Bard WH611 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE HEAT PUMPS
Model
WH611
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual : 2100-347F Supersedes: 2100-347E File: Volume III Tab 17 Date: 03-27-06
© Copyright 2003
Manual 2100-347F Page 1 of 24
CONTENTS
Getting Other Information and Publications
For More Information ............................................... 3
Wall Mount General
Heat Pump Wall Mount Model Nomenclature ....... 4
Shipping Damage ................................................. 6
General .............................................................. 6
Duct Work ....................................................... 6 & 7
Filters .............................................................. 7
Fresh Air Intake ..................................................... 7
Condensate Drain – Evaporator ........................... 8
Condensate Drain – Condenser ........................... 8
Installation Instructions
Wall Mounting Information .................................... 9
Mounting the Unit .................................................. 9
Wiring – Main Power ........................................... 14
Wiring – Low Voltage Wiring ............................... 14
Optional Outdoor Thermostats Applications ........ 15
Electric Heat Hold-Off ......................................... 16
Thermostat Indicators ......................................... 17
Emergency Heat Position ................................... 17
Compressor Malfunction Light ............................ 17
Start Up
Important Installer Note....................................... 18
Crankcase Heaters ............................................. 18
High Pressure Switch ......................................... 18
Two Speed Outdoor Fan motors ......................... 18
Three Phase Scroll Compressor Start Up........... 18
Phase Monitor..................................................... 19
Service Hints ....................................................... 19
Sequence of Operation ....................................... 19
Pressure Service Ports ....................................... 19
Defrost Cycle .............................................. 19 & 20
Troubleshooting
Solid State Heat Pump Control
Troubleshooting Procedure................................. 21
Checking Temperature Sensor
Outside Unit Circuit ............................................. 22
Temperature vs. Resistance of Temperature ...... 22
Fan Blade Setting Dimensions ........................... 23
Removal of Fan Shroud ...................................... 23
Refrigerant Charge ............................................. 23
Pressure Tables .................................................. 24
Figures
Figure 1 Unit Dimensions .................................. 5
Figure 2 Fresh Air Damper Assembly ................ 7
Figure 3 Condensate Drains .............................. 8
Figure 4 Mounting Instructions ........................ 10
Figure 5 Electric Heat Clearance ..................... 11
Figure 6 Wall Mounting Instructions ................. 12
Figure 7 Wall Mounting Instructions ................. 12
Figure 8 Common Wall Mounting Installations . 13
Figure 9 Unit 24V Terminal Board .................... 14
Figure 10 Compressor Cutoff Thermostat
Wiring ................................................ 15
Figure 11 Compressor Cutoff Thermostat
Wiring ................................................ 15
Figure 12 Electric Heat Hold-Off Wiring ............. 16
Figure 13 Electric Heat Hold-Off Wiring ............. 16
Figure 14 Start Up Procedure Decal .................. 18
Figure 15 Defrost Control Board ........................ 20
Figure 16 Fan Blade Setting .............................. 23
Tables
Table 1 Electric Heat Table ................................ 4
Table 2 Electrical Specifications ........................ 6
Table 3 Thermostat Wire Size ......................... 14
Table 4 Wall thermostat and
Subbase Combinations....................... 17
Table 5 Troubleshooting .................................. 21
Table 6 Fan Blade Dimensions........................ 23
Table 7 Refrigerant Charge ............................. 23
Table 8 Rated CFM and Rated ESP ............... 23
Table 9 Indoor Blower Performance ................ 23
Table 10 Maximum ESP of Operation ............... 23
Table 11 Pressure Table - Cooling .................... 24
Table 12 Pressure Table - Heating .................... 24
Manual 2100-347F Page 2 of 24
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-347F Page 3 of 24
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
WH 61 1 – A 08 X X X X X B
MODEL NUMBER
CAPACITY
38 - 3 Ton 43 - 3½ Ton 49 - 4 ton
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate C - Commercial Ventilator - Motorized w/o Exhaust M - Motorized Fresh Air Damper A - Adjustable Fresh Air Damper
NOTE: All vent options are without exhaust capability. May require separate field supplied barometric relief in building.
