Bard WH242, WH183 User Manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE HEAT PUMP
Models
WH183 WH242
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual : 2100-373A Supersedes: 2100-373 File: Volume III Tab 17 Date: 05-13-02
© Copyright 2002
Contents
Getting Other Informations and Publications ........ 1
Wall Mount General Information ............................. 2
Heat Pump Wall Mount Model Nomenclature.......... 2
Shipping Damage .................................................... 2
General ................................................................ 2
Duct Work................................................................ 4
Filters ................................................................ 5
Fresh Air Intake........................................................ 5
Condensate Drain .................................................... 5
Installation Instructions ........................................... 6
Wall Mounting Information ....................................... 6
Mounting the Unit ..................................................... 6
Wiring – Main Power.............................................. 10
Wiring – Low Voltage Wiring ..................................11
Compressor Cutoff Thermostat and
Outdoor Thermostats ..............................................1 1
Heat Anticipation.................................................... 12
Thermostat Indicator Lamps .................................. 12
Compressor Malfunction Light ............................... 12
Figures
Figure 1 Unit Dimensions...................................... 3
Figure 2 Fresh Air Damper Assembly ................... 5
Figure 3 Mounting Instructions.............................. 7
Figure 4 Wall Mounting Instructions...................... 8
Figure 5 Wall Mounting Instructions...................... 8
Figure 6 Common Wall Mounting Installations...... 9
Figure 7 Unit 24V Terminal Board ....................... 10
Figure 8 Compressor Cutoff and Outdoor
Thermostat Wiring ................................. 11
Figure 9 Start Up Procedure Decal ..................... 13
Figure 10 Defrost Control Board ........................... 14
Figure 11 Fan Blade Setting ................................. 17
Figure 12 Compressor Burnout
Cleanup Procedure ............................... 13
Start Up ................................................................... 13
Important Installer Note ......................................... 13
Crankcase Heaters................................................ 13
Service Hints ......................................................... 13
Sequence of Operation.......................................... 13
Pressure Service Ports .......................................... 14
Defrost Cycle ......................................................... 14
Troubleshooting ..................................................... 15
Solid State Heat Pump Control
Troubleshooting Procedure ................................... 15
Checking Temperature Sensor Outside
Unit Circuit ............................................................. 16
Fan Blade Setting Dimensions .............................. 17
Removal of Fan Shroud......................................... 17
Refrigerant Charge ................................................ 17
Pressure Tables ..................................................... 18
Optional Accessories............................................. 19
Tables
Table 1 Electric Heat Table .................................. 1
Table 2 Fuse, HACR Breakers, Wire Size........... 4
Table 3 Thermostat Wire Size ............................11
Table 4 Wall Thermostat and Subbase
Combinations ........................................ 12
Table 5 Troubleshooting .................................... 15
Table 6 Fan Blade Dimensions.......................... 17
Table 7 System Charge Ratings ........................ 17
Table 8 Indoor Blower Performance .................. 17
Table 9 Rated CFM and Raded ESP................. 17
Table 10 Maximum ESP of Operation ................. 17
Table 11 Pressure Table ...................................... 18
Table 12 Pressure Table ...................................... 18
Table 13 Optional Accessories ............................ 19
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ......................ANSI/NFPA 70
Standard for the Installation ................. ANSI/NFPA
90A of Air Conditioning and Ventilating Systems
Standard for Warm Air.........................ANSI/NFPA
90B Heating and Air Conditioning Systems
Load Calculation for.............................ACCA Manual J
Residential Winter and Summer Air Conditioning
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAEAmerican Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
Duct Design for Residential .................ACCA Manual
D Winter and Summer Air Conditioning and Equipment Selection
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-373 Page 1
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
MODEL NUMBER
CAPACITY 18 - 1 1/2 Ton 24 - 2 Ton 36 - 3 Ton 48 - 4 Ton 60 - 5 Ton
VOLTS & PHASE A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
NOTE: For 0 KW and circuit breakers (230/208 Volt) or pull disconnects (460 Volt) applications, insert 0Z in the KW field of model number.
