Integrated Part Load Value (IPLV) Efficiency Up To 15.2 BTU/WATT
WA3S – WA5S Right Side Control Panel
GREEN REFRIGERANT
WL3S – WL5S Left Side Control Panel
3 to 5 Ton (35,400 to 56,500 Btuh) 60Hz
The Bard WA/L "S" Series is the world's most energy efficient wall mounted
air conditioner featuring a multi-step capacity compressor with
environmentally friendly non-ozone depleting refrigerant.
The Bard Wall-Mount Air Conditioner is a self contained energy efficient
system, which is designed to offer maximum indoor comfort at a minimal
cost without using valuable indoor floor space or outside ground space.
This unit is the ideal product for versatile applications such as: new
construction, modular offices, school modernization, telecommunication
structures, portable structures or correctional facilities. Factory or field
installed accessories are available to meet specific job requirements.
Engineered Features
Multi-Capacity Two-Stage:
Simple thermostatic control
seamlessly stages the compressor
and indoor airflow rate between high
and low capacity operations without
cycling the compressor. This helps
to maximize comfort, humidity
control, energy efficiency and overall
reduction in compressor cycling for
improved system life.
Multi-Step Capacity
Compressor:
Copeland step-capacity scroll
compressors are designed for
increased efficiency, quieter operation
and improved reliability for longer life.
R-410A Refrigerant:
Designed with R-410A (HFC) nonozone depleting refrigerant in
compliance with the Montreal
protocol and 2010 EPA requirements.
ECM Indoor Blower Motor:
Features a variable speed motor
providing super-high efficiency, low
sound levels and soft-start
capabilities.
adjusting to provide the proper airflow
rate for the staged capacity, and for
higher static pressure in ducted
installations without user adjustment
or wiring changes.
The motor is self-
Aluminum Finned Copper Coils:
Grooved tubing and enhanced
louvered fin for maximum heat
transfer and energy efficiency.
Twin Blowers:
Move air quietly. All models feature
variable speed blower motors
providing automatic airflow
adjustment for high static or free
blow (non-ducted) operation at a very
low sound level. Motor overload
protection is standard on all models.
Foil Faced Insulation:
Standard on all units.
Start Kit:
A PTCR compressor start assist
(Positive Temperature Coefficient
Resistor) is standard on all -A singlephase models to increase system
reliability. This helps to insure
compressor starts at adverse
conditions by increasing the
compressor starting torque.
Compressor Control Module:
Built-in off-delay timer adjustable
from 30 seconds to 5 minutes. 2minute on-delay if power interrupt.
120-second bypass for low pressure
control, and both soft and manual
lockouts for high and low pressure
controls. Alarm output for alarm
relay.
Liquid Line Filter Drier:
Standard on all units. Protects
system against moisture.
High & Low Pressure Switches are
Auto-Reset:
Standard on all units. Built-in lockout circuit resets from the room
thermostat. Provides commercial
quality protection to the compressor.
Crankcase Heaters:
Factory installed crankcase heaters
are standard on all models. This
helps to insure ease of start at low
temperatures and improves
compressor life.
Phase Rotation Monitor:
Standard on all 3 phase scroll
compressors. Protects against
reverse rotation if power supply is not
properly connected.
Galvanized 20 Gauge Zinc
Coated Steel Cabinet:
Cleaned, rinsed, sealed and dried
before the polyurethane primer is
applied. The cabinet is handsomely
finished with a baked on textured
enamel, which allows it to withstand
1000 hours of salt spray tests per
ASTM B117-03.
Galvanized 16 Gauge Zinc
Coated Unit Base:
The unit base is treated with the
same paint coatings as the cabinet
above, insuring years of service
without visible corrosion.
Drain Pan:
The evaporator drain pan is
constructed of stainless steel
material for maximum corrosion
resistance.
Electrical Components:
Are easily accessible for routine
inspection and maintenance through
a right side, service panel opening.
