1.2.1Delivery state ..................................................................................................................... 6
1.2.2Operator's obligation to exercise diligence ........................................................................ 6
1.2.3Description of instructions.................................................................................................. 7
1.3Documentation issue status ..............................................................................................................7
1.4Version history of the TwinSAFE product..........................................................................................8
2 System description ...................................................................................................................................9
4.7Service life .......................................................................................................................................45
This description is only intended for the use of trained specialists in control and automation engineering who
are familiar with the applicable national standards.
It is essential that the following notes and explanations are followed when installing and commissioning
these components.
The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Origin of the document
This original documentation is written in German. All other languages are derived from the German original.
Currentness
Please check whether you are using the current and valid version of this document. The current version can
be downloaded from the Beckhoff homepage at http://www.beckhoff.com/english/download/twinsafe.htm.
In case of doubt, please contact Technical Support [}50].
Product features
Only the product features specified in the current user documentation are valid. Further information given on
the product pages of the Beckhoff homepage, in emails or in other publications is not authoritative.
Disclaimer
The documentation has been prepared with care. The products described are subject to cyclical revision. For
that reason the documentation is not in every case checked for consistency with performance data,
standards or other characteristics. We reserve the right to revise and change the documentation at any time
and without prior announcement. No claims for the modification of products that have already been supplied
may be made on the basis of the data, diagrams and descriptions in this documentation.
Trademarks
Beckhoff®, TwinCAT®, EtherCAT®, EtherCATG®, EtherCATG10®, EtherCATP®, SafetyoverEtherCAT®,
TwinSAFE®, XFC®, XTS® and XPlanar® are registered trademarks of and licensed by Beckhoff Automation
GmbH. Other designations used in this publication may be trademarks whose use by third parties for their
own purposes could violate the rights of the owners.
Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and
patents: EP1590927, EP1789857, EP1456722, EP2137893, DE102015105702 with corresponding
applications or registrations in various other countries.
EP29185Version: 1.1.0
Foreword
EtherCAT® and Safety over EtherCAT® are registered trademarks and patented technologies, licensed by
Beckhoff Automation GmbH, Germany.
In addition, the general delivery conditions of the company Beckhoff Automation GmbH & Co. KG apply.
1.2Safety instructions
1.2.1Delivery state
All the components are supplied in particular hardware and software configurations appropriate for the
application. Modifications to hardware or software configurations other than those described in the
documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
1.2.2Operator's obligation to exercise diligence
The operator must ensure that
• the TwinSAFE products are only used as intended (see chapter Product description);
• the TwinSAFE products are only operated in sound condition and in working order.
• the TwinSAFE products are operated only by suitably qualified and authorized personnel.
• the personnel is instructed regularly about relevant occupational safety and environmental protection
aspects, and is familiar with the operating instructions and in particular the safety instructions contained
herein.
• the operating instructions are in good condition and complete, and always available for reference at the
location where the TwinSAFE products are used.
• none of the safety and warning notes attached to the TwinSAFE products are removed, and all notes
remain legible.
EP29186Version: 1.1.0
1.2.3Description of instructions
In these operating instructions the following instructions are used.
These instructions must be read carefully and followed without fail!
DANGER
Serious risk of injury!
Failure to follow this safety instruction directly endangers the life and health of persons.
WARNING
Risk of injury!
Failure to follow this safety instruction endangers the life and health of persons.
CAUTION
Personal injuries!
Failure to follow this safety instruction can lead to injuries to persons.
NOTE
Damage to the environment/equipment or data loss
Failure to follow this instruction can lead to environmental damage, equipment damage or data loss.
Foreword
Tip or pointer
This symbol indicates information that contributes to better understanding.
1.3Documentation issue status
Version Comment
1.1.0• Chapter Decommissioning updated
1.0.0• First release
0.6• Safety parameters updated
• EN81 notes removed
• Maximum temperature added
0.5• Data for the functional overcurrent cut-off added
0.4• Technical data updated
0.3• Note on commissioning test added
• Note on safe output added
0.2• Revision following review
• EN81 Notes on TwinSAFE EtherCAT Boxes adapted
• Derating information added
0.1• First draft
EP29187Version: 1.1.0
Foreword
1.4Version history of the TwinSAFE product
This version history lists the software and hardware version numbers. A description of the changes
compared to the previous version is also given.
Updated hardware and software
TwinSAFE products are subject to a cyclical revision. We reserve the right to revise and change the
TwinSAFE products at any time and without prior notice.
No claims for changes to products already delivered can be asserted from these hardware and/or
software changes.
A description of how a firmware (software) update can be performed can be found in chapter Firmwareupdate of TwinSAFE products [}46].
DateSoftware versionHardware versionModifications
2019-11-140100First release of the EP2918-0032
EP29188Version: 1.1.0
System description
2System description
2.1EtherCAT Box Modules
The EtherCAT system has been extended with EtherCAT Box modules with protection class IP67. Through
the integrated EtherCAT interface the modules can be connected directly to an EtherCAT network without an
additional Coupler Box. The high-performance of EtherCAT is thus maintained into each module.
The extremely low dimensions of only e.g.126x30x26.5mm are identical to those of the Fieldbus Box
extension modules. They are thus particularly suitable for use where space is at a premium. The small mass
of the EtherCAT modules facilitates applications with mobile I/O interface (e.g. on a robot arm). The
EtherCAT connection is established via screened M8 connectors.
Fig.1: EtherCAT Box modules extend the EtherCAT system with IP67 protection
The robust design of the EtherCAT Box modules enables them to be used directly at the machine. Control
cabinets and terminal boxes are now no longer required. The modules are fully sealed and therefore ideally
prepared for wet, dirty or dusty conditions.
Pre-assembled cables significantly simplify EtherCAT and signal wiring. Very few wiring errors are made, so
that commissioning is optimized. In addition to pre-assembled EtherCAT, power and sensor cables, fieldconfigurable connectors and cables are available for maximum flexibility. Depending on the application, the
sensors and actuators are connected through M8 or M12 connectors.
Basic EtherCAT documentation
You will find a detailed description of the EtherCAT system in the Basic System Documentation for
EtherCAT, which is available for download from our website (www.beckhoff.com) under Downloads.
EP29189Version: 1.1.0
Product description
3Product description
3.1EP2918-0032
The EP2918-0032 is an EtherCAT Box with digital outputs for 24VDC actuators. The EtherCAT Box has 8
fail-safe outputs, each with a maximum output current of 2A (at 24VDC).
The EP2918-0032 meets the requirements of the following standards:
◦ EN 61508:2010 (SIL 3)
◦ EN 62061:2005/A2:2015 (SIL CL 3)
◦ EN ISO 13849-1:2015 (Cat. 4, PL e)
Fig.2: EP2918-0032 – TwinSAFE EtherCAT Box with 8 fail-safe outputs
The TwinSAFE EtherCAT Box has the usual design of an EtherCAT Box with a width of 60mm and a height
of 150mm.
EP291810Version: 1.1.0
Product description
3.2Intended use
WARNING
Caution - Risk of injury!
TwinSAFE components may only be used for the purposes described below!