REVISIONS
WH 24 2 — A 08 X X X X X B
COLOR OPTIONS X - Beige (Standard) 1 - White 2 - Mesa Tan 3 - Colonial White 4 - Buckeye Gray
FILTER OPTIONS X - One Inch Throwaway (Standard) W- One Inch Washable P - Two Inch Pleated
KW
VENTILATION OPTIONS X - Barometric Fresh Air Damper
(Standard) B - Blank-off Plate M - Motorized Fresh Air Damper V - Commercial Room Ventilator
-
Motorized with Exhaust E - Economizer (Internal) - Fully
Modulating with Exhaust R - Energy Recovery Ventilator -
with Exhaust
CONTROL MODULES
(See Chart Below)
COIL OPTIONS X- Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator
and Condenser
OUTLET OPTIONS X- Front (Standard) T - Top (on WH30 and
WH36 models.
TABLE 1
ELECTRIC HEAT TABLE
sledoMA-381HWA-242HWB-242HWC-242HW
1-0421-8021-0421-8023-0423-8023-064
WKAUTBAUTBAUTBAUTBAUTBAUTBAUTB 4 8
7.61056314.41042017.61056314.4104201
3.33003728.82574023.33003728.8257402
6
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
4.41005025.21063512.757402
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 1 for information on codes and standards.
Manual 2100-373 Page 2
MIS-992
FIGURE 1
UNIT DIMENSIONS
Manual 2100-373 Page 3
TABLE 2
ELECTRICAL SPECIFICATIONS
TIUCRICELGNIS
j
mumixaM detaR stloV
dna
ledoM
Z0A,00A-381HW 40A
l 80A
Z0A,00A-242HW 40A
l 80A
Z0B,00B-242HW 60B
Z0C,00C-242HW 60C
Maximum size of the time delay fuse or HACR type circuit breaker for protection
Q
of field wiring conductors. Based on 75° C copper wire. All wiring must conform to NEC and all local
R
codes. Maximum KW that can operate with heat pump on.
S
These Minimum Circuit Ampacity values are to be used for sizing the field
T
power conductors. Refer to the National Electric Code (latest revision), article 310, for power conductor sizing.
power conductor circuit is run through one conduit the conductors must be derated. Pay special attention to note 89 of table 310 regarding Ampacity Adjustment Factors when more than 3 are in a raceway.
esahP
1-802/032
1-802/032
1-802/032
3-064
dleiF.oN
rewoP
stiucriC
1 1 1
1 1 1
1 1
1 1
m
muminiM tiucriC
yticapmA
71 83 95
81 93 06
51 33
8
71
CAUTION: When more than one field
lanretxE
roesuF
tiucriC
rekaerB
52 04 06
52 04 06
02 53
51 02
k
6
6
8
dleiF
rewoP
21 01
21 01
21
41 21
k
dnuorG
eziSeriW
eziSeriW
21 01 01
21 01 01
21 01
41 21
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
DUCT WORK
Any heat pump is more critical of proper operating charge and an adequate duct system that a straight air conditioning unit. All duct work, supply and return, must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide
Manual 2100-373 Page 4
to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 10 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Pages Wall Mounting Instructions and Figure 3 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture from entering the wall cavity.
CAUTION
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inches.
Any grille that meets the 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 thru RG5 or RFG2 thru RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 1 inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 1 inch washable filter and a 2 inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2 inch filter by loosening two (2) screws in each bracket assembly and sliding the brackets apart to the required width and retightening the four (4) screws.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service panel.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.
All capacity, efficiency, and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
FIGURE 2
FRESH AIR DAMPER ASSEMBLY
BLADE IS LOCKED CLOSED FOR SHIPPING
MIS-938
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Manual 2100-373 Page 5
INST ALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation, but is not required.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the unit being installed.
4. The unit is suitable for 0 inch clearance from the unit, and from the supply and return air ducts.
MOUNTING THE UNIT
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.
2. Locate and mark lag bolt locations and bottom mounting bracket location, if desired. See Figure 3.
3. Mount bottom mounting bracket, if used.
4. Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.
5. Position unit in opening and secure with 5/16 lag bolts. Use 5/16” diameter flat washers on the lag bolts.
6. Secure rain flashing to wall and caulk across entire length of top. See Figure 3.
7. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
8. On side by side installations, maintain a minimum of 20 inches clearance on right side of unit to allow access to control panel and heaters, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
Manual 2100-373 Page 6
FIGURE 3
MOUNTING INSTRUCTIONS
Manual 2100-373
Page 7
MIS-353
FIGURE 4
WALL MOUNTING INSTRUCTIONS
SEE FIGURE 3 – MOUNTING INSTRUCTIONS
FIGURE 5
WALL MOUNTING INSTRUCTIONS
SEE UNIT DIMENSIONS, FIGURE 1, FOR ACTUAL DIMENSIONS
MIS-548
MIS-549
Manual 2100-373 Page 8
FIGURE 6
COMMON WALL MOUNTING INSTALLATIONS
MIS-550
Manual 2100-373 Page 9
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
UNIT 24V TERMINAL BOARD
The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut a padlock may be placed through the hole in the tab preventing entry.
