Bosch 2000 User Manual

2000 Series
Program Entry Guide
EN
Control Panels
2000 Series | Program Entry Guide | About This Manual EN | 2
About This Manual
This guide describes the programming parameters available to the 2000 Series Control Panels (except D2012/D2012U). This guide follows the organization of the D2212 Product Handler in the D5200 Programmer.
The table of contents lists each programming section, program item, and its page number.
Throughout this manual, programming prompts are shown in bold italic letters (such as
Phone 1
Use the Program Record Sheet (P/N: 35113) to record your program entries. Installation instructions can be found in the panel’s Installation Guide. The Keypad Diagnostics Sheet provides specific diagnostic and testing information. A Security System User Guide comes with the keypad.
).
E Version Control Panels
The E versions of the 2000 Series Control Panels (for example, the D2412UE) do not include point expansion. They are limited to the on-board points.
Any programming for point expanders does not apply to E version control panels.
Using this Guide for Keypad Programming
Keypad programming requires a text keypad. For an explanation, refer to Section 18.0 Keypad Programming of this manual.
Display text and keypad programming appear as shown:
0000
0 to 9, B to F
Default entries and selections for keypad programming also appear in shaded boxes.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | Contents EN | 3
Contents
1.0 System Configuration......................................5
2.0 Phone ..................................................................7
2.1 Phone Routing Set to No...................................7
2.2 Phone Routing Set to Yes..................................7
3.0 Reports..............................................................11
4.0 Receiver............................................................15
4.1 Modem Reports................................................15
4.2 Pulse Report Groups ........................................18
5.0 Remote Programming...................................21
6.0 Open/Close .....................................................23
6.1 Step Outside......................................................24
6.2 Exit .....................................................................25
7.0 ABC Keys.........................................................27
8.0 Bell.....................................................................29
9.0 Test Timer........................................................31
10.0 Address Configuration..................................33
11.0 Point Codes......................................................35
11.1 Digit 1, Point Type...........................................37
11.2 Digit 2, Alarm Responses ................................43
11.3 Digit 3, Point Options ......................................44
11.4 Digit 4, Device Address...................................45
11.5 Digit 5, Sensor Loop ........................................46
11.6 Recommended Point Codes..................................48
12.0 Point Text.........................................................51
13.0 Relays................................................................53
13.1 Relay Function Logic.......................................53
13.2 Relay Functions ................................................53
13.3 Relay Parameters, for Keypad Programming Only 56
14.0 User Test...........................................................57
15.0 Passcodes..........................................................59
16.0 RF Parameters.................................................61
17.0 Program Lock..................................................63
18.0 Keypad Programming...................................65
18.1 Getting Started ..................................................65
18.2 View Mode........................................................65
18.3 Modify Mode ....................................................66
18.4 Scroll Lists .........................................................66
18.5 Yes and No Entries...........................................66
18.6 An Example, Entering Custom Text..............67
18.7 Keypad Programming Tips .............................68
Index ............................................................................69
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | Contents EN | 4
Figures
Figure 1: Pulse Report Groups......................................18
Figure 2: View Mode......................................................65
Figure 3: Modify Mode ..................................................66
Tables
Table 1: Phone Routing Set to No..................................7
Table 2: Modem II Reports Chart................................15
Table 3: Pulse Format.....................................................18
Table 4: Answer Machine Programmed Yes...............22
Table 5: Digit 1 Selections..........................................37
Table 6: Digit 2 Selections.......................................43
Table 7: Digit 3 Selections.......................................44
Table 8: Digit 4 Selections.............................................45
Table 9: Digit Selection Summary................................47
Table 10: Smoke Detector (trouble on open,
alarm output)..............................................48
Table 11: Door with Entry/Exit Delay
(swinger bypass, alarm output,
alarm report delay)....................................48
Table 12: Door or Window with No Entry/Exit
Delay (swinger bypass, alarm output,
alarm report delay)....................................48
Table 13: Garage Door with Extended Entry/Exit
Delay (swinger bypass, alarm output,
alarm report delay)....................................48
Table 14: Motion Detector (swinger bypass,
alarm output, alarm report delay)............48
Table 15: Tamper (swinger bypass, alarm output,
alarm report delay)....................................48
Table 16: Panic Device (swinger bypass).................49
Table 17: Keyswitch (swinger bypass, alarm
output).........................................................49
Table 18: Relay Function Selections ........................54
Table 19: Relay Parameters.......................................56
Table 20: View Mode Keys ........................................65
Table 21: Modify Mode Keys.....................................66
Table 22: Entering Custom Text at the Keypad .........67
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 1.0 System Configuration EN | 5
3 Keyswitch
1.0 System Configuration
The System Configuration Group contains the
Account Number, Swinger Count, Keyswitch Custom Idle Text
, and
Custom Service Text
prompts.
