Intrusion Alarm Systems | DS7432 Series Eight‑input Remote Modules
DS7432 Series Eight‑input Remote
Modules
www.boschsecurity.com
u Address up to eight input loops
u Serial dual end-of-line (EOL) wiring with tamper
status (DS7432E)
The DS7432 Series Eight-input Remote Modules
include the DS7432, the DS7432-CHI, and the
DS7432E. All modules address up to eight input loops
of conventional contacts to the multiplex bus of the
control panel. The DS7432E has an additional serial
dual end-of-line (EOL) wiring configuration. The
DS7432E addresses up to sixteen input contacts
(alarm and tamper for each loop).The DS7432 and
DS7432-CHI each use one 47 kΩ resistor per input.
The DS7432E uses 22 kΩ + 47 kΩ per input.
Certifications and approvals
Region Certification
Europe CE 1999/5/CE Radio Eqipment & Tele-
phone Equipment Directive
(R&TTE)
CE 2004/108/EC EMC Directive (EMC),
2006/95/EC Low-Voltage Directive
(LVD)
USA UL DS7432: AMCX: Central Station Alarm
Units (UL1610, UL1635), APAW: Police
Station Alarm Units (UL365, UL464),
UOXX: Control Unit Accessories, System
(UL864, 9th edition), UTOU: Control
Units and Accessories - Household System Type (UL985)
Region Certification
CSFM 7165-1615:0242
CSFM 7165-1615:0119
CSFM 7167-1615:0239
NYCMEA
NYCMEA
DS7432: 274-94-E, Vol. IV
DS7432: 274-94-E, Vol. III
Installation/configuration notes
Compatibility Information
The DS7432 Series modules can only connect to the
following control panels with an attached multiplex
expansion module.
Control Panels D9412GV3 Control Panel
D7412GV3 Control Panel
D9412GV2 Control Panel
D7412GV2 Control Panel
D9412G Control Panel
D7412G Control Panel
2 | DS7432 Series Eight‑input Remote Modules
DS7400XiV4 Control Panel
DS7400Xi Control Panel
Multiplex Modules D8125MUX Multiplex Bus Interface
DS7430 Multiplex Expansion Module
DS7436 Multiplex Expansion Module
Notice
The DS7432E is compatible with the D9412GV3,
D7412GV3, D9412GV2, D7412GV2, D9412G, and
D7412G when the PCB jumper is set to DS7432
mode.
Number of Modules
The number of DS7432 Series Modules connected to a
system depends on the control panel.
Control Panel Number of Multiplex
DS7400Xi
DS7400XiV4
D9412GV3, D9412GV2, D9412G
D7412GV3, D7412GV2, D7412G
Expansion Modules
Up to 15
Up to 30
Up to 30
Up to 8
Wiring
Refer to the multiplex expansion module’s reference
guide for multiplex wiring requirements.
Maximum Impedance: 4.05 Ω at +20°C (+68°F) nominal
Distance (approximate) Size
Technical specifications
Circuit Parameters
Initiating Device Type: Class B, Style A
Signaling Line Circuit Type: Class B, Style 4
Environmental Considerations
Temperature (operating): 0°C to +50°C (+32°F to +122°F)
Power Requirements
Current Draw: 10 mA maximum
DS7432 EOL Resistor: 47 kΩ
DS7432E EOL Resistor: 22 kΩ+47 kΩ per input
Voltage: 12 VDC nominal
Ordering information
DS7432E Eight‑Input Remote Module
Includes serial dual end-of-line (EOL) wiring
configuration. Addresses up to sixteen input contacts
(alarm and tamper for each loop).
Order number DS7432E
DS7432 Eight‑Input Remote Module
Addresses up to eight input loops of conventional
contacts to the multiplex bus of the control panel.
Order number DS7432
76 m 0.65 mm
193 m 1.02 mm
250 ft 22 AWG
600 ft 18 AWG
The recommended wiring to the control panel is quad
(four-wire) cable. Do not use shielded or twisted pair
cable.
Notice
If used in fire applications, 18 AWG wire is
required.
Parts included
QuantityComponent
1 Eight-input remote module
1 Literature pack