Never use this device as a sensing device for personnel protection. Doing so could lead to
serious injury or death. This device does not include the self-checking redundant circuitry necessary
to allow its use in personnel safety applications. A sensor failure or malfunction can cause either an
energized or de-energized sensor output condition.
1.1 Models
• Easy to set up and use with a 2-line, 8-character display
• Various sizes of visible red laser, depending on target size, distance,
and color characteristics
• Sensing range options up to 1 meter
• IO-Link v1.1
Information about additional L-GAGE LE models, such as analog output models, is available at
www.bannerengineering.com.
1.2 Overview
The L-GAGE LE250/550 IO-LINK Laser Gauging Sensor is a visible, bore-sighted laser displacement sensor designed for
precise, color-insensitive measurements. The LE series of sensors includes models covering various ranges, spot sizes, and
measurement performance.
A 2-line LCD shows the real-time distance measurement, in either millimeters or inches, and provides an intuitive interface
for easy sensor setup.
See Factory Default Settings on page 25 for a list of sensor default settings.
Models with current or voltage analog outputs are available.
www.bannerengineering.com - Tel: 763.544.31643
Power LED
Indicator
Discrete Output 1
LED Indicator
Display
Discrete Output 2
LED Indicator
Push Buttons
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
1.2.1 Features and Indicators
Figure 1. LE IO-Link Sensor Features
1.2.2 Display
Three LED indicators provide ongoing indication of the sensing
status.
Power LED Indicator
Solid Green = Normal operation, power On and laser On
Flashing Green (1 Hz) = Power On and laser Off (laser enable
mode)
Discrete Output LED Indicators
Solid Amber = Discrete Output is On
Off = Discrete Output is Off
The display is a 2-line, 8-character LCD. The main screen is
the Run mode screen, which shows the real-time distance
measurement.
Figure 2. LE550 Display in Run Mode
1.2.3 Buttons
Use the sensor buttons Down, Up, Enter, and Escape to program the sensor and to access sensor information.
Down and Up Buttons
Press Down and Up to:
• Access the Quick Menu from Run mode
• Navigate the menu systems
• Change programming settings
When navigating the menu systems, the menu items loop.
Press Down and Up to change setting values. Press and hold the buttons to cycle through numeric values.
After changing a setting value, it slowly flashes until the change is saved using the Enter button.
Enter Button
Press Enter to:
• Access the Sensor Menu from Run mode
• Access the submenus
• Save changes
In the Sensor Menu, a check mark
accesses a submenu.
Press Enter to save changes. New values flash rapidly and the sensor returns to the parent menu.
in the lower right corner of the display indicates that pressing Enter
4www.bannerengineering.com - Tel: 763.544.3164
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
Escape Button
Press Escape to:
• Leave the current menu and return to the parent menu
• Return to Run mode from the Quick Menu
Important: Pressing Escape discards any unsaved programming changes.
In the Sensor Menu, a return arrow in the upper left corner of the display indicates that pressing Escape
returns to the parent menu.
Press and hold Escape for 2 seconds to return to Run mode from any menu or remote teach.
1.3 Laser Description and Safety Information
CAUTION: Use of controls or adjustments or performance of procedures other than those specified herein may
result in hazardous radiation exposure. Do not attempt to disassemble this sensor for repair. A defective unit must
be returned to the manufacturer.
1.3 Class 2 Laser Models
CAUTION: Never stare directly into the sensor lens. Laser light can damage your eyes. Avoid placing any
mirror-like object in the beam. Never use a mirror as a retroreflective target.
For Safe Laser Use - Class 2 Lasers
• Do not stare at the laser.
• Do not point the laser at a person’s eye.
• Mount open laser beam paths either above or below eye level, where practical.
• Terminate the beam emitted by the laser product at the end of its useful path.
Reference IEC 60825-1:2007, Section 8.2.
Class 2 Lasers
Class 2 lasers are lasers that emit visible radiation in the wavelength range from 400
nm to 700 nm, where eye protection is normally afforded by aversion responses,
including the blink reflex. This reaction may be expected to provide adequate
protection under reasonably foreseeable conditions of operation, including the use of
optical instruments for intrabeam viewing.
Class 2 Laser Safety Notes
Low-power lasers are, by definition, incapable of causing eye injury within the
duration of a blink (aversion response) of 0.25 seconds. They also must emit only
visible wavelengths (400 to 700 nm). Therefore, an ocular hazard may exist only if
individuals overcome their natural aversion to bright light and stare directly into the
laser beam.
Figure 3. FDA (CDRH) warning label
(Class 2)
www.bannerengineering.com - Tel: 763.544.31645
COMPLIES WITH IEC 60825-1:2007
CLASS 1
LASER PRODUCT
Output Complies with 21 CFR 1040.10
and 1040.11 except for deviations
pursuant to Laser Notice No. 50,
dated June 24, 2007.
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
1.3 Class 1 Laser Models
Class 1 lasers are lasers that are safe under reasonably foreseeable conditions of
operation, including the use of optical instruments for intrabeam viewing.
Laser wavelength: 650
nm
Output: < 0.22
mW
Pulse Duration: 150 µs to
900 µs
Figure 4. FDA (CDRH) warning label
(Class 1)
6www.bannerengineering.com - Tel: 763.544.3164
IncorrectCorrect
IncorrectCorrect
IncorrectCorrect
IncorrectCorrect
IncorrectCorrect
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
2 Sensor Installation
NOTE: Handle the sensor with care during installation and operation. Sensor windows soiled by fingerprints, dust,
water, oil, etc. may create stray light that may degrade the peak performance of the sensor. Blow the window clear
using filtered, compressed air, then clean as necessary using 70% isopropyl alcohol and cotton swabs or water and
a soft cloth.
