiring is missing or is not
installed properly.
c) 8-Input remote module DIP switches
are not set properly.
d) 8-Input remote module covers are
removed.
e) The BusLoc® code is set incorrectly or
has not been programmed into
modules.
f) Zone Programming is incorrect.
a) Make sure the multiplex expansion module is
seated properly in the upper pins on the
DS7400Xi circuit board.
b) Check wiring and perform a system reset.
c) Correctly set the DIP switches for the 8-Input
remote modules.
d) Replace covers or install the tamper bypass
jumper.
e) BusLoc® can not be used with 8-Input remote
modules. If using 8-Input modules, remove the
BusLoc® code.
OR
If using two-input remote modules or the
DS7465, be sure to use BusLoc® when
programming. If not using BusLoc®, be sure to
remove the BusLoc® code from address 9999.
f) Program as a multiple zone input for DS7432 or
DS7460, a single zone input for contacts and
sensors, or program as a DS7465.
Invisible or silent zone activates
alarm output.
Keypad displays Fire Trouble, but
does not indicate any zones.
g) Multiplex module not programmed.
h) Multiplex Bus voltage is 12VDC or
greater. (Normal is approximately 8 to
10VDC.)
i) Multiplex Bus voltage is 5VDC or less.
(Normal is approximately 8 to 10VDC.)
The output is programmed as “latch on
alarm” (0).
A ground fault condition exists.
g) Program the module.
h) Two modules are programmed with the same
address. The problem will only occur when both
modulees are off normal. Isolate the duplicate
module by disconnecting sections of the bus
and performing a [PIN] + [System Reset].
Reprogram modules.
OR
The system is in the programming mode. Exit
the programming mode.
OR
Zones have been added to a system protected
by Busloc®. Clear Busloc®.
i) There is a short on the multiplex bus.
OR
There is a bad module on the bus.
OR
One or more modules on the bus are connected
backwards - reverse polarity.
Program the output to follow zone alarms (6).
See system trouble: Ground fault.
Keypad displays Not Ready, but no
zone number is displayed.
An invisible zone is not ready.
Press [PIN] + [OFF] to display the zone number of
the invisible zone that is not ready.
15.4General System Problems
SymptomProbable CausePossible Solution
How to set the programming values
to the factory default.
module (DS7420i) is defective or the
wiring to the module is defective.
b) There is no DS7420i or a DS7420i has
been removed from the system.
There is a phone line fault on line 1.
There is a phone line fault on line 2.
The bell circuit on the DS7420i is open or
shorted.
The auxiliary circuit on the DS7420i is open
or shorted.
e) If error still persists, replace the panel.
Check history #89 to determine the source:
Report Failure 1 = Phone number 1
Report Failure 2 = Phone number 2
Report Failure 3 = Phone number 3
(remote programmer)
Report Failure 4 = DS7416i Communications fault
a) Check the wiring to the module.
b) Enter, then exit programming mode. This will re-
scan the options bus and clear the problem.
Check phone line 1 for proper operation.
Check phone line 2 for proper operation. If you wish
to monitor only one phone line, reprogram address
4021.
Check the bell circuit wiring. Be sure that the end-
of-line resistor is in place. If you don’t wish to use
the bell circuit, place an end-of-line resistor across
the bell terminals.
Check the auxiliary circuit wiring. Be sure that the
end-of-line resistor is in place. If you don’t wish to
use the auxiliary circuit, place an end-of-line resistor
across the auxiliary terminals. If you wish to use the
auxiliary circuit but do not wish to supervise it, cut
the auxiliary supervision jumper on the DS7420i.
b) A keypad is missing.
c) A keypad has been programmed, but is
not intended in this system.
There is a short to ground somewhere in
the system.
b) Install a keypad.
c) Remove from programming (3131-3138).
Disconnect field wiring from each terminal while
watching the keypad display. When the keypad power
LED stops flashing, you have found the wire that is
causing the ground fault.
Note:The LED will not stop flashing if there is
another system fault present.
If there is no keypad nearby, or another control
problem exists, you can use a volt-meter to find the
ground fault:
1) Connect the negative lead of a volt-meter to the
panel ground terminal.
2) Connect the positive terminal to the Aux Power –
terminal.
You should read -4.5 to -7.5 Volts DC. A reading
considerably higher or lower indicates a ground
fault.
Disconnect field wiring from each terminal while
watching the meter. When the voltage reading
returns to between -4.5 and -7.5 VDC, you have
found the wire that is causing the ground fault.