Features a lockable, hinged access
cover to the circuit breaker or toggle
disconnect switch.
R-410A
Electric Heat Strips:
Features line break automatic limit
and dual backup safety controls.
Heater packages can be factory or
field installed for all models.
Filter Service Door:
Separate service door provides easy
access for filter change.
Two-Inch, Pleated Disposable
Air Filters:
Are standard equipment.
Condenser Fan and Motor
Shroud Assembly:
Slides out for easy access.
Circuit Breakers/Rotary
Disconnect:
Standard on all versions of single (230/
208 volt) and three phase (230/208
volt) equipment. Rotary disconnects
are standard on all versions of three
phase (460 volt) equipment.
Slope Top:
Standard feature for water run-off.
Full Length Mounting Brackets:
Built into cabinet for improved
appearance and easy installation.
NOTE: Bottom mounting bracket
included to assist in installation.
Top Rain Flashing:
Standard feature on all models.
• Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2010.
• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL
1995/CSA 22.2 No. 236-05, Fourth Edition.
• Commercial Product - Not intended for Residential application.
Form No.S3378-1112
Supersedes S3378-712
Page1 of 12
Capacity and Efficiency Ratings
c
1
SLEDOM
noitarepOegatSdn2,HUTByticapaCgnilooC
noitarepOegatSdn2REE21
)lioCteW(MFCdetaR
noitarepOegatSts1,HUTByticapaCgnilooC
noitarepOegatSts1REE2
)lioCteW(MFCdetaR
3S3AW
2S3LW
004,53
1.11
0011
000,42
7.11
008
3S4AW
2S4LW
000,64
2.11
0051
000,43
6.11
0011
3S5AW
2S5LW
005,65
1.01
0071
000,04
8.01
0031
VLPI31.512.513.41
1 Certified in accordance with ANSI/ARI Standard 390-2003 for single package vertical units.
2 EER = Energy Efficiency Ratio - BTU/WATT efficiency.
3 Integrated Part Load Value - BTU/WATT efficiency and certified in accordance with ANSI/ARI Standard 390-2003.
All capacity, efficiency and cost of operation information is based on operation with fresh air cover plate. Cover plate is recommended for use to
obtain maximum energy efficiency where ventilation air is not required.
Indoor Blower Performance - CFM (0.00" through 0.80" H2O) 1
ylnOrewolBgnilooCegatSts1gnilooCegatSdn2
3S3AW
2S3LW
3S4AW
2S4LW
3S5AW
2S5LW
008008001100110041
5280011005100110051
0580031007100110051
cirtcelEWK01-5
taeH
1 These systems contain Variable Speed ECM Motor, which maintains airflow across static range at
Form No.S3378-1112
Supersedes S3378-712
Page2 of 12
Ventilation System Packages
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All
units are equipped with a blank off plate as the standard ventilation package. All ventilation packages can be built-in at the factory, or fieldinstalled at a later date.
BLANK OFF PLATE - BOPSTANDARD
A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any
outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not
required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air,
up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed
with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered
open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower
operation or can be field connected to be managed based on building occupancy.
Motorized Fresh Air Damper
COMMERCIAL ROOM VENTILATOR
NOTE: This vent system is intake only without built-in exhaust capability. Building will likely require separate field
installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Other building systems will
govern actual amount of intake air.
COMMERCIAL ROOM VENTILATOR - CRVMPOPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside
ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings.
It includes a built-in exhaust air damper with integral bug screen. Automatic control is integrated to maintain
desired ventilation air at the various supply airflows.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by
providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control
the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field
controlled based on room occupancy. The CRV is power open - spring return on power loss. Complies with
ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality.”
Economizer
ENERGY RECOVERY VENTILATOR
ECONOMIZER - ECONWM-SeriesOPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be
introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and
settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide
“free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running
the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
• ECONWMT Equipment Building versions have extended air intake hood to deliver up to 100% of cooling rated airflow.