The TwinSAFE EtherCAT Box expands the application range of the Beckhoff system with functions that
enable it to be used for machine safety applications. The TwinSAFE Boxes are designed for machine safety
functions and directly associated industrial automation tasks. They are therefore only approved for
applications with a defined fail-safe state. This safe state is the wattless state. Fail-safety according to the
relevant standards is required.
The TwinSAFE EtherCAT Box allows the connection of:
24VDC actuators such as
• contactors, protective door switches with tumblers, valves etc.
WARNING
The fail-safe principle!
The basic rule for a safety system such as TwinSAFE is that failure of a part, a system component or the
overall system must never lead to a dangerous condition. The safe state is always the switched off and wattless state.
WARNING
Power supply from SELV/PELV power supply unit!
The TwinSAFE components must be supplied with 24VDC by an SELV/PELV power supply unit with an output voltage limit U
of 36VDC. Failure to observe this can result in a loss of safety.
max
WARNING
System limits
The TÜV SÜD certificate applies to this TwinSAFE component, the function blocks available in it, the documentation and the engineering tool. TwinCAT 3.1 and the TwinSAFE Loader are permitted as engineering
tools. Any deviations from these procedures or tools, particularly externally generated xml files for TwinSAFE import or externally generated automatic project creation procedures, are not covered by the certificate.
WARNING
Commissioning test
Before the EP2918-0032 can be used for the safety task, the user must carry out a commissioning test so
that sensor and actuator wiring faults can be ruled out.
CAUTION
Follow the machinery directive!
The TwinSAFE components may only be used in machines as defined in the machinery directive.
CAUTION
Ensure traceability!
The buyer has to ensure the traceability of the device via the serial number.
EP291811Version: 1.1.0
Product description
3.3Technical data
Product designationEP2918-0032
FieldbusEtherCAT
Number of outputs8
Connection of the outputsM12
Status display8 (one green LED per output), 5 diagnostic LEDs, 2 LEDs for Us/Up, 2 LEDs
Response time
(read input/write to E-bus)
Watchdog timeadjustable from 2ms to 60s
Fault response time≤ watchdog time
Cable length between actuator and EtherCAT BoxUnshielded: 100m max. (at 0.75 or 1 mm²)
Safe outputsmax. 2.0A (at 24VDC) per channel
Outputs (functional)Functional overcurrent cut-off of the output driver:
Input process image6 bytes (via FSoE if using the default project)
Output process image7 bytes (via FSoE if using the default project)
EP2918 supply voltage24VDC (–15%/+20%)
Current consumption US
(8 output channels switched)
Current consumption U
(8 output channels switched, plus load current)
Power dissipation of the EtherCAT Boxtypically 4.9watts
Electrical isolation (between the channels)no
Electrical isolation (between the channels and Ether-
CAT)
Insulation voltage (between the channels and Ether-
CAT, under common operating conditions)
Dimensions (WxHxD)60(+0.5)mmx150(+0.5)mmx26.5mm
Housing materialPBT+PET (Valox 855)
Sealing compoundPolyurethane PU552L
Weightapprox.470g
Permissible ambient temperature
(operation)
Permissible ambient temperature
(transport/storage)
Permissible air pressure
(operation/storage/transport)
Inadmissible operating conditionsTwinSAFE EtherCAT boxes must not be used under the following conditions:
EMC tests according toEN61326-3-1:2017(SIL3)
Vibration resistanceconforms to EN60068-2-6
Shock resistanceconforms to EN60068-2-27
Protection class (when screwed together)IP67 (according to EN 60529)
Correct installation positionvariable
ApprovalsCE, TÜV SÜD
P
for EtherCAT Link/Act
typically: 4ms (in the default setting without local TwinSAFE logic),
maximum: see fault response time
Shielded: 100m max. (at 0.75 or 1 mm²)
Diagnostic thresholds:
>4.7V -> high signal is detected
<1.0V -> low signal is detected
typically between 2.9A and 6.3A
(this overcurrent cut-off is implemented purely functionally and cannot be
loaded from a safety aspect)
8 channels occupied: typically 120mA
0 channels occupied: typically 80mA
(provide a 4A fuse)
750hPa to 1100hPa
(this is equivalent to an altitude of approx. -690m to 2450m above sea level
assuming an international standard atmosphere)
• under the influence of ionizing radiation (exceeding the natural
background radiation)
• in corrosive environments
IEC61131-2:2017 chapter 6.2 and 7 (ZoneB)
5 Hz ≤ f < 8.4 Hz (3.5 mm peak)
8.4 Hz ≤ f < 150 Hz (10 m/s2 peak)
15g with pulse duration 11ms in all three axes
DC
EP291812Version: 1.1.0
Product description
Derating table for altitudes above 2000m
The derating table (table 8) from the IEC61131-2:2017 standard can be referred to for the use of the
TwinSAFE components above the specified maximum altitude.
Altitude in mDerating factor for the temperature
0 to 2000
2
1.0
1
30000.9
40000.8
50000.7
Note: Linear interpolation is permissible between the altitudes
1)
Ambient temperature of the device at an altitude of 2000m
2)
The air pressure and air density increase as the altitude decreases. Therefore the derating factor for 0 to
2000 m (1.0) is used for altitudes below sea level.
Calculation example
In the following example the calculation is performed for a TwinSAFE component at an operating altitude of
4000m.
Permissible ambient temperature up to 2000 m above sea level = 55°C
Permissible ambient temperature up to 4000m above sea level = 55°C * 0.8 = 44°C
CAUTION
Compliance with the temperature limits
The TwinSAFE component has a maximum internal temperature at which a switch-off takes place. This is
designed for the maximum permissible ambient temperature. If the derating factor for the temperature for
higher altitudes is used, the user is solely responsible for ensuring that the calculated maximum ambient
temperature is complied with.
3.4Safety parameters
Characteristic numbersEP2918-0032
Lifetime [a]20
Proof test interval [a]not required
PFH
D
4.16E-09
PFD2.00E-05
MTTF
D
high
DChigh
Performance levelPL e
Category4
HFT1
Element classification
1)
Special proof tests throughout the service life of the EtherCAT Box are not required.
2)
Classification according to IEC 61508-2:2010 (see chapters 7.4.4.1.2 and 7.4.4.1.3)
2
Type B
1
The EP2918-0032 EtherCAT Box can be used for safety-related applications according to IEC61508:2010
up to SIL3 and ENISO13849-1:2015 up to PLe(Cat4).
Further information on calculating or estimating the MTTFD value from the PFHD value can be found in the
TwinSAFE Application Guide or in ENISO13849-1:2015, TableK.1.
In terms of safety-related parameters, the Safety-over-EtherCAT communication is already considered with
1% of SIL3 according to the protocol specification.
EP291813Version: 1.1.0
Product description
3.5Safe output
The safe outputs are implemented as a single channel per module. It is essential to pay attention to the
following note if two or more outputs run in a common sheathed cable.
DANGER
Clocked signals inside a sheathed cable
If clocked signals from different modules are used inside a single sheathed cable, then a module error such
as a cross-circuit or external power supply must lead to the switch-off of all of these modules. This is
achieved by setting the Module Fault Link active parameter for all modules involved. This parameter is set
to TRUE by default.