2.1 Sensor Orientation
Correct sensor-to-object orientation is important to ensure proper sensing. See the following figures for examples of
correct and incorrect sensor-to-object orientation as certain placements may pose problems for sensing distances.
Figure 5. Orientation by a wall
Figure 8. Orientation for a height difference
Figure 6. Orientation in an opening
Figure 9. Orientation for a color or luster
difference
Figure 7. Orientation for a turning object
Figure 10. Orientation for a highly reflective
target
Applying tilt to sensor may improve performance on reflective targets. The direction and magnitude of the tilt depends on
the application, but a 15° tilt is often sufficient.
2.2 Mount the Sensor
1. If a bracket is needed, mount the sensor onto the bracket.
2. Mount the sensor (or the sensor and the bracket) to the machine or equipment at the desired location. Do not tighten
the mounting screws at this time.
3. Check the sensor alignment.
4. Tighten the mounting screws to secure the sensor (or the sensor and the bracket) in the aligned position.
www.bannerengineering.com - Tel: 763.544.31647
shield
+
12–30 V dc
D1_Out / IO-Link
D2_Out
Input
–
3
1
2
4
5
Load
Load
2
3
4
1
5
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
2.3 Wiring Diagrams
Figure 11. IO-Link Models
Key
1 = Brown
2 = White
3 = Blue
4 = Black
5 = Gray
8www.bannerengineering.com - Tel: 763.544.3164
from Run Mode
Access
Quick Menu
Access
Sensor Menu
Quick Menu
D1 SPt1 (value)
Run Mode
D1 SPt2*(value)
D2 SPt1 (value)
D2 SPt2*(value)
Spt2 not available unless in
Window Mode
set value with
or
Save setting
and return to
Quick Menu
Cancel and
return to
Quick Menu
access Sensor
Menu (Top Menu)
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
3 Sensor Programming
Program the sensor using the buttons on the sensor or the remote input (limited programming options).
From Run mode, use the buttons to access the Quick Menu and the Sensor Menu. See Quick Menu on page 9 and
Sensor Menu (MENU) on page 10 for more information on the options available from each menu. For TEACH options,
follow the TEACH instructions.
In addition to programming the sensor, use the remote input to disable the buttons for security, preventing unauthorized
or accidental programming changes. See Remote Input on page 10 for more information.
See Figure 13 on page 9See Sensor Menu Full Map on page 33
Figure 12. Accessing the Menus
3.1 Quick Menu
The sensor includes a Quick Menu with easy access to view and change the discrete output switch points. Access the Quick
Menu by pressing Down
displays on the first line and the menu name and the discrete output switch points alternate on the second line of the
display. Press Enter
value. Press Enter to save the new value and return to the Quick Menu.
or Up from Run mode. When in the Quick Menu, the current distance measurement
to access the switch points. Press Down or Up to change the switch point to the desired
www.bannerengineering.com - Tel: 763.544.31649
Figure 13. Quick Menu Map (Window Mode)
MENU D1_OUT
Access discrete 1 output settings
MENU INPUT
Select input line settings (remote TEACH, etc.)
MENU MEASURE
Select response speed
MENU DISPLAY
Select display units and orientation
MENU INFO
View sensor information
MENU RESET
Reset to factory defaults
Sensor Menu
Run
Mode
(See Sensor Menu Full Map for the complete map)
or
or
Go Back to Parent Menu
Select Menu Item
Press to Save Setting
Press and Hold to Go Back
to Run Mode
MENU D2_OUT
Access discrete 2 output settings
L-GAGE
®
LE250/550 IO-Link Laser Gauging Sensors
3.2 Sensor Menu (MENU)
Access the Sensor Menu by pressing Enter from Run mode, when MENU is displayed. The Sensor Menu includes
several submenus that provide access to view and change sensor settings and to view sensor information.
Figure 14. Sensor Menu Basic Map
See Sensor Menu Full Map and the Menu sections of this manual for more information.
3.3 Remote Input
Use the remote input to program the sensor remotely. The remote input provides limited programming options.
To use the Active High function, connect the gray input wire to V+ (12 to 30 V dc). Pulse the remote input according to the
diagram and the instructions provided in this manual.
The length of the individual programming pulses is equal to the value T: 0.04 seconds ≤ T ≤ 0.8 seconds.
Exit remote programming modes by holding the remote input low for > 2 seconds, or waiting for the automatic 60-second
timeout, or by pressing and holding Escape
for 2 seconds. The sensor returns to Run mode without saving any new
settings.
10www.bannerengineering.com - Tel: 763.544.3164
5x
6x
4x
3x
2x
1x
Set Window Size to X1, then back to Run mode
Set Window Size to X2, then back to Run mode
Set Window Size to X3, then back to Run mode
Set Window Size to X4, then back to Run mode
Set Window Size to X5, then back to Run mode
Set Window Size to X6, then back to Run mode
1x
2x
1x
1x
8x
Enter Remote TEACH RMT TCH with measurement value
Enter Remote Setup REMOTE SETUP
Teaching..(D1SPt1) TchSPt1 (D1) with measurement value, then to TchSPt2 (D1)
Teaching..(D1SPt2) TchSPt2 (D1) with measurement value, then back to Run mode
1x
REMOTE TEACH
REMOTE SETUP
D1 Sensor Mode D1-Mode with current value
Window Size WndSize with value
Sensor Lock / Unlock Locks or Unlocks Sensor
Lock Sensor
Unlock Sensor
Reset to Default Settings Resets Sensor to Factory Default Settings
0.04 seconds < T < 0.8 seconds
Timing between Pulse groups > 1 second
Pulse Timing (T)
NOTE: Follow procedure for the TEACH/SET method
(highlighted in black box) chosen in the TEACH Selection menu.
