DS150i/DS151i Installation Guide Request-to-Exit PIR Detectors
1.0 Description
The DS150i is a passive-infrared detector designed for request to exit
(REX) applications. It is UL Listed as an access control device under the
UL 294 standard and is listed for Class I for UL Canada (ULC-S319). For
C-UL listed installation applications, the REX shall be connected to ULCS319 listed compatible devices (i.e. control units, power supply and
locks). Intended for indoor use only.
The relay output consists of two Form "C" contacts that can be adjusted to
latch from approximately 0.5 sec to 64 sec. The latch time features two
modes of operation: resettable (R) and non-resettable (NR). The relay can
also be programmed to fail safe or fail secure during a power loss.
You can mount the DS150i on the ceiling or wall and aim and/or mask its
pattern for more effective use based on installation needs. The DS150i is
not designed as the primary means of exit for emergency egress
applications.
The DS150i is available in a light grey (DS150i) or a black (DS151i)
enclosure. An optional trimplate is also available in light grey (TP160) and
black (TP161).
2.0 Mounting
1. Select a mounting location over the center of the door or doors to be
covered. The target must walk directly toward the detector.
Mount the detector on the ceiling, wall, or door frame. The detector
can be surface mounted or mounted to a keyswitch plate with a "D"
size hole.
The DS150i is not tall enough to completely cover a single
gang box. Where aesthetics are important, mount it using
the optional trimplate (TP160 or TP161). Refer to Figure 1
Figure 1: Optional Trimplate
for additional instructions for mounting with the trimplate.
DS150i/DS151i
DOOR
Optional Trimplate
(TP160/TP161)
Figure 2: Location of Major Items
Ceiling Mount
Angles
-14° 4° 14°
-14° 4° 14°
Wire
Plug
ON DIP
DIP
Switches
LED
Wall Mount
Angles
Wire
Entrance
3.0 Wiring
3.1 General Information
Only apply power after all connections are made and
inspected. Remove all system power (AC and standby
Attach the wiring connector (provided) to the wire plug on the circuit board
(refer to Figure 3).
Figure 3: Connector to Plug Orientation (Default Switch Settings)
Refer to Figure 4 to wire the detector’s relay contacts.
Figure 4: Relay Contact Wiring
battery) before wiring the device.
Gang box
DOOR
The arrows on the base indicate its correct mounting
orientation relative to the door.
The mounting height range is from 7 ft to 15 ft.
(2.1 m to 4.6 m) above the floor.
2. Remove the back cover from the detector. Insert the head of a small
straight edge screwdriver into the locking tab and pry the back cover
off.
When the back cover is removed, the front cover and
detector module separate.
3. Route the wiring as necessary through the wiring entrance (refer to
Figure 2). For surface wiring, use the break out wiring entrance on
the front cover (at the same end as the wire entrance).
4. Loosely mount the back cover to the mounting surface using the
supplied mounting screws.
5. Mount the detector module to the back cover. Aim the detector for
the desired coverage.
Coil excess wiring behind the back cover along the
channels provided.
3.2 EMF (Voltage) Spike-Protected Relay
Pins 6 through 8 (wire colors gray, green, and orange) comprise the EMF
spike-protected relay. Refer to Figure 3.
Use this relay when connecting inductive loads to the detector. This relay
protects the detector from inductive loads that might deliver damaging
EMF spikes.
3.3 Non-EMF (Voltage) Spike-Protected Relay
Pins 3 through 5 (wire colors yellow, violet, and blue) comprise the nonEMF spike-protected relay. Refer to Figure 3.
This relay is best used for non-inductive loads. When connecting an
inductive load that is not spike-protected, such as a magnetic door lock, to
the detector, use either a bridge rectifier (such as a KBL01) or a diode
(such as a 1N4007). Failure to use a bridge rectifier/diode may reduce the
lifetime of the relay. Refer to Figure 5.
Figure 5: Wiring the Bridge Rectifier
Power
Supply
DS150i
Relay Contact
(non-spike protected)
+
-
+
S
S
KBL01
Bridge Rectifier
Inductive
Load
Power
Supply
OR
DS150i
Relay Contact
(non-spike protected)
+
-
Inductive
Load
1N4007
Diode
UL 1034 listed magnetic locks typically are already EMF
spike-protected, and therefore do not require the bridge
rectifier or diode as shown in Figure 5. Adding a bridge
rectifier/diode to an EMF spike-protected device can cause
unwanted delays in response. Refer to the magnetic lock’s
documentation for more information.
4.0 Configuration
Use the on-board DIP switches to configure the operation of the detector.
Refer to Figure 6 for proper switch positioning.
Figure 6: DIP Switch ON/OFF Positions
Table 1: Resettable/Non-resettable DIP Switch Settings
Switch 1 Function
OFF Non-resettable
ON Resettable (Default)
4.2 Relay Mode
DIP Switch 2 selects the relay mode. This allows you to select a fail safe
by default, or a fail secure mode. Refer to Table 2 and Figure 6 for more
information.
Fail Safe: In the event of a power loss, the REX detector releases
the device connected to it (for example, magnetic door lock or
electric door strike).
Fail Secure: In the event of a power loss, the REX detector does not
release the device connected to it (for example, magnetic door lock
or electric door strike).
In Fail Secure mode, the REX detector shall be installed in a manner
that does not impair the intended operation of panic hardware used
in conjunction with the REX detector.
Failure Secure mode must be authorized by the local Authority
Having Jurisdiction (AHJ).
Table 2: Relay Mode DIP Switch Settings
Switch 2 Function
OFF Fail Secure
ON Fail Safe (Default)
Refer to Figure 4 relay wiring options.
4.3 Led Enable/Disable
DIP Switch 3 selects whether the on-board LED is enabled or disabled. If
enabled, the LED operates normally when motion is detected.
Table 3: LED Enable/Disable DIP Switch Settings
Switch 3 Function
OFF Disabled
ON Enabled (Default)
When LED is enabled, it will flash on and off when first
powered up. Once the flashing LED stops, the REX is
ready to be used.
ON DIP
ON
ON
ON
OFF
4.1 Resettable/Non-resettable Timer Selection
DIP Switch 1 determines if the relay resets at the end of latch time, or if
latch time is extended by additional motion. Refer to Table 1 and Figure 6
for more information.
Resettable: The relay activates when the detector first sees motion.
Any additional motion restarts the latch timer so the relay deactivates
only when the detector no longer sees motion and the latch time has
expired. Hint: This setting works best when bypassing a 24-hour
contact.
Non-resettable: The relay activates when the detector first sees
motion. It deactivates when the latch time ends, even if motion is still
present. Hint: This setting works best when used with an access
control system.
© 2011 Bosch Security Systems, Inc.
130 Perinton Parkway, Fairport, NY 14450-9199 USA
www.boschsecurity.com
4.4 Latch Time
DIP Switches 4, 5, and 6 set the relay latch time. Latch time is adjustable
from 0.5 sec to 64 sec. It indicates the amount of time the relay can
remain active after the detector first sees motion.
Table 4: Latch Time DIP Switch Settings
Time (sec) Switch 4 Switch 5 Switch 6
0.5 (Default) OFF OFF OFF
1 OFF OFF ON
2 OFF ON OFF
4 OFF ON ON
8 ON OFF OFF
16 ON OFF ON
32 ON ON OFF
64 ON ON ON
F01U252565-01
Installation Guide
DS150i/DS151
Page 2 of
9/11