Bosch DS7432 Installation Manual

Installation Instructions for the

DS7432 Eight Input Remote Module

1.0 Description

The DS7432 is an Eight Input Remote Module that provides a means of addressing up to eight input loops of conventional contacts to the multiplex bus of the control.

2.0 Specifications

Control Panel Requirements: The DS7432 is designed to work with the following control panels:

A DS7400, DS7400X, DS7400Xi, DS7400Xi Rev. 3 or DS7400Xi Rev. 4.

Up to 7 DS7432s can be used per DS7400 system.

Up to 15 DS7432 modules are allowed on DS7400X, Xi and Xi Rev. 3.

The DS7400Xi Rev. 4 control panel can support up to 30 DS7432 modules.

One DS7430, DS7436 or DS9431 Multiplex Expansion Module is required in the system to use the DS7432 Remote Module.

Current Draw: 10 mA Standby, 10 mA Alarm

Minimum Bus Voltage For Operation: 8 VDC peak

Wiring: Refer to the reference guide for the panel’s multiplex expansion module for multiplex wiring requirements. The length of the wire connected to the loop inputs on the DS7432 must be less than 250 ft. (76 m) per loop.

The recommended wiring to the control is standard #18 (1.22 mm) or #22 (0.74 mm) AWG, quad (4-wire) cable. Do not use shielded or twisted pair cable.

For fire applications, #18 AWG (1.2 mm) wire is required.

3.0 Installation

P3 of the DS7432 is for European application only. Do not put a jumper here.

P2 of the DS7432 allows the tamper switch to be bypassed with a jumper when testing or servicing.

Remove jumper P2 when testing or servicing has been completed.

Use the mounting holes (upper left and lower right corners) to mount. It can be mounted inside or outside of the control enclosure.

Route wiring as necessary from the DS7430, DS7436 or DS9431 in the control enclosure and from the remote devices to the DS7432.

Connect wiring as shown in Figure 3.

If using separate powered detectors (other than smoke detectors) with a DS7400 Series Control/ Communicator, the DS7432 can be powered from the control panel auxiliary power (terminals 7 and 8). The detector can be connected to the DS7432 (see Figure 4). This eliminates the need for home-run power wiring from each detector to the control when the DS7432 is mounted outside of the enclosure.

Be sure all wiring is unpowered before routing.

If the wiring is to enter through the rear of the enclosure, open the DS7432's rear wire entrance. If the wiring is to run along the surface of the enclosure, open the DS7432's surface wire entrance. See Figure 2.

4.0Programming

4.1System Programming

Refer to the System Programming section in your panel’s reference guide for Zone programming information.

4.1 DIP Switch Settings

The DIP switches select which zones will be activated by the loop inputs. Set the DIP switches as shown in Table 1 (Page 2).

No two DS7432s should be set the same.

The DS7432 occupies eight zones when connected to the control panel. The input loops of the DS7432 correspond to the zones of the control as shown in Table 2.

 

Figure 1: DIP Switch Orientation

 

Locking tab

 

P3

 

DIP switch

 

Tamper Switch

 

P2

+ – + – 1 2 3 4 5 6 7 8

POWER

BUS

 

Rear Wire Entrance

 

Surface Wire Entrance

Figure 2: DS7432 Front View Without Cover

Bosch DS7432 Installation Manual

 

 

 

DIP Switches

 

 

 

 

 

 

 

 

Zones

1

2

3

4

5

 

 

 

 

 

 

9-16

Off

Off

Off

Off

On

 

 

 

 

 

 

17-24

Off

Off

Off

On

Off

 

 

 

 

 

 

25-32

Off

Off

Off

On

On

 

 

 

 

 

 

33-40

Off

Off

On

Off

Off

 

 

 

 

 

 

41-48

Off

Off

On

Off

On

 

 

 

 

 

 

49-56

Off

Off

On

On

Off

 

 

 

 

 

 

57-64

Off

Off

On

On

On

 

 

 

 

 

 

65-72

Off

On

Off

Off

Off

 

 

 

 

 

 

73-80

Off

On

Off

Off

On

 

 

 

 

 

 

81-88

Off

On

Off

On

Off

 

 

 

 

 

 

89-96

Off

On

Off

On

On

 

 

 

 

 

 

97-104

Off

On

On

Off

Off

 

 

 

 

 

 

105-112

Off

On

On

Off

On

 

 

 

 

 

 

113-120

Off

On

On

On

Off

 

 

 

 

 

 

121-128

Off

On

On

On

On

 

 

 

 

 

 

129-136

On

Off

Off

Off

Off

 

 

 

 

 

 

137-144

On

Off

Off

Off

On

 

 

 

 