Timeout is 60 seconds.
3x
2x
Teaching.. (D2SPt1) TchSPt1 (D2) with measurement value, then to TchSPt2 (D2)
Teaching..(D2SPt2) TchSPt2 (D2) with measurement value, then back to Run mode
1x
3x
Teaching.. (D1D2SPt1) TchSPt1 (D1 and D2) with measurement value, then to TchSPt2 (D1 & D2)
Teaching..(D1D2SPt2) TchSPt2 (D1 & D2) with measurement value, then
1x
4x
Teaching.. (D1MdPt) TchMdPt (D1) with measurement value, then back to Run mode
5x
Teaching.. (D2MdPt) TchMdPt (D2) with measurement value, then back to Run mode
6x
Teaching.. (D1D2MdPt) TchMdPt (D1 & D2) with measurement value, then back to Run mode
(teaches Spt in Switch Mode)
5x
6x
4x
3x
2x
1x
Set Mode to Alarm, then back to Run mode
Set Mode to Health, then back to Run mode
Set Mode to Switch , then back to Run mode
Set Mode to Switch , then back to Run mode
Set Mode to Window , then back to Run mode
Set Mode to Window , then back to Run mode
D2 Sensor Mode D2-Mode with current value
2x
Run
Mode
2x
1x
4x
back to Run mode
(teaches SPt in Switch Mode)
(teaches SPt in Switch Mode)
5x
6x
4x
3x
2x
1x
Set Mode to Alarm, then back to Run mode
Set Mode to Health, then back to Run mode
Set Mode to Switch , then back to Run mode
Set Mode to Switch , then back to Run mode
Set Mode to Window , then back to Run mode
Set Mode to Window , then back to Run mode
Refer to the Window size table for the acceptable values.
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
www.bannerengineering.com - Tel: 763.544.316411
Figure 15. Remote Input Map
TT
T
TT
TTT
TT
T
TT
T
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
Table 1: Window Size (WndSize)
VariableLE250 ModelsLE550 Models
X11 mm10 mm
X210 mm50 mm
X350 mm100 mm
VariableLE250 ModelsLE550 Models
X4100 mm300 mm
X5150 mm500 mm
X6250 mm800 mm
3.4 Locking and Unlocking the Sensor
Use the lock and unlock feature to prevent unauthorized or accidental programming changes. A lock symbol displays in
the upper left corner of the display to indicate when the sensor is locked. When locked, the menus are available to view
settings, but the values cannot be changed. The remote input is also disabled, except for the unlock function.
Button Instructions
To lock or unlock the sensor using the buttons, press and hold Down
Remote Input Instructions
1. Access the setup mode.
Action
Double-pulse the remote input.
and Escape simultaneously for 3 seconds.
Result
"REMOTE SETUP" displays.
2. Access the lock/unlock function.
Action
Four-pulse the remote input.
3. Lock or unlock the sensor.
Action
Unlock : Single-pulse the remote line.
Lock: Double-pulse the remote input.
Result
"LOCK" and the current status (unlocked or
locked) display.
Result
"Unlocked" flashes and the sensor returns
to Run mode. The sensor is unlocked.
"Locked" flashes and the sensor returns to
Run mode. The sensor is locked and the
lock symbol displays in the upper left
corner.
12www.bannerengineering.com - Tel: 763.544.3164
MENU D1_OUT
or
or
Go Back to Parent Menu
Select Menu Item
Press to Save Setting
Press and Hold to Go Back
to Run Mode
OffDly 0 ms
Off1Sho 0 ms
OnDly 0 ms
On1Sho 0 ms
TchSPt1 100 mm
TchSPt2 1000 mm
Tch2Pt TchSPt2
Tch2Pt TchSPt1
Mode Health
Mode Alarm
Timer On1Sho
Timer OffDly
Mode Swtch
Mode Swtch
Mode Wnd
Mode Wnd
Timer Off1Sho
Timer OnDly
AdjSPt2 1000 mm
AdjSPt1 100 mm
D1_OUT Tch2Pt
D1_OUT Mode
D1_OUT Timer
D1_OUT AdjSPt1
D1_OUT AdjSPt2
(in Swtch mode only)
WndSize 300 mm
TchMdPt 500 mm
TchMid TchMdPt
TchMid WndSize
D1_OUT TchMid
Offset 0 mm
TchMid Offset
(available only when
SPtRef Custom is
selected)
SPtRef Object
SPtRef Custom
Offset 0 mm
D1_OUT Offset
SPtRef Backgrnd
D1_OUT SPtRef
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
3.5 Discrete Output Menu (Dx_OUT)
Use this menu to view or change
• Setpoints
• Midpoint
• Mode
• Timers
• Polarity
The menu options are identical for
D1_OUT and D2_OUT.
3.5.1 Two-Point TEACH
The TchSpt1 and TchSPt2 options teach the desired switch points. When using the buttons, the switch points can be taught
independently. Both values must be taught when using the remote input. The same TEACH menus exist for both the
D1_OUT and D2_OUT, but the switch points are set independently.
Navigate: MENU > Dx_OUT > Tch2Pt > TchSPt1 and navigate: MENU > Dx_OUT > Tch2Pt > TchSPt2
Remote Input: Available
Button Instructions
1. Present the target.
Action
Present the target. The target must be within the sensor's range..
