Bosch DS1109I Installation Manual

Glass Break Detector
Door
Door Closed
Door Frame
Door Frame
Sensor A per tu re
Magnet
DS1109i
DS1109i
Door Open
DS1109i
en Installation and Operation Guide
1 Specifi cations
1.1 Coverage
10 ft (3 m) maximum to farthest point of glass being protect­ed. For glass sizes over 12 in x 12 in (30 cm x 30 cm); types of 1/4 in (64 mm) Plate, Tempered, Laminated, and Wired glass; and 1/8 in (32 mm) Plate glass (DSB).
1.2 Mounting
Directly (or using the supplied bracket) to a ceiling, wall, door or window frame.
1.3 Input Power
12 VDC (6 VDC min to 15 VDC max), 23 mA nominal @ 12 VDC (29 mA max in the LED Latch mode).
1.4 Standby Power
Connect to power sources capable of supplying standby power of 23 mAh for each hr of required standby time. Four hr mini­mum standby time required for UL Listed Requirements.
1.5 Alarm Relay
Normally Closed (NC/C) reed relay contacts rated 3.5 Watts, 125 mA @ 28 VDC for DC resistive loads. Protected by a 10 ohm resistor in the common “C” leg. The contact opens for 3 sec upon a glassbreak alarm. For a magnetic contact alarm, the contacts remain open as long as the magnet is more than 1 - 2 inches away from the detector.
1.6 Tamper
Normally Closed (NC/C) rated 125 mA @ 28 VDC maximum. For UL Listed Requirements, the tamper switch must be con­nected to a 24 hr protection circuit.
1.7 Operating Temperature
-20° to +120°F (-29° to +49°C). For UL Listed Requirements, the temperature range is +32° to +120°F (0° to +49°C).
1.8 Enclosure
ABS high impact plastic. 1.25 in H x 3.75 in W x 0.875 in D (32 mm H x 95 mm W x 23 mm D).
1.9 Accessories
DS1110i Glass Breakage Tester. mm) Plate glass (DSB).
If you must install the DS1109i in a zone that is armed • when occupied:
Avoid acoustically live areas such as kitchens and bath-• rooms. Use a delay zone to allow time to acknowledge user caused • false alarms. Instruct users of the system how to respond to such an • alarm.
Remember:
The best mounting location is less than 10 ft (3 m) from • the glass, and in direct line of sight of the glass. Do not exceed the maximum range. Range will be reduced in areas that are acoustically soft. • This may be due to carpeting, drapes, plants, or other sound absorbing materials. The DS1110i Glass Breakage Tester should be used to verify range in all installations. Glass break detectors are intended only as a component of • a perimeter protection system. They should always be used in conjunction with motion sensors. Glass breakage detectors are designed to detect the break-• age of framed glass and may not detect such things as bul­let holes, spontaneous breakage of glass (with no impact), and removal of glass.
Maximum Range:
The maximum detection range is 10 ft (3 m) from the farthest corner, for glass sizes 12 in x 12 in (30 cm x 30 cm) and larger.
3 Selecting a Mounting Location
Opposite Wall Mounting Using the Door Contact
Mount the detector where there are no objects between itself and the glass. Make sure the detector is no farther than 10 ft (3 m) from
Top of
Door
Frame
DS1109i
Magnet
Side View
Figure 3.2: Side View
Figure 3.3: View Looking up from Floor
Single Window Coverage Using the Magnetic Contact
Mount the detector where there are no objects be-• tween itself and the glass. Make sure the detector is no farther than 10 ft (3 m) • from the farthest corner of the glass (line A in Figure
3.4). Do not mount the unit with the Sensor Aperture facing • away from the window.
Do Not Adjust
Test Switch
Tamper Switch
Figure 1.1: Board Layout
© 2011 Bosch Security Systems, Inc.
P2 P3
2 Installation Considerations
NOTICE!
Always pretest the detector’s location using the
A
DS1110i Glass Breakage Tester.
NC C T T
Block
Do Not:
Mount the detector on iron or steel surfaces if the mag-• netic contact will be used. Aluminum and stainless stell frames are acceptable. Mount the detector with obstructions between the glass • being protected and the detector. Mount closer than 2 ft (61 cm) to heating or cooling out-• lets; mount as far away as possible. If drafts from these outlets blow on the detector, select a different location for the detector. Use the environmental test (see Section 6) to verify good installation locations. Install alarm contacts on 24 hr protection circuits.
Figure A
Figure 3.1: Opposite Wall Mounting Using Door Contact
any corner of the glass (line A in Figure 3.1).
Mounting Above Glass Doors
Mount the DS1109i at the top of the door frame with • the Sensor Aperture pointing downward. Mount the magnet to the top of the door. The magnet • should be placed so that it aligns with the side of the DS1109i. Do not allow the magnet to cover the front of the detector. See Figure 3.2. The detector must be mounted so that the door swings • outward from the detector. See Figure 3.3.
Figure 3.4: Single Window Coverage Using the Magnetic Contact
Ceiling Mounting Without the Magnetic Contact
The recommended location is half the distance be-• tween the glass and the opposite wall or 7 ft (2.1 m) whichever is smaller. Mount the detector where there are no objects be-• tween the glass and itself. Make sure the detector is no further than 10 ft (3 m) • from any corner of the glass (line A in fi gure 3.5). The detector should be within ±30° of the center of • the glass to be protected (line B in fi gure 3.5). Jumper P3 must be installed to disable the magnetic • contact. See Section 5.