Default:
,
Selection:
0 Easikey
Momentary
Easikey, Momentary
1 Account Number
Default:
Selection:
Enter four characters for the
0000
0 to 9, B to F
Account Number
to transmit to the receiver. Enter leading zeroes (0) for account numbers with fewer than four digits. For example: Enter 0123 for account number 123.
2 Swinger Count
Default:
Selection:
The
Swinger Count
4
1, 2, 3, 4
prompt sets the swinger count for the Swinger Bypass point option. When the number of alarms or troubles reaches the swinger count, the system automatically bypasses points programmed for Swinger Bypass. Turning the system off clears the bypass. If a 24-hour point swinger bypasses while the system is off, turning the system on (starting exit delay) and then turning it off (pressing [CLEAR] during exit delay) clears the bypass. Swinger bypass is a point trouble and activates the Point Trouble Relay function.
When a point is Swinger Bypassed, the Point Trouble Relay function activates. Refer to Section
13.2 Relay Functions.
SIA recommends the swinger count be set to 1.
Using Digit 2 of the point code assigns the Swinger Bypass feature to a point.
1 Momentary
Refer to the Installation Guide for instructions on connecting a momentary keyswitch to a point.
This control panel is not compatible with maintained contact keyswitches.
Operating the keyswitch (shorting the point) turns the system All On with delays if the system is off. Any faulted controlled points (Point Code Digit 1 = 6, 7, 8, 9, B, or C) are automatically bypassed.
If the system is All On or Part On, with or without delays, operating the keyswitch (shorting the point) turns the system off.
Leave the
Keyswitch
prompt set to Momentary if
you are not using a keyswitch on your system. Setting the
Keyswitch
prompt to Easikey allows a properly connected Easikey system to disarm the system. It cannot be used to arm the system. If the system is All On or Part On, with or without delays, presenting the electronic key to the Easikey reader (the Easikey shorts the point) turns the system off. If the system is off, presenting the electronic key to the Easikey reader (the Easikey shorts the point) has no effect.
4 Custom Idle Text1
5 Custom Idle Text2
Default:
Selection:
Bosch Security Systems A to Z, 0 to 9,
! # , . - / : < >
The system displays at all text keypads the two lines of custom text you enter here whenever the system is off and idle. Each line contains a maximum of sixteen characters.
Bosch Security Systems | 7/05 | 35114F
It can take up to 15 seconds for the custom text you program here to appear in all text keypads connected to the system.
2000 Series | Program Entry Guide | 1.0 System Configuration EN | 6
6 Custom Service Text
Default:
Selection:
Blank A to Z, 0 to 9,
! # , . - / : < >
The system displays the text you enter here in the second line of the keypad display when ever the first line reads, CALL FOR SERVICE. You can enter the phone number for your service department as the
Custom Service Text
.
Up to 15 Seconds for Text to Load: It can take up to 15 seconds for the custom text you program here to appear in all text keypads connected to the system.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 2.0 Phone EN | 7
Table 1: Phone Routing Set to No
2.0 Phone
The Phone Group contains prompts that configure the system for dialing and sending reports on the telephone line.
1 DTMF Dialing
Default:
Selection:
Yes
Yes, No
0 No
1 Yes
When
DTMF Dialing
is set to Yes, the control panel dials in the Dual Tone Multi-Frequency (DTMF) format for all dialing attempts.
When
DTMF Dialing
is set to No, the control panel pulse dials for all dialing attempts.
Attempt Phone Number
1 Phone Number 1 2 Phone Number 1 3 Phone Number 2 4 Phone Number 2 5 Phone Number 1 6 Phone Number 2 7 Phone Number 1 8 Phone Number 2 9 Phone Number 1 10 Phone Number 2 11 Communication Fail event
If
Phone 2
Phone 1
is left blank, five attempts are made to
.
2 Phone 1
3 Phone 2
Default:
Selection:
Blank
0 to 9, C, D, #, *, Blank
Leaving both Phone 1 and Phone 2 “Blank” creates a local system with no reports transmitted.
Enter up to nineteen characters for each phone number. The # and * characters only work when the control panel is DTMF dialing. The control panel dials these characters just as if you pressed them on a telephone keypad. Enter C for a 3-second delay. Enter D for a 7-second dial tone wait.
