The vb6 Portable Vibration Data Collector instrument is a
portable four channel, high resolution vibration data
collector. It is ergonomically designed and lightweight for all
day comfort. You can use this device for on-route as well as
off-route data collection.
The vb6 Portable Vibration Data Collector samples all four
channels simultaneously to provide recordings with up to
12,800 lines of resolution and up to 40 kHz Fmax. Our patented
adaptive settling algorithm and 6Pack recording system offer
quick, one-step data recording.
The data collector has plenty of storage and long battery life,
and is backed by a five year warranty.
The vb6 Portable Vibration Data Collector is one of Bently
Nevada hardware monitoring assets that work with System 1
Evolution software.
111M7155 Rev. E
The vb6 Portable Vibration Data Collector offers the
following features:
l Four channel simultaneous recordings
l 12,800 lines FFTresolution
l Supports triaxial sensors
l Supports 40 kHz Fmax
l 1 GB memory
l ≥ 95 dB dynamic range
l Supports voltage-output sensors
l Spectrum and waveform recordings
l Demodulation for early detection of rotating machinery
problems such as bearing faults
l Unique 6Pack recording system
vb6 Portable Vibration Data Collector
Datasheet111M7155 Rev. E
l User-defined recordings for temperature,
pressure, mass flow, force and power
l Cable test mode
l Option to add flex features such as
balancing and Remote Comms
l Upgradable Proflash system and free
firmware updates for 5 years
l Five-year warranty on the instrument
hardware
2/7
vb6 Portable Vibration Data Collector
Datasheet111M7155 Rev. E
Parameter Indication
Specifications
Sensors
Sensor input
Compatible
sensor types
AC coupled
range
DC coupled
ranges
Connectors
Analog to
digital
conversion
Sensor
excitation
current
Sensor
detection
Tachometer Sensor (Optional)
Sensor type
Laser sensor
range
Tachometer Input
Supported
sensor types
Power supply
to sensor
TTL pulse
rating
Keyphasor
thresholds
Speed range
Accuracy± 0.1 %
Four channels Simultaneous
sampling
Accelerometer, velocity, displacement,
current, 4 to 20 mA, voltage output
16 V peak-peak Allows for ± 8 V
sensor output swing (± 80 g)
0 V to 20 V, -10 V to 10 V, -20 V to 0 V
and readings from voltage output
sensors
1 x BNC (CH1) 1 x LEMO (CH2 / CH3 /
CH4)
Safety feature:Break-free inline
connector
24-bit ADC
0 mA or 2.2 mA (configurable), 24 V
maximum
2.2 mA required power for IEPE/ICP
type accelerometer
Warns if short circuit or not connected
Laser sensor with reflective tape
Sensor triggers on beam reflection
10 cm to 2 m nominal Range
depends on size of reflective tape
23 bandwidth options From 125 Hz to
1250 Hz Up to 16 kHz to 20 kHz
Up to 40 kHz & 3200 lines (1 channel)
Up to 20 kHz & 1600 lines (3 channel)
Spectrum and waveform for lowfrequency, high-frequency and
demodulation
Up to 6 kHz Fmax Orders-based
Order tracking
Order tracking
- Distortion
Tachometer required Mounted on
high-speed shaft
Less than -65 dB
Within 50% to 200% speed variation
during recording
Display and Communication
Display
Resolution & size 480 x 320 (HVGA), 5.7” Readable in
Supported
Languages
Communication
with PC
USB host port
Graphic Grayscale LCD LED
Backlight
direct sunlight
English, Chinese, French, German,
Japanese, Portuguese, Russian
and Spanish Firmware released in
English, translations will follow
USB or Ethernet
Use PROFLASH to upgrade
instrument firmware
USB 2.0, supplying 5V, 250mA
Save folders to USB flash drive
Battery and Charger
Battery typeCustom Lithium Ion pack, 7.4 V, 5 Ah
Operating
time
Charger type
Charge rate
10 hours Backlight on — 60 second
timeout
Internal charging, automatic control
External power pack 12 V DC, 3 A
output
3 A nominal 3 hours for complete
charge
Mechanical
Size9.9" W x 5.8" l x 2.4" H (252 x148 x60 mm)
Weight2.7 lb (1.2 kg) Including battery and strap
Environmental Limits
Operating
temperature
Storage
temperature
and humidity
Ruggedness
14 °F to 122 °F (-10 to 50 °C)
-4 °F to 140 °F (-20 to 60 °C), 95% RH
Up to 95 F (35 C), 85% RH if storage
exceeds 1 month
IP65 sealed 4’ (1.2 m) drop onto
concrete Procedure: 26 drops
following MIL-STD-810F-516.5-IV
4/7
vb6 Portable Vibration Data Collector
Datasheet111M7155 Rev. E
Hazardous Area Approvals
Compliance and
Certifications
FCC
This device complies with part 15 of the
FCC Rules. Operation is subject to the
following two conditions:
l This device may not cause harmful
interference.
l This device must accept any
interference received, including
interference that may cause
undesired operation.