#87 display = AR IB Queue Full
#89 display = System Fault 51
#87 display = AR Host Down
#89 display = System Fault 52
#87 display = AR Unreg. Modem
#89 display = System Fault 53
#87 display = AR Power Fail
#89 display = System Fault 54
#87 display = AR Network Lost
#89 display = System Fault 55
#87 display = AR Modem HW Err
#89 display = System Fault 56
#87 display = AR Modem SW Err
#89 display = System Fault 57
#87 display = AR Opt. Bus Err
#89 display = System Fault 58
#87 display = AR Corrupt MSG
#89 display = System Fault 59
Unable to arm the system.
The message queue in the RF modem is
full and no messages can get out to the
radio network.
The central station receiver has ceased to
be available to the network.
The modem is not registered through all
parts of the network.
There is a possible problem with the
DS7416i Module.
The DS7416i Module has lost contact with
the radio network.
There is a possible problem with the radio
modem.
The DS7416i Module is having trouble
communicating with the radio modem.
The panel can no longer communicate
with the DS7416i Module.
The communication between the panel
and the DS7416i Module is getting
corrupted.
a) Zone(s) faulted.
Check RF coverage of the unit and check for RF
noisy environment.
Contract the central station and notify of status.
Contact the network administrators or technical
service.
Return for service.
Check the location and coverage of the unit.
Replace the unit.
Check for noisy environment and replace the unit if
the problem continues.
Check the wiring between the DS7400Xi and the
DS7416i Module.
Check for noisy environment, and check the wiring
between the DS7400Xi and the DS7416i Module.
a) If there has just been a power failure, wait at
least two hours for the battery to recharge then
perform a System Reset to re-test the battery
and clear the error.
#87 display = Zone Trouble
#87 display = AC Power Failure
b) The battery is defective.
c) The wiring to the battery is
disconnected.
a) A zone is not responding to the control
panel.
b) The zone is programmed for “Trouble
on Open” and the loop is open.
There is a power failure and the panel is
operating on battery backup. If there is a
general power failure, wait for the power to
return. If there is not a general power failure
in the building.
a) The transformer is unplugged.
b) The wiring from the transformer is
defective.
c) The circuit to the transformer is off or
defective.
b) Replace the battery.
c) Check wiring.
a) Check wiring to the zone.
or
If the zone is not to be used, remove from
programming.
b) If using Normally Closed contacts, re-program
zone for alarm on open.
or
If using Normally Open contacts and trouble on
open is desired, check for opens in the loop.
Remove wiring and place an EOL resistor across
the zone to eliminate a problem with the control.
If the trouble goes away, the problem is in the
wiring or in a contact connected to the zone.
a) Plug the transformer in.
b) Check the wiring.
c) Check the circuit and circuit breakers.
Fire Alarm displays “000”.
Fire Trouble, no zone number.
Fire Trouble ____________
zone number. Dirty
Chamber ____________
zone number.
d) The transformer is defective.
e) In some cases, the transformer may
be connected to a circuit controlled by
a switch or a circuit breaker that is
periodically turned off.
The Fire Alarm was caused by the “A” key.
When in Commercial Fire Mode, a ground
fault causes this display.
Fire zone wiring problems.
A multiplex smoke detector has failed its
internal sensitivity test.
d) Replace the transformer.
e) Connect to a circuit that is not controlled this
way.
Use the System Reset command to clear the
display.
See #87 Ground Fault display for solution.
If you try to disable the zone by reprogramming it,
you need to reset the control by either entering then
exiting programmer’s mode, or removing then
restoring power to the control panel.
Clean or replace the dirty smoke detector or
chamber. DO NOT USE WATER TO CLEAN THE
CHAMBER.