FIGURE 7
IMPORTANT NOTE: Only the thermostat and subbase combinations as shown in Figure 7 will work with this
equipment. The thermostat and subbase must be matched, and the correct operation can be assured only be proper selection and application of these parts.
Manual 2100-373 Page 10
WIRING – LOW VOLTAGE WIRING
230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
TAP RANGE
240 253 - 216 208 220 - 187
NOTE: The voltage should be measured at the field
power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
Nine (9) wires should be run from thermostat subbase to the 24V terminal board in the unit. A nine conductor, 18 gauge copper, color-coded thermostat cable is recommended.. The connection points are shown in Figure 7.
TABLE 3
THERMOSTAT WIRE SIZE
mumixaM
remrofsnarT
AVALFeguaGeriW
553.2
eguag02 eguag81 eguag61 eguag41 eguag21
ecnatsiD
teeFnI
54 06
001 061
052
COMPRESSOR CUTOFF THERMOSTAT AND OUTDOOR THERMOSTATS
Heat pump compressor operation at outdoor temperatures below 0° F are neither desirable not advantageous in terms of efficiency. Since most equipment at time of manufacture is not designated for any specific destination of the country and most of the equipment is installed in areas not approaching the lower outdoor temperature range, the compressor cutoffs are not factory installed.
Outdoor thermostats are available to hold off various banks of electric heat until needed as determined by outdoor temperature. The set point of either type of thermostat is variable with geographic region and sizing of the heating equipment to the structure. Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points.
See Figure 8 for compressor cutoff and outdoor thermostat wiring.
FIGURE 8 – COMPRESSOR CUTOFF AND OUTDOOR THERMOSTAT WIRING
4 & 8 KW 1 Phase – 6 KW 3 Phase
MIS-409
Manual 2100-373 Page 11
HEAT ANTICIPATION
Group A and Group B thermostats shown in Table 4 have a fixed heat anticipator for stage 1 with no adjustment required. Stage 2 has an adjustable anticipator for the W2 connection and fixed for the W3 connection. Both the W2 and W3 circuits are controlled by the stage 2 bulb. The only heat anticipator that needs to be checked is stage 2 and it should be set to match the load carried by the W2 circuit. The normal factory wiring provides for only one electric heat contactor to be controlled by W2, and the anticipator should be set at .40A. If special field wiring is done, it is best to actually measure the load but a good rule is .40A for each heat contactor controlled by W2.
WALL THERMOSTAT AND SUBBASE COMBINATIONS
tatsomrehTesabbuSserutaeFtnanimoderP
540-3048
)1671A148T(
710-3048
)9211R478T(
810-3048
)4201N478T(
---
900-4048
)1811L476Q(
010-4048
)1621F476Q(
THERMOSTAT INDICATOR LAMPS
The green lamp marked “Check” will come on if there is any problem that prevents the compressor from running when it is supposed to be.
COMPRESSOR MALFUNCTION LIGHT
Actuation of the green “Check” lamp is accomplished by a relay output from the heat pump control board which is factory installed. Any condition such as loss of charge, high head pressure, etc., that will prevent compressor from operating will cause green lamp to activate. This is a signal to the operator of the equipment to place system in emergency heat position.
TABLE 4
blubyrucreM;taeh.gts2;looc.gts1
revoegnahclaunaM
blubyrucreM;taeh.gts2;looc.gts2
revoegnahclaunaM
blubyrucreM;taeh.gts2;looc.gts2
revoegnahclaunaMrootuA
240-3048
)0701G1158T(
940-3048
)083-39F1(
IMPORTANT NOTE: The thermostat and subbase combinations shown
above incorporate the following features: Man-Auto fan switch, Off-Heat-Cool-Em. Heat Switch, and two (2) indicator lamps; one for emergency heat and one for compressor malfunction.