If you program a # or * to disable call waiting, warn your customer that eliminating their call waiting service requires a change to their security system.
4 Phone Routing
Default:
Selection:
No
Yes, No
If you set the Phone Routing prompt to No, skip to Section 4.2 Pulse Report Groups. The prompts in the remainder of this group set the routing groups.
2.2 Phone Routing Set to Yes
Set this prompt to Yes to route reports to Phone 1 or Phone 2. Reports are routed by group. A description of each routing group follows. The control panel makes five attempts to each routing destination.
Reports routed to Phone 1 have a higher priority than reports routed to Phone 2. When the control panel has reports to send to Phone 1 and Phone 2, it sends all reports for Phone 1, then sends the reports for Phone 2. If the control panel fails to send an event to Phone 1, it creates a Communication Fail event for Phone 1 and begins the Phone 2 Reports.
If the control panel works on Phone 2 Reports and there is a new event for Phone 1, the control panel continues with the Phone 2 Reports until the Phone 2 buffer is empty, and then continues to the Phone 1 event.
0 No
1 Yes
2.1 Phone Routing Set to No
When this prompt is set to the default, No, the control panel dials as shown in Table 1. The control panel only sends reports to sending to
Phone 2
Phone 1
Bosch Security Systems | 7/05 | 35114F
after two failed attempts
.
2000 Series | Program Entry Guide | 2.0 Phone EN | 8
5 Fire Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports: Fire Alarm Reports from points or ABC keys.
6 Non-Fire Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports:
Non-Fire Alarm Reports from points or ABC
keys
Point Tamper Alarms
Point Missing Alarms.
7 Pt Trbl Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports:
Trouble, Missing, Missing RF, Low Battery RF,
Bypass, or Swinger Bypass Reports from, Fire and Non-fire points combined.
8 Restoral Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports:
Restoral Reports from Fire and Non-Fire points
combined
RF Battery Restorals
Point Tamper Restorals.
9 Closing Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports: Closing Reports
10 Opening Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports: Opening Reports
Point Tamper Troubles.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 2.0 Phone EN | 9
11 Cancel Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports: Cancel Reports
12 Sys Trbl Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports:
RAM Access Fail Reports (unsuccessful attempt
to connect a remote programmer)
Comm Fail Reports (Communication Failure
event) for Phone 1 and Phone 2
Watchdog Reset Reports (system automatically
reset)
Battery Missing Reports
Battery Low Reports
AC Fail Reports
RF Receiver Trouble (Address 7, Address 8)
RF Receiver Tamper (Address 7, Address 8)13
Sys Res Route
13 Sys Trbl Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports:
RAM Access OK Reports (successful connection
to a remote programmer)
Comm Restoral Reports (successful
communication after a Communication Failure event)
Re-Boot Reports (control panel reset with the
stand-by switch or a remote programmer
Battery Restoral Reports (missing or low battery
restored)
AC Restore Reports
RF Receiver Trouble Restoral (Address 7,
Address 8)
RF Receiver Tamper Restoral (Address 7,
Address 8)
14 Duress Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports:
Bosch Security Systems | 7/05 | 35114F
Duress Reports
User Tamper (six attempts with bad passcode).
2000 Series | Program Entry Guide | 2.0 Phone EN | 10
15 Test Route
Default:
Selection:
Local Local, Phone 1 only, Phone 2 only,
Both
Local 0
Phone 1 only 1
Phone 2 only 2
Both 3
Reports:
Test Reports
Service Start (stand-by pin locked down, installer
code entered.)
Service Stop (standby-by pin unlocked. The
control panel only sends a Service Stop Report if a Service Start Report was transmitted).
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 3.0 Reports EN | 11
3 Restricted O/C
3.0 Reports
No
Yes, No
prompt to Yes. The system
Restricted O/C
prompt set to Yes, the
prompt to No to send
0
0 to 255
helps prevent False Alarm
Special Voice Verification function when you set the Delay Alrm Rpt prompt to 255: Refer to 255 = Voice Verification in this section.
Delay Alrm Rpt
Delay Alrm Rpt
Delay Alrm Rpt
prompt
expires:
1 O/C Rpts – All On
Default:
Selection:
No
Yes, No
0 No
1 Yes
If you set the
O/C Rpts-All On
prompt to Yes, the system transmits Closing Reports to the receiver when users turn the system All On. If any points are bypassed, Bypass Reports are also sent. The control panel transmits Opening
Reports when users turn
the system off from the All On state. If the user turns the system off after an alarm, the
system attaches an AFTER ALARM message to the Modem II Opening Report. Refer to Section 4.0 Receiver for a description of the Modem II Report Format.