3.6Dimensions
Fig.3: EP2918 Dimensions
The EP2918-0032 module has the following dimensions:
Width60.0(+0.5)mm
Height150.0(+0.5)mm
Depth26.5 mm
When fully wired, the connected cables increase the total depth of the module.
EP291814Version: 1.1.0
Operation
4Operation
4.1Environmental conditions
Please ensure that the TwinSAFE Boxes are only transported, stored and operated under the specified
conditions (see technical data)!
WARNING
Risk of injury!
The TwinSAFE EtherCAT boxes must not be used under the following conditions.
• under the influence of ionizing radiation (that exceeds the level of the natural environmental radiation)
• in corrosive environments
NOTE
Electromagnetic compatibility
The TwinSAFE components comply with the current standards on electromagnetic compatibility with regard
to spurious radiation and immunity to interference in particular.
However, in cases where devices such as mobile phones, radio equipment, transmitters or high-frequency
systems that exceed the interference emissions limits specified in the standards are operated near TwinSAFE components, the function of the TwinSAFE components may be impaired.
4.2Installation
4.2.1Fixing
NOTE
Protect connectors against soiling!
Protect all connections from contamination during installation and operation of the modules! Protection
class IP67 is only guaranteed if all cables and plug connectors are connected, and unused connections are
protected with the appropriate cover plugs!
Connector sets see catalog.
• Modules with narrow housing are installed with two M3 screws.
• Modules with wide housing are installed with two M3 screws in the mounting holes in the corners or
two M4 screws in the central fastening holes (see also chapter Power connection and grounding).
• The bolts must be longer than 15mm. The fastening holes in the modules have no thread.
• Note when mounting that the overall height is increased further by the fieldbus connections.
4.2.2Connection
4.2.2.1Nut torque for connectors
M8 connector
We recommend fastening the M8 connector with a torque of 0.4Nm. A max. torque of 0.5Nm is also
permissible if using a torque screwdriver (Beckhoff article ZB8800).
EP291815Version: 1.1.0
Operation
Fig.4: EtherCAT Box with M8 plug connectors
M12 connector
We recommend fastening the M12 connector with a torque of 0.6Nm.
Fig.5: EtherCAT Box with M8 and M12 connectors
7/8" plug connectors
We recommend fastening the 7/8" plug connectors with a torque of 1.5Nm.
Fig.6: 7/8" plug connectors
Torque wrench
Fig.7: Torque wrench ZB8801
NOTE
Ensure the proper torque is used
Use torque wrenches available from Beckhoff to tighten the connectors (see accessories)!
EP291816Version: 1.1.0
Operation
4.2.2.2EtherCAT connection
The EtherCAT Box (EPxxxx) has two M8 connectors marked green for the incoming and outgoing EtherCAT
connection.
Fig.8: EtherCAT connection 30 mm housing M8
Connection
There are various different standards for the assignment and colors of connectors and cables for EtherCAT.
For connecting EtherCAT devices only Ethernet cables that meet the requirements of at least category 5
(CAT5) according to EN 50173 or ISO/IEC 11801 should be used.
Wiring recommendations
Detailed recommendations for EtherCAT wiring can be found in the documentation "Design recommendations for EtherCAT/Ethernet infrastructure", which is available for download from www.Beck-hoff.de.
EtherCAT uses four cable wires for signal transmission. Due to automatic cable detection (auto-crossing)
symmetric (1:1) or cross-over cables can be used between EtherCAT devices from BECKHOFF.
4.2.2.4Power connection and grounding
This chapter provides you with basic information about the power supply and grounding of the EP2918-0032
TwinSAFE EtherCAT Box. In particular, please note that the General information on connecting thefunctional earth only serves as an example.
Supply voltages (power connection)
The supply and distribution of the supply voltages takes place via the connections:
• Us/Up IN for feeding in the supply voltages
• Us/Up OUT for distribution of the supply voltages.
EP291817Version: 1.1.0
Operation
Both connections have a 7/8" thread and are located to the left (Us/Up IN) and right (Us/Up OUT) of the
TwinSAFE EtherCAT Box (see figure: EP2918 - power connection).
Information: An overview of pin assignment for the two connections can be found later in this chapter.
General information for connecting the functional earth
The grounding lugs of the EP2918 are internally connected to the safe outputs (pin 5 of the M12
connections).
To provide functional earthing , if possible the connection should:
• have a large surface
• have low resistance and
• be permanent.
In order to establish a permanent connection, all operating states of the machine, such as vibrations, must
be taken into account.
The connection can be established using the following two methods:
1. via a bolted connection from the TwinSAFE-EtherCAT Box to the machine bed
2. through a ring terminal (hole dia. 4.3 mm) with cable connection to the functional earth
A grounding lug is available at the upper and lower mounting points (hole dia. 5 mm for M4 thread) on the
housing.
NOTE
Connecting the functional earth
The functional earth connection should have low resistance and a large surface.
EP2918 – Power connection
ContactVoltage
1GND Up
2GND Us
3
7/8" connector pin assignment
Connecting the functional earth
4Control voltage Us, +24VDC (provide a 4A fuse)
5Peripheral voltage Up, +24VDC (provide a 16A fuse)
The contacts of the 7/8" plug connectors can conduct a maximum current of 16A.
Two LEDs indicate the status of the supply voltages.
EP291818Version: 1.1.0
Operation
NOTE
Do not confuse the power port with EtherCAT port!
Never connect the power cables (M8, 24VDC) to the green-marked EtherCAT sockets of the EtherCAT Box
Modules. This can cause the destruction of the modules!
Control voltage Us
The fieldbus and the processor logic are supplied from the 24VDC control voltage Us. The control voltage is
electrically isolated from the fieldbus circuitry.
Peripheral voltage Up
The peripheral voltage Up supplies the digital safe outputs.
Redirection of the supply voltages
The power IN and OUT connections are bridged in the module. Hence, the supply voltages Us and Up can
be passed from EtherCATBox to EtherCATBox in a simple manner.
CAUTION
Note the maximum current!
Also ensure when forwarding the supply voltages Us and Up that the maximum permissible current of 16A
for each contact of the 7/8" plug connector is not exceeded!
EP291819Version: 1.1.0
Operation
4.2.2.5Signal connection for outputs
The EP2918 has 8 fail-safe outputs, each with a maximum output current of 2.0A (at 24VDC).
Fig.9: EP2918 – safe outputs 1 to 8
Fig.10: PinOut safe output
EP291820Version: 1.1.0
M12 connectionContactChannelSignal
11-not connected
2not connected
31GND Up
4Output 1
5-Functional earth FE
21-not connected
2not connected
32GND Up
4Output 2
5-Functional earth FE
31-not connected
2not connected
33GND Up
4Output 3
5-Functional earth FE
41-not connected
2not connected
34GND Up
4Output 4
5-Functional earth FE
51-not connected
2not connected
35GND Up
4Output 5
5-Functional earth FE
61-not connected
2not connected
36GND Up
4Output 6
5-Functional earth FE
71-not connected
2not connected
37GND Up
4Output 7
5-Functional earth FE
81-not connected
2not connected
38GND Up
4Output 8
5-Functional earth FE
Operation
Functional earth
The functional earth on pin 5 of the M12 connections of the outputs is internally connected to the
grounding lugs of the EtherCAT Box.