0000General Control
0001Zone Function 1
0002Zone Function 2
0003Zone Function 3
0004Zone Function 4
0005Zone Function 5
0006Zone Function 6
0007Zone Function 7
0008Zone Function 8
0009Zone Function 9
0010Zone Function 10
00 11Zone Function 11
0012Zone Function 12
0013Zone Function 13
0014Zone Function 14
0015Zone Function 15
0016Zone Function 16
0017Zone Function 17
0018Zone Function 18
0019Zone Function 19
0020Zone Function 20
0021Zone Function 21
0022Zone Function 22
0023Zone Function 23
0024Zone Function 24
0025Zone Function 25
0026Zone Function 26
0027Zone Function 27
0028Zone Function 28
0029Zone Function 29
0030Zone Function 30
0031Zone Number 1
0032Zone Number 2
0033Zone Number 3
0034Zone Number 4
0035Zone Number 5
0036Zone Number 6
0037Zone Number 7
0038Zone Number 8
0039Zone Number 9
0040Zone Number 10
0041Zone Number 11
0042Zone Number 12
0043Zone Number 13
0044Zone Number 14
0045Zone Number 15
0046Zone Number 16
0047Zone Number 17
0048Zone Number 18
0049Zone Number 19
0050Zone Number 20
0051Zone Number 21
0052Zone Number 22
0053Zone Number 23
0054Zone Number 24
0055Zone Number 25
0056Zone Number 26
0057Zone Number 27
0058Zone Number 28
0059Zone Number 29
0060Zone Number 30
0061Zone Number 31
0062Zone Number 32
0063Zone Number 33
0064Zone Number 34
0065Zone Number 35
0066Zone Number 36
0067Zone Number 37
0068Zone Number 38
0069Zone Number 39
0070Zone Number 40
0071Zone Number 41
0072Zone Number 42
0073Zone Number 43
0074Zone Number 44
0075Zone Number 45
0076Zone Number 46
0077Zone Number 47
0078Zone Number 48
0079Zone Number 49
0080Zone Number 50
0081Zone Number 51
0082Zone Number 52
0083Zone Number 53
0084Zone Number 54
0085Zone Number 55
0086Zone Number 56
0087Zone Number 57
0088Zone Number 58
0089Zone Number 59
0090Zone Number 60
0091Zone Number 61
0092Zone Number 62
0093Zone Number 63
0094Zone Number 64
0095Zone Number 65
0096Zone Number 66
0097Zone Number 67
0098Zone Number 68
0099Zone Number 69
0100Zone Number 70
0101Zone Number 71
0102Zone Number 72
0103Zone Number 73
0104Zone Number 74
0105Zone Number 75
0106Zone Number 76
0107Zone Number 77
0108Zone Number 78
0109Zone Number 79
0110Zone Number 80
0111Zone Number 81
0112Zone Number 82
0113Zone Number 83
0114Zone Number 84
0115Zone Number 85
0116Zone Number 86
0117Zone Number 87
0118Zone Number 88
0119Zone Number 89
0120Zone Number 90
0121Zone Number 91
0122Zone Number 92
0123Zone Number 93
0124Zone Number 94
0125Zone Number 95
Address Description
0126Zone Number 96
0127Zone Number 97
0128Zone Number 98
0129Zone Number 99
0130Zone Number 100
0131Zone Number 101
0132Zone Number 102
0133Zone Number 103
0134Zone Number 104
0135Zone Number 105
0136Zone Number 106
0137Zone Number 107
0138Zone Number 108
0139Zone Number 109
0140Zone Number 110
0141Zone Number 111
0142Zone Number 112
0143Zone Number 113
0144Zone Number 114
0145Zone Number 115
0146Zone Number 116
0147Zone Number 117
0148Zone Number 118
0149Zone Number 119
0150Zone Number 120
0151Zone Number 121
0152Zone Number 122
0153Zone Number 123
0154Zone Number 124
0155Zone Number 125
0156Zone Number 126
0157Zone Number 127
0158Zone Number 128
0159Zone Number 129
0160Zone Number 130
0161Zone Number 131
0162Zone Number 132
0163Zone Number 133
0164Zone Number 134
0165Zone Number 135
0166Zone Number 136
0167Zone Number 137
0168Zone Number 138
0169Zone Number 139
0170Zone Number 140
0171Zone Number 141
0172Zone Number 142
0173Zone Number 143
0174Zone Number 144
0175Zone Number 145
0176Zone Number 146
0177Zone Number 147
0178Zone Number 148
0179Zone Number 149
0180Zone Number 150
0181Zone Number 151
0182Zone Number 152
0183Zone Number 153
0184Zone Number 154
0185Zone Number 155
0186Zone Number 156
0187Zone Number 157
0188Zone Number 158
Address Description
0189Zone Number 159
0190Zone Number 160
0191Zone Number 161
0192Zone Number 162
0193Zone Number 163
0194Zone Number 164
0195Zone Number 165
0196Zone Number 166
0197Zone Number 167
0198Zone Number 168
0199Zone Number 169
0200Zone Number 170
0201Zone Number 171
0202Zone Number 172
0203Zone Number 173
0204Zone Number 174
0205Zone Number 175
0206Zone Number 176
0207Zone Number 177
0208Zone Number 178
0209Zone Number 179
0210Zone Number 180
0211Zone Number 181
0212Zone Number 182
0213Zone Number 183
0214Zone Number 184
0215Zone Number 185
0216Zone Number 186
0217Zone Number 187
0218Zone Number 188
0219Zone Number 189
0220Zone Number 190
0221Zone Number 191
0222Zone Number 192
0223Zone Number 193
0224Zone Number 194
0225Zone Number 195
0226Zone Number 196
0227Zone Number 197
0228Zone Number 198
0229Zone Number 199
0230Zone Number 200
0231Zone Number 201
0232Zone Number 202
0233Zone Number 203
0234Zone Number 204
0235Zone Number 205
0236Zone Number 206
0237Zone Number 207
0238Zone Number 208
0239Zone Number 209
0240Zone Number 210
0241Zone Number 211
0242Zone Number 212
0243Zone Number 213
0244Zone Number 214
0245Zone Number 215
0246Zone Number 216
0247Zone Number 217
0248Zone Number 218
0249Zone Number 219
0250Zone Number 220
0251Zone Number 221
0252Zone Number 222
0253Zone Number 223
0392Zone 211 & 212 Partition Assign.