If you set the
O/C Rpts-All On
prompt to No, the system does not send Closing Reports to the receiver when users turn the system All On.
2 O/C Rpts – Part On
Default:
Selection:
No
Yes, No
0 No
1 Yes
If you set the
O/C Rpts-Part On
prompt to Yes, the system transmits Closing Reports to the receiver when users turn the system Part On with the [0] key. If any points are bypassed, Bypass Reports are also sent. It transmits Opening Reports when users turn the system off from the Part On state.
If the user turns the system off after an alarm, the system attaches an AFTER ALARM message to the Modem II Opening Report. Refer to Section 4.0 Receiver for a description of the Modem II Report Format.
If you set the
O/C Rpts-Part On
prompt to No, the system does not send Closing Reports to the receiver when users turn the system Part On with the [0] key.
Default:
Selection:
0 No
1 Yes
Set the
Restricted O/C
only sends Opening Reports when the user turns the system off after an alarm. The system attaches an AFTER ALARM message to the Modem II Opening Report. Refer to Section 4.0 Receiver for a description of the Modem II Report Format.
With the system only sends Closing Reports when a point is bypassed.
Set the
Restricted O/C
unrestricted opening and Closing Reports.
4 Delay Alrm Rpt
Default:
Selection:
Delay Alrm Rpt
Reports. Reporting characteristics for individual points are programmed in Digit 2 of the point code.
If a point with 2, 3, 7, or 8 in Digit 2 creates an Alarm event, the system waits the number of seconds entered at the before transmitting reports to the receiver.
If a user enters a passcode to silence an alarm or turns the system off before
No Alarm, Cancel, or Restoral Reports are sent
to the receiver for these points.
All other reports, including Alarm Reports for
points programmed with a 1, 4, 5, 6, or 9 in Digit 2 are sent. If programmed for Cancel Report, a Cancel Report sends for points with a 1, 4, 5, 6, or 9 for Digit 2.
Missing alarms are sent as missing troubles.
Tamper alarms are sent as tamper troubles.
If no passcode is entered before expires, all reports are sent.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 3.0 Reports EN | 12
If the system is on with No Delay, alarm output at Terminals 4 and 5 follows the alarm delay programmed here. The alarm sounds at the keypad without delay.
When mixing Delay Alarm points (Digit 2 set for 7 or 8), with No Delay Alarm points (Digit 2 set for 5, 6, or 9), the alarm output follows the programmed alarm delay if Delay Alarm points are faulted first.
255 = Voice Verification: Only set the
Alrm Rpt
prompt to 255 when using an optional
two-way voice verification module. When the
Alrm Rpt
prompt is set to 255, an Alarm event on a
Delay
Delay
point with 2, 3, 7, or 8 in Digit 2 sends an Alarm Report and begins the two-way voice verification process. Do not set the
Delay Alrm Rpt
prompt to 255 if a voice verification module is not connected to the control panel, because unexpected control panel operation results.
Duress Reports and A, B, C Key Reports are affected by Alarm Report Delay. These reports are sent immediately in all cases.
The Security Industry Association (SIA) recommends the Delay Alarm Report feature be enabled with the delay set to 15 seconds. Enter 15 at this prompt to comply with the SIA recommendation.
Press the [0] key to disable the
Delay Alrm Rpt
prompt for all points.
5 Cancel Rpt
6 Restoral Rpts
Default:
Selection:
No
No, Yes, Delay
0 No
1 Yes
2 Delay
Set the
Restoral Rpts
prompt to Yes to send
Restoral Reports to the receiver for all points. The system sends Restoral Reports when points return to normal (not faulted) after an Alarm or Trouble Report.
Set the
Restoral Rpts
prompt to No to prevent the
system from sending Restoral Reports for any point. Set the
Restoral Rpts
prompt to Delay to delay
sending Restoral Reports until bell time expires.
7 AC Fail Buzz/Rpt
Default:
Selection:
No Buzz, No Report No Buzz, No Report
Buzz, No Report Buzz, Report Buzz, Tag-Along Rpt No Buzz, Report No Buzz, Tag-Along Rpt
No Buzz No Report 0
Buzz, No Report 1
Default:
Selection:
Yes
Yes, No
0 No
1 Yes
Set the
Cancel Rpt
prompt to Yes to enable Cancel Report. If a user turns the system off after an alarm, but before bell time expires, a Cancel
Report follows
the Alarm Report. If the user turns the system off before
Rpt
prompt time expires, the control panel sends no
Delay Alrm
Alarm, Cancel, or Restoral Report for points programmed with a 2, 3, 7, or 8 in Digit 2 of the point code.