16" for ECONWMT-E2 or T2, and E3 or T3
18" for ECONWMT-E5 or T5
• ECONWMS Classroom versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.
Standard Features:
•
Fully modulating
• Honeywell Direct Drive Hi-Torque Actuator
• No linkage required
• Simple single blade design
• Positive shut-off with non-stick gaskets
• Electronic DB and/or Enthalpy sensors depending upon version
• Honeywell JADE electronic economizer module with precision settings and diagnostics
• DB or Enthalpy economizer versions available
WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVFOPTIONAL
The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality
ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM
(depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and
humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs.
Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.
The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat
transfer capabilities during summer and winter conditions. Various control schemes are addressed including
limiting ventilation during building occupancy only.
The ERV is designed to be internally mounted behind the service door in the WA/LS model wall-mount units. It
can be built-in at the factory or field installed as an option. ERVF-*5 can be independently adjusted for intake and
exhaust rates.
Manufactured under U.S. Patent Nos. 5,485,878; 5,301,744.
Form No.S3378-1112
Supersedes S3378-712
Page3 of 12
800
700
600
CRVMP-5
WA3S/WL3S Ventilation Airflow
500
400
300
Ventilation Airflow (CFM)
200
100
0
02.557.51012.51517.52022.52527.530
Vent Position
CRVMP-5
1000
900
800
700
600
500
400
Ventilation Airflow (CFM)
300
WA4S/WL4S Ventilation Airflow
Stage #2
Operation
Blower Only
& Stage #1
Operation
Stage #2
Operation
Stage #1
Operation
Blower Only
Ventilation Airflow (CFM)
Form No.S3378-1112
Supersedes S3378-712
Page4 of 12
Form No.S3378-1112
Supersedes S3378-712
Page6 of 12
50A-
511
311
16
78
2ro1
2ro1
3ro1
1-802/032
01A-
51A-
80A-
02A-
3S3AW
2S3LW
030304
527263
111
Z0B-
60B-
3S3AW
51
51
06
02
03
5454060709
5.31
31
91
55
1
3-802/032
111
3-064
82
8383353698
1
111
021
040404
06
020252
03
0505060709
511
929283
2ro1
2ro1
3ro1
111
1-802/032
3-802/032
65
1
51
61
111
12
3-064
03
6464353698
1
111
021
040404
511
434383
2ro1
2ro1
3ro1
111
1-802/032
525252
71
71
111
03
12
03
1
3-064
06
65
1
3-802/032
carrying conductors are in a raceway.
51C-
Z0C-
60C-
90B-
3S3AW
2S3LW
2S3LW
01A-
Z0A-
51A-
50A-
80A-
02A-
3S4AW
2S4LW
51B-
Z0B-
60B-
90B-
3S4AW
2S4LW
90C-
51B-
51C-
Z0C-
60C-
90C-
3S4AW
2S4LW
01A-
Z0A-
51A-
50A-
80A-
02A-
3S5AW
2S5LW
51B-
Z0B-
60B-
90B-
3S5AW
2S5LW
51C-
Z0C-
60C-
90C-
3S5AW
2S5LW
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current
* Top outlet supply option is available only factory installed and only on the selected models.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.
Form No.S3378-1112
Supersedes S3378-712
Page7 of 12
Return Air Acoustical Plenum
O
D
)
R
A
D
A
F
A
WAPR11
Free Blow Acoustical Plenum
WAPFB51
20 1/4"
42 3/8"
13 3/4"
34 1/4"
76"
12 1/8"
MIS-2208 A
Supply Air Acoustical Plenum
WAPS51-G
3 3/4"
1 1/2"
42 1/4"
44"
3 3/4"
1 1/2"
3/8"
9 7/8"
29 7/8"
18 1/2"
1 1/2"
MIS-2284 A
seirosseccAnoitallatsnIlanoitp
noitpircse
riAnrute
munelPlacitsuoc
riAylppuSdetcu
munelPlacitsuoc
riAylppuSwolBeer
munelPlacitsuoc
ledoMroloC
X-11RPAW
4-11RPAW
egieB
yarGeyekcuB
G-15SPAWdezinavlaG091
X-15BFPAW
4-15BFPAW
egieB
yarGeyekcuB
gnippihS
sbL(thgieW
812
46
12"
9 7/8"
5"
14"
14"
12" DIA. HOLES FOR DUCT COLLARS.