A
A
Figure C
F01U069268 | 02 | 2011.10 | 1
Sensor Aperture
Window
Frame
Side View
Figure 3.5: Ceiling Mounting Without the Magnetic Contact
5 Setting the Jumpers
The DS1109i has two jumpers located on the main board. P2 is used to allow the LED to latch on to a glass breakage alarm. P3 is used to determine if the magnetic contact is used.
Remove the jumper from P2 if you do not want the LED • to latch into alarm when a glass breakage occurs. The relay contacts will only change state for approximately 3 sec upon a glass breakage alarm. The LED may be reset by a momentary interruption of the power. Remove the jumper from P3 if you want to use the mag-• netic contact.
Turn on all sources of noise (e.g. forced air blowers, air • conditioners, compressor motors, etc.). The LED will fl ash 5 times per second each time a low frequency disturbance is detected. If the 5 fl ashes per second occur more than once every 15 sec or if the unit alarms, then do not mount in this location. The LED will fl ash once each time a high frequency disturbance is detected. If any fl ashes occur more than once every 15 sec, do not mount in this location.
Remember: If the detector happens to alarm during this test, the alarm relay will activate as well.
During the last 10 sec of the detector’s test mode, its • LED will pulse. To end the test mode before the 5 min­ute time-out period, press the Test Switch.
Automatic Sound Check
This detector features Automatic Sound Check, to allow the end user to test the unit on a periodic basis. To perform the test, simply clap your hands or create some other loud sound. When the detector hears this sound the LED (but not the alarm relay) will activate. This feature works in the normal operat­ing mode and does not require that the detector be in the test mode.
NOTICE!
Adjacent wall mounting is not recommended for this detector.
Mounting the Detector
After verifying an acceptable location, permanently • mount the detector. Use the two mounting holes in the enclosure to secure it to the mounting surface. Mount the detector and the Contact Magnet within 1 • in (2.5 cm) of each other. The Contact Magnet must be mounted facing the side of the detector with the Sen­sor Aperture. See Figure 3.6.
Magnet
DS1109i
Sensor Aperture
Magnet
DS1109i
Mounting Holes
Wire Knockouts
Magnet
DS1109i
Wall Tamper Sring
Knockout
Figure 3.6: Mounting the Detector
Do not mount the magnet so it covers the Sensor • Aperture.
Avoid misaligning the detector and the magnet.
Magnet
DS1109i
Figure 3.7: Alignment Caution
4 Wiring the Detector
Wire the detector as shown in Figure 4.1. Leave extra • wire so the case can be opened for testing.
Alarm
Power
NC
Contacts shown with power on, no alarm and Tamper Switch closed (cover on).
Figure 4.1: Wiring the Detector
C
Tamper
T
T
Latch
Jumper
Bypass Jumper
P2 P3
Contact
NC C T T
+
-
Figure 5.1: Setting the Jumpers
6 Installing the Tamper Screw
Install the tamper screw as shown in Figure 6.1.
Figure 6.1: Installing the Tamper Screw
7 Testing
Testing the Location
Temporarily mount the detector using 2-sided tape.• Power the detector using a 9 Volt battery.• The detector will enter the test mode for fi ve min as soon as power is applied. The detector will indicate that it is in the test mode by fl ashing the LED for 10 sec. At the end of fi ve min the detector will fl ash the LED again for 10 sec to indicate the test period is over. The test mode can be restarted at any time by powering the unit off and then on or by pressing the Test Switch (see the Board Layout drawing). Pressing the Test Switch when the unit is in the test mode will terminate the test.
NOTICE!
All testing should be done with the detector’s cover in place.
Test #1 Environmental Test
Remember: The detector must be in test mode to perform this test. During the 5 minute test mode, the LED will indicate low or high frequency disturbances by fl ashing at specifi c rates. Occasional (random) fl ashes of the LED are normal. To rule out random fl ashes affecting this test, observethe LED for the full 5 min.
Test #2 Response Test
Remember: The detector must be in test mode to perform this test. This test should be performed using the DS1110i Glass Break­age Tester. The DS1110i produces a high frequency tone designed to alarm the unit to further verify proper location.
CAUTION!
Don’t point the tester directly at your or any­one’s ear. Doing so could damage hearing.
Hold the DS1110i Glass Breakage Tester against the • window being tested and point it at the detector.If there are curtains or blinds covering the window, close them over the Tester. See Figure 7.1.
DS1110i Tester Hold against window and point at detector.
Figure 7.1: Test #2 Response Test
Activate the tester. Setting the Tester to automatic • mode causes it to activate every 6 sec. This will allow you to better observe the detector’s LED. For large windows, perform this test at different place-• ments along the window. The alarm/test LED and the alarm relay will activate for • three sec if this is an acceptable detector placement.
NOTICE!
The low frequency response of the detector can be tested (while still in the test mode) by open­ing a door about 1 inch and slamming it shut. The detector should indicate an alarm.
It is recommended that a full Response Test (as outlined above) and magnetic contact test (if used) be performed on an annual basis.
Reading Bosch Security Systems, Inc. Product Date Codes
For Product Date Code information, refer to the Bosch Security Systems, Inc. Web site at: http://www.boschsecurity.com/datecodes/.
© 2011 Bosch Security Systems, Inc.
F01U069268 | 02 | 2011.10 | 2
Loading...