Beko BP109C, BP113H, BP109AC, BP112H, BP112C, BP109AH User manual
Portable
Air-conditioner
User Manual
BP109CBP112CBP112H
BP113HBP109ACBP109AH
ENFRITNL
Please read this user manual rst!
Dear Customer,
Thank you for preferring a Beko product. We hope that you get the best results
from your product which has been manufactured with high quality and state-ofthe-art technology. Therefore, please read this entire user manual and all other
accompanying documents carefully before using the product and keep it as a
reference for future use. If you handover the product to someone else, give the user
manual as well. Follow all warnings and information in the user manual.
Meanings of the symbols
Following symbols are used in the various section of this manual:
C
A
B
Important information or
useful hints about usage.
Warning for hazardous
situations with regard to life
and property.
Warning to actions that must
never perform.
Warning for electric shock.
Warning for hot surfaces.
Do not cover it.
This symbol shows that the
operation manual should be
read carefully.
This symbol shows that a
service personnel should be
handling this equipment with
reference to the installation
manual.
This symbol
shows that this
appliance used
a flammable
refrigerant. If
the refrigerant
is leaked and
exposed to an
external ignition
source, there is
a risk of fire.
This product has been produced in environmentally friendly, modern facilities
Complies with the WEEE Regulation.Does not contain PCB.
Please do not install or use your portable air conditioner before you
have carefully read this manual. Please keep this instruction manual
for an eventual product warranty and for future reference.
Warnng
Do not use means to accelerate the defrosting process or to clean,
other than those recommended by the manufacturer.
The appliance shall be stored in a room without continuously
operating ignition sources (for example: open flames, an operating
gas appliance or an operating electric heater).
Do not pierce or burn.
Be aware the refrigerants may not contain an odour.
Appliance shall be installed, operated and stored in a room with a
Specific information regarding appliances with R290 refrigerant gas.
•Thoroughly read all of the warnings.
•When defrosting and cleaning the appliance, do not use any tools
other than those recommended by the manufacturing company.
•The appliance must be placed in an area without any continuously
sources of ignition (for example: open flames, gas or electrical
appliances in operation).
•Do not puncture and do not burn.
•This appliance contains Y g (see rating label back of unit) of R290
refrigerant gas.
•R290 is a refrigerant gas that complies with the European directives
on the environment. Do not puncture any part of the refrigerant
circuit.
•If the appliance is installed, operated or stored in an unventilated
area, the room must be designed to prevent to the accumulation of
refrigerant leaks resulting in a risk of fire or explosion due to ignition
of the refrigerant caused by electric heaters, stoves, or other
sources of ignition.
•The appliance must be stored in such a way as to prevent
mechanical failure.
•Individuals who operate or work on the refrigerant circuit must have
the appropriate certification issued by an accredited organization
that ensures competence in handling refrigerants according to a
specific evaluation recognized by associations in the industry.
6 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
•Repairs must be performed based on the recommendation from the
manufacturing company. Maintenance and repairs that require the
assistance of other qualified personnel must be performed under
the supervision of an individual specified in the use of flammable
refrigerants.
General safety nstructon
1. The appliance is for indoor use only.
2. Do not use the unit on a socket under repairs or not installed
properly.
3. Do not use the unit, follow these precautions:
A: Near to source of fire.
B: An area where oil is likely to splash.
C: An area exposed to direct sunlight.
D: An area where water is likely to splash.
E: Near a bath, a laundry, a shower or a swimming pool.
4. Never insert your fingers, rods into the air outlet. Take special care
to warn children of these dangers.
5. Keep the unit upward while transport and storage, for the
compressor locates properly.
6. Before cleaning the air-conditioner, always turn off or disconnect
the power supply.
7. When moving the air-conditioner, always turn off and disconnect
the power supply, and move it slowly.
Portable Air-conditioner / User Manual
7 / 220 EN
1 Safety awareness
8. To avoid the possibility of fire disaster, the air-conditioner shall
not be covered.
9. All the air-conditioner sockets must comply with the local
electric safety requirements. If necessary, please check it for the
requirements.