4.2.2.6Overvoltage protection
If protection against overvoltage is necessary in your system, provide a protective circuit (surge filter) against
overvoltage for the power supply to the EtherCAT Box.
4.2.3EP2918 temperature measurement
The temperature measurement of the TwinSAFE EtherCAT Box consists of a single EtherCAT Box that is
wired with corresponding supply and communication cables. The inputs and/or outputs of the EtherCAT Box
are switched on for the test.
The maximum permissible ambient temperature of 60°C was checked with the example configuration described above. Impaired convection or an unfavorable location near heat sources may have a negative effect on the internal heating of the TwinSAFE components.
The key parameter is always the maximum permitted internally measured temperature of 95°C, above
which the TwinSAFE components switch to safe state and report an error. The internal temperature can be
read from the TwinSAFE components via CoE.
4.2.4Signal cables
Permitted cable length
Fig.11: EP2918 signal cables
When connecting a single switching contact via its own continuous cabling (or via a sheathed cable), the
maximum permitted cable length with test pulses activated is 100 meters.
The use of contact points, connectors or additional switching contacts in the cabling reduces the maximum
propagation.
EP291822Version: 1.1.0
Operation
Cable routing
Fig.12: Cable routing
NOTE
Route the signal cable separately
The signal cable must be routed separately from potential sources of interference, such as motor supply cables, 230 VAC power cables etc.!
Interference caused by cables routed in parallel can influence the signal form of the test pulses and thus
cause diagnostic messages (e.g. sensor errors or OpenLoad errors).
D: Distance between the cable ducts should be as large as possible
blue arrows: signal line
red arrows: potential source of interference
The common routing of signals together with other clocked signals in a common cable also reduces the
maximum propagation, since crosstalk of the signals can occur over long cable lengths and cause diagnostic
messages.
EP291823Version: 1.1.0
Operation
4.3Configuration of the EP2918 in TwinCAT
CAUTION
Do not change CoE objects!
Do not change any of the CoE objects in the TwinSAFE terminals. Any modifications (e.g. via TwinCAT) of
the CoE objects will permanently set the terminals to the Fail-Stop state or lead to unexpected behavior of
the terminals!
4.3.1Adding an EtherCAT device
See TwinCAT automation software documentation.
4.3.2Inserting an EP2918
An EP2918 is inserted in exactly the same way as any other Beckhoff EtherCAT Box. Open the TwinSAFE
Fieldbus Boxes item in the list and select the EP2918.
Fig.13: Inserting an EP2918
4.3.3Using the integrated TwinSAFE Logic functions
On delivery, the EP2918 behaves like a safe TwinSAFE I/O slave, which can be used as an alias device
within a TwinSAFE Logic, e.g. EL6910.
Alternatively, the local logic function of the EP2918 can be used. To this end please create a TwinSAFE
project in the Safety Editor and select the EP2918 as the target system. Further information on creating a
project can be found in the EL6910 documentation and the description of the function blocks under http://www.beckhoff.de/german/download/twinsafe.htm.
In order to be able to use the EP2918 again as a safe TwinSAFE I/O slave, please delete the logic, the
mapping and the parameter data on the EtherCAT Box and switch the voltage off and on again.
EP291824Version: 1.1.0
Fig.14: EP2918 - Delete Project Data
4.3.4Project design limits of the EP2918
Project design limits
The maximum project design size of the EP2918 is limited by the available memory. This is managed dynamically. The values specified in the following table are therefore only guide values and
may differ from the actual values, depending on the safety project.
Operation
NOTE
Execution time of the logic function
Compared to the EL6910 with an identical logic program, the execution time will be typically longer as the
safe I/O signals have to be processed in addition. Accordingly this also affects the processing of the I/O signals, as they can only be evaluated less frequently as the size of the project increases.
Process image sizemax. 1486bytes per data direction
(Max. memory size 0x1E00 for 3 buffers, i.e. with the same size of
input and output process data a maximum size of 1280 bytes per
data direction results. Only even-numbered start addresses are
possible, therefore padding bytes may have to be included.)
TwinSAFE connectionsmaximum 212 (Maximum 255 CRCs in total - 1 CRC is required for
a TwinSAFE connection with 1 or 2 bytes of safe data.)
Safe data per TwinSAFE connection maximum 126bytes (telegram length 255bytes)
TwinSAFE function blocksmaximum 512 (For using ESTOP function blocks with complete
input and output mapping. Other function blocks may lead to a
lower maximum number.)
TwinSAFE groupsmaximum 128
TwinSAFE usermaximum 40
Standard PLC inputsdynamic (memory-dependent), max. 1483bytes
Standard PLC outputsdynamic (memory-dependent), max. 1483bytes
NOTE
Project planning
TwinCAT 3.1 Build 4022.28 or later is required for the use of the internal logic functions. If the EP2918 is
used as a TwinSAFE slave with the default project, at least an EL6910, EK1960 or newer logic components
are required as a TwinSAFE master.
EP291825Version: 1.1.0
Operation
4.3.5Address settings on the TwinSAFE EtherCAT Box
Fig.15: EtherCAT Box - Rotary switches on the underside
The TwinSAFE address of the Box must be set using the three rotary switches on the underside of the
TwinSAFE-EP Box. TwinSAFE addresses between 1 and 4095 are available.
Each TwinSAFE address must be unique within a network!
The address 0 is not a valid address.
EP291826Version: 1.1.0
Operation
4.3.6Alias devices
The communication between the safety logic and the I/O level is realized via an alias level. At this alias level
(subnode Alias Devices) corresponding alias devices are created for all safe inputs and outputs, and also for
standard signal types. For the safe inputs and outputs, this can be done automatically via the I/O
configuration.
The connection- and device-specific parameters are set via the alias devices.
Fig.16: Starting the automatic import from the I/O configuration
If the automatic import is started from the I/O configuration, a selection dialog opens, in which the individual
terminals to be imported can be selected.
Fig.17: Selection from the I/O tree
The alias devices are created in the safety project when the dialog is closed via OK.
Alternatively, the user can create the alias devices individually. To this end select Add and New item from
the context menu, followed by the required device.
EP291827Version: 1.1.0
Operation
Fig.18: Creating alias devices by the user
EP291828Version: 1.1.0
Operation
4.3.7EP2918 parameters
After creating the alias device, it can be parameterized according to the user specifications. The FSoE
address is set under the Linking tab, and the link to the physical device is created.
