Fire Alarm Systems | AMT 12/24 R Multitone Electronic Appliance (red)
AMT 12/24 R Multitone Electronic
Appliance (red)
www.boschsecurity.com
The Wheelock AMT-12/24-R Multitone Electronic Appliances provide eight groups of three distinct selfprioritized sound outputs from separate electrically isolated input terminals. Priority 1 overrides all other commands upon activation.
Choose from high dBA or standard dBA sound output. These appliances operate on 12 VDC or 24 VDC, filtered or FWR. They are listed for indoor or outdoor use with the specified back boxes.
Use these appliances in suppression releasing systems, combination security and emergency evacuation systems, and high risk installations.
Functions
Self-Prioritized Tones
Choose any of the following eight groups of selfprioritized tones:
Self-Prioritizing Groups
|
Priority 1 |
Priority 2 |
Priority 3 |
1 |
Horn |
Bell |
Siren |
2 |
Code 3 Horn* |
Siren |
Vibrating Chime |
uThree separate supervised prioritized inputs activate three electrically isolated signals
uPower taps for high dBA and standard dBA
uLow current draw with low temperature compensation
uSelectable voltage input (12 VDC or 24 VDC)
uVoltage inputs polarized for use with reverse polarity supervision systems
3 |
Slow Whoop |
March Time Horn |
Hi Lo |
4 |
March Time Horn |
Hi Lo |
Vibrating Chime |
5 |
Code 3 Horn* |
Bell |
Siren |
6 |
Siren |
Horn |
Vibrating Chime |
7 |
Bell |
March Time Horn |
Siren |
8 |
Code 3 Tone* |
Hi Lo |
Siren |
* The Code 3 Horn and Code 3 Tone, when set for high dBA, incorporate the temporal pattern specified by ANSI and NFPA for standard emergency evacuation signaling. Use them only for fire evacuation signaling and not for any other purpose.
Notice
The prioritized tones used in each group are factory set and cannot be changed.
Input Voltage and Sound Output Settings
The input voltage (12 VDC or 24 VDC) and the sound output (high dBA or standard dBA) are set with a jumper plug and a DIP switch.
2 | AMT 12/24 R Multitone Electronic Appliance (red)
Certifications and approvals
Region |
Certification |
|
|
|
|
USA |
UL |
UCST: Audible Signal Appliances, Gener- |
|
|
al Siganal (UL464), ULSZ: Audible Sig- |
|
|
nal Appliances (UL464) |
|
CSFM |
see our website |
Canada |
ULC |
ULSZC: Audible Signal Appliances and |
|
|
Accessories, Fire Alarm |
|
|
|
Installation/configuration notes
Compatible Products
The following products are compatible with the AMT 12/24 appliances:
Categor |
Product ID |
y |
|
Control |
D9412GV21 |
Panels |
|
|
D7412GV21 |
|
D7212GV21 |
|
D9412G1 |
|
D7412G1 |
|
D7212G1 |
|
DS7400XiV41 |
|
DS7400Xi1 |
|
DS7200 Series1 |
|
DS7080iP-321 |
|
DS7060 Series1 |
|
6000 Series1 |
|
2000 Series1 |
|
D70222 |
|
D70243 |
|
D7024 |
|
D80244 |
|
D91244 |
|
D10024A4 |
|
FPD-70243 |
|
FPD-7024 |
|
FPA-1000 |
Modules |
SM 12/24 R |
|
DSM 12/24 R |
RSSP 121575W FR
Product Description
Control Panel
Control Panel
Control Panel
Control Panel
Control Panel
Control Panel
Control Panel
Control Panel
Control Panels
Control Panel
Control Panels
Control Panels
Control Panels Conventional FACP Addressable FACP Conventional FACP Analog FACP Addressable FACP Analog FACP Addressable FACP Conventional FACP
Analog Addressable FACPs Synchronization module (red)
Dual synchronization module (red)
Fixed candela retrofit strobe plate (12 V)
RSSP 241575W FR |
Fixed candela retrofit strobe |
|
plate (24 V) |
RSSP 24MCW FR |
Multi candela retrofit strobe |
|
plate (24 V) |
RSSP 24MCWH FR |
High candela retrofit strobe |
|
plate (24 V) |
1 For synchronization, use the SM or DSM modules with these control panels and set the horns and synchronization module for 12 VDC operation.
2 The D7022 can be used in either 12 VDC or 24 VDC mode, but the horns and synchronization module must be set for the same operating voltage as the control panel.
3 When used with a D7039 Multiplex Expansion Module, the FPD-7024 and D7024 become addressable fire alarm control panels (FACPs).
4 For synchronization, use the SM or DSM modules with these control panels and set the horns and synchronization module for 24 VDC operation.
Notice
The retrofit strobe plates are available in 12 V or 24 V models. Choose a model with the correct voltage for the control panel being used. Refer to
Use as Combination Appliance.
Mounting Considerations
Mount these horns on the indicated back boxes for the indicated applications:
|
Conduit |
Surface |
Semi flush or |
|
Applications |
Mounted |
Flush Mount |
Double gang |
|
|
• |
Four inch square* |
|
• |
• |
DBB Back Box* |
|
• |
• |
IOB Back Box |
• |
• |
|
* Use an ISP2 Surface Adapter between the appliance and the back box.
Retrofit Applications
Where an oversize electrical box is already installed, the appliances can be installed with the RP R Retrofit Plate that measures 8 in. (20.3 cm) high by 5.875 in. (14.9 cm) wide.
Use as Combination Appliance
Where combination appliances are required, the AMT appliances can be used with the RSSP 121575W FR (12 V, 15/75 cd), RSSP 241575W FR (24 V, 15/75 cd), RSSP 24MCW FR (24 V, 15 cd, 30 cd, 75 cd, or
110 cd), or RSSP 24MCWH FR (24 V, 135 cd or 185 cd) Retrofit Strobe Plates that are designed to
meet or exceed the latest requirements of NFPA 72, ANSI 117.0 and UL 1971. The multitone appliances and retrofit strobe plates are also compatible with the SBL2 R Retrofit Device Back Box.
Outdoor or Severe Environment Applications