10. Children should be supervised to ensure that they do not play with
the appliance.
11. If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
12. This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in
a safe way and understand the hazards involved. Children shall not
play with the appliance. Cleaning and user maintenance shall not
be made by children without supervision.
13. The appliance shall be installed in accordance with national wiring
regulations.
14. Details of type and rating of fuses: T, 250V AC, 2A or higher.
15. Contact authorized service technician for repair or maintenance of
this unit.
16. Do not pull, deform, or modify the power supply cord, or immerse
it in water. Pulling or misuse of the power supply cord can result in
damage to the unit and cause electrical shock.
17. Compliance with national gas regulations shall be observed.
8 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
18. Keep ventilation openings clear of obstruction.
19. Any person who is involved with working on or breaking into
arefrigerant circuit should hold a current valid certificate from
anindustry-accredited assessment authority, which authorizes
their competence to handle refrigerants safely in accordance with
an industry recognized assessment specification.
20. Servicing shall only be performed as recommended by the
equipment manufacturer. Maintenance and repair requiring the
assistance of other skilled personnel shall be carried out under
the supervision of the person competent in the use of flammable
refrigerants.
21. Do not operate or stop the unit by inserting or pulling out Die power
plug, it may cause electric shock or fire due to heat generation.
22. Unplug the unit if strange sounds, smell, or smoke comes from it.
23. This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been given
supervision or instruction concerning use of the appliance by
aperson responsible for their safety.
24. If the supply cord is damaged, it must be replaced by the
manufacturer or its agent or similarly qualified person in order to
avoid hazard.
25. The appliance shall state the insulation of a residual current device
(RCD) having rated residual operating current not exceeding
30mA.
Portable Air-conditioner / User Manual
9 / 220 EN
1 Safety awareness
26. This appliance is intended to be used in household and similar
applications such as
–
Staff kitchen areas in shops, offices and other working
environments;
–
farm houses;
–
by clients in hotels, motels and other residential type
environments;
–
bed and breakfast type environments;
The appliance shall state the insulation of a residual current
device (RCD) having rated residual operating current not
exceeding 30mA.
10 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
Note:
•If any parts damage, please contact the dealer or a
designated repair shop;
•In case of any damage, please turn off the air switch,
disconnect the power supply, and contact the dealer or
C
adesignated repair shop;
•In any case, the power cord shall be firmly grounded.
•To avoid the possibility of danger, if power cord is
damaged, please turn off the air switch and disconnect
the power supply. It must be replaced from the dealer or
adesignated repair shop.
Portable Air-conditioner / User Manual
11 / 220 EN
1 Safety awareness
Warnngs (for usng R290 refrgerant only)
1. General nstructons
1.1 Checks to the area
Prior to beginning work on systems containing flammable
refrigerants, safety checks are necessary to ensure that the risk
of ignition is minimized. For repair to the refrigerating system, the
following precautions shall be complied with prior to con-ducting
work on the system.
1.2 Work procedure
Work shall be undertaken under a controlled procedure so as to
minimize the risk of a flammable gas or vapour being present while
the work is being performed.
1.3 General work area
All maintenance staff and others working in the local area shall be
instructed on the nature of work being carried out. Work in confined
spaces shall be avoided. The area around the workspace shall be
sectioned off. Ensure that the conditions within the area have been
made safe by control of flammable material.
1.4 Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant
detector prior to and during work, to ensure the technician is
aware of potentially flammable atmospheres. Ensure that the leak
detection equipment being used is suitable for use with flammable
refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.
12 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
1.5 Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or
any associated parts, propriate fire extinguishing equipment shall
be available to hand. Have a dry powder or CO
fire extinguisher
2
adjacent to the charging area.
1.6 No ignition sources
No person carrying out work in relation to a refrigeration system
which involves exposing any pipe work that contains or has
contained flammable refrigerant shall use any sources of ignition
in such a manner that it may lead to the risk of fire or explosion.