If you set the
Cancel Rpt
prompt to No, the control
panel does not send Cancel Reports.
Bosch Security Systems | 7/05 | 35114F
Buzz, Report 2
Buzz, Tag-Along Rpt 3
No Buzz Report 4
No Buzz, Tag-Along Rpt 5
The control panel monitors AC power. When AC power to terminals 1 and 2 is interrupted, the control panel waits 60 seconds. If AC power is not restored within 60 seconds, it provides the response programmed in
AC Fail Buzz/Rpt
.
When set to No Buzz, No Report the system only flashes the OK light at the keypad to indicate a system trouble. It does not sound the trouble tone or send a report to the receiver.
When set to Buzz, No Report the system flashes the OK light at the keypad to indicate a system trouble and sounds the trouble tone. No report is sent to the receiver.
2000 Series | Program Entry Guide | 3.0 Reports EN | 13
When set to Buzz, Report the system flashes the OK light at the keypad, sounds the trouble tone, and sends an AC Fail Report to the receiver.
When set to Buzz, Tag-Along Rpt the system flashes the OK light and sounds the trouble tone at the keypad after 60 seconds. It sends an AC Fail Report to the receiver as a tag along with all reports sent to the receiver until AC restores.
When set to No Buzz, Report the system flashes the OK light at the keypad and sends an AC Fail Report to the receiver.
When set to No Buzz, Tag-Along Rpt the system flashes the OK light. It sends an AC Fail Report to the receiver as a tag along with all reports sent to the receiver until AC restores.
8 Point User Flag
Default:
Selection:
No
Yes, No
0 No
1 Yes
Set this prompt to Yes to send a flag with each Modem II Report that tells the D6500 to convert point numbers to Bosch Security System’s D8112 style Zonex Format, and User ID numbers to D8112 type COMEX Format.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 3.0 Reports EN | 14
Notes:
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 4.0 Receiver EN | 15
4.0 Receiver
4.1 Modem Reports
1 Rcvr Format
Default:
Selection:
Modem
Modem, Pulse
0 Pulse
1 Modem
Set
Rcvr Format
You need firmware revision 8.00 or greater installed in your D6500 Receiver.
to Modem to transmit reports in Modem II format with its advanced reporting capabilities.
Table 2 shows the reports available. The D6500 line card ack tone table must contain “Modem II for D9112.” Refer to the 6500: Line Program Entry
Guide. Set
Rcvr Format
to the Section
to Pulse to transmit in 4x2 Pulse Format. Be sure to program codes for each report group. Refer
4.2 Pulse Report Groups.
Table 2: Modem II Reports Chart
Modem II Report Description
AC FAILURE
AC RESTORE
ALARM REPORT POINT 001 (-099)
ALARM REPORT RECENT CLOSING ID=001 POINT=001(24)
ALARM CROSS POINT 001 (-099)
BATTERY LOW
BATTERY MISSING
BATTERY RESTORE
CANCEL REPORT
CANCEL REPORT ID 001 (-008)
No AC power to system. Control panel runs on battery. AC Power is restored to normal. Alarm Report from Points 1 to 24 or from an A, B, C, key. Refer to Section 7.0 ABC Keys for
instructions on setting reports from the keys. If an alarm occurs within 2 minutes of a Closing event, the system sends an Alarm Recent
Close Report.
Alarm Report from Points 1 to 24 with point code for Cross or Partner point. The ALARM RECENT CLOSE message overrides the ALARM CROSS POINT message. The ALARM EXIT ERROR message does not apply to Cross, Partner, Double Knock, or Alarm
Verification points System battery is low.