0393Zone 213 & 214 Partition Assign.
0394Zone 215 & 216 Partition Assign.
0395Zone 217 & 218 Partition Assign.
0396Zone 219 & 220 Partition Assign.
0397Zone 221 & 222 Partition Assign.
0398Zone 223 & 224 Partition Assign.
0399Zone 225 & 226 Partition Assign.
0400Zone 227 & 228 Partition Assign.
0401Zone 229 & 230 Partition Assign.
0402Zone 231 & 232 Partition Assign.
0403Zone 233 & 234 Partition Assign.
0404Zone 235 & 236 Partition Assign.
0405Zone 237 & 238 Partition Assign.
0406Zone 239 & 240 Partition Assign.
0407Zone 241 & 242 Partition Assign.
0408Zone 243 & 244 Partition Assign.
0409Zone 245 & 246 Partition Assign.
0410Zone 247 & 248 Partition Assign.
0415Zone 1 & 2 Zone Type
0416Zone 3 & 4 Zone Type
0417Zone 5 & 6 Zone Type
0418Zone 7 & 8 Zone Type
0419Zone 9 & 10 Zone Type
0420Zone 11 & 12 Zone Type
0421Zone 13 & 14 Zone Type
0422Zone 15 & 16 Zone Type
0423Zone 17 & 18 Zone Type
0424Zone 19 & 20 Zone Type
0425Zone 21 & 22 Zone Type
0426Zone 23 & 24 Zone Type
0427Zone 25 & 26 Zone Type
0428Zone 27 & 28 Zone Type
0429Zone 29 & 30 Zone Type
0430Zone 31 & 32 Zone Type
0431Zone 33 & 34 Zone Type
0432Zone 35 & 36 Zone Type
0433Zone 37 & 38 Zone Type
0434Zone 39 & 40 Zone Type
0435Zone 41 & 42 Zone Type
0436Zone 43 & 44 Zone Type
0437Zone 45 & 46 Zone Type
0438Zone 47 & 48 Zone Type
0439Zone 49 & 50 Zone Type
0440Zone 51 & 52 Zone Type
0441Zone 53 & 54 Zone Type
0442Zone 55 & 56 Zone Type
0443Zone 57 & 58 Zone Type
0444Zone 59 & 60 Zone Type
0445Zone 61 & 62 Zone Type
0446Zone 63 & 64 Zone Type
0447Zone 65 & 66 Zone Type
0448Zone 67 & 68 Zone Type
0449Zone 69 & 70 Zone Type
0450Zone 71 & 72 Zone Type
0451Zone 73 & 74 Zone Type
0452Zone 75 & 76 Zone Type
0453Zone 77 & 78 Zone Type
0454Zone 79 & 80 Zone Type
0455Zone 81 & 82 Zone Type
0456Zone 83 & 84 Zone Type
0457Zone 85 & 86 Zone Type
0458Zone 87 & 88 Zone Type
0459Zone 89 & 90 Zone Type
0460Zone 91 & 92 Zone Type
0461Zone 93 & 94 Zone Type
0462Zone 95 & 96 Zone Type
0463Zone 97 & 98 Zone Type
0464Zone 99 & 100 Zone Type
0465Zone 101 & 102 Zone Type
0466Zone 103 & 104 Zone Type
0467Zone 105 & 106 Zone Type
0468Zone 107 & 108 Zone Type
0469Zone 109 & 110 Zone Type
0470Zone 111 & 112 Zone Type
0471Zone 113 & 114 Zone Type
0472Zone 116 & 115 Zone Type
0473Zone 117 & 118 Zone Type
0474Zone 119 & 120 Zone Type
0475Zone 121 & 122 Zone Type
0476Zone 123 & 124 Zone Type
0477Zone 125 & 126 Zone Type
0478Zone 127 & 128 Zone Type
0479Zone 129 & 130 Zone Type
0480Zone 131 & 132 Zone Type
0481Zone 133 & 134 Zone Type
0482Zone 135 & 136 Zone Type
0483Zone 137 & 138 Zone Type
0484Zone 139 & 140 Zone Type
0485Zone 141 & 142 Zone Type
0486Zone 143 & 144 Zone Type
0487Zone 145 & 146 Zone Type
0488Zone 147 & 148 Zone Type
0489Zone 149 & 150 Zone Type
0490Zone 151 & 152 Zone Type
0491Zone 153 & 154 Zone Type
0492Zone 155 & 156 Zone Type
0493Zone 157 & 158 Zone Type
0494Zone 159 & 160 Zone Type
0495Zone 161 & 162 Zone Type
0496Zone 163 & 164 Zone Type
0497Zone 165 & 166 Zone Type
0498Zone 167 & 168 Zone Type
0499Zone 169 & 170 Zone Type
0500Zone 171 & 172 Zone Type
0501Zone 173 & 174 Zone Type
0502Zone 175 & 176 Zone Type
0503Zone 177 & 178 Zone Type
0504Zone 179 & 180 Zone Type
0505Zone 181 & 182 Zone Type
0506Zone 183 & 184 Zone Type
0507Zone 185 & 186 Zone Type
0508Zone 187 & 188 Zone Type
0509Zone 189 & 190 Zone Type
0510Zone 191 & 192 Zone Type