DUCT COLLARS FIELD SUPPLIED.
50 3/4"
29 7/8"
6"
MIS-2164
Typical installation with isolation curb, free blow, supply air acoustical plenum & return air acoustical plenum.
Form No.S3378-1112
Supersedes S3378-712
Page8 of 12
WMICF5
ISOLATION CURB
WAPF51 FREE-BLOW
SUPPLY AIR PLENUM
WAPR11 RETURN AIR
ACCOUSTICAL PLENUM
WMICF5
ISOLATION CURB
WAPF51 FREE-BLOW
SUPPLY AIR PLENUM
WAPR11 RETURN AIR
ACCOUSTICAL PLENUM
Patent Pending
MIS-2604
Typical Sound Performance with Installation/Isolation Curbs & Acoustical Plenums
WA/L3S Sound Data Matrix (dBA @ 10 feet)
WA/L4S Sound Data Matrix (dBA @ 10 feet)
WA/L5S Sound Data Matrix (dBA @ 10 feet)
Unit MountingDirect
Supply Air TreatmentGrille
Return Air TreatmentGrille
Blower Only Operation
Compressor Stage 1
Compressor Stage 2 with
ERV High Speed Operation
Indoor Integrated dBA43.835.040.737.232.832.6
Compressor Stage 2
Outdoor Sound Level
Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical varianc es.
Outdoor Sound Level
Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical varianc es.
Outdoor Sound Level
Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical varianc es.
1 Intake and exhaust can be independently adjusted.
2 Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)
3 WMDK Door Kit must be ordered in addition to ERVF Assembly and ECONWMS & color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)
4 Partial Full Flow (75% of Rated Cooling CFM). All ECONWMS versions have 3" deep intake hood.
5 Full Flow (100% of Rated Cooling CFM). ECONWMT2 and 3 have 16" deep intake hood; ECONWMT-5 has 18" deep intake hood.
dellatsnIyrotcaF
.oNedoC
dellatsnIdleiF
.oNtraP
seludoMlortnoCgninoitidnoCriA
SNOITPOLORTNOCELBALIAVA
CPH1CPL2MCC3CAL4RLA5KS 6CDD7
DTSDTSDTSDTSX
DTSDTSDTS
DTSDTSDTS
DTSDTSDTS
STD = Standard equipment for these specified models.
z
zz
zz
DTSH82-AMC
DTSJylnOyrotcaF
DTS
z
V 7ylnOyrotcaF
sledoMllA
edoCdellatsnIyrotcaFtraPdellatsnIdleiF
A/N
1 HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3.
2 LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3.
3 CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the
delay-on-make will be 2-minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also
provides the lockout feature (with 1 retry) for high and/or low-pressure controls, and a 2-minute timed bypass for low-pressure control.
4 LAC. Low ambient control permits cooling operation down to 0°F.
5 ALR. The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low
pressure controls.
6 SK. Start kit standard on all -A single phase models only. Is not used or available for -B or -C three phase models.
7 DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function
to input analog data such as temperature, as well as digital data such as airflow, compressor status or filter status.
Form No.S3378-1112SupersedesS3378-712
Page12 of 12
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Due to our continuous product improvement
policy, all specifications subject to change
without notice.
Before purchasing this appliance, read important energy
cost and efficiency information available from your retailer.
Form No.
S3378
November, 2012
Supersedes: S3378-712
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.