System battery is disconnected. Battery must be missing for 60 seconds. Missing or low battery is restored. Cancel Report from keyswitch. Cancel Report with user ID for users 1 to 8.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 4.0 Receiver EN | 16
Table 2: continued
Modem II Report Description
CLOSING REPORT
CLOSING REPORT ID 001 (-008)
COMM FAIL PHONE (1-2)
COMM RESTORAL PHONE (1-2)
DURESS ID 008
EXIT ERROR 001 (-024)
FIRE ALARM POINT 001 (-099)
FIRE ALARM CROSS POINT 001 (-024)
MISSING ALARM POINT 001 (-024)
MISSING TROUBLE POINT 001 (-024)
OPENING REPORT
OPENING REPORT ID 001 (-008)
OPEN FROM ALARM
OPEN FROM ALARM ID 001 (-008)
PERM INST ARMED
PERM INST ARMED ID 001 (-008)
PERM DLAY ARMED
PERM DLAY ARMED ID 001 (-008)
Closing Report when passcode is not used. Refer to the Passcode Rquired prompt in Section
15.0 Passcodes. Using a Keyswitch or a remote programmer also sends this Closing Report
with no user ID. Closing Report with user ID for users 1 to 8.
Communication Failure event. Refer to Phone 1, Phone 2 in Section 2.0 Phone.
Successful communication after a Communication Failure event. Refer to Phone 1, Phone 2 in the Section 2.0 Phone.
Passcode 8 used to turn the system on, turn the system off, or to silence an alarm. Refer to the Code 8 = Duress prompt in Section 15.0 Passcodes.
When a point is faulted at the end of exit delay it generates an Exit Alarm. Exit Alarm Report from Points 1 to 24. Fire Alarm Report from Points 1 to 24.
Cross Point Fire Alarm Report from Points 1 to 24.
Missing Non-fire Controlled point, point is on (armed). Alarm response locally.
Missing Non-fire Controlled point, point is off (disarmed), or 24-hour Non-fire point. Trouble response locally.
Turning the system off with a keyswitch or a remote programmer sends this Opening Report with no User ID.
Opening Report with User ID for users 1 to 8.
Turning the system off after an alarm with a Keyswitch point or a remote programmer sends this Opening Report with no User ID.
Opening Report after an alarm with User ID for users 1 to 8.
Remote programmer used to turn the system Part On with No Delays, or user turned the system Part On with No Delays and no passcode required. Refer to the Passcode Rquired prompt in Section 15.0 Passcodes.
User with ID shown (1 to 8) turned the system Part On with No Delays.
Remote programmer used to turn the system Part On (with Delays), or user turned the system Part On with Delays and no passcode required. Refer to the Passcode Rquired prompt in Section 15.0 Passcodes.
User with ID shown (1 to 8) turned the system Part On (with Delays).
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 4.0 Receiver EN | 17
Table 2: continued
Modem II Report Description
POINT BYPASS POINT 001 (-024)
Point 1 to 24 bypassed. Points can be bypassed from the keypad or from a remote programmer. Bypass Reports are only sent when Opening and Closing Reports are enabled in Section 6.0 Open/Close.
RAM ACCESS OK
RAM ACCESS FAIL
Normal remote programmer session termination. Remote programmer made connection with control panel, but passcode was incorrect, or call
was not terminated with a Good-bye or Reset-Bye.
RESTORAL REPORT
Restoral Report from Points 1 to 24.
POINT 001 (-024)
RE-BOOT
Control panel reset with the standby pin (Refer to Installation Manual) or a remote programmer.
RF BATTERY LOW POINT
Low battery in RF sensor, keypad, or arming device.
001 (-024)
RF BATT RESTORE
Restored battery in RF sensor, keypad, or arming device.
POINT 001 (-024)
RF Rcvr Tamper SDI 7 (8)
RF Rcvr Tamper Restoral SDI 7 (8)
RF Rcvr Trouble Device 7 (8)
RF Rcvr Trbl Restoral Device 7 (8)
RF TAMPER TROUBLE
RF TAMPER RESTORAL
SERVICE START
SERVICE STOP
SWINGER BYPASS POINT 001 (-024)
Enclosure tamper from premises RF receiver (D208RF, D216RF). SDI number is the device address (7 or 8). Refer to Section 10.0 Address Configuration. Enclosure tamper restoral from premises RF receiver (D208RF, D216RF). SDI number is the device address (7 or 8). Refer to Section 10.0 Address Configuration.
Trouble from premises RF receiver (D208RF, D216RF) SDI number is the device address (7 or 8). Refer to Section 10.0 Address Configuration. Restoral from premises RF receiver (D208RF, D216RF) SDI number is the device address (7 or 8). Refer to Section 10.0 Address Configuration.
Tamper RF point, Controlled point, system off. Tamper restoral, RF point. Installer mode entered (Stand-by locked down, installer passcode entered). Installer mode exited. Points 1 to 24 bypassed automatically by the system after four alarms or troubles in one armed
or disarmed period. You can program the Swinger Bypass feature to activate after less than four alarms or troubles. Refer to Swinger Count prompt in Section 1.0 System Configuration.