 

 

145-152

On

Off

Off

On

Off

 

 

 

 

 

 

153-160

On

Off

Off

On

On

 

 

 

 

 

 

161-168

On

Off

On

Off

Off

 

 

 

 

 

 

169-176

On

Off

On

Off

On

 

 

 

 

 

 

177-184

On

Off

On

On

Off

 

 

 

 

 

 

185-192

On

Off

On

On

On

 

 

 

 

 

 

193-200

On

On

Off

Off

Off

 

 

 

 

 

 

201-208

On

On

Off

Off

On

 

 

 

 

 

 

209-216

On

On

Off

On

Off

 

 

 

 

 

 

217-224

On

On

Off

On

On

 

 

 

 

 

 

225-232

On

On

On

Off

Off

 

 

 

 

 

 

233-240

On

On

On

Off

On

 

 

 

 

 

 

241-248

On

On

On

On

Off

 

 

 

 

 

 

249-256

On

On

On

On

On

Table 1: DIP Switch Settings

 

 

 

 

Zone Number

 

 

 

DS7432 Input

1

2

3

4

5

6

7

8

Loop

 

 

 

 

 

 

 

 

Zones 9-16

9

10

11

12

13

14

15

16

 

 

 

 

 

 

 

 

 

Zones 17-24

17

18

19

20

21

22

23

24

 

 

 

 

 

 

 

 

 

Zones 25-32

25

26

27

28

29

30

31

32

 

 

 

 

 

 

 

 

 

Zones 33-40

33

34

35

36

37

38

39

40

 

 

 

 

 

 

 

 

 

Zones 41-48

41

42

43

44

45

46

47

48

 

 

 

 

 

 

 

 

 

Zones 49-56

49

50

51

52

53

54

55

56

 

 

 

 

 

 

 

 

 

Zones 57-64

57

58

59

60

61

62

63

64

 

 

 

 

 

 

 

 

 

Zones 65-72

65

66

67

68

69

70

71

72

 

 

 

 

 

 

 

 

 

Zones 73-80

73

74

75

76

77

78

79

80

 

 

 

 

 

 

 

 

 

Zones 81-88

81

82

83

84

85

86

87

88

 

 

 

 

 

 

 

 

 

Zones 89-96

89

90

91

92

93

94

95

96

 

 

 

 

 

 

 

 

 

Zones 97-104

97

98

99

100

101

102

103

104

 

 

 

 

 

 

 

 

 

Zones 105-112

105

106

107

108

109

110

111

112

 

 

 

 

 

 

 

 

 

Zones 113-120

113

114

115

116

117

118

119

120

 

 

 

 

 

 

 

 

 

Zones 121-128

121

122

123

124

125

126

127

128

 

 

 

 

 

 

 

 

 

Zones 129-136

129

130

131

132

133

134

135

136

 

 

 

 

 

 

 

 

 

Zones 137-144

137

138

139

140

141

142

143

144

 

 

 

 

 

 

 

 

 

Zones 145-152

145

146

147

148

149

150

151

152

 

 

 

 

 

 

 

 

 

Zones 153-160

153

154

155

156

157

158

159

160

 

 

 

 

 

 

 

 

 

Zones 161-168

161

162

163

164

165

166

167

168

 

 

 

 

 

 

 

 

 

Zones 169-176

169

170

171

172

173

174

175

176

 

 

 

 

 

 

 

 

 

Zones 177-184

177

178

179

180

181

182

183

184

 

 

 

 

 

 

 

 

 

Zones 185-192

185

186

187

188

189

190

191

192

 

 

 

 

 

 

 

 

 

Zones 193-200

193

194

195

196

197

198

199

200

 

 

 

 

 

 

 

 

 

Zones 201-208

201

202

203

204

205

206

207

208

 

 

 

 

 

 

 

 

 

Zones 209-216

209

210

211

212

213

214

215

216

 

 

 

 

 

 

 

 

 

Zones 217-224

217

218

219

220

221

222

223

224

 

 

 

 

 

 

 

 

 

Zones 225-232

225

226

227

228

229

230

231

232

 

 

 

 

 

 

 

 

 

Zones 233-240

233

234

235

236

237

238

239

240

 

 

 

 

 

 

 

 

 

Zones 241-248

241

242

243

244

245

246

247

248

 

 

 

 

 

 

 

 

 

Zones 249-256

249

250

251

252

253

254

255

256

 

 

 

 

 

 

 

 

 

Table 2: Loop/Zone Number Relationship

Points 249 - 256 are not available for DS9400 use.

Page 2

© 2011 Bosch Security Systems, Inc.

DS7432 Installation Instructions

Loading...
+ 2 hidden pages