Fig.19: EP2918 – Linking tab
NameDescription
FSoE addressParameterized FSoE address (to be set by the user)
External safe addresscurrently not supported
Linking mode• Automatic (automatic linking to the physical device)
• Manual (manual linking, e.g. to network variables)
• Local (signals are used in the local logic)
Physical deviceLink to the TwinSAFE component within the TwinCAT solution
DIP switchDIP or rotary switch address read from the TwinSAFE component
Input: Full nameIn manual mode:
Display of the variables below the TwinSAFE Logic, e.g. EL6910
Input: Linked to:In manual mode:
Display of the linked variables
Output: Full nameIn manual mode:
Display of the variables below the TwinSAFE Logic, e.g. EL6910
Output: Linked toIn manual mode:
Display of the linked variables
NameIn manual mode:
Name of the TwinSAFE message below the TwinSAFE Logic and for the info
data
EP291829Version: 1.1.0
Operation
Under the Connection tab you can make further settings, e.g. the mapping of the info data or the behavior in
case of a module error.
Fig.20: EP2918 - Connection tab
NameDescription
Conn. no.Connection number (issued by the system)
Conn. IdConnection ID:
Pre-allocated by system, can be changed by the user. The connection ID must be
unique within the TwinCAT project.
Mode• FSoE master (the logic is the master for this alias device)
• FSoE slave (the logic is a slave for this alias device)
WatchdogSetting the watchdog time in ms for this connection. This setting directly affects
the fault response time.
Module Fault is ComError If the checkbox is checked, module error also triggers a ComError, which
switches the TwinSAFE group where the connection was created to the error
state.
Com ERR AckFor each connection, an additional error acknowledge can be configured. In this
case, the connection must also be acknowledged, in addition to the Err Ack for
the respective group.
Map stateThe connection state is placed in the cyclic process data.
Map diagThe connection diagnostics is placed in the cyclic process data.
Map inputsThe safe input information of the connection is placed in the cyclic process data.
Map outputsThe safe output information of the connection is placed in the cyclic process data.
EP291830Version: 1.1.0
Operation
The Safety Parameters tab contains the parameters of the EP2918 to be set. The outputs are parameterized
via the objects 0x8000 etc.
Fig.21: EP2918 - Parameters
IndexNameDefault value/
8000:01ModuloDiagTestPulse
(FSOUT module 1)
8000:02MultiplierDiagTestPulse
(FSOUT module 1)
8000:03Standard outputs active
(FSOUT module 1)
8000:04Diag test pulse active
(FSOUT module 1)
8000:07Module Fault Link active
(FSOUT Module 1)
8010:01-07Parameters for FSOUT module 2 see module 1see module 1
8020:01-07Parameters for FSOUT module 3 see module 1see module 1
8030:01-07Parameters for FSOUT module 4 see module 1see module 1
8040:01-07Parameters for FSOUT module 5 see module 1see module 1
8050:01-07Parameters for FSOUT module 6 see module 1see module 1
8060:01-07Parameters for FSOUT module 7 see module 1see module 1
8070:01-07Parameters for FSOUT module 8 see module 1see module 1
unit
0x00 / integerModulo value for the frequency of the generation of a test pulse.
0x01 / integerLength of the test pulse in multiples of 400µs
FALSE / Boolean Activation of the logical AND operator of the safe and standard
TRUE / BooleanActivation of test pulses for the corresponding output module
TRUE / BooleanIf a module error occurs in this module, a module error is also set
Description
0 -> every time
1 -> every second time
and so on
outputs of the module
for all other output modules of this TwinSAFE component for
which this parameter is also set to TRUE.
EP291831Version: 1.1.0
Operation
4.3.8Process image of the EP2918
The process image of EP2918 consists of 6 bytes of input data and 7 bytes of output data. The 6-byte
telegram contains 1 byte of safe data, while the 7-byte telegram contains 2 bytes of safe data.
Fig.22: EP2918 Process image
The assignment of the individual signals in the safe data is listed in the following table.
NameProcess imageBit positionDescription
FSOUT module 1. module faultIN0.0Module error information for safe output 1
FSOUT module 2. module faultIN0.1Module error information for safe output 2
FSOUT module 3. module faultIN0.2Module error information for safe output 3
FSOUT module 4. module faultIN0.3Module error information for safe output 4
FSOUT module 5. module faultIN0.4Module error information for safe output 5
FSOUT module 6. module faultIN0.5Module error information for safe output 6
FSOUT module 7. module faultIN0.6Module error information for safe output 7
FSOUT module 8. module faultIN0.7Module error information for safe output 8
FSOUT Module1.OutputOUT0.0Safe output 1
FSOUT Module1.ErrAckOUT0.1Error acknowledge for safe output module 1
FSOUT Module2.OutputOUT0.2Safe output 2
FSOUT Module2.ErrAckOUT0.3Error acknowledge for safe output module 2
FSOUT Module3.OutputOUT0.4Safe output 3
FSOUT Module3.ErrAckOUT0.5Error acknowledge for safe output module 3
FSOUT Module4.OutputOUT0.6Safe output 4
FSOUT Module4.ErrAckOUT0.7Error acknowledge for safe output module 4
FSOUT Module5.OutputOUT1.0Safe output 5
FSOUT Module5.ErrAckOUT1.1Error acknowledge for safe output module 5
FSOUT Module6.OutputOUT1.2Safe output 6
FSOUT Module6.ErrAckOUT1.3Error acknowledge for safe output module 6
FSOUT Module7.OutputOUT1.4Safe output 7
FSOUT Module7.ErrAckOUT1.5Error acknowledge for safe output module 7
FSOUT Module8.OutputOUT1.6Safe output 8
FSOUT Module8.ErrAckOUT1.7Error acknowledge for safe output module 8
EP291832Version: 1.1.0
Operation
3 *3 *
typSensorInputCommLogicCommOutputActuator
ReactionTimeRTRTRTRTRTRTRT=++++++
543 *1103 *132048
typ
ReactionTimemsmsmsmsmsmsmsms=++++++=
4.4TwinSAFE reaction times
The TwinSAFE terminals form a modular safety system that exchanges safety-oriented data via the Safetyover-EtherCAT protocol. This chapter is intended to help you determine the system's reaction time from the
change of signal at the sensor to the reaction at the actuator.
Typical response time
The typical response time is the time required for transferring a piece of information from the sensor to the
actuator, when the whole system operates normally, without error.
Fig.23: Typical response time
Definition Description
RT
Sensor
Response time of the sensor, until the signal is made available at the interface. Typically
provided by the sensor manufacturer.
RT
Input
Response time of the safe input, e.g. EL1904 or EP1908. This time can be found in the
technical data. In the case of the EL1904 it is 4ms.
RT
Comm
Response time of the communication. This is typically 3 times the EtherCAT cycle time, since a
new Safety-over-EtherCAT telegram has to be generated before new data can be sent. These
times depend directly on the higher-level standard controller (cycle time of the PLC/NC).
RT
Logic
Response time of the logic terminal. This is the cycle time of the logic terminal and typically
ranges from 500µs to 10ms for the EL6900, depending on the size of the safety project. The
actual cycle time can be read from the terminal.
RT
RT
Output
Actuator
Response time of the output terminal. This is typically between 2 and 3ms.
Response time of the actuator. This information is typically provided by the actuator
manufacturer
WD
Comm
Watchdog time of the communication
The typical response time is based on the following formula:
with
Worst case response time
The worst-case response time is the maximum time required for switching off the actuator in the event of an
error.