Use the point code to program this feature by point. Refer to Section 11.0 Point Codes.
TEST REPORT
TROUBLE REPORT POINT
Automatic Test Timer Report. Trouble on Points 1 to 24, Fire and Non-fire combined.
001 (-024)
USR CODE TAMPER
WATCHDOG RESET
This report transmitted after six attempts to enter an invalid passcode. System automatically reset. Call Bosch Security Systems if reports persist.
0101 0101 0101
If you choose Modem Format, go to Section 5.0 Remote Programming. The prompts in the remainder of the Receiver Group have no meaning for the Modem Format.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 4.0 Receiver EN | 18
4.2 Pulse Report Groups
If you select the Pulse Format you need to set the report code for each report group. Pulse 4x2 reports consist of a four-digit account number, a one-digit report group code, and a one-digit point or User ID number.
For example, a control panel with the pulse, the
Fire Group
prompt set to 3, and Point 1 programmed as a Fire point would send the report shown in
Account Number
prompt set to 1213, the
Rcvr Format
prompt set to
Figure 1 for an alarm on Point 1.
Figure 1: Pulse Report Groups
1213 3 1
1
2
1 - Account number 2 - Report group 3 - Point, user
The Pulse Format allows for only one digit in the Point, User position. If you install more than eight points and report in Pulse Format, the control panel combines reports as shown in Table 3.
3
Table 3: Pulse Format
Point Number reported in Pulse
1 2 3 4 5 6 7 8
Format Point Number displayed at keypad 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Use the following Pulse Report Groups to designate Pulse Report Group codes for this installation.
Do not duplicate Pulse Report Group codes. You cannot distinguish reports from groups with duplicated codes.
The expanded reports available in Modem II format are not available in the Pulse Format.
2 Fire Group
Default:
Selection:
0
0 to 9, B to F 1 to 8 Fire alarm from Points 1 to 24. 9 or 0
Fire alarm from key A, B, or C. Refer to Section
7.0
ABC Keys.
There is no Pulse Format version of the Modem II Alarm Cross Point Report. The Cross Point
feature creates two point alarms. Refer to Section 11.0 Point Codes.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 4.0 Receiver EN | 19
3 Non-Fire Group
Default: Selection:
0 0 to 9, B to F
1 to 8 Non-Fire alarm from Points 1 to 24. 9 or 0 Non-Fire alarm from key A, B, or C.
Refer to Section
7.0
ABC Keys.
There are no Pulse Format versions of the Modem II Alarm recent Close, Alarm Cross Point, or Exit Alarm Reports. All occur as Alarm
Reports. The Cross Point feature creates two point alarms. Refer to Section 11.0 Point Codes.
4 Pt Trbl Group
Default: Selection:
1 to 8
0 0 to 9, B to F Trouble, Missing, Bypass, or Swinger
Bypass Reports from Fire and Non-Fire points combined.
Multiple trouble conditions can create duplicate Trouble Reports. For example, a point can send a trouble for a open sensor loop, then a trouble for missing.
5 Restoral Group
Default: Selection:
1 to 8
0 0 to 9, B to F Restoral on points 1 to 24, Fire and
Non-Fire combined.
6 Closing Group
Default: Selection:
0
0 0 to 9, B to F Closing Report when a passcode is not
required to turn system on (refer to
Passcode Rquired
prompt in Section
15.0 Passcodes) or a keyswitch is used.
1 to 8
Closing Report with User ID for users 1 to 8.
7 Opening Group
Default: Selection:
0
0 0 to 9, B to F Opening Report when keyswitch is
used, or Part On No Delay, or Part On with delay.
1 to 8
Opening Report with User ID for users 1 to 8.
8 Cancel Group
Default: Selection:
0
1 to 8
0 0 to 9, B to F
Cancel Report when keyswitch is used.
Cancel Report with User ID for users 1 to 8.
9 Sys Trbl Group
Default: Selection:
0 0 to 9, B to F
1 Reports an unsuccessful attempt to connect a
remote programmer.
2
Reports an unsuccessful attempt to connect a remote programmer.
3 The system automatically reset. Call Bosch
Security Systems if reports persist. 4 Not used. 5 Not used. 6 Reports missing battery. 7 Reports low battery. 8 No AC power to system. Control panel is
running on battery. 9 Communication Failure event for Phone 1. B Communication Failure event for Phone 2. C RF tamper (points or receiver). D RF low battery. E RF receiver 7 trouble. F RF receiver 8 trouble.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 4.0 Receiver EN | 20
10 Sys Res Group
Default: Selection:
0 0 to 9, B to F
1 Successful connection to a remote
programmer.