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW
COLOR OPTIONS
X - Beige (Standard) 4 - Buckeye Gray
FILTER OPTIONS
X - 1 Inch Throwaway (Standard) W- 1 Inch Washable P - 2 Inch Pleated
COIL OPTIONS
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator
OUTLET OPTIONS
X - Front (Standard)
CONTROL MODULES
and Condenser
TABLE 1
ELECTRIC HEAT TABLE
sledoMA-116HWB-116HWC-116HW
1-0421-8023-0423-8023-064
WKspmAUTBspmAUTBspmAUTBspmAUTBspmAUTB 5 8 9
01
8.02560,711.81008,21------------------
3.33082,728.82054,02------------------
------------7.12006,037.81030,328.01007,03
6.14031,432.63006,52------------------
Manual 2100-347F Page 4 of 24
MIS-1270
BACK VIEW
FIGURE 1
UNIT DIMENSIONS
EFGI J KLMNOPQABCB
ylppuSnruteR
thgieH
H
htpeD
D
htdiW
W
tinU
SIDE VIEWFRONT
VIEW
116HW244/1-228/7-498/7-98/7-928/7-518/7-928/7-34918/5-140361/11-24734/3-442/1-244/1-3348/7-3301
Manual 2100-347F Page 5 of 24
TABLE 2
ELECTRICAL SPECIFICATIONS
TIUCRICELGNIS TIUCRICLAUD
3
.oN
detaR
ledoM
Z0A,00A-116HW 50A 80A 01A
Z0B,00B-116HW 90B
Z0C,00C-116HW 90C
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
1
Based on 75° C copper wire. All wiring must conform to NEC and all local codes.
2
These “minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to
3
the National Electric Code (latest revision), article 310 for power conductor sizing.
more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.
&stloV esahP
3-064 3-064
dleiF
rewoP
stiuriC
1-802/032
1 1-802/032 1-802/032 1-802/032
1-802/032 1-802/032
2ro1 2ro1 2ro1
1
1
1
1
25 47 88 89
63 06
81 23
1
muminiM tiucriC
yticapmA
06
05 07
52 53
2
mumixaM
lanretxE
roesuF
tiucriC
rekaerB
6 001 011 021
4
3
3
8
6
8
2
dleiF
rewoP eriW eziS
01
eriW eziS
01 8 6 6
01
01
01
01
3
muminiM tiucriC
dnuorG
yticapmA
.tkC
.tkC
A
B
---
---
25
62
25
24
25
25
---
---
---
---
---
---
---
---
1
mumixaM
lanretxE
roesuF
tiucriC
rekaerB
.tkC
.tkC
A
B
---
---
06
03
06
05
06
06
---
---
---
---
---
---
---
---
CAUTION: When
2
dleiF
rewoP
eziSeriW
.tkC
A
B
---
---
6
01
6
8
6
6
---
---
---
---
---
---
---
---
2
dnuorG
eziSeriW
.tkC
.tkC
.tkC
A
B
---
---
01
01
01
01
01
01
---
---
---
---
--
---
---
---
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment, required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
Manual 2100-347F Page 6 of 24
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
DUCT WORK
Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work, supply and return, must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 4 and 5 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
FILTERS
A 1-inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 1-inch washable filter and a 2-inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending down the two horizontal tabs on each filter bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service panel.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.
All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air Blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
FIGURE 2
FRESH AIR DAMPER
BLADE IS LOCKED CLOSED FOR SHIPPING.
MIS-938
Manual 2100-347F Page 7 of 24
CONDENSATE DRAIN – EVAPORATOR
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
CONDENSATE DRAINS
CONDENSATE DRAIN – CONDENSER
A hole is provided in the unit base to accept a Drain Connection Kit 8620-160. This allows connection of the unit base pan to a drain if so desired. (See Figure 3 and instructions provided with the 8620-160 kit.) In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
FIGURE 3
EVAPORATOR CONDENSATE DRAIN
Manual 2100-347F Page 8 of 24
CONDENSER CONDENSATE DRAIN
MIS-1278
Loading...
+ 16 hidden pages