EP291833Version: 1.1.0
Operation
maxCommCommActuator
ReactionTimeWDWDRT=++
max
2 *152050ReactionTimemsmsms=+=
Fig.24: Worst case response time
It is assumed that a signal change takes place at the sensor, and that this is passed to the input. A
communication error occurs just at the moment when the signal is to be passed to the communication
interface. This is detected by the logic once the watchdog time of the communication link has elapsed. This
information should then be passed on to the output, resulting in a further communication error. This fault is
detected at the output once the watchdog time has elapsed, resulting in shutdown.
This results in the following formula for the worst-case response time:
with
EP291834Version: 1.1.0
4.5Diagnostics
4.5.1EtherCAT- Fieldbus LEDs
Fig.25: EP2918 Diagnostic LEDs
LED displays
LEDDisplayMeaning
IN Link/Actoffno connection to the preceding EtherCAT module
litLINK: connection to the preceding EtherCAT module
flashesACT: communication with the preceding EtherCAT module
OUT Link/Act offno connection to the following EtherCAT module
litLINK: connection to the following EtherCAT module
flashesACT: Communication with the following EtherCAT module
RunoffStatus of the EtherCAT module is Init
flashes quicklyStatus of the EtherCAT module is pre-operational
flashes slowlyStatus of the EtherCAT module is safe-operational
litStatus of the EtherCAT module is operational
Operation
EP291835Version: 1.1.0
Operation
4.5.2Status LEDs
Fig.26: EP2918 Status LEDs
LEDDisplayMeaning
Out 1onOutput 1 is connected
offOutput 1 is not connected
Out 2onOutput 2 is connected
offOutput 2 is not connected
Out 3onOutput 3 is connected
offOutput 3 is not connected
Out 4onOutput 4 is connected
offOutput 4 is not connected
Out 5onOutput 5 is connected
offOutput 5 is not connected
Out 6onOutput 6 is connected
offOutput 6 is not connected
Out 7onOutput 7 is connected
offOutput 7 is not connected
Out 8onOutput 8 is connected
offOutput 8 is not connected
UsonControl voltage Us is available
offControl voltage Us is not available
UponPeripheral voltage Up is present
offPeripheral voltage Up is not present
EP291836Version: 1.1.0
Operation
4.5.3Diagnostic LEDs
Fig.27: EP2918 - Diagnostic LEDs
LED displays
LEDlitflashesflickeringoff
Dia1
(green)
Dia2
(red)
Dia3
(red)
Dia4
(red)
1)
A global fault permanently disables the TwinSAFE component, so that it has to be replaced. A global
shutdown temporarily disables the TwinSAFE component. The error can be reset by switching off and back
on again.
Environment variables,
operating voltage and
internal tests are in the
valid range
• If Dia2 flashes, a logic
error code applies
Together with Dia3 and 4:
Global shutdown1) has
occurred. (see diag history
of the TwinSAFE
components)
Global fault or global
shutdown on µC1
Global fault or global
shutdown on µC2
1)
1)
-Environment variables,
operating voltage and
internal tests are outside
the valid range
• If Dia2 flashes, an
environment error code
applies
Logic or environment
error code according
to Dia1 and tables
below is output
-No global fault or global
-No global fault or global
fault in a safe input
or output module
Together with Dia3 and 4:
Global fault1) has occurred.
(see diag history of the
TwinSAFE components)
shutdown on µC1
shutdown on µC2
1)
1)
Logic error codes of LED Dia2 (if LED Dia1 is lit)
Flashing CodeDescription
1Function block error in one of the TwinSAFE groups
2Communication error in one of the TwinSAFE groups
3Error combination: Function block and communication
4General error in one of the TwinSAFE groups
5Error combination: General and function block
6Error combination: General and communication
7Error combination: General, function block and communication
EP291837Version: 1.1.0
Operation
Environment error codes of LED Dia2 (if LED Dia1 is off)
Flashing CodeDescription
1Maximum supply voltage µC1 exceeded
2Supply voltage µC1 below minimum value
3Maximum supply voltage µC2 exceeded
4Supply voltage µC2 below minimum value
5Maximum internal temperature exceeded
6Internal temperature below minimum value
7Valid temperature difference between µC1 and µC2 exceeded
8not used
9not used
10General error
4.5.4Flash code display
LEDDisplayDescription
flashing400ms ON / 400ms OFF
1 second pause between the flash codes
flickering50ms ON / 50ms OFF
4.5.5Diagnostic objects
CAUTION
Do not change CoE objects!
Do not make any modifications to the CoE objects in the TwinSAFE components! Any modifications (e.g.
using TwinCAT) of the CoE objects will permanently set the TwinSAFE components to the Fail-Stop state.
Index F984
CoE object F984
IndexNameMeaningFlagsDefault
F984:01Voltage C2Voltage µC2RO0
F984:02Temperature C1Temperature µC1RO0
F984:03Firmware CRC C1CRC of the firmware on µC1ROF984:04Vendor data CRC C1 CRC of the vendor data on µC1RO-
Index F985
: Device Info Data C1
hex
currently displays internal temperature and voltage values for the TwinSAFE component.
hex
: Device Info Data C2
hex
dec
dec
CoE object F985
currently displays internal temperature and voltage values for the TwinSAFE component.
F985:03Firmware CRC C2CRC of the firmware on µC2ROF985:04Vendor data CRC C2 CRC of the vendor data on µC2RO-
Diagnostics history
Any errors, which occur during operation of the TwinSAFE component, such as overtemperature or
undervoltage, are entered in the diagnostics history with a corresponding timestamp.
EP291838Version: 1.1.0
Operation
Index F100
The CoE object F100
IndexNameMeaningFlagsDefault
F100:01Safe Logic StateStatus of the internal logic:
F100:02Cycle CounterLife cycle counter, which is incremented with each TwinSAFE logic
The following table contains a description of all values of the index F100
IndexValueDescription
F100:010: OFFLINEIn the OFFLINE state no TwinSAFE logic program is loaded. No TwinSAFE groups and no
: FSLOGIC status
hex
shows the current status of the TwinSAFE component.
1: RUNIn the RUN state all TwinSAFE groups and all TwinSAFE connections configured in the
3: SAFEThe SAFE state is assumed from the RUN state when the TwinSAFE logic program is
6: STARTThe START state is assumed if the TwinSAFE logic program is loaded but the standard
8: PREPAREThe PREPARE state is assumed at the transition from START to RUN or from SAFE to
10: RESTOREIn the RESTORE state the loaded TwinSAFE restore program is to be checked by com-
11: PROJECT-CRC-OKThe PROJECT-CRC-OK state is assumed once the project CRC of the loaded TwinSAFE
TwinSAFE logic program are processed.
stopped.
If the TwinSAFE logic program is restarted without a new TwinSAFE logic program having
been transferred, the TwinSAFE logic should switch again from SAFE to RUN. All TwinSAFE groups should be initialized with the initial state STOPERROR, so that an error acknowledgement occurs before safe outputs are connected again.