EMC
EN 61326-1: 2012
EN 61326-2-3: 2012
EMC Directive 2014/30/EU
Electrical Safety
For the detailed listing of country and product
specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from
Bently.com.
CSA/NRTL/C (Approval
Option 01)
Class I, Division 2, Groups
A, B, C, D
EN 62133: 2002
LV Directive 2014/35/EU
RoHS
RoHS Directive 2011/65/EU
5/7
vb6 Portable Vibration Data Collector
Datasheet111M7155 Rev. E
Part NumberDescriptionQty
Ordering Information
For the detailed listing of country and product
specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from
Bently.com.
VB6-AA
NKST0553
108M4044AC power adapter1
DCCA0041DC car adapter1
108M3536
MVBX0250Instrument Reference guide1
vbx neck strap with Sensor
Keeper
SCOUT100 Series and vbSeries
Quick Start Guide
1
1
A: Agency Approval
01CSA
Basic Kit
We offer the vb6 Portable Vibration Data
Collector instrument in a basic kit with the
option to purchase the System 1 Evolution
software and license separately.
* Kit items below with multiple part
numbers listed have limited regional
availability due to certification
requirements.
Part NumberDescriptionQty
vb6 Portable Vibration Data
ACCL0547 or
200350 *
ACCL0561 or
200350 *
138M7748 Transducer cable, 4 ft. straight4
MAGF0104Accelerometer magnetic base4
CABB0560BNC to BNC cable, 1m1
CABU0213USB data transfer cable1
CBTB0278Triple BNC cable1
110M8172-012
PLUS0230
PLSA0241
PLAU0228
PLHK0245
PLEU0229Category C Power plug, Europe1
CBVB0552vbx instrument carry bag1
Collector four channel portable
data collector
Straight accelerometers3
Right-angle accelerometer or
straight accelerometer
LEMO-BNC TTL Tach/Keyphasor
cable
Category A power plug, USA /
Canada
Category D power plug, South
Africa / India
Category M power plug,
Australia / New Zealand / China
100M5828The vbSeries hard case
DTC70262The vbSeries dust cover
BATT0575
KTTC0331
108M4069
CBL50216
113M5529-01
Replacement battery pack, Li-Ion 7.4
V 5 Ah
Triaxial sensor kit
100 mV/g +/- 20%
Magnet
6 ft coiled cable, with breakaway
connector
Zone 2 and Class 1, Div 2 rating
Laser Tach powered by vb6 Portable
Vibration Data Collector
Five-meter laser Tach cable for
108M4069
Reflective tape One roll, 60 cm (23.7
in)
6/7
vb6 Portable Vibration Data Collector
Datasheet111M7155 Rev. E
Copyright 2020 Baker Hughes Company. All rights reserved.
Bently Nevada, vb Series, System 1, Keyphasor and Orbit Logo are registered trademarks of Bently Nevada, a Baker
Hughes Business, in the United States and other countries. The Baker Hughes logo is a trademark of Baker Hughes
Company. All other product and company names are trademarks of their respective holders. Use of the trademarks
does not imply any affiliation with or endorsement by the respective holders.
Baker Hughes provides this information on an “as is” basis for general information purposes. Baker Hughes does
not make any representation as to the accuracy or completeness of the information and makes no warranties of
any kind, specific, implied or oral, to the fullest extent permissible by law, including those of merchantability and
fitness for a particular purpose or use. Baker Hughes hereby disclaims any and all liability for any direct, indirect,
consequential or special damages, claims for lost profits, or third party claims arising from the use of the
information, whether a claim is asserted in contract, tort, or otherwise. Baker Hughes reserves the right to make
changes in specifications and features shown herein, or discontinue the product described at any time without
notice or obligation. Contact your Baker Hughes representative for the most current information.
The information contained in this document is the property of BakerHughes and its affiliates; and is subject to
change without prior notice. It is being supplied as a service to our customers and may not be altered or its content
repackaged without the express written consent of Baker Hughes. This product or associated products may be
covered by one or more patents. See Bently.com/legal.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1.775.782.3611 or 1.800.227.5514 (US only)
Bently.com
7/7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.