05 11Zone 193 & 194 Zone Type
0512Zone 195 & 196 Zone Type
0513Zone 197 & 198 Zone Type
0514Zone 199 & 200 Zone Type
0515Zone 201 & 202 Zone Type
0516Zone 203 & 204 Zone Type
0517Zone 205 & 206 Zone Type
0518Zone 207 & 208 Zone Type
0519Zone 209 & 210 Zone Type
0520Zone 211 & 212 Zone Type
0521Zone 213 & 214 Zone Type
0522Zone 215 & 216 Zone Type
0523Zone 217 & 218 Zone Type
0524Zone 219 & 220 Zone Type
0525Zone 221 & 222 Zone Type
Address Description
0526Zone 223 & 224 Zone Type
0527Zone 225 & 226 Zone Type
0528Zone 227 & 228 Zone Type
0529Zone 229 & 230 Zone Type
0530Zone 231 & 232 Zone Type
0531Zone 233 & 234 Zone Type
0532Zone 235 & 236 Zone Type
0533Zone 237 & 238 Zone Type
0534Zone 239 & 240 Zone Type
0535Zone 241 & 242 Zone Type
0536Zone 243 & 244 Zone Type
0537Zone 245 & 246 Zone Type
0538Zone 247 & 248 Zone Type
0545Alpha for Partition 1
0561Alpha for Partition 2
0577Alpha for Partition 3
0593Alpha for Partition 4
0609Alpha for Partition 5
0625Alpha for Partition 6
0641Alpha for Partition 7
0657Alpha for Partition 8
0673Alpha for Zone Number 1
0689Alpha for Zone Number 2
0705Alpha for Zone Number 3
0721Alpha for Zone Number 4
0737Alpha for Zone Number 5
0753Alpha for Zone Number 6
0769Alpha for Zone Number 7
0785Alpha for Zone Number 8
0801Alpha for Zone Number 9
0817Alpha for Zone Number 10
0833Alpha for Zone Number 11
0849Alpha for Zone Number 12
0865Alpha for Zone Number 13
0881Alpha for Zone Number 14
0897Alpha for Zone Number 15
0913Alpha for Zone Number 16
0929Alpha for Zone Number 17
0945Alpha for Zone Number 18
0961Alpha for Zone Number 19
0977Alpha for Zone Number 20
0993Alpha for Zone Number 21
1009Alpha for Zone Number 22
1025Alpha for Zone Number 23
1041Alpha for Zone Number 24
1057Alpha for Zone Number 25
1073Alpha for Zone Number 26
1089Alpha for Zone Number 27
1105Alpha for Zone Number 28
1121Alpha for Zone Number 29
1137Alpha for Zone Number 30
1153Alpha for Zone Number 31
1169Alpha for Zone Number 32
1185Alpha for Zone Number 33
1201Alpha for Zone Number 34
1217Alpha for Zone Number 35
1233Alpha for Zone Number 36
1249Alpha for Zone Number 37
1265Alpha for Zone Number 38
1281Alpha for Zone Number 39
1297Alpha for Zone Number 40
1313Alpha for Zone Number 41
1329Alpha for Zone Number 42
1345Alpha for Zone Number 43
1361Alpha for Zone Number 44
Address Description
1377Alpha for Zone Number 45
1393Alpha for Zone Number 46
1409Alpha for Zone Number 47
1425Alpha for Zone Number 48
1441Alpha for Zone Number 49
1457Alpha for Zone Number 50
1473Alpha for Zone Number 51
1489Alpha for Zone Number 52
1505Alpha for Zone Number 53
1521Alpha for Zone Number 54
1537Alpha for Zone Number 55
1553Alpha for Zone Number 56
1569Alpha for Zone Number 57
1585Alpha for Zone Number 58
1601Alpha for Zone Number 59
1617Alpha for Zone Number 60
1633Alpha for Zone Number 61
1649Alpha for Zone Number 62
1665Alpha for Zone Number 63
1681Alpha for Zone Number 64
1697Alpha for Zone Number 65
1713Alpha for Zone Number 66
1729Alpha for Zone Number 67
1745Alpha for Zone Number 68
1761Alpha for Zone Number 69
1777Alpha for Zone Number 70
1793Alpha for Zone Number 71
1809Alpha for Zone Number 72
1825Alpha for Zone Number 73
1841Alpha for Zone Number 74
1857Alpha for Zone Number 75
1873Alpha for Zone Number 76
1889Alpha for Zone Number 77
1905Alpha for Zone Number 78
1921Alpha for Zone Number 79