In the SAFE state no TwinSAFE groups and no TwinSAFE connections are processed.
communication channel (e.g. EtherCAT) is not yet in process data exchange or the
process data lengths configured via the standard communication channel do not match the
process data lengths calculated using the TwinSAFE logic program.
The START state is also assumed when a user is logged in for the purpose of deleting the
current TwinSAFE logic program or transferring the user list.
In the START state no TwinSAFE groups and no TwinSAFE connections are processed.
RUN.
In the PREPARE state, the stored data read in from the FRAM is checked and then the
RUN state is assumed.
If an error is detected during checking of the stored data, all TwinSAFE groups assume
the initial state STOPERROR.
If no error is detected during checking of the stored data, all TwinSAFE groups assume
the initial state STOP.
paring its project CRC with the project CRCs read in via the corresponding TwinSAFE
connections.
In the RESTORE state all TwinSAFE connections configured in the TwinSAFE Restore
program are processed.
restore program has been successfully checked via the TwinSAFE connections.
In the PROJECT-CRC-OK state no TwinSAFE groups and no TwinSAFE connections are
processed.
RO0
.
bin
bin
This CoE object is additionally copied into the cyclic process image of the TwinSAFE component. From
there, this information can be directly linked into the PLC.
Fig.28: Diagnostic object - FSLOGIC Status (F100
) in the process image of the TwinSAFE component
hex
EP291839Version: 1.1.0
Operation
4.5.6Cycle time of the safety project
The execution time of the TwinSAFE logic can be read from the CoE objects listed below. To determine the
cycle time, it has to be multiplied with 1.25, because this is the factor used internally for generating a delay
time before the next cycle.
Index FEA0
: CTRL Diag Data
hex
IndexNameMeaningFlags Default
FEA0:09 Actual Safety Control
Task Execution Time
Current execution time of the TwinSAFE logic with a
logic state of1(RUN)
RO0
hex
Cycle time = 1.25 * value
(average value of 64 cycles)
FEA0:0A Min Safety Control
Task Execution Time
Minimum execution time of the TwinSAFE logic with a
logic state of 1(RUN)
RO0
hex
Cycle time = 1.25 * value
FEA0:0B Max Safety Control
Task Execution Time
Maximum execution time of the TwinSAFE logic with a
logic state of 1(RUN)
RO0
hex
Cycle time = 1.25 * value
FEA0:15 Actual Safety Control
Task Execution Time
Current execution time of the TwinSAFE logic with a
logic state of<>1
RO0
hex
Cycle time = 1.25 * value
(average value of 64 cycles)
FEA0:16 Min Safety Control
Task Execution Time
Minimum execution time of the TwinSAFE logic with a
logic state of<>1
RO0
hex
Cycle time = 1.25 * value
FEA0:17 Max Safety Control
Task Execution Time
Maximum execution time of the TwinSAFE logic with a
logic state of<>1
RO0
hex
Cycle time = 1.25 * value
Resetting the values
The max. and min. values can be reset by writing a value to the CoE object 0x1C32:08.
4.5.7Diag History tab
All errors occurring within the TwinSAFE components are stored in their diag history. The diag history can be
viewed by selecting the corresponding TwinSAFE component in the I/O tree structure and then selecting the
Diag History tab. Use the Update History button to fetch the current data from the TwinSAFE component.
Errors within the logic, the function blocks, the connections or the component itself are stored with a
corresponding time stamp.
Fig.29: Diag history
Use the Advanced… button to open the advanced settings. Here, the user can customize the behavior of the
diag history.
EP291840Version: 1.1.0
Operation
Fig.30: Diag history – advanced settings
Advanced Settings
SettingDescription
Message Types• disable Info
Messages with the Info status are not saved in the diag history
• disable Warnings
Messages with the Warning status are not saved in the diag history
• disable Errors
Messages with the Error status are not saved in the diag history
EmergencyIn addition to saving the message in the diag history, an emergency object
is also sent and displayed in the TwinCAT logger window.
Overwrite/Acknowledge Mode This setting is currently not supported.
4.5.8Diagnosis History
The diagnostic history of the TwinSAFE devices that support this function is implemented in accordance with
the ETG guideline ETG.1020 Chapter 13 "Diagnosis Handling". The diagnostic messages are saved by the
TwinSAFE device in a dedicated CoE object under 0x10F3 and can be read out by the application or by
TwinCAT.
Both the control entries and the history itself can be found in the CoE object 0x10F3. The entry Newest
Message (0x10F3:02) contains the subindex of 0x10F3, which contains the latest diagnostic message, e.g.
0x06 for diagnostic message 1.
EP291841Version: 1.1.0
Operation
Index 10F3
Diagnosis History
hex
Index (hex) NameMeaningData type Flags Default
10F3:0Diagnosis
History
10F3:01Maximum
Messages
Maximum number of stored messages. A
maximum of 64 messages can be stored.
UINT8RO0x40 (64
After that the respective oldest messages are
overwritten.
10F3:02Newest
Subindex of the latest messageUINT8RO0x00 (0
Message
10F3:03Newest
Subindex of the last confirmed messageUINT8RW0x00 (0
Acknowledged
Message
10F3:04New
Indicates that a new message is availableBOOLEAN RO0x00 (0
Messages
Available
10F3:05FlagsSet via the startup list. If set to 0x0001, the
diagnostic messages are additionally sent by
UINT16RW0x0000
(0
)
dec
emergency to the EtherCAT master
10F3:06Diagnosis
Diagnosis message 1BYTE[32]RO{0}
Message 001
..................
10F3:45Diagnosis
Diagnosis message 64BYTE[32]RO{0}
Message 064
dec
dec
dec
dec
)
)
)
)
Structure of the diagnosis messages
• DiagCode (4 bytes) – in this case always 0x 0000 E000
• Flags (2 bytes) - diagnosis type (info, warning or error), time stamp and number of parameters
contained (see the following table)
• Text ID (2 bytes) – ID of the diagnosis message as a reference to the message text from the ESI/XML
• Time stamp (8 bytes) – local slave time in ns since switching on the TwinSAFE device
• dynamic parameters (16 bytes) – parameters that can be inserted in the message text (see following
table)
Text parameters and formats are
specified in ETG.2000.
Parameter 1Data type in accordance with
flags
Flags parameter 2 UINT16see Flags parameter 1
Parameter 2Data type in accordance with
flags
...
Value of parameter 1
Value of parameter 2
Operation
The diagnostic messages are saved in text form in the ESI/XML file belonging to the TwinSAFE device. On
the basis of the Text ID contained in the diagnostic message, the corresponding plain text message can be
found in the respective languages. The parameters can be inserted in the appropriate positions. In the
following example, %x is used for a hexadecimal representation of the parameters.
Fig.31: ESI/XML message text
Via the entry New Messages Available the user receives information that new messages are available. The
messages can be read out via CompleteAccess (a CoE read command for the complete CoE object
0x10F3). The New Messages Available bit is reset after reading the messages.
The sending of emergency messages to the EtherCAT master is activated by adding the CoE object
0x10F3:05 to the startup list (Transition IP, value 0x0001). If new diagnostic messages arrive, they are
entered in object 0x10F3 and additionally sent by emergency to the EtherCAT master.
