Basler Electric APR63-5X User Manual

FOR
VOLTAGE REGULATOR
APR 63-5X
INTRODUCTION
The APR 63-5X Voltage Regulator controls the dc field power of a conventional, 400 Hz brushless generator that has a 63 Vdc field to regulate the generator output voltage. The APR 63-5X regulates the generator output by sensing the generator output voltage, converting it to a dc signal, and comparing the signal to a reference voltage. An error signal is developed and used to control the dc field power in order to maintain a con­stant generator voltage.
The APR 63-5X is contained in an encapsu­lated, plastic case.
SPECIFICATIONS
Power Input
Configuration: 1-phase, 400 Hz Range: 190 to 277 Vac, ±10% Burden: 650 VA maximum Dissipation: 25 W maximum
Sensing Voltage
Configuration: 1-phase, 400 Hz Range 240 Vac: 190 to 240 Vac 480 Vac: 380 to 480 Vac Burden: 5 VA
Power Output
Continuous:63 Vdc, 5 Adc, 315 W 1-Min. Forcing: 105 Vdc, 8.5 Adc, 893 W With 240 Vac input power.
DC Exciter Field Resistance
12.6 to 100
Voltage Adjustment Range
Internal
170 to 264 Vac or 340 to 528 Vac using the internal voltage adjust.
External
±10% of the nominal value determined by the internal voltage adjust. A 1 k, 2 W potentiometer with a locking, screwdriver­adjusted shaft is supplied with the APR 63­5X for remote mounting.
Regulation
Accuracy: ±0.5% Voltage Drift: <±1% variation for a 50°C
(90°F) change
Response: <1 cycle
Voltage Buildup
Automatic voltage buildup from generator residual voltage as low as 6 Vac.
Frequency Compensation
See Figure 1
Overexcitation Shutdown
See Figure 2. If the field voltage exceeds 100 ±5 Vdc, the APR 63-5X automatically removes the field current after a time delay. The time delay is inversely proportional to the magnitude of the detected overvoltage condition. At approximately 135 ±5 Vdc, the field voltage is removed instantaneously.
Upon detection of overexcitation and the resulting field voltage shutdown, the APR 63-5X will not reset or return to an opera-
tional condition until the generator output drops to less than 6 Vac for 10 seconds.
Shock
Withstands up to 15 G in each of 3 mutually perpendicular axes.
Vibration
5 to 26 Hz: 1.2 G 27 to 53 Hz: 0.036” double amplitude 54 to 1,000 Hz: 5.0 G
Temperature
Operating: –40 to 60°C (–40 to 140°F) Storage: –65 to 85°C (–85 to 185°F)
Weight
1,110 g (2.5 lb)
INSTALLATION
Mounting
The APR 63-5X may be mounted in any position. The APR 63-5X may be mounted directly on the generator using ¼” hardware. Select the proper hardware to withstand any expected transportation and operating con­ditions. Outline drawings are provided in Figures 3 and 4.
Connections
APR 63-5X connection diagrams are pro­vided in Figures 5 through 7.
Connecting Procedure
CAUTION
Do not make any connections to the 50 Hz, 60 Hz, or COM terminals.
1. Connect terminals F+ and F– to the field. Observe proper polarity.
2. Connect terminals 3 and 4 to the genera­tor output. Fuse both leads. If desired, in­stall a shutdown switch.
3. Connect either the 240 or 480 terminal to the sensing source. Sensing should be connected line-to-line.
ADJUSTMENTS
Field Flashing
When the regulator is operated with the generator for the first time, the polarity of the residual magnetism may be incorrect or of insufficient magnitude. If the residual voltage at terminals 3 and 4 is greater than 6 Vac, replace the regulator. If generator residual voltage is less than 6 Vac, stop the prime mover and proceed with the following steps.
CAUTION
The regulator may be damaged if the field is flashed with the generator in motion.
1. With the prime mover at rest, apply an ungrounded dc source of not more than 48 Vdc to terminals F+ and F– in series with a limiting resistor. Use 1 of resis­tance for each volt from the dc power source with a power rating of at least 1 W per ohm. For example, if using a 24 Vdc source, use a 24 , 24 W resistor.
2. Allow the field to be flashed for approxi­mately 10 seconds before removing the dc source.
3. If voltage does not build up after perform­ing steps 1 and 2, verify the polarity of the dc source and perform steps 1 and 2 again.
APR 63-5X Controls
FREQ
This control prevents generator and regula­tor damage by decreasing the generator output voltage when the generator fre­quency decreases. To set the frequency roll­off, perform the following steps:
1. Adjust the generator rpm to the desired frequency compensation (corner fre­quency roll-off) point.
2. Adjust the FREQ control until the output voltage begins to drop-off.
3. Increase the generator rpm to nominal. The output voltage should return to nor­mal.
STAB
This control allows the generator response time (and thus voltage stability) to be ad­justed. Use an oscilloscope or other voltage recording device to set the STAB control.
