Bard WH361, WH-301 User Manual

WALL MOUNTED
INSTALLATION INSTRUCTIONS
PACKAGED HEAT PUMP
Models:
WH301, WH361
© Copyright 2003
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914. . .Moving ahead just as planned.
Manual No.: 2100-193O Supersedes: 2100-193N File: Volume III, Tab 17 Date: 05-04-07
Manual 2100-193O Page 1 of 26
CONTENTS
G
etting Other Information and Publications
For more information,
contact these publishers ........................................3
Wall Mount General Information
Heat Pump Wall Mount Model Nomenclature ........ 4
Shipping Damage .................................................. 4
General ............................................................. 4
Duct Work ...................................................... 4 & 8
Filters ............................................................. 8
Fresh Air Intake ...................................................... 8
Condensate Drain .................................................. 8
Installation Instructions
Wall Mounting Information ..................................... 9
Mounting the Unit................................................... 9
Top Outlet Only ...................................................... 9
Wiring — Main Power .......................................... 15
Wiring — Low Voltage Wiring............................... 15
Low Voltage Connections .................................... 15
Optional Outdoor Thermostat Applications .......... 17
Thermostat Indicator ............................................ 19
Start Up
Important Installer Note........................................ 20
Crankcase Heaters .............................................. 20
Service Hints ........................................................20
Sequence of Operation ........................................20
Pressure Service Ports ........................................ 21
Defrost Cycle ....................................................... 21
Troubleshooting
Solid State Heat Pump Control
Troubleshooting Procedures ................................ 22
Checking Temperature Sensor Outside
Unit Circuit ........................................................... 23
Fan Blade Setting Dimensions ............................ 24
Removal of Fan Shroud ....................................... 24
Refrigerant Charge .............................................. 24
Pressure Tables ................................................... 25
Optional Accessories ...........................................26
Figures
Figure 1 Unit Dimensions ................................... 6
Figure 2 Fresh Air Damper Assembly ................. 8
Figure 3 Mounting Instructions ......................... 10
Figure 4 Electric Heat Clearance ...................... 11
Figure 5 Attaching Top Outlet to Unit ................ 12
Figure 6 Top Outlet Model Mounted ................. 12
Figure 7 Wall-Mounting Instructions ................. 13
Figure 8 Wall-Mounting Instructions ................. 13
Figure 9 Common Wall-Mounting Installations . 14
Figure 10 Low Voltage Wiring ............................. 16
Figure 11 Compressor Cutoff
Thermostat Wiring .............................. 17
Figure 12 Compressor Cutoff
Thermostat Wiring .............................. 17
Figure 13 Electric Heat Hold-Off Wiring ..............18
Figure 14 Electric Heat Hold-Off Wiring ..............18
Figure 15 Start Up Label ..................................... 20
Figure 16 Defrost Control Board ......................... 21
Figure 17 Fan Blade Setting ...............................24
Tables
Table 1 Electric Heat Table ................................5
Table 2 Dimensions of Basic Unit ......................6
Table 3 Electrical Specifications ........................ 7
Table 4 Operating Voltage Range ...................15
Table 5 Thermostat Wire Size ......................... 16
Table 6 Wall Thermostat .................................. 19
Table 7 Troubleshooting .................................. 22
Table 8 Fan Blade Dimensions ....................... 24
Table 9 Suction Line Temperatures ................. 24
Table 10 Indoor Blower Performance ................ 24
Table 11 CFM and ESP..................................... 24
Table 12 Maximum ESP of Operation
Electric Heat Only ............................... 24
Table 13 Cooling Pressures .............................. 25
Table 14 Heating Pressures ..............................25
Table 15 Optional Accessories .......................... 26
Manual 2100-193O Page 2 of 26
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ....................... ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ........................ ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................. ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ................ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue NW Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manufactured under the following U.S. patent numbers:
5,485,878; 5,301,744; 5,002,116; 4,924,934;
4,875,520; 4,825,936
Manual 2100-193O Page 3 of 26
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
WH 36 1 A 10 X X X X X A
MODEL NUMBER
CAPACITY
30 - 2½ Ton 36 - 3 Ton
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate M - Motorized Fresh Air Damper V - Commercial Room Ventilator - Motorized with Exhaust E - Economizer (Internal - Fully Modulating with Exhaust R - Energy Recovery Ventilator - with Exhaust
NOTE: For 0 KW and circuit breakers (230/208 Volt) or pull disconnects (460 Volt) applications, insert 0Z in the KW field of model number.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW
COLOR OPTIONS
X - Beige (Standard) 1 - White 2 - Mesa Brown 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
FILTER OPTIONS
X - 1-Inch Throwaway (Standard) W- 1-Inch Washable P - 2-Inch Pleated
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
COIL OPTIONS X - Standard
1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator
and Condenser
OUTLET OPTIONS
X - Front (Standard) T - Top on WH30 and WH36
Models
CONTROL MODULES
Size of unit for a proposed installation should be based
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
on heat loss calculations made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer
The unit is designed for use with or without duct work.
should adhere to local codes.
Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
DUCT WORK
Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Manual 2100-193O Page 4 of 26
UTB
TABLE 1
ELECTRIC HEAT TABLE
1-0421-8023-0423-8023-0641-0421-8023-0423-8023-064
sledoMA-103HWB-103HWC-103HWA-163HWB-163HWC-163HW
WKAUTBAUTBAUTBAUTBAUTBAUTBAUTBAUTBAUTBA
51 5.26002151.4500483
016.14031432.63006526.14031432.6300652
58.02560711.81008218.02560711.8100821
64.41005025.21063512.7574024.41005025.21063512.757402
510.81002152.63002152.13004830.8100215
97.12006037.81030328.01007037.12006037.81030328.0100703
Manual 2100-193O Page 5 of 26
TABLE 2
FIGURE 1
UNIT DIMENSIONS
EFGIJKLMNOPQRSTABCB
DIMENSIONS OF BASIC UNIT (NOMINAL)
ylppuSnruteR
thgieH
)H(
htpeD
)D(
htdiW
)W(
ledoM
Manual 2100-193O Page 6 of 26
03HW
FRONT VIEW BACK VIEWSIDE VIEW
002.83521.71365.0788.788.7288.3188.7200.0405.8157.5239.7157.6257.8252.9200.7257.291.9357.2241.991.400.2100.5
OPTIONAL TOP OUTLET (FACTORY INSTALLED ONLY) FOR WH30 AND WH36 MODELS ONLY.
63HW
*
2
---
---
---
---
---
---
---
---
eziSeriW
dnuorG
01
---
---
01
---
---
---
---
---
---
---
---
---
---
---
---
---
01
01
---
---
---
01
01
---
---
---
---
---
---
---
---
---
---
---
---
rewoPdleiF
eziSeriW
---
2
---
esuFlanretxE
tiucriCro
mumixaM
rekaerB
---
1
---
eriW
eriW
tiucriC
---
ATKCBTKCATKCBTKCATKCBTKCATKCBTKC
---
eziS
01
eziS
8
rekaerB
530508
yticapmA
muminiM
tiucriC
4
dnuorG
2
rewoP
TABLE 3
dleiF
2
lanretxE
roesuF
mumixaM
1
ELECTRICAL SPECIFICATIONS
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
210101
210101
025203
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
010101
01
8
520405
---
---
---
---
---
---
---
---
------
---
---
---
---
---
---
---
---
---
41
210101
41
210101
8
51
025203
---
01
--­8
---
03
---
05
---
62
---
05
01
8
8
4
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
01
01
04
01
--­6
---
03
---
06
---
62
---
35
01
8
6
4
060809
6
6
06
06
25
35
8
4
---
---
---
---
---
---
---
---
---
---
010101
01
888
520405
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
01
41
41
51
05
4
yticapmA
muminiM
tiucriC
42
.oN
detaR
111
dnAstloV
esahP
stiucriC
rewoP
dleiF
Z0A-,00A-103HW
91
05
67
111
1-802/032
50A-
Z0B-,00B-103HW
ledoM
3 01A-
01
91
111
42
62
723597
1
1
1
1-802/032
73
64
3-802/032
02
837405
38
2r
2ro1
111
o1
3-802/032
3-064
60B-
60C-
Z0C-,0
0C-103HW
3 90B-
3 90C-
50A-
Z0A-,00A-163HW
5 51C-
3 01A-
60B-
Z0B-,00B-163HW
5 51A-
11
0252
62
1
111
1
3-064
60C-
Z0C-,00C-163HW
5 51C-
5 51B-
3 90B-
3 90C-
National Electric Code (latest revision), Article 310 for power conductor sizing.
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75° copper wire. All wiring must conform to the National Electrical Code and all local codes.
3 Maximum KW that can operate with heat pump on these "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the
power conductor sizing.
4 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest version), Article 310 for
310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Not available on dehumidification models.
5
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table
Not available in top outlet version.
Manual 2100-193O Page 7 of 26
Refer to Table 12 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the first three (3) feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3, 4, 7 & 8 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service panel.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.
All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
CAUTION
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inches.
Any grille that meets the 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG-2 through RG-5 or RFG-2 through RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 1-inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 1-inch washable filter and a 2-inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the two inch filter by loosening two screws in each bracket assembly and sliding the brackets apart to the required width and retightening the four screws.
FIGURE 2
FRESH AIR DAMPER ASSEMBLY
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Manual 2100-193O Page 8 of 26
Loading...
+ 18 hidden pages