2. Access the TEACH mode and TEACH the sensor.
www.bannerengineering.com - Tel: 763.544.316413
Figure 16. Discrete 1 Output Menu Map (Discrete 2 is identical)
NOTE: When in Switch mode, use TEACH Switch Point on page 17.
Result
The target's distance measurement value
displays.
T
TT
T
T
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
ActionResult
Navigate: MENU > Dx_OUT > Tch2Pt > TchSPt1
OR
Navigate: MENU > Dx_OUT > Tch2Pt > TchSPt2
3. Repeat steps 1 to 2 for the other switch point, if desired.
Remote Input Instructions
1. Access the TEACH mode.
ActionResult
The selected TEACH mode and "Teaching"
display while the sensor is being taught.
TEACH Accepted
The new value is shown on the second line
of the display and flashes before it is saved
and the sensor returns to the parent menu.
TEACH Not Accepted
"FAIL" and a warning message display, and
the sensor returns to the parent menu.
Single-pulse the remote input.
2. Present the target.
ActionResult
Present the switch point one target.
3. TEACH the sensor.
Action
Double-pulse the remote input.
4. Present the target.
Action
Present the switch point two target.
"RMT TCH" and the current switch point
value displays.
"RMT TCH" and the target's measurement
value display.
Result
"TchSPt1 Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value displays on the second line
of the display, flashes, and the sensor goes
to "TchSPt2" and the current
measurement value.
TEACH Not Accepted
"FAIL" flashes, the sensor returns to step
2, and "RMT TCH" displays.
Result
"TchSPt2" and the target's measurement
value display.
5. TEACH the sensor.
Action
Single-pulse the remote input.
14www.bannerengineering.com - Tel: 763.544.3164
Result
"TchSPt2 Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value displays on the second line
of the display, flashes, and the sensor
returns to Run mode.
TEACH Not Accepted
"FAIL" flashes, the sensor returns to step
2, and "RMT TCH" displays.
Output OFF
0 mm
(500 mm)(700 mm)
(600 mm)
1000 mm
SP1SP2
Midpoint
Output ON
TT
T
TTTT
T
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
3.5.2 Midpoint TEACH
The Midpoint TEACH uses both the window size and the
TEACH midpoint to determine the actual measurement
window. For example, a window of 200 mm with a midpoint
of 600 mm places the measurement window from 500 mm to
700 mm.
To use Midpoint TEACH:
1. Set the window size.
2. Set the measurement window using TEACH Midpoint
Figure 17. Window and Midpoint Example
Window Size
The WndSize option sets the window size that the Midpoint TEACH uses to set the setpoint one and setpoint two
thresholds.
The Midpoint TEACH fails if the window is not taught within the valid measurement range.
on page 16.
LE250 Laser Sensor
Window Size Minimum1 mm10 mm
Window Size Maximum250 mm800 mm
Range100 mm to 400 mm100 mm to 1000 mm
Default Window Size50 mm300 mm
Navigate: MENU > Dx_OUT > TchMid > WndSize
Remote Input: Available
1. Access the setup mode.
Method
Push Button
Remote Input
ActionResult
Navigate: MENU > Dx_OUT > TchMid > WndSize .
a. Double-pulse the remote input to enter
setup mode.
b. Three-pulse the remote input to enter
window size mode.
2. Set the window size.
Method
Push Button
ActionResult
a. Use Down and Up to set the desired window size—the
value changes in increments of 2.
b. Press Enter
to save the new value.
LE550 Laser Sensor
"WndSize" and the current window
size value display.
a. "REMOTE SETUP" displays.
b. "WndSize" and the current value
display.
a. "WndSize" and the new value
display.
b. The new value flashes and returns
to "TchMid WndSize".
www.bannerengineering.com - Tel: 763.544.316415
T
L-GAGE
®
LE250/550 IO-Link Laser Gauging Sensors
MethodActionResult
Pulse the remote input 1 to 6 times to select the desired window
size.
Window Size
PulsesLE250LE550
Remote Input
(Sets A_OUT
and D_OUT
window Size)
11 mm10 mm
210 mm50 mm
350 mm100 mm
4100 mm300 mm
5150 mm500 mm
6250 mm800 mm
TEACH Midpoint
The TchMdPt option sets the midpoint that determines the actual measurement window.
Navigate: MENU > Dx_OUT > TchMid > TchMdPt
Remote Input: Available
Button Instructions
1. Present the target.
The new value flashes and the sensor
returns to Run mode.
Action
Present the target.
2. Access the TEACH midpoint mode and TEACH the sensor.
Action
Navigate: MENU > Dx_OUT > TchMid > TchMdPt
Remote Input Instructions
1. Access the TEACH mode.
Action
Single-pulse the remote input.
Result
The target's distance measurement value
displays.
Result
"TchMdPt Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value is shown on the second line
of the display and flashes before it is saved
and the sensor returns to "TchMid
TchMdPt".
TEACH Not Accepted
"FAIL" and a warning message display, and
the sensor returns to "TchMid TchMdPt".
Result
"RMT TCH" and the current measurement
value display.
2. Present the target.
Action
Present the target.
Result
"RMT TCH" and the target's measurement
value display.
3. TEACH the sensor.
16www.bannerengineering.com - Tel: 763.544.3164
TTTT
T
T
T
T
T
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
ActionResult
"TchMdpt Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value displays on the second line
Five-pulse the remote input.
of the display, flashes, and the sensor
returns to Run mode.