Clockwise rotation of the STAB control slows response time and counterclockwise rotation of the STAB control speeds re­sponse time. If the STAB control is rotated too far counterclockwise, the generator volt­age may oscillate (hunt).
When adjusting the generator response time, rotate the STAB control counterclock­wise until the system starts oscillating and then rotate the control clockwise just past the point where oscillation occurred.
VOLT
Clockwise rotation of the VOLT control in­creases the generator output voltage.
Replacing the jumper connected across terminals 6 and 7 with a 1 k, 2 W potenti­ometer allows a ±10% voltage range ad­justment with the nominal level set by the VOLT control. If a range less or greater than that provided by the 1 k potentiometer is desired, a 2 W potentiometer of any value from 50 to 5,000 may be substituted.
OPERATION
Before proceeding with system startup, confirm the following:
Verify that the APR 63-5X specifications conform with the requirements of the generator system.
Ensure that the APR 63-5X has been installed and connected in accordance with
Installation, Mounting
tions
.
During periods of prime mover idling, use the shutdown switch to remove power from the APR 63-5X.
System Startup
System startup is achieved by performing the following steps. If the desired results are not achieved during startup, refer to the procedures listed under
and
Connec-
Troubleshooting
.
Publication
9168700992
Revision
D
First Printing: 08/93
Revised: 07/05
Copyright
1. Start the prime mover and bring it up to rated speed.
2. Slowly adjust the VOLT control (or exter­nal potentiometer) until nominal generator voltage is achieved.
3. Check stability by applying and removing load.
4. Check regulation under normal operating conditions.
5. Reduce the generator frequency to ap­proximately 373 Hz. The generator output should decrease from this point.
Troubleshooting
If the system does not operate as expected, use the following information to determine the cause and remedy.
Generator Voltage Does Not Build
There may be no or incorrect input voltage applied to APR 63-5X terminals 3 and 4. Verify the wiring and check the fuses and shutdown switch.
The field may require flashing—flash the field.
The overexcitation function may be shutting the APR 63-5X off. Stop the prime mover and then restart. Watch for high voltage.
Voltage Builds and then Decays
The voltage adjust circuit may be open. If an external potentiometer is not used, verify that a jumper is installed across terminals 6 and 7. If an external potentiometer is used, the potentiometer may be defective or of the wrong value. Check the potentiometer and wiring and correct as necessary.
Voltage Does Not Build to the Rated Value
The jumper across APR 63-5X terminals CB+ and CB– may be missing—install the jumper.
Sensing may be connected to the wrong terminal. Correct the sensing connections as required.
The setting of the internal or external voltage adjust may be incorrect. Adjust the VOLT control or external potentiometer as needed.
Voltage High and Uncontrollable
Generator sensing may not be connected to the APR 63-5X or may be connected to the wrong terminal. Correct the sensing connec­tions as needed.
Generator Response is Too Slow or Hunting
The generator load may be excessive or the generator output may be shorted. Check the generator load.
The STAB control may be improperly set. Adjust the STAB control according to the guidelines provided in
5X Controls, Stab
Adjustments, APR 63-
.
Poor Regulation
The resistance of the field may not be matched to the capability of the APR 63-5X. Compare the field resistance with the speci­fied field resistance range of the APR 63-5X.
The APR 63-5X output rating does not meet the requirement of the generator. Compare the excitation requirement of the generator with the specified output range of the APR 63-5X.
The speed of the prime mover may be too low. Check the speed of the prime mover.
The voltmeter may not be connected at the same point as the regulator sensing. Verify the voltmeter connections. Also verify that an average-sensing voltmeter is used—not an rms-sensing voltmeter.
Frequency Roll-Off Not Working
The FREQ control may be improperly set. Adjust the FREQ control according to the guidelines provided in
5X Controls, Stab
Operational Test
To verify APR 63-5X functionality, perform the following steps.
1. Connect the regulator as shown in Figure 8 and apply 240 Vac as shown.
2. Adjust the VOLT control fully counter­clockwise. Observe that the lamp does not light.
3. Adjust the VOLT control fully clockwise.
4. Adjust the VOLT control counterclockwise until the lamp just goes out.
Regulator operation is satisfactory if the above results are obtained. However, stabil­ity must be tested with the regulator and generator operating.
Adjustments, APR 64-
.
Figure 1. Frequency Compensation Curves
Figure 2. Typical Inverse Time Delay
Characteristic Curves
Page 2 First Printing: 08/93
Revised: 07/05
Figure3. Mounting Dimensions
Revision
D
Publication
9168700992
Loading...
+ 2 hidden pages