Beacon-Morris BTU User Manual

0 (0)
Beacon-Morris BTU User Manual

MAINTENANCE

PERIODIC SERVICE

NOTICE: The heater and vent system should be checked once a year by a qualified technician.

All Maintenance/Service information should be recorded accordingly on the Inspection Sheet provided in this manual.

Open all disconnect switches and disconnect all electrical and gas supplies and secure in that position before servicing unit. Failure to do so may result in personal injury or death from electrical shock.

Should maintenance be required, perform the following inspection and service routine:

1.Inspect the area near the unit to be sure that there is no combustible material located within the minimum clearance requirements listed in this manual.

Under no circumstances should combustible material be located within the clearances specified in this manual. Failure to provide proper clearance could result in personal injury or equipment damage from fire.

2.Turn off the manual gas valve and electrical power to the unit heater.

3.To clean or replace the main burners, remove burner cover. Remove top strip from above main burners. Lift burners up and pull away from manifold to remove.

4.With the burners removed, wire brush the inside surfaces of the heat exchanger.

5.Remove any dirt, dust, or other foreign matter from the burners using a wire brush and/or compressed air. Ensure that all parts are unobstructed. Inspect and clean the pilot burner if necessary.

6.Reassemble the unit heater by replacing all parts in reverse order.

7.Relight the pilot (see lighting instruction on the unit nameplate). Complete the appropriate unit startup procedure as given in the “Operation” section of this manual.

8.Check the burner adjustment.

9.Check all gas control valves and pipe connections for leaks.

10.Check the operation of the automatic gas valve by lowering the setting of the thermostat, stopping the operation of the gas duct furnace. The gas valve should close tightly, completely extinguishing the flame on the main burners.

11.Inspect and service motor/fan assembly. To maintain efficient air flow, inspect and clean the fan blades and guard to prevent buildup of foreign matter.

12.Check lubrication instructions on motor. If oiling is required, add 3 or 4 drops of electric motor oil as follows:

a.Light Duty - After 3 years or 25,000 hours of operation.

b.Average Duty - Annually after 3 years or 8,000 hours of operation.

c.Heavy Duty - Annually after 1 year or at least 1500 hours of operation.

Never over oil the motor or premature failure may occur!

14.Check and test the operational functions of all safety devices supplied with your unit.

LIMITED WARRANTY

Power Vented Tubular Propeller Unit Heaters

1.The "Manufacturer" warrants to the original owner at original installation site that the above model Gas-Fired Heater ("the Product") will be free from defects in material or workmanship for

(1)year from the date of shipment from the factory, or one and one-half (1-1/2) years from the date of manufacture, whichever occurs first. The Manufacturer further warrants that the complete heat exchanger, and burners be free from defects in material or workmanship for a period of ten (10) years from the date of manufacture. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective.

2.This limited warranty does not apply:

a.if the product has been subjected to misuse or neglect, has been accidentally or intentionally damaged, has not been installed, maintained, or operated in accordance with furnished written instructions, or has been altered or modified in any way by any unauthorized person.

b.to any expenses, including labor or material, incurred during removal or reinstallation of the Product

c.to any damage due to corrosion by chemicals, including halogenated hydrocarbons, precipitated in the air

d.to any workmanship of the installer of the Product

3.This limited warranty is conditional upon:

a.advising the installing contractor, who in turn notify the distributor or manufacturer

b.shipment to the Manufacturer of that part of the Product thought to be defective. Goods can only be returned with prior written approval of the Manufacturer. All returns must be freight prepaid.

c.determination in the reasonable opinion of the Manufacturer that there exists a defect in material or workmanship

4.Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period.

5. THIS LIMITED WARRANTY IS IN LIEU OF ALL WARRANTIES,

EITHER EXPRESS OR IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY JURISDICTION.

In the interest of product improvement, we reserve the right to make changes without notice.