---
---
taeh.gts2;looc.gts1
elbammargorP-noNcinortcelE
revoegnahclaunaMrootuA
taeh.gts3;looc.gts2
cinortcelEelbammargorP
revoegnahclaunaMrootuA
Manual 2100-373 Page 12
ST ART UP
IMPORTANT INSTALLER NOTE
For improved start up performance, wash the indoor coil with a dish detergent.
CRANKCASE HEATERS
WH241 units are provided with compressor crankcase heat.
These models have an insertion well-type heater located in the lower section of the compressor housing. This is a self-regulating type heater that draws only enough power to maintain the compressor at a safe temperature.
Some form of crankcase heat is essential to prevent liquid refrigerant from migrating to the compressor causing oil pump out on compressor start up and possible valve failure due to compressing a liquid.
The decal in Figure 9 is affixed to all outdoor units detailing start up procedure. This is very important.
Please read carefully.
SERVICE HINTS
1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system which shortens equipment service life as well as increasing operating costs.
2. Switching to heating cycle at 75° F or higher outside temperature may cause a nuisance trip of the remote reset high pressure switch. Turn thermostat off, then on, to reset the high pressure switch..
3. The heat pump wall thermostats perform multiple functions. Be sure that all function switches are correctly set for the desired operating mode before trying to diagnose any reported service problems.
4. Check all power fuses or circuit breakers to be sure they are the correct rating.
5. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation.
HEATING – a 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing “Auto” changeover from cycle to cycle, and the other constantly energizing solenoid coil during heating season and thus eliminating pressure equalization noise except during defrost, are to be used. On “Auto” option, a circuit is completed from R-W1 and R-Y on each heating “ON” cycle energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat Pump heating cycle now in operation. The second option has no “Auto” changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in “Heat” position, the “B” terminal being constantly energized from R. A thermostat demand for heat completes R-Y circuit pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.
FIGURE 9
IMPORTANT
THESE PROCEDURES MUST BE FOLLOWED A T INITIAL START UP AND AT ANY TIME POWER HAS BEEN
REMOVED FOR 12 HOURS OR LONGER.
TO PREVENT COMPRESSOR DAMAGE WHICH MAY RESULT FROM THE PRESENCE OF LIQUID REFRIGERANT IN THE COMPRESSOR CRANK­CASE:
1. MAKE CERTAIN THE ROOM THERMOSTAT IS IN THE OFF POSITION. (THE COMPRESSOR IS NOT TO OPERATE.)
2. APPLY POWER BY CLOSING THE SYSTEM DISCONNECT SWITCH. THIS ENERGIZES THE COMPRESSOR HEATER WHICH EVAPORATES THE LIQUID REFRIGERANT IN THE CRANK­CASE.
3. ALLOW 4 HOURS OR 60 MINUTES PER POUND OF REFRIGERANT IN THE SYSTEM AS NOTED ON THE UNIT RATING PLATE, WHICHEVER IS GREATER.
4. AFTER PROPERL Y ELAPSED TIME THE THERMOSTAT MAY BE SET TO OPERATE THE COMPRESSOR.
5. EXCEPT AS REQUIRED FOR SAFETY WHILE SERVICING DO NOT OPEN SYSTEM
DISCONNECT SWITCH.
7961-061
Manual 2100-373 Page 13
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure curves can be found later in the manual covering all models on both cooling and heating cycles. It is imperative to match the correct pressure curve to the unit by model number.
DEFROST CYCLE
The defrost cycle is controlled by temperature and time on the solid state heat pump control. See Figure 10.
When the outdoor temperature is in the lower 40° F temperature range or colder, the outdoor coil temperature is 32° F or below. This coil temperature is sensed by the coil sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30° F or below, the coil sends a signal to the control logic of the heat pump control and the defrost timer will start.
After 30 minutes at 30° F or below, the heat pump control will place the system in the defrost mode.
During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57° F, the coil sensor will send a signal to the heat pump control which will return the system to heating operations automatically.
If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 10 minutes.
There are three settings on the heat pump control – 30 minute, 60 minute, and 90 minute. Models are shipped wired on the 30 minute setting for greatest operating
economy. If special circumstances require a change to another time, remove wire connected to terminal 30 and reconnect to desired terminal. Refer to Figure 10. The manufucturer’s recommendation is for 3 minute defrost cycles.
