Bosch AMT-12-24-R-NYC, AMT-12-24-R Specsheet

Bosch AMT-12-24-R-NYC, AMT-12-24-R Specsheet

Fire Alarm Systems | AMT 12/24 R Multitone Electronic Appliance (red)

AMT 12/24 R Multitone Electronic

Appliance (red)

www.boschsecurity.com

The Wheelock AMT-12/24-R Multitone Electronic Appliances provide eight groups of three distinct selfprioritized sound outputs from separate electrically isolated input terminals. Priority 1 overrides all other commands upon activation.

Choose from high dBA or standard dBA sound output. These appliances operate on 12 VDC or 24 VDC, filtered or FWR. They are listed for indoor or outdoor use with the specified back boxes.

Use these appliances in suppression releasing systems, combination security and emergency evacuation systems, and high risk installations.

Functions

Self-Prioritized Tones

Choose any of the following eight groups of selfprioritized tones:

Self-Prioritizing Groups

 

Priority 1

Priority 2

Priority 3

1

Horn

Bell

Siren

2

Code 3 Horn*

Siren

Vibrating Chime

uThree separate supervised prioritized inputs activate three electrically isolated signals

uPower taps for high dBA and standard dBA

uLow current draw with low temperature compensation

uSelectable voltage input (12 VDC or 24 VDC)

uVoltage inputs polarized for use with reverse polarity supervision systems

3

Slow Whoop

March Time Horn

Hi Lo

4

March Time Horn

Hi Lo

Vibrating Chime

5

Code 3 Horn*

Bell

Siren

6

Siren

Horn

Vibrating Chime

7

Bell

March Time Horn

Siren

8

Code 3 Tone*

Hi Lo

Siren

* The Code 3 Horn and Code 3 Tone, when set for high dBA, incorporate the temporal pattern specified by ANSI and NFPA for standard emergency evacuation signaling. Use them only for fire evacuation signaling and not for any other purpose.

Notice

The prioritized tones used in each group are factory set and cannot be changed.

Input Voltage and Sound Output Settings

The input voltage (12 VDC or 24 VDC) and the sound output (high dBA or standard dBA) are set with a jumper plug and a DIP switch.

2 | AMT 12/24 R Multitone Electronic Appliance (red)

Certifications and approvals

Region

Certification

 

 

 

USA

UL

UCST: Audible Signal Appliances, Gener-

 

 

al Siganal (UL464), ULSZ: Audible Sig-

 

 

nal Appliances (UL464)

 

CSFM

see our website

Canada

ULC

ULSZC: Audible Signal Appliances and

 

 

Accessories, Fire Alarm

 

 

 

Installation/configuration notes

Compatible Products

The following products are compatible with the AMT 12/24 appliances:

Categor

Product ID

y

 

Control

D9412GV21

Panels

 

 

D7412GV21

 

D7212GV21

 

D9412G1

 

D7412G1

 

D7212G1

 

DS7400XiV41

 

DS7400Xi1

 

DS7200 Series1

 

DS7080iP-321

 

DS7060 Series1

 

6000 Series1

 

2000 Series1

 

D70222

 

D70243

 

D7024

 

D80244

 

D91244

 

D10024A4

 

FPD-70243

 

FPD-7024

 

FPA-1000

Modules

SM 12/24 R

 

DSM 12/24 R

RSSP 121575W FR

Product Description

Control Panel

Control Panel

Control Panel

Control Panel

Control Panel

Control Panel

Control Panel

Control Panel

Control Panels

Control Panel

Control Panels

Control Panels

Control Panels Conventional FACP Addressable FACP Conventional FACP Analog FACP Addressable FACP Analog FACP Addressable FACP Conventional FACP

Analog Addressable FACPs Synchronization module (red)

Dual synchronization module (red)

Fixed candela retrofit strobe plate (12 V)

RSSP 241575W FR

Fixed candela retrofit strobe

 

plate (24 V)

RSSP 24MCW FR

Multi candela retrofit strobe

 

plate (24 V)

RSSP 24MCWH FR

High candela retrofit strobe

 

plate (24 V)

1 For synchronization, use the SM or DSM modules with these control panels and set the horns and synchronization module for 12 VDC operation.

2 The D7022 can be used in either 12 VDC or 24 VDC mode, but the horns and synchronization module must be set for the same operating voltage as the control panel.

3 When used with a D7039 Multiplex Expansion Module, the FPD-7024 and D7024 become addressable fire alarm control panels (FACPs).

4 For synchronization, use the SM or DSM modules with these control panels and set the horns and synchronization module for 24 VDC operation.

Notice

The retrofit strobe plates are available in 12 V or 24 V models. Choose a model with the correct voltage for the control panel being used. Refer to

Use as Combination Appliance.

Mounting Considerations

Mount these horns on the indicated back boxes for the indicated applications:

 

Conduit

Surface

Semi flush or

 

Applications

Mounted

Flush Mount

Double gang

 

 

Four inch square*

 

DBB Back Box*

 

IOB Back Box

 

* Use an ISP2 Surface Adapter between the appliance and the back box.

Retrofit Applications

Where an oversize electrical box is already installed, the appliances can be installed with the RP R Retrofit Plate that measures 8 in. (20.3 cm) high by 5.875 in. (14.9 cm) wide.

Use as Combination Appliance

Where combination appliances are required, the AMT appliances can be used with the RSSP 121575W FR (12 V, 15/75 cd), RSSP 241575W FR (24 V, 15/75 cd), RSSP 24MCW FR (24 V, 15 cd, 30 cd, 75 cd, or

110 cd), or RSSP 24MCWH FR (24 V, 135 cd or 185 cd) Retrofit Strobe Plates that are designed to

meet or exceed the latest requirements of NFPA 72, ANSI 117.0 and UL 1971. The multitone appliances and retrofit strobe plates are also compatible with the SBL2 R Retrofit Device Back Box.

Outdoor or Severe Environment Applications