1937Alpha for Zone Number 80
1953Alpha for Zone Number 81
1969Alpha for Zone Number 82
1985Alpha for Zone Number 83
2001Alpha for Zone Number 84
2017Alpha for Zone Number 85
2033Alpha for Zone Number 86
2049Alpha for Zone Number 87
2065Alpha for Zone Number 88
2081Alpha for Zone Number 89
2097Alpha for Zone Number 90
2113Alpha for Zone Number 91
2129Alpha for Zone Number 92
2145Alpha for Zone Number 93
2161Alpha for Zone Number 94
2177Alpha for Zone Number 95
2193Alpha for Zone Number 96
2209Alpha for Zone Number 97
2225Alpha for Zone Number 98
2241Alpha for Zone Number 99
2257Alpha for Zone Number 100
2273Alpha for Zone Number 101
2289Alpha for Zone Number 102
2305Alpha for Zone Number 103
2321Alpha for Zone Number 104
2337Alpha for Zone Number 105
2353Alpha for Zone Number 106
2369Alpha for Zone Number 107
2385Alpha for Zone Number 108
2401Alpha for Zone Number 109
2417Alpha for Zone Number 110
2433Alpha for Zone Number 111
2449Alpha for Zone Number 112
2465Alpha for Zone Number 113
2481Alpha for Zone Number 114
2497Alpha for Zone Number 115
2513Alpha for Zone Number 116
2529Alpha for Zone Number 117
2545Alpha for Zone Number 118
2561Alpha for Zone Number 119
2577Alpha for Zone Number 120
2593Alpha for Zone Number 121
2609Alpha for Zone Number 122
2625Alpha for Zone Number 123
2641Alpha for Zone Number 124
2657Alpha for Zone Number 125
2673Alpha for Zone Number 126
2689Alpha for Zone Number 127
2705Alpha for Zone Number 128
2721Zone Function Bypass 1-8
2722Zone Function Bypass 9-16
2723Zone Function Bypass 17-24
2724Zone Function Bypass 25-30
2725Command 4 (Cust.) Arming 1-8
2726Command 4 (Cust.) Arming 9-16
2727Command 4 (Cust.) Arming 17-24
2728Command 4 (Cust.) Arming 25-30
2729RF Zone Group Program. 129-248
2731Receiver Configuration
2732Force Arming & Ground Fault
2733Commerical Fire Mode
2734Alarm Output
2735Programmable Output Type 1
2736Programmable Output Type 2
2737Output Part. Assign. & Bell Output
2738Output Part. Assign. & Keyfob Chirp
2740Octal Module #1, Relay #1
2742Octal Module #1, Relay #2
2744Octal Module #1, Relay #3
2746Octal Module #1, Relay #4
2748Octal Module #1, Relay #5
2750Octal Module #1, Relay #6
2752Octal Module #1, Relay #7
2754Octal Module #1, Relay #8
2756Octal Module #2, Relay #1
2758Octal Module #2, Relay #2
2760Octal Module #2, Relay #3
2762Octal Module #2, Relay #4
2764Octal Module #2, Relay #5
2766Octal Module #2, Relay #6
2768Octal Module #2, Relay #7
2770Octal Module #2, Relay #8
2772Output Function 1
2775Output Function 2
2778Output Function 3
2781Output Function 4
2784Output Function 5
2787Output Function 6
2790Output Function 7
2793Output Function 8
2796Output Function 9
2799Output Function 10
2802Output Function 11
2805Output Function 12
2808Output Function 13
Address Description
28 11Output Function 14
2814Output Function 15
2817Output Function 16
2820Output Function 17
2823Output Function 18
2826Output Function 19
2829Output Function 20
2832Output Function 21
2835Output Function 22
2838Output Function 23
2841Output Function 24
2844Octal Relay Partition Assignment
2845Octal Relay Partition Assignment
2846Octal Relay Partition Assignment
2847Octal Relay Partition Assignment
2848Octal Relay Partition Assignment
2849Octal Relay Partition Assignment
2850Octal Relay Partition Assignment
2851Octal Relay Partition Assignment
2852Output Function Partition Assign.