There is a cycle speed up jumper on the control. This can be used to reduce the time between defrost cycle operation without waiting for time to elapse.
Use a small screwdr4iver or other metallic object, or another 1/4 inch QC, to short between the SPEEDUP terminals to accedlerate the HPC timer and initiate defrost.
Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals. It may take up to 10 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start.
As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and run through the 1 minute maximum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence.
There is an initiate defrost jumper (sen jump) on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature. This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region.
By placing a jumper across the SEN JMP terminals (a 1/ 4 inch QC terminal works best) the defrost sensor mounted on the outdoor coil is shunted out and will activate the timing circuit. This permits the defrost cycle to be checked out in warmer weather conditions without the outdoor temperature having to fall into the defrost region.
Manual 2100-373 Page 14
FIGURE 10
DEFROST CONTROL BOARD
In order to terminate the defrost test the SEN JMP jumper must be removed. If left in place too long the compressor could stop due to the high pressure control opening because of high pressure condition created by operating in the cooling mode with outdoor fan off. Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition.
There is also a 5 minute compressor time delay function built into the HPC. This is to protect the compressor from short cycling conditions. In some instances it is helpful to the service technician to override or speed up this timing period, and shorting out the SPEEDUP terminals for a few seconds can do this.
MIS-1174
TROUBLESHOOTING
SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE
1. Turn on AC power supply to indoor and outdoor units.
2. Turn thermostat blower switch to “fan on” – the indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.)
TROUBLESHOOTING
MOTPMYSSESUACELBISSOPKCEHCOTTAHWRIAPERROKCEHCOTWOH
rotcatnocrosserpmoC
ezigrenetonseod
)gnitaehrognilooc(
noitcetorp
evitcefed
rotomroodtuonaF
gnilooc(nurtonseod
tpecxegnitaehro
)tsorfedgnirud
evitcefed
ezigreneton
tsorfed
tsorfedfo
seodevlavgnisreveR
)ylnognitaeh(
evitcefed
otniogtonlliwtinU
)ylnognitaeh(
tuoemoctonlliwtinU
)ylnognitaeh(
evitcefed
evitcefed
gniriwtiucriclortnoCtanoitcennocRrofkcehC
tuokcolrosserpmoCneewtebV42rofkcehC.1
elcyctrohsrosserpmoC
lortnocpmuptaeH
evitcefedrotcatnoCliocdetrohsroneporofkcehC
evitcefedrotoMdetrohsroneporofkcehC
evitcefedroticapacrotoM.gnitarroticapackcehC
lortnocpmuptaeH
dionelosevlavgnisreveR
evitcefedlioc
lortnocpmuptaeH
rorosneserutarepmeT
lortnocpmuptaeh
rorosneserutarepmeT
lortnocpmuptaeh
TABLE 5
.gnidniw
gnidniwrotom
.roticapac
C-Bdna
.etunimeno
3. Turn thermostat blower switch to “auto” position. Indoor blower should stop.
4. Set system switch to “heat” or “cool”. Adjust thermostat to call for heat or cool – the indoor blower, compressor and outdoor fan should start.
NOTE: If there was no power to 24 volt transformer,
the compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.
C-RneewtebV42dna,tinu
lortnocpmuptaehnoC-1L
.hctiws
hgihssorcakcehC.2
.hctiwserusserp
C-CCneewtebV42rofkcehC
lortnocpmuptaehnoC-Ydna
elbissoprehtollakcehC
560-0012launaM.sesuac
detrohsroneporofkcehC
noyalernafssorcakcehC
)CN-moC(lortnocpmuptaeh
liocdetrohsroneporofkcehCliocdionelosecalpeR
C-VRneewtebV42rofkcehC
erutarepmrettcennocsiD
repmujdnadraobmorfrosnes
slanimretpudeepsssorca
sihT.slanimretpmujnesdna
ogottinuehtesuacdluohs
nihtiwelcyctsorfedahguorht
pudeepsssorcarepmuJ
esuacdluohssihT.slanimret
tsorfedfotuoemocottinueht
.etunimenonihtiw
lortnocpmuptaeh
erusserphgihteserotniaganodnaffo
.hctiwserusserphgihecalper,teser
evomeR.C-CCneewtebraeppadluohs
.sdnoces01retfarepmujpudeeps
lortnocpmuptaehecalpeR
rotcatnocecalpeR
rotomecalpeR
roticapacecalpeR
lortnocpmuptaehecalpeR
gniriwtiucriclortnockcehC.1
lortnocpmuptaehecalpeR.2
rosneserutarepmet
lortnocpmuptaehecalper
.rosneserutarepmret
.lortnocpmuptaehecalper
rewopottinuroodtuootnoitcennocRnuR
tatsomrehtnrutC-LneewtebegatlovonfI.1
tonlliwdnaneposihctiwserusserphgihfI.2
deepsrepmuj,C-CCnewwtebegatlovonfI
rewopsdnoces01nihtiwdnalanimretpu
ecalper,elcyctsorfedhguorhtseogtinufI.1
,elcyctsorfedhguorhtogtonseodtinufI.2
ecalper,elcyctsorfedfotuosemoctinufI.1
,elcyctsorfedfotuoemoctonseodtinufI.2
Manual 2100-373 Page 15
CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT.
1. Disconnect temperature sensor from outdoor coil.
2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.
TEMPERATURE F VS RESISTANCE R OF TEMPERATURE SENSOR
F R F R F R
-25.0
-24.0
-23.0
-22.0
-21.0
-20.0
-19.0
-18.0
-17.0
-16.0
-15.0
-14.0
-13.0
-12.0
-11.0
-10.0
-9.0
-8.0
-7.0
-6.0
-5.0
-4.0
-3.0
-2.0
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
196871 190099 183585 177318 171289 165487 159904 154529 149355 144374 139576 134956 130506 126219 122089 118108 114272 110575 107010 103574 100260
97064 93981 91008 88139 85371 82699 80121 77632 75230 72910 70670 68507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077
25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0
33.0
34.0
35.0
36.0
37.0
38.0
39.0
40.0
41.0
42.0
43.0
44.0
45.0
46.0
47.0
48.0
49.0
50.0
51.0
52.0
53.0
54.0
55.0
56.0
57.0
58.0
59.0
60.0
61.0
62.0
63.0
64.0
65.0
66.0
67.0
68.0
69.0
70.0
71.0
72.0
73.0
74.0
3. Check resistance reading to chart of resistance use ambient temperature. (Tolerance of part is ± 10%.)
4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the heat pump control.
5. If sensor is out of tolerance, shorted, open or reads very low ohms then it should be replaced
39898 38757 37652 36583 35548 34545 33574 32634 31723 30840 29986 29157 28355 27577 26823 26092 25383 24696 24030 23384 22758 22150 21561 20989 20435 19896 19374 18867 18375 17898 17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762
75.0
76.0
77.0
78.0
79.0
80.0
81.0
82.0
83.0
84.0
85.0
86.0
87.0
88.0
89.0
90.0
91.0
92.0
93.0
94.0
95.0
96.0
97.0
98.0
99.0
100.0
101.0
102.0
103.0
104.0
105.0
106.0
107.0
108.0
109.0
110.0
111.0
112.0
113.0
114.0
115.0
116.0
117.0
118.0
119.0
120.0
121.0
122.0
123.0
124.0
10501 10247 10000
9760 9526 9299 9077 8862 8653 8449 8250 8057 7869 7686 7507 7334 7165 7000 6840 6683 6531 6383 6239 6098 5961 5827 5697 5570 5446 5326 5208 5094 4982 4873 4767 4663 4562 4464 4367 4274 4182 4093 4006 3921 3838 3757 3678 3601 3526 3452
Manual 2100-373 Page 16
FAN BLADE SETTING DIMENSIONS
.P.S.E
HnI
2
O
,381HW
242HW
yrD/ teW
0.
1.
2.
3.
4.
5.
6.
0201 069 568 028 537 516
--
/ / / / / / /
579 509 008 537 056 535
--
Shown in the drawing below are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be check and blade adjusted in or out on the motor shaft accordingly.
FIGURE 11
TABLE 6
The suction line temperatures in Table 7 are based upon 80° F dry bulb/67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.
TABLE 8
INDOOR BLOWER PERFORMANCE
CFM @ 230V
ledoM
381HW 242HW
noisnemiD
A
00.1
TABLE 9
REMOVAL OF THE FAN SHROUD
1. Disconnect all power to unit.
2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3. Remove screws (9) holding fan shroud to condenser
ledoM
381HW05604.527---575 242HW00802.059---007
* Rated CFM and ESP on high speed tap
detaR
*MFC
detaR
*PSE
dednemmoceR
egnaRwolfriA
.
and bottom.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud assembly out the left side of the unit.
6. Service motor/fan as needed.
MAXIMUM ESP OF OPERATION
TABLE 10
7. Reverse steps to reinstall.
ledoMPSE
REFRIGERANT CHARGE
The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 7.
381HW 242HW
242HW
242HW
00A 40A 80A
00B 60B
00C 60C
05.
05.
04.
05.
05.
05.
05.
TABLE 7
(Temperatures °F)
o
DO
59
85-65 95-75
28oDO
erutarepmeT
erutarepmeT
56-36 76-56
ledoM
381HW 242HW
detaR wolfriA
056 008
Values shown are for units equipped with standard throwaway filter or 1 washable filter. Derate ESP by .15 for 2 pleated filter.
Manual 2100-373 Page 17
TABLE 11 – PRESSURE TABLE
COOLING
ledoM
381HW
242HW
Air T emperature Entering Outdoor Coil °F
riAnruteR
erutarepmeTerusserP5708580959001501011511
BD.ged57
BW.ged26
BD.ged08
BW.ged76
BD.ged58
BW.ged27
BD.ged57
BW.ged26
BD.ged08
BW.ged76
BD.ged58
BW.ged27
ediSwoL
ediShgiH
ediSwoL
ediShgiH
ediSwoL
ediShgiH
ediSwoL
ediShgiH
ediSwoL
ediShgiH
ediSwoL
ediShgiH
77
87
08
18
38
48
68
78
391
902
422
042
552
172
782
203
28
48
58
78
98
09
29
39
891
412
032
642
262
872
492
013
88
09
29
49
59
79
99
001
502
222
832
552
172
882
403
123
57
67
77
97
08
18
38
48
612
922
242
652
172
682
203
813
08
18
38
48
58
78
88
09
122
532
842
362
872
392
013
723
68
88
98
09
29
39
59
79
922
342
752
272
882
403
123
833
98 813
59 623
201 733
68 633
29 443
99 653
TABLE 12 – PRESSURE TABLE
HEATING
riAnruteR
ledoM
381HW07
242HW07
Low Side Pressure ± 2 PSIG High Side Pressure ± 5 PSIG
T ables are based upon rated CFM (airflow) across the evaporator coil and should be found under section titled Refrigerant Charge elsewhere in manual. If there is any doubt as to correct operation charge being in the system, the charge should be removed, system evacuated, and recharged to serial plate instructions.
erutarepmeTerusserP0501517102520353045474055506
ediSwoL
02
42
72
ediShgiH
871
181
481
ediSwoL
03
03
13
ediShgiH
851
851
951
Air T emperature Entering Outdoor Coil °F
13
23
53
93
44
94
981
191
491
102
802
612
23
33
43
73
14
54
261
461
761
571
481
591
45
95
26
56
522
532
932
942
05
65
95
36
802
322
032
142
17
87
752
072
17
97
062
182
Manual 2100-373 Page 18
TABLE 13
OPTIONAL ACCESSORIES
LEDOMNOITPIRCSED
40A-A20HWHE 80A-A20AWHE
60B-41HWHE
60C-B42HWHE
2-POB
2-DAFB
2-DAFM
2-VRC
2-MFIE
42A-VREW
3-HMC 7-HMC 9-HMC
41-HMC 51-MHC
A20-BCMW A30-BCMW B20-CBMW C10-CBMW
WH183-A
segakcaPretaeH segakcaPretaeH segakcaPretaeH segakcaPretaeH
etalPffOknalB
repmaDriAhserFcirtemoraB
repmaDriAhserFdezirotoM
tsuahxEhtiwrotalitneVmoorssalC
tsuahxEhtiwrezimonocE
rotalitneVyrevoceRygrenE
)CPL(lortnoCerusserPwoL
)CAL(lortnoCtneibmAwoL
CPL+CAL
)TDO(tatsomrehTroodtuO
)KS(tiKtratS
tiKrekaerBtiucriC tiKrekaerBtiucriC tiKrekaerBtiucriC
tiKtcennocsiDlluP
X X
X X X X X X
X X X X X
X
WH242-A
X X
X X X X X X
X X X X X
X
WH242-B
X
X X X X X X
X X X
X
WH242-C
X X
X X X X
X
X
Manual 2100-373 Page 19
Loading...