Allpossible ignition sources, including cigarette smoking, should
be kept sufficiently far away from the site of installation, repairing,
removing and disposal, during which flammable refrigerant can
possibly be released to the surrounding space. Prior to work taking
place, the area around the equipment is to be surveyed to make sure
that there are no flammable hazards or ignition risks. “No Smoking”
signs shall be displayed.
1.7 Ventilated area
Ensure that the area is in the open or that it is adequately ventilated
before breaking into the system or conducting any hot work.
Adegree of ventilation shall continue during the period that the
work is carried out. The ventilation should safely disperse any
released refrigerant and preferably expel it externally into the
atmosphere.
Portable Air-conditioner / User Manual
13 / 220 EN
1 Safety awareness
1.8 Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit
for the purpose and to the correct specification. At all times the
manufacturer’s maintenance and service guidelines shall be followed.
If in doubt consult the manufacturer’s technical department for
assistance.The following checks shall be applied to installations using
flammable refrigerants: the charge size is in accordance with the
room size within which the refrigerant containing parts are installed;
the ventilation machinery and outlets are operating adequately and
are not obstructed; if an indirect refrigerating circuit is being used,
the secondary circuit shall be checked for the presence of refrigerant;
marking to the equipment continues to be visible and legible. Markings
and signs that are illegible shall be corrected; refrigeration pipe or
components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing
components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably
protected against being so corroded.
1.9 Checks to electrical devices
Repair and maintenance to electrical components shall include
initial safety checks and component inspection procedures. If afault
exists that could compromise safety, then no electrical supply
shall be connected to the circuit until it is satisfactorily dealt with.
If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties
are advised.
14 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
Initial safety checks shall include: that capacitors are discharged: this
shall be done in a safe manner to avoid possibility of sparking; that
there no live electrical components and wiring are exposed while
charging, recovering or purging the system; that there is continuity
of earth bonding.
2. Repars to sealed components
2.1 During repairs to sealed components, all electrical supplies shall
be disconnected from the equipment being worked upon prior
to any removal of sealed covers, etc. If it is absolutely necessary
to have an electrical supply to equipment during servicing, then
a permanently operating form of leak detection shall be located
at the most critical point to warn of a potentially hazardous
situation.
2.2 Particular attention shall be paid to the following to ensure that
by working on electrical components, the casing is not altered
in such a way that the level of protection is affected. This shall
include damage to cables, excessive number of connections,
terminals not made to original specification, damage to seals,
incorrect fitting of glands, etc. Ensure that apparatus is
mounted securely. Ensure that seals or sealing materials have
not degraded such that they no longer serve the purpose of
preventing the ingress of flammable atmospheres. Replacement
parts shall be in accordance with the manufacturer’s
specifications.
Portable Air-conditioner / User Manual
15 / 220 EN
1 Safety awareness
Note:
effectiveness of some types of leak detection equipment.
C
3. Repar to ntrnscally safe components
Do not apply any permanent inductive or capacitance loads to the
circuit without ensuring that this will not exceed the permissible
voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked
on while live in the presence of a flammable atmosphere. The test
apparatus shall be at the correct rating. Replace components only
with parts specified by the manufacturer. Other parts may result in
the ignition of refrigerant in the atmosphere from a leak.
4. Cablng
Check that cabling will not be subject to wear, corrosion, excessive
Intrinsically safe components do not have to be isolated
prior to working on them.
The use of silicon sealant may inhibit the
pressure, vibration, sharp edges or any other adverse environmental
effects. The check shall also take into account the effects of aging
or continual vibration from sources such as compressors or fans.
5. Detecton of flammable refrgerants
Under no circumstances shall potential sources of ignition be used
in the searching for or detection of refrigerant leaks. A halide torch
(or any other detector using a naked flame) shall not be used.
16 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
6. Leak detecton methods
The following leak detection methods are deemed acceptable
for systems containing flammable refrigerants. Electronic leak
detectors shall be used to detect flammable refrigerants, but
the sensitivity may not be adequate, or may need recalibration.