2 Not used.
3 Control panel reset with the stand-by switch
(refer to the Installation Guide) or a remote
programmer. 4 Not used. 5 Not used. 6 Not used. 7 Reports missing or low battery restored. 8 Restored AC power. 9 Communication Restoral event for Phone 1. B Communication Failure event for Phone 2. C RF tamper restore (points or receiver). D RF battery restore. E RF receiver 7 restoral. F RF receiver 8 restoral.
11 Duress Group
Default: Selection:
0 0 to 9, B to F
1 to 3 Not used. 4 This report transmitted after six
attempts to enter an invalid passcode.
5 Duress passcode entered at keypad.
Refer to
Code 8 = Duress
in Section
15.0 Passcodes.
7, 8 Not used.
12 Test Group
Default: Selection:
0 0 to 9, B to F
1 to 5 Not used. 6 Service stop. 7 Service start. 8 Test Report.
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 5.0 Remote Programming EN | 21
3 Answer Armed
5.0 Remote Programming
Use the prompts in this group to configure your system for programming with a Bosch Security Systems remote programmer.
1 RAM Passcode
Default: Selection:
999999 0 to 9, A to F
Six characters required. Remote programmers send this code to the control panel to gain access to the control panel.
2 RAM Phone
Default: Selection:
Blank 0 to 9, C, D, #, *, Blank
Enter up to nineteen characters for the control panel to dial to reach a remote programmer. The # and * characters are only dialed when the control panel is programmed for DTMF dialing. Refer to the
Dialing
prompt in Section 2.0 Phone. The control panel
DTMF
dials these characters just as if you pressed them on a telephone keypad.
If you program a # or * to disable call waiting, warn your customer that canceling call waiting service requires a change to their security system.
Programming C produces a 3-second dial delay. Programming D produces a 7-second dial tone wait. If
the control panel detects a dial tone before the 7­second delay expires, it continues dialing immediately.
0101 0101 0101
Remote programming initiated from the keypad ([2] key)
RAM Phone is blank: After you press [2] key, the control panel seizes the phone line and waits for the remote programmer handshake.
RAM Phone is programmed with a phone number: After you press the [2] key, the
control panel seizes the phone line, dials the RAM Phone number, and waits for the remote programmer handshake.
Default: Selection:
Set the number of rings you want the control panel to wait before seizing the phone line for a remote programming session when the system is All On (armed).
The control panel cannot seize the phone line when the system is All On (armed) if this prompt is set to 0 (zero).
0101 0101 0101
4 Answer Disarmed
Default: Selection:
Set the number of rings you want the control panel to wait before seizing the phone line for a remote programming session when the system is off (disarmed), Part On, or On with No Delay.
If this prompt is set to 0 (zero), the control panel cannot seize the phone line when the system is off (disarmed), Part On, or On with No Delay.
0101 0101 0101
5 Answer Machine
Default: Selection:
Set this prompt to Yes to enable the Answering Machine Bypass feature.
When
Answer Machine
must set the answering machine to pick up the phone on four or more rings. This feature does not work if the answering machine picks up the phone after one ring.
When
Answer Machine
control panel picks up the phone for a remote programming session if it detects the following events listed in Table 4.
0 0 to 15
When Answer Machine is programmed Yes, the entry in Answer Armed has no affect on the control panel’s operation.
0 0 to 15
When Answer Machine is programmed Yes, the entry in Answer Disarmed has no affect on the control panel’s operation.
0 0 to 15
is programmed Yes, you
is programmed Yes, the
Bosch Security Systems | 7/05 | 35114F
2000 Series | Program Entry Guide | 5.0 Remote Programming EN | 22
Table 4: Answer Machine Programmed Yes
Events at the Control Panel What you do from the Remote Programmer
1. Two rings. Dial the control panel phone number. Listen for two rings. Hang up.
2. 30 seconds with no rings. Wait 30 seconds.
3. Two rings. Re-dial the control panel phone number. Listen for two rings. Hang up.
4. 30 seconds with no rings. Wait 30 seconds.
5. Control panel picks up on
first ring.
Re-dial the control panel phone number. When the control panel picks up the phone, begin remote programming. If you are using a text keypad, SYSTEM PROGRAM, USING PHONE LINE
appears in the keypad display.
Bosch Security Systems | 7/05 | 35114F
Loading...
+ 50 hidden pages