Fig.32: Startup list
EP291843Version: 1.1.0
Operation
4.6Maintenance
Maintenance
The TwinSAFE components are maintenance-free!
Environmental conditions
WARNING
Observe the specified environmental conditions!
Please ensure that the TwinSAFE components are only stored and operated under the specified conditions
(see technical data).
If the TwinSAFE component is operated outside the permitted temperature range it will switch to GlobalShutdown state.
Cleaning
Protect the TwinSAFE component from unacceptable soling during operation and storage!
If the TwinSAFE component was subjected to unacceptable soiling it may no longer be operated!
WARNING
Have soiled terminals checked!
Cleaning of the TwinSAFE component by the user is not permitted!
Please send soiled terminals to the manufacturer for inspection and cleaning!
EP291844Version: 1.1.0
4.7Service life
The TwinSAFE EtherCAT Boxes have a service life of 20 years.
Due to the high diagnostic coverage within the lifecycle no special proof tests are required.
Datecode
The TwinSAFE EtherCAT Boxes have a datecode (D:), which is structured as follows:
Datecode: WWYYSWHW
Operation
Key:
WW: Calendar week of manufacture
YY: Year of manufacture
SW: Software version
HW: Hardware version
Serial number (S. no.)
In addition, the TwinSAFE EtherCAT Boxes have a unique serial number (S. no.).
Bring the bus system into a safe, de-energized state before starting disassembly of the devices!
Disposal
The device must be removed for disposal.
Observe the applicable national laws and guidelines for disposal!
• Housing components (Valox 855 - PBT+PET), made from recyclable plastic
• Sealing compound: Polyurethane resin (PU552L)
• Metal parts can be sent for metal recycling.
• Electronic parts such as disk drives and circuit boards must be disposed of in accordance with national
electronics scrap regulations.
EP291845Version: 1.1.0
Operation
4.9Firmware update of TwinSAFE products
For TwinSAFE products there is the option of performing a firmware update via the EtherCAT interface. The
complete firmware of the TwinSAFE component is deleted and replaced by a new version.
The latest firmware can be downloaded from the Beckhoff website. The versions are available in an
encrypted form and can only be loaded onto the matching TwinSAFE product. An incorrect firmware file is
rejected by the respective TwinSAFE product.
Prerequisite for a firmware update
DANGER
Put the machine into a safe state!
A firmware update stops the current processing of the firmware of the TwinSAFE product. It is essential that
you switch the TwinSAFE system to the safe state before you start an update.
All safe outputs must be in a safe, de-energized state. If hanging or pulling loads are present on the machine or the TwinSAFE system, these must also be brought into a safe state through external safety measures if necessary.
DANGER
Monitor the machine state!
It is necessary that you have control over the machine, i.e. you can see it and thus ensure that it is in a safe
state and that a firmware update can be carried out without endangering the operators or other personnel.
NOTE
Avoid communication interruptions during the download
Please avoid disconnecting the EtherCAT connection while downloading the firmware under any circumstances. If a communication error does occur, the TwinSAFE product may subsequently be unusable and
must be sent to the Beckhoff Service.
WARNING
Default project for TwinSAFE I/O components with local logic function!
After a firmware update, any implemented default project starts automatically. An EK1960, for example,
would start up as a TwinSAFE I/O slave after a firmware update.
NOTE
Firmware update of TwinSAFE logics
If a firmware update is performed for a TwinSAFE logic component, e.g. on a TwinSAFE logic EL6910, the
safety-related user program must be reloaded to the TwinSAFE logic after the update. After the update the
user administration is set to the default settings.
EtherCAT communication
When an EtherCAT component is updated, it is switched to BOOTSTRAP mode. This can have an
effect on the EtherCAT communication with other EtherCAT devices.
EP291846Version: 1.1.0
Operation
Performing the firmware update
Click the button (1) in the TwinCAT system to enter Config mode. Confirm the query with OK (2). After that a
further window appears which must be confirmed with Yes (Ja) (3). Deactivate the "Free Run" with No (Nein)
(4). The system is now in Configuration mode.
Fig.34: Firmware update of TwinSAFE products - Part 1
To perform the firmware update, select the "Online" tab (6) for the "EtherCAT Device" (5). If you want to
update several components, you can select the corresponding components (7) together; for individual
components, select only these. Subsequently, click with the right mouse button inside the selected area and
select the command "Firmware Update..." (8) in the command overview.
EP291847Version: 1.1.0
Operation
Fig.35: Firmware update of TwinSAFE products - Part 2
In the place where you have stored the desired firmware version, select the firmware file (9) and click
"Open" (10). Confirm the window that then opens with "OK" (11); the firmware update is then performed.
After successful completion you must click OK (12) in the concluding "Function Succeeded" window. You
can then switch the system back to Run mode and use the TwinSAFE system.
Fig.36: Firmware update of TwinSAFE products - Part 3
EP291848Version: 1.1.0
Appendix
5Appendix
5.1Protection classes according to IP code
The levels of protection are defined and divided into different classes in the IEC 60529 standard (DIN EN
60529). The designation follows the scheme below.
1st digit: Protection against ingress of dust and access to hazardous parts
1st digitMeaning
0Non-protected
1Protection against access to hazardous parts with back of hand. Protection against ingress of
solid foreign objects = 50 mm diameter
2Protection against access to hazardous parts with a finger. Protection against ingress of solid
foreign objects = 12.5 mm diameter
3Protection against access to hazardous parts with a tool. Protection against ingress of solid
foreign objects = 2.5 mm diameter
4Protection against access to hazardous parts with a wire. Protection against ingress of solid
foreign objects = 1 mm diameter
5Protection against access to hazardous parts with a wire. Protection against ingress of dust.
Ingress of dust is not prevented completely, although the quantity of dust able to penetrate is
limited to such an extent that the proper function of the device and safety are not impaired
6Protection against access to hazardous parts with a wire. Dust-proof. No ingress of dust
2nd digit: Protection against ingress of water*
2nd digitMeaning
0Non-protected.
1Protection against dripping water.
2Protection against dripping water when housing tilted up to 15°.
3Protection against spraying. Water sprayed at an angle of up to 60° from vertical must not have
any adverse effect.
4Protection against splashing. Water splashing against the housing from any direction must not
have any adverse effects.
5Protection against jetting.
6Protection against powerful jetting.
7Protection against the effects of temporary immersion. The quantity of water being able to
penetrate if the housing is submerged in water for 30 minutes at a depth of 1 m must not have
any adverse effects.
*) These protection classes only define protection against water, not against other liquids.
EP291849Version: 1.1.0
Appendix
5.2Support and Service
Beckhoff and their partners around the world offer comprehensive support and service, making available fast
and competent assistance with all questions related to Beckhoff products and system solutions.
Beckhoff's branch offices and representatives
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff
products!
The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet
pages:
http://www.beckhoff.com
You will also find further documentation for Beckhoff components there.
Support offers you comprehensive technical assistance, helping you not only with the application of
individual Beckhoff products, but also with other, wide-ranging services:
• support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components