(Detection equipment shall be calibrated in a refrigerant-free
area.) Ensure that the detector is not a potential source of ignition
and is suitable for the refrigerant used. Leak detection equipment
shall be set at a percentage of the LFL of the refrigerant and shall
be calibrated to the refrigerant employed and the appropriate
percentage of gas (25% maximum) is confirmed. Leak detection
fluids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may
react with the refrigerant and corrode the copper pipe-work. If a
leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of
the refrigerant shall be recovered from the system, or isolated (by
means of shut off valves) in a part of the system remote from the
leak. Oxygen free nitrogen (OFN) shall then be purged through the
system both before and during the brazing process.
Portable Air-conditioner / User Manual
17 / 220 EN
1 Safety awareness
7. Removal and evacuaton
When breaking into the refrigerant circuit to make repairs – or for any
other purpose – con-ventional procedures shall be used.However,
it is important that best practice is followed since flammability is a
consideration. The following procedure shall be adhered to: remove
refrigerant; purge the circuit with inert gas; evacuate; purge again
with inert gas; open the circuit by cutting or brazing.The refrigerant
charge shall be recovered into the correct recovery cylinders. The
system shall be “flushed” with OFN to render the unit safe. This
process may need to be repeated several times.Compressed air or
oxygen shall not be used for this task. Flushing shall be achieved by
breaking the vacuum in the system with OFN and continuing to fill
until the working pressure is achieved, then venting to atmosphere,
and finally pulling down to a vacuum. This process shall be repeated
until no refrigerant is within the system. When the final OFN charge
is used, the system shall be vented down to atmospheric pressure to
enable work to take place.This operation is absolutely vital if brazing
operations on the pipework are to take place.
Ensure that the outlet for the vacuum pump is not close to any
ignition sources and there is ventilation available.
8. Chargng procedures
In addition to conventional charging procedures, the following
requirements shall be followed.
-
Ensure that contamination of different refrigerants does not occur
when using charging equipment. Hoses or lines shall be as short as
possible to minimise the amount of refrigerant contained in them.
18 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
-
Cylinders shall be kept upright.
-
Ensure that the refrigeration system is earthed prior to charging
the system with refrigerant.
-
Label the system when charging is complete (if not already).
-
Extreme care shall be taken not to overfill the refrigeration
system.
Prior to recharging the system it shall be pressure tested with OFN.
The system shall be leak tested on completion of charging but prior
to commissioning. A follow up leak test shall be carried out prior to
leaving the site.
9. Decommssonng
Before carrying out this procedure, it is essential that the technician
is completely familiar with the equipment and all its detail. It is
recommended good practice that all refrigerants are recovered
safely. Prior to the task being carried out, an oil and refrigerant
sample shall be taken in case analysis is required prior to re-use of
reclaimed refrigerant. It is essential that electrical power is available
before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that: mechanical
handling equipment is available, if required, for handling
refrigerant cylinders; all personal protective equipment is
available and being used correctly; the recovery process
is supervised at all times by a competent person; recovery
equipment and cylinders conform to the appropriate standards.
Portable Air-conditioner / User Manual
19 / 220 EN
1 Safety awareness
d) Pump down refrigerant system,if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant
can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before
recovery takes place.
g) Start the recovery machine and operate in accordance with
manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid
charge).
i) Do not exceed the maximum working pressure of the
cylinder,even temporarily.
j) When the cylinders have been filled correctly and the process
completed, make sure that the cylinders and the equipment
are removed from site promptly and all isolation valves on the
equipment are closed off.
k) Recovered refrigerant shall not be charged into another
refrigeration system unless it has been cleaned and checked.
10. Labellng
Equipment shall be labelled stating that it has been decommissioned and emptied of refrigerant.The label shall be dated
and signed.
Ensure that there are labels on the equipment stating the
equipment contains flammable refrigerant.
20 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
11. Recovery
When removing refrigerant from a system, either for servicing
or decommissioning, it is recommended good practice that all
refrigerants are removed safely. When transferring refrigerant
into cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of cylinders
for holding the total system charge are available. All cylinders to be
used are designated for the recovered refrigerant and labelled for
that refrigerant (i.e. special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure relief valve and associated
shut-off valves in good working order. Empty recovery cylinders are
evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be
suitable for the recovery of flammable refrigerants.In addition, a set
of calibrated weighing scales shall be available and in good working
order. Hoses shall be complete with leak-free disconnect couplings
and in good condition. Before using the recovery machine, check
that it is in satisfactory working order, has been properly maintained
and that any associated electrical components are sealed to prevent
ignition in the event of a refrigerant release. Consult manufacturer
if in doubt.
The recovered refrigerant shall be returned to the refrigerant
supplier in the correct recovery cylinder, and the relevant waste
transfer note arranged. Do not mix refrigerants in recovery units
and especially not in cylinders.
Portable Air-conditioner / User Manual
21 / 220 EN
1 Safety awareness
If compressors or compressor oils are to be removed, ensure that
they have been evacuated to an acceptable level to make certain
that flammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the
compressor to the suppliers. Only electric heating to the compressor
body shall be employed to accelerate this process.When oil is
drained from a system, it shall be carried out safely.
Note about fluornated gasses:
-
Fluorinated greenhouse gases are contained in
hermetically sealed equipment. For specific information
on the type, the amount and the CO
of the fluorinated greenhouse gas(on some models),
C
Competence of servce personnel
General
Special training additional to usual refrigerating equipment repair
procedures is required when equipment with flammable refrigerants
is affected.
please refer to the relevant label on the unit itself.
-
Installation, service, maintenance and repair of this unit
must be performed by a certified technician.
-
Product uninstallation and recycling must be performed
by a certified technician.
equivalent in tonnes
2
22 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
In many countries, this training is carried out by national training
organizations that are accredited to teach the relevant national
competency standards that may be set in legislation.
The achieved competence should be documented by a certificate.
Tranng
The training should include the substance of the following:
Information about the explosion potential of flammable refrigerants to
show that flammables may be dangerous when handled without care.
Information about potential ignition sources, especially those that
are not obvious, such as lighters, light switches, vacuum cleaners,
electric heaters.
Information about the different safety concepts:
Unventilated – (see Clause GG.2) Safety of the appliance does not
depend on ventilation of the housing. Switching off the appliance
or opening of the housing has no significant effect on the safety.
Nevertheless, it is possible that leaking refrigerant may accumulate
inside the enclosure and flammable atmosphere will be released
when the enclosure is opened.
Ventilated enclosure – (see Clause GG.4) Safety of the appliance
depends on ventilation of the housing. Switching off the appliance
or opening of the enclosure has a significant effect on the safety.
Care should be taken to ensure a sufficient ventilation before.
Portable Air-conditioner / User Manual
23 / 220 EN
1 Safety awareness
Ventilated room – (see Clause GG.5) Safety of the appliance depends
on the ventilation of the room. Switching off the appliance or opening
of the housing has no significant effect on the safety. The ventilation
of the room shall not be switched off during repair procedures.
Information about the concept of sealed components and sealed
enclosures according to IEC 60079-15:2010.
Information about the correct working procedures:
a) Commissioning
•
Ensure that the floor area is sufficient for the refrigerant charge
or that the ventilation duct is assembled in a correct manner.
•
Connect the pipes and carry out a leak test before charging with
refrigerant.
•
Check safety equipment before putting into service.
b) Maintenance
•
Portable equipment shall be repaired outside or in a workshop
specially equipped for servicing units with flammable refrigerants.
•
Ensure sufficient ventilation at the repair place.
•
Be aware that malfunction of the equipment may be caused by
refrigerant loss and a refrigerant leak is possible.
•
Discharge capacitors in a way that won’t cause any spark. The
standard procedure to short circuit the capacitor terminals usually
creates sparks.
•
Reassemble sealed enclosures accurately. If seals are worn,
replace them.
•
Check safety equipment before putting into service.
24 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
c) Repair
•
Portable equipment shall be repaired outside or in a workshop
specially equipped for servicing units with flammable refrigerants.
•
Ensure sufficient ventilation at the repair place.
•
Be aware that malfunction of the equipment may be caused by
refrigerant loss and a refrigerant leak is possible.
•
Discharge capacitors in a way that won’t cause any spark.
•
When brazing is required, the following procedures shall be
carried out in the right order:
-
Remove the refrigerant. If the recovery is not required by national
regulations, drain the refrigerant to the outside. Take care that
the drained refrigerant will not cause any danger. In doubt, one
person should guard the outlet. Take special care that drained
refrigerant will not float back into the building.
-
Evacuate the refrigerant circuit.
-
Purge the refrigerant circuit with nitrogen for 5 min.
-
Evacuate again.
-
Remove parts to be replaced by cutting, not by flame.
-
Purge the braze point with nitrogen during the brazing procedure.
-
Carry out a leak test before charging with refrigerant.
•
Reassemble sealed enclosures accurately. If seals are worn,
replace them.
•
Check safety equipment before putting into service.
Portable Air-conditioner / User Manual
25 / 220 EN
1 Safety awareness
d) Decommissioning
•
If the safety is affected when the equipment is putted out
of service, the refrigerant charge shall be removed before
decommissioning.
•
Ensure sufficient ventilation at the equipment location.
•
Be aware that malfunction of the equipment may be caused by
refrigerant loss and a refrigerant leak is possible.
•
Discharge capacitors in a way that won’t cause any spark.
•
Remove the refrigerant. If the recovery is not required by national
regulations, drain the refrigerant to the outside. Take care that
the drained refrigerant will not cause any danger. In doubt, one
person should guard the outlet. Take special care that drained
refrigerant will not float back into the building.
•
Evacuate the refrigerant circuit.
•
Purge the refrigerant circuit with nitrogen for 5 min.
•
Evacuate again.
•
Fill with nitrogen up to atmospheric pressure.
•
Put a label on the equipment that the refrigerant is removed.
e) Disposal
•
Ensure sufficient ventilation at the working place.
•
Remove the refrigerant. If the recovery is not required by national
regulations, drain the refrigerant to the outside. Take care that
the drained refrigerant will not cause any danger. In doubt, one
person should guard the outlet. Take special care that drained
refrigerant will not float back into the building.
26 / 220 EN
Portable Air-conditioner / User Manual
1 Safety awareness
•
Evacuate the refrigerant circuit.
•
Purge the refrigerant circuit with nitrogen for 5 min.
•
Evacuate again.
•
Cut out the compressor and drain the oil.
Transportaton, markng and storage for unts that employ
flammable refrgerants
Transport of equpment contanng flammable refrgerants
Attention is drawn to the fact that additional transportation
regulations may exist with respect to equipment containing
flammable gas. The maximum number of pieces of equipment or
the configuration of the equipment, permitted to be transported
together will be determined by the applicable transport regulations.
Markng of equpment usng sgns
Signs for similar appliances used in a work area generally are
addressed by local regulations and give the minimum requirements
for the provision of safety and/or health signs for a work location.
All required signs are to be maintained and employers should ensure
that employees receive suitable and sufficient instruction and
training on the meaning of appropriate safety signs and the actions
that need to be taken in connection with these signs.
The effectiveness of signs should not be diminished by too many
signs being placed together.
Any pictograms used should be as simple as possible and contain
only essential details.
Portable Air-conditioner / User Manual
27 / 220 EN
1 Safety awareness
Dsposal of equpment usng flammable refrgerants
See national regulations.
Storage of equpment/applances
The storage of equipment should be in accordance with the
manufacturer’s instructions.
Storage of packed (unsold) equipment
Storage package protection should be constructed such that
mechanical damage to the equipment inside the package will not
cause a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted to be
stored together will be determined by local regulations.
After unpacking, please check whether the above-mentioned accessories are included, and check their
purposes in the installation introduction in this manual.
30 / 220 EN
Portable Air-conditioner / User Manual
Loading...
+ 190 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.