TEACH Not Accepted
"FAIL" and a warning message display, the
sensor returns to step 2, and "RMT TCH"
displays.
Offset
Use the TEACH MidPoint Offset menu to set an offset from the taught surface. This menu is available only for a midpoint
TEACH (TchMid). The default is 0 mm because the window is centered around the taught target. Use and to
select a value. Values increase or decrease by 0.1 mm (LE250) or 1.0 mm (LE550). A positive offset value always shifts
the window towards the sensor.
The taught surface must be inside of the defined sensing range. After the offset is applied, some portion of the window
must be located within the sensing range. If the entire window is offset out of range, the TEACH fails and the "Fail / OfSt"
error message displays.
3.5.3 Adjust Switch Point One
The AdjSPt1 option manually adjusts the value of the switch point one threshold for the Discrete Output when the sensor is
in Window mode. The value is adjustable within the sensor's range. It is required to be maintain the minimum window size
between switch points. This menu is not available when the sensor is in Switch, Alarm, or Health mode.
Navigate: MENU > Dx_OUT > AdjSPt1
Remote Input: Not available
Default: 100 mm for both the LE250 and LE550 models.
3.5.4 Adjust Switch Point Two
The AdjSPt2 option manually adjusts the value of the switch point two threshold for the Discrete Output when the sensor is
in Window mode. The value is adjustable with the sensor's range. It is required to be maintain the minimum window size
between switch points. This menu is not available when the sensor is in Switch, Alarm, or Health mode.
Navigate: MENU > Dx_OUT > AdjSPt2
Remote Input: Not available
Default: 400 mm for LE250 models and 1000 mm for LE550 models.
3.5.5 TEACH Switch Point
The TchSPt option teaches the distance at which the switch point threshold is placed when the Discrete Output is in Switch
mode. This menu is not available when the sensor is in Window, Alarm, or Health mode.
Navigate: MENU > Dx_OUT > TchSPt
Remote Input: Available
Button Instructions
1. Present the target.
Action
Present the target. The target must be within the sensor's range.
Result
The target's distance measurement value
displays.
2. Access the switch point TEACH mode and TEACH the sensor.
www.bannerengineering.com - Tel: 763.544.316417
T
TTTT
T
T
T
T
T
L-GAGE
®
LE250/550 IO-Link Laser Gauging Sensors
ActionResult
Navigate: MENU > Dx_OUT > TchSPt
Remote Input Instructions
1. Verify the sensor is in Switch mode.
2. Access the TEACH mode.
ActionResult
"TchSPt Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value is shown on the second line
of the display and flashes before it is saved
and the sensor returns to "Dx_OUT
TchSPt".
TEACH Not Accepted
"FAIL" and a warning message display, and
the sensor returns to "Dx_OUT TchSPt".
Single-pulse the remote input.
"RMT TCH" and the current measurement
value display.
3. Present the target.
ActionResult
Present the target.
"RMT TCH" and the target's measurement
value display.
4. TEACH the sensor.
Action
Five-pulse the remote input.
Result
"TchSPt Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value displays on the second line
of the display, flashes, and the sensor
returns to Run mode.
TEACH Not Accepted
"FAIL" flashes, the sensor returns to step
3, and "RMT TCH" displays.
3.5.6 Adjust Switch Point
The AdjSPt option manually adjusts the value of the switch point threshold for the discrete output when the sensor is in
Switch mode. The value is adjustable within the sensor's range. This menu is not available when the sensor is in Window,
Alarm, or Health mode.
Navigate: MENU > Dx_OUT > AdjSPt
Remote Input: Not available
Default: 100 mm for the LE250 and LE550 models
3.5.7 Mode
The Mode option sets the output to the desired mode.
Navigate: MENU > Dx_OUT > Mode
Remote Input: Available
Default: Wnd mode
The following table describes the sensor modes.
18www.bannerengineering.com - Tel: 763.544.3164
TT
T
TT
T
ModeDescription
AlarmAlarm Mode: The Discrete Output is Off while a target is detected by the sensor at any distance.
HealthHealth Mode: The Discrete Output is On while a target is detected by the sensor at any distance.
Switch
Switch
Wnd
Wnd
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
When a loss of signal occurs, the Discrete Output is On.
This mode has no associated thresholds.
When a loss of signal occurs, the Discrete Output is Off.
This mode has no associated thresholds.
Switch Mode: The Discrete Output is On while a target is detected nearer than the switch point threshold.
When a target is detected farther than the switch point threshold or the signal is lost, the Discrete Output is Off.
Switch Mode: The Discrete Output is Off while a target is detected nearer than the switch point threshold.
When a target is detected farther than the switch point threshold or the signal is lost, the Discrete Output is On.
Window Mode: The Discrete Output is On while a target is detected between the SPt1 and SPt2 thresholds.
(Default)
When a target is detected outside the SPt1 and SPt2 thresholds or the signal is lost, the Discrete Output is Off.
Window Mode: The Discrete Output is Off while a target is detected between the SPt1 and SPt2 thresholds.
When a target is detected outside the SPt1 and SPt2 thresholds or the signal is lost, the Discrete Output is On.
Remote Input Instructions
1. Access the setup mode.
Action
Double-pulse the remote input.
2. View the current mode.
Action
Double-pulse the remote input.
3. Program the sensor.
Result
"REMOTE SETUP" displays.
Result
The current mode displays.
www.bannerengineering.com - Tel: 763.544.316419
T
TT
T
TTTT
T
TT
TTT
TT
TTTT
T
T
T
T
T
TTTT
T
T
T
T
T
T
T
L-GAGE
®
LE250/550 IO-Link Laser Gauging Sensors
ActionResult
Pulse the remote input 1 to 6 times to select the desired mode.