2853Output Function Partition Assign.
2854Output Function Partition Assign.
2855Output Function Partition Assign.
2856Output Function Partition Assign.
2857Output Function Partition Assign.
2858Output Function Partition Assign.
2859Output Function Partition Assign.
2860Output Function Partition Assign.
2861Output Function Partition Assign.
2862Output Function Partition Assign.
2863Output Function Partition Assign.
3131Keypad Assignment
3132Keypad Assignment
3133Keypad Assignment
3134Keypad Assignment
3135Keypad Assignment
3136Keypad Assignment
3137Keypad Assignment
3138Keypad Assignment & Backlight
Routing
3152System Routing
3153Phone/DS7416i Routing
3154Phone/DS7416i Routing
3155Phone Number General Control
3156Phone Number 1 Control
3157Phone Number 2 Control
3158Answer Ring Count (Arm/Disarm)
3159Phone Number 1
3175Phone Number 2
3191Phone Number 3
3207Keypad Fire Alarm Report
3208Keypad Fire Restoral Report
Address Description
3209Zone Function 1 Alarm Report
3210Zone Function 2 Alarm Report
32 11Zone Function 3 Alarm Report
3212Zone Function 4 Alarm Report
3213Zone Function 5 Alarm Report
3214Zone Function 6 Alarm Report
3215Zone Function 7 Alarm Report
3216Zone Function 8 Alarm Report
3217Zone Function 9 Alarm Report
3218Zone Function 10 Alarm Report
3219Zone Function 11 Alarm Report
3220Zone Function 12 Alarm Report
3221Zone Function 13 Alarm Report
3222Zone Function 14 Alarm Report
3223Zone Function 15 Alarm Report
3224Zone Function 16 Alarm Report
3225Zone Function 17 Alarm Report
3226Zone Function 18 Alarm Report
3227Zone Function 19 Alarm Report
3228Zone Function 20 Alarm Report
3229Zone Function 21 Alarm Report
3230Zone Function 22 Alarm Report
3231Zone Function 23 Alarm Report
3232Zone Function 24 Alarm Report
3233Zone Function 25 Alarm Report
3234Zone Function 26 Alarm Report
3235Zone Function 27 Alarm Report
3236Zone Function 28 Alarm Report
3237Zone Function 29 Alarm Report
3238Zone Function 30 Alarm Report
3239Keypad Emergency Report
3240Keypad Panic Report
3241Zone Function 1 Restoral Report
3242Zone Function 2 Restoral Report
3243Zone Function 3 Restoral Report
3244Zone Function 4 Restoral Report
3245Zone Function 5 Restoral Report
3246Zone Function 6 Restoral Report
3247Zone Function 7 Restoral Report
3248Zone Function 8 Restoral Report
3249Zone Function 9 Restoral Report
3250Zone Function 10 Restoral Report
3251Zone Function 11 Restoral Report
3252Zone Function 12 Restoral Report
3253Zone Function 13 Restoral Report
3254Zone Function 14 Restoral Report
3255Zone Function 15 Restoral Report
3256Zone Function 16 Restoral Report
3257Zone Function 17 Restoral Report
3258Zone Function 18 Restoral Report
3259Zone Function 19 Restoral Report
3260Zone Function 20 Restoral Report
3261Zone Function 21 Restoral Report
3262Zone Function 22 Restoral Report
3263Zone Function 23 Restoral Report
3264Zone Function 24 Restoral Report
3265Zone Function 25 Restoral Report
3266Zone Function 26 Restoral Report
3267Zone Function 27 Restoral Report
3268Zone Function 28 Restoral Report
3269Zone Function 29 Restoral Report
3270Zone Function 30 Restoral Report
3271Zone Function 1 Trouble Report
3272Zone Function 2 Trouble Report
3273Zone Function 3 Trouble Report
Programmer Call-Out
4027CR/LF Control
4028Entry Delay Time 1
4029Entry Delay Time 2
4030Exit Delay Time
4032Fire Bell Cutoff
4033Burglary Bell Cutoff
4034AC Fail Report Delay
4038Pager Delay Timer
4039RF Receiver Jam Detection Level
5001Alpha for Zone Number 129
5017Alpha for Zone Number 130
5033Alpha for Zone Number 131
5049Alpha for Zone Number 132
5065Alpha for Zone Number 133
5081Alpha for Zone Number 134
5097Alpha for Zone Number 135
5113Alpha for Zone Number 136
5129Alpha for Zone Number 137
5145Alpha for Zone Number 138
5161Alpha for Zone Number 139
5177Alpha for Zone Number 140
5193Alpha for Zone Number 141
5209Alpha for Zone Number 142
5225Alpha for Zone Number 143
5241Alpha for Zone Number 144
5257Alpha for Zone Number 145
5273Alpha for Zone Number 146
5289Alpha for Zone Number 147
5305Alpha for Zone Number 148
5321Alpha for Zone Number 149
5337Alpha for Zone Number 150
5353Alpha for Zone Number 151
5369Alpha for Zone Number 152
5385Alpha for Zone Number 153
5401Alpha for Zone Number 154
5417Alpha for Zone Number 155
5433Alpha for Zone Number 156
5449Alpha for Zone Number 157
5465Alpha for Zone Number 158
5481Alpha for Zone Number 159
5497Alpha for Zone Number 160
5513Alpha for Zone Number 161
5529Alpha for Zone Number 162
5545Alpha for Zone Number 163
5561Alpha for Zone Number 164
5577Alpha for Zone Number 165
5593Alpha for Zone Number 166
5609Alpha for Zone Number 167
5625Alpha for Zone Number 168
5641Alpha for Zone Number 169
5657Alpha for Zone Number 170
5673Alpha for Zone Number 171
5689Alpha for Zone Number 172
5705Alpha for Zone Number 173
5721Alpha for Zone Number 174
5737Alpha for Zone Number 175
5753Alpha for Zone Number 176
5769Alpha for Zone Number 177
5785Alpha for Zone Number 178
5801Alpha for Zone Number 179
5817Alpha for Zone Number 180
5833Alpha for Zone Number 181
5849Alpha for Zone Number 182
5865Alpha for Zone Number 183
5881Alpha for Zone Number 184
5897Alpha for Zone Number 185
5913Alpha for Zone Number 186
5929Alpha for Zone Number 187
5945Alpha for Zone Number 188
5961Alpha for Zone Number 189
5977Alpha for Zone Number 190
5993Alpha for Zone Number 191
6009Alpha for Zone Number 192
6025Alpha for Zone Number 193
6041Alpha for Zone Number 194
6057Alpha for Zone Number 195
6073Alpha for Zone Number 196
Address Description
6089Alpha for Zone Number 197
6105Alpha for Zone Number 198
6121Alpha for Zone Number 199
6137Alpha for Zone Number 200
6153Alpha for Zone Number 201
6169Alpha for Zone Number 202
6185Alpha for Zone Number 203
6201Alpha for Zone Number 204
6217Alpha for Zone Number 205
6233Alpha for Zone Number 206
6249Alpha for Zone Number 207
6265Alpha for Zone Number 208
6281Alpha for Zone Number 209
6297Alpha for Zone Number 210
6313Alpha for Zone Number 211
6329Alpha for Zone Number 212
5345Alpha for Zone Number 213
6361Alpha for Zone Number 214
6377Alpha for Zone Number 215
6393Alpha for Zone Number 216
6409Alpha for Zone Number 217
6425Alpha for Zone Number 218
6441Alpha for Zone Number 219
6457Alpha for Zone Number 220
6473Alpha for Zone Number 221
6489Alpha for Zone Number 222
6505Alpha for Zone Number 223
6521Alpha for Zone Number 224
6537Alpha for Zone Number 225
6553Alpha for Zone Number 226
6569Alpha for Zone Number 227
6585Alpha for Zone Number 228
6601Alpha for Zone Number 229
6617Alpha for Zone Number 230
6633Alpha for Zone Number 231
6649Alpha for Zone Number 232
6665Alpha for Zone Number 233
6681Alpha for Zone Number 234
6697Alpha for Zone Number 235
6713Alpha for Zone Number 236
6729Alpha for Zone Number 237
6745Alpha for Zone Number 238
6761Alpha for Zone Number 239
6777Alpha for Zone Number 240
6793Alpha for Zone Number 241
6809Alpha for Zone Number 242
6825Alpha for Zone Number 243
6841Alpha for Zone Number 244
6857Alpha for Zone Number 245
6873Alpha for Zone Number 246
6889Alpha for Zone Number 247
6905Alpha for Zone Number 248
Index
Symbols
24-Hour Zone ............................................... 19