PulsesMode
1
2
3
4
5
6
Alarm
Health
Swtch
The selected mode flashes and the sensor
returns to Run mode.
Swtch
Wnd
Wnd
3.5.8 Switch Point Reference (SPtRef)
The SPtRef menu only displays for a discrete output when it is set to switch mode. The SPtRef settings, object or
background, for the two discrete outputs are set independently. This setting cannot be changed with remote teach.
• Object (default). Object mode sets the switching threshold just past the location of the taught object, farther away
from the sensor's face.
• Background. Background mode sets the switching threshold in front of the taught object, closer to the sensor's
face.
• Custom. Custom mode allows the user to define the location of the switching threshold relative to a taught
distance using the Offset menu that appears only after selecting Custom Switch Point Reference.
The distance between the surface of the taught object and the switching threshold varies depending on measurement
strength and can be affected by target distance, color, reflectivity, etc. Use object mode when teaching an object if a
change in state is required when the object is no longer present. Use background mode when teaching background so that
the output state changes when a new object is in front of the background.
Navigate: MENU > Dx_OUT > SPtRef
Remote Input: Not available
Default: Object
3.5.9 Switch Point TEACH Offset
Use this menu to set an offset from the taught distance after a switch point TEACH, if SPtRef is set to Custom.
By default, the value is 0 mm. A positive offset value always shifts the threshold towards the sensor.
Navigate: MENU > Dx_OUT > TchMd > Offset
Remote Input: Not available
Default: 0 mm
20www.bannerengineering.com - Tel: 763.544.3164
Output
OFF Delay
ON Delay
Time
OFF 1-Shot
ON 1-Shot
ON
OFF
D
D
D
D
D
D
D
D
(D = 1 - 9999 ms)
or
or
Go Back to Parent Menu
Select Menu Item
Press to Save Setting
Press and Hold to Go Back
to Run Mode
MENU INPUT
Type LasrEnbl
Type Teach
Type SyncMstr
Type SyncSlve
Type Disabled
INPUT Type
Default Setting
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
3.5.10 Timer
The Timer option sets the delays and timers.
On/Off Delays and On/Off One-Shot timers can
be programmed between 1 to 9999 ms (a value
of 0 disables the delay/timer). Figure 18 on
page 21 defines how the delays/timers affect
the output behavior.
Navigate: MENU > Dx_OUT > Timer
Remote Input: not available
Default: 0 ms for all timers
Figure 18. Delays/Timers
Some combinations of delays/timers are not allowed. The programming menu automatically disables invalid combinations
of delays/timers. The following table shows the allowable combinations of delays/timers.
Off Delay
Off Delay (OffDly)OKOKOKN/A
Off One-Shot Timer (Off1Sho)OKOKN/AN/A
On Delay (OnDly)OKN/AOKOK
On One-Shot Timer (On1Sho)N/AN/AOKOK
Off One-Shot TimerOn DelayOn One-Shot Timer
3.6 Input Menu (INPUT)
Use this menu to view or change the:
• Multi-function input type
3.6.1 Input Type
The Type option sets the input type.
www.bannerengineering.com - Tel: 763.544.316421
Figure 19. Input Menu Map
or
or
Go Back to Parent Menu
Select Menu Item
Press to Save Setting
Press and Hold to Go Back
to Run Mode
Default Setting
MENU MEASURE
Speed Standard
Speed Fast
Speed Medium
Speed Slow
MEASURE Speed
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
Navigate: MENU > INPUT > Type
Remote Input: Not available
Default: Disabled
Input TypeDescription
TeachThe remote input is used to TEACH and program the sensor. (Default)
LasrEnblThe remote input is used to control when the laser emitter is On/Off.
SyncMstrThe remote input is used as the Master Sync output to an attached Slave sensor (see Sync Master/
SyncSlveThe remote input is used as the Slave Sync input from an attached Master sensor (see Sync Master/
DisabledThe remote input is disabled.
Slave on page 26).
Slave on page 26).
3.7 Measure Menu (MEASURE)
Use this menu to view or change the:
• Speed
3.7.1 Speed
The Speed option sets the speed at which the measurement is calculated. This process uses averaging in the digital
processing of the signal to calculate the measurement. A slower speed increases the response time of the sensor but
improves the repeatability. See Figure 27 on page 30 for repeatability specifications for each speed.
Navigate: MENU > MEASURE > Speed
Remote Input: Not available
Default: Standard
SpeedResponse TimeResponse Time in Sync
Fast2 ms4 ms2 ms4 ms
Standard10 ms (default)20 ms5 ms (default)10 ms
Medium30 ms60 ms15 ms30 ms
Slow100 ms200 ms50 ms100 ms
22www.bannerengineering.com - Tel: 763.544.3164
Class 1 Laser Models
Mode
Figure 20. Measure Menu Map
Class 2 Laser Models
Response TimeResponse Time in Sync
Mode
or
or
Go Back to Parent Menu
Select Menu Item
Press to Save Setting
Press and Hold to Go Back
to Run Mode
MENU DISPLAY
Sleep 1min
Sleep Disabled
Units in
Units mm
View Invert
View Normal
Sleep 5min
Sleep 15min
Sleep 60min
DISPLAY Sleep
DISPLAY Units
DISPLAY View
DISPLAY Zero
Zero Near
Zero Far
DISPLAY Shift
Shift Off
Shift SetZero
Shift AutoSet
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
3.8 Display Menu (DISPLAY)
Use this menu to view or change the:
• Display units
• Display orientation
• Sleep mode settings
3.8.1 Units
The Units option sets the displayed units to millimeters (mm) or inches (").
Navigate: MENU > DISPLAY > Units
Remote Input: Not available
Default: mm
3.8.2 Zero
Use this menu to select the zero reference location. The default is Near, where 0 = the front of the sensor.
• Near—0 = the front of the sensor; the measurement increases further from the sensor
• Far—0 = maximum range; the measurement increases closer to the sensor
Navigate: MENU > DISPLAY > Zero
Remote Input: Not available
Default: Near
3.8.3 Shift
Use this menu to select whether the sensor shifts the zero reference location based on the last TEACH process. The default
is off, where 0 = the front of the sensor or the maximum range.
• Off—0 = the front of the sensor or the maximum range, depending on the Zero setting.
• AutoSet—Shift the zero reference location to one of the taught positions with each TEACH. The zero reference
location is reset when teaching either output.
• SetZero—Teaches the current target as its new zero reference location.
3.8.4 View
The View option sets the display orientation of the sensor. For applications where the sensor must be mounted so that the
display is not right-reading, invert the display for readability. The Down and Up buttons do not change when the display is
inverted.
The Sleep option sets when the display is put to sleep. Four timing options are available: 1, 5, 15, or 60 minutes. Sleep
mode is disabled by default. Sleep occurs in Run mode and any menu. To wake the sensor and return to the last viewed
mode or menu, press any button.
Navigate: MENU > DISPLAY > Sleep
Remote Input: Not available
Default: Disabled
3.9 Information Menu (INFO)
Use this menu to view model, part number (P/N), serial number (S/N), and firmware version (Version) information. Select
one of these options to view specific information for your sensor. This information is read-only.
Navigate: MENU > INFO
Remote Input: Not available
24www.bannerengineering.com - Tel: 763.544.3164
Figure 24. LE550 Information Menu Map
T
T
T
T
T
T
T
T
T
T
T
TTTT
MENU RESET
or
or
Go Back to Parent Menu
Select Menu Item
Press to Save Setting
Press and Hold to Go Back
to Run Mode
RESET No
RESET Yes
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
3.10 Reset Menu (RESET)
Use this menu to restore the sensor to the factory default
settings.
Navigate: MENU > RESET. Select Yes to apply the
factory defaults; select No to return to the Reset option
without changing any sensor settings.
Remote Input: Eight-pulse the remote input
Figure 25. Reset Menu Map
3.10.1 Factory Default Settings
Discrete Output
Settings
Adjust Switch Point One100 mm100 mm
Adjust Switch Point Two400 mm1000 mm
Mode
Timer0 ms for all timers
Window Size50 mm300 mm
LE250LE550
Wnd
Input SettingsLE250 and LE550
Input TypeDisabled
Measure SettingsLE250 and LE550
SpeedStandard
Display SettingsLE250 and LE550
SleepDisabled
Unitsmm
ViewNormal
www.bannerengineering.com - Tel: 763.544.316425
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
4 Sync Master/Slave
Two LE250/550 Laser sensors may be used together in a single sensing application. To eliminate crosstalk between the
two sensors, configure one sensor to be the master and one to be the slave. In this mode, the sensors alternate taking
measurements and the response speed doubles.
1. Configure the first sensor as the master; navigate: MENU > INPUT > Type > SyncMstr.
2. Configure the second sensor as the slave; navigate: MENU > INPUT > Type > SyncSlve.
3. Connect the gray (input) wires of the two sensors together.
If using a combination of Class 1 and Class 2 laser models, the Class 1 laser model must be used as the master.
26www.bannerengineering.com - Tel: 763.544.3164
T
TTTT
T
T
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
5 Additional Remote TEACH Procedures
5.1 TEACH Both Discrete Output Switch Points Together
Use the following procedure to teach both Discrete Output switch points at the same time using the remote input. This
feature is not available using the buttons.
1. Access the TEACH mode.
ActionResult
Single-pulse the remote input.
2. Present the target.
ActionResult
Present the switch point one target.
3. TEACH the sensor.
ActionResult
Three-pulse the remote input.
4. Present the target.
Action
Present the switch point two target.
"RMT TCH" and the current measurement
value display.
"RMT TCH"and the target's measurement
value display.
"D1D2Spt1 Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value displays on the second line
of the display, flashes, and then
"D1D2Spt2" and the current measurement
value display.
TEACH Not Accepted
"FAIL" flashes, the sensor returns to step
2, and "RMT TCH" displays.
Result
"D1D2Spt2" and the target's measurement
value display.
5. TEACH the sensor.
Action
Single-pulse the remote input.
Result
"D1D2Spt2 Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value displays on the second line
of the display, flashes, and the sensor
returns to Run mode.
TEACH Not Accepted
"FAIL" flashes, the sensor returns to step
2, and "RMT TCH" displays.
5.2 TEACH Both Discrete Output Midpoints Together
Use the following procedure to teach an identical discrete output midpoint (switch point) for both D1_OUT and D2_OUT at
the same time using the remote input. This feature is not available using the buttons. Note that if the window sizes were
set independently (using the buttons), the windows taught using the following procedure could be different.
1. Access the TEACH mode.
www.bannerengineering.com - Tel: 763.544.316427
T
TTTT
T
T
T
T
T
T
T
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
ActionResult
Single-pulse the remote input.
2. Present the target.
ActionResult
Present the midpoint (switch point) target.
3. TEACH the sensor.
ActionResult
Six-pulse the remote input.
"RMT TCH" and the current measurement
value display.
"RMT TCH"and the target's measurement
value display.
"D1D2MdPt Teaching" displays while the
sensor is being taught.
TEACH Accepted
The new value displays on the second line
of the display, flashes, and the sensor
returns to Run mode.
TEACH Not Accepted
"FAIL" flashes, the sensor returns to step
2, and "RMT TCH" displays.
28www.bannerengineering.com - Tel: 763.544.3164
x
y
Beam
Spot
Pattern
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
6 Specifications
Supply Voltage (Vcc)
12 to 30 V dc
Power and Current Consumption, exclusive of load
Normal Run Mode: 1.7 W, Current consumption < 70 mA at 24
V dc
Supply/Output Protection Circuitry
Protected against reverse polarity and transient overvoltages
Output Configuration
D1_Out: IO-Link, Push/pull
D2_Out: PNP
Output Ratings
100 mA maximum capability each output
Saturation: Less than 2 V
Off-State Leakage Current: Less than 50 µA PNP at 30 V (N.A.
push/pull)
Remote Input
Allowable Input Voltage Range: 0 to Vcc
Active High (internal weak pulldown—sourcing current):
High State > Vcc – 1.5 V dc
Low State < Vcc – 5 V dc
Input Impedance > 10 kOhm
Measurement/Output Rate
Class 2 Laser Models: < 1 ms
Class 1 Laser Models (Fast): < 1 ms
Class 1 Laser Models (Std/Medium/Slow): < 2 ms
Typical Beam Spot Size
1
Sensing Beam
Class 2 laser models: visible red, 650 nm
Class 1 laser models: visible red, 650 nm
Sensing Range
LE250: 100 mm to 400 mm (3.94 to 15.75 inches)
LE550: 100 mm to 1000 mm (3.94 to 39.37 inches)
Minimum Window Size
LE250: 1 mm (0.039 inches)
LE550: 10 mm (0.39 inches)
Boresighting
LE250: 4 mm radius at 400 mm
LE550: 1 cm radius at 1 m
Maximum Torque
2 N·m (17.7 in-lbs)
Indicators
Power LED Indicator
Solid Green = Normal operation, power On and laser On
Flashing Green (1 Hz) = Power On and laser Off (laser
enable mode)
Discrete Output LED Indicator
Solid Amber = Discrete Output is On
Off = Discrete Output is Off
Construction
Housing: die-cast zinc
Window: acrylic
Ambient Light Immunity
Class 2 laser models: > 10,000 lux
Class 1 laser models: > 5,000 lux
Response Time
Distance (mm)
LE250 ModelsLE550 Models
1002504001005501000
x3.22.11.28.410.512.1
y2.21.50.93.54.24.9
IO-Link Interface
Supports Smart Sensor Profile: Yes
Baud Rate: 38400 bps
Process Data Widths: 32 bits
IODD files: Provides all programming options of the display, plus
additional functionality
Class 1 Laser
Models
2
Fast
Standard10 ms5 ms
Medium30 ms15 ms
Slow100 ms50 ms
Delay at Power Up
3 s
Repeatability
See Performance Curves
Temperature Effect
See Performance Curves
2 ms2 ms
Class 2 Laser
Models
1
Beam spot size is calculated as 1.6 times the D4σ measured value
2
Response time for lateral entry of object into measurement range < 5 ms
www.bannerengineering.com - Tel: 763.544.316429
Industrial
Control
Equipment
3TJJ
0.6
0.5
0.4
0.3
0.2
0.1
0
100200300
DISTANCE (mm)
REPEATABILITY ( ± mm)
400
Fast
Response Time
Standard
Medium
Slow
1
2
3
4
5
6
7
8
0
2000
DISTANCE (mm)
REPEATABILITY ( ± mm)
4006008001000
Fast (Class 2 Laser models only)
Fast (Class 1 Laser models only)
Response Time
Standard (Class 1 and Class 2 Laser models)
Medium (Class 1 and Class 2 Laser models)
Slow (Class 1 and Class 2 Laser models)
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
Environmental Rating
IEC IP67, NEMA 6
Operating Conditions
−20 °C to +55 °C (−4 °F to +131°F)
90% at +55 °C maximum relative humidity (non-condensing)
Storage Temperature
−30 °C to +65 °C (−22 °F to +149 °F)
Vibration/Mechanical Shock
All models meet Mil. Std. 202 G requirements method 201A. Also
meets IEC 60947-5-2.
Application Note
For optimum performance, allow 10 minutes for the sensor to
warm up
Certifications
UL Environmental Rating: Type 1
Required Overcurrent Protection
WARNING: Electrical connections
must be made by qualified
personnel in accordance with local
and national electrical codes and
regulations.
Overcurrent protection is required to be provided by end
product application per the supplied table.
Overcurrent protection may be provided with external fusing
or via Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to
All measurements are listed in millimeters [inches], unless noted otherwise.
Figure 29. Temperature Effect
www.bannerengineering.com - Tel: 763.544.316431
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
7 Troubleshooting
Message/IndicatorDescriptionResolution
Fail/
Min Wnd
OutRnge
Fail/
Out
of Range
The minimum window size is 1 mm for the
LE250 models and 10 mm for the LE550
models. One point of the adjusted or taught
window is out of range.
The TEACH failed, the target is out of
range. The target might have moved out of
range after the TEACH process began.
The sensor automatically returns to the previous
setting.
TEACH the switch point within the measurement
range.
Fail/
OfSt Out
of Range
MIN Wnd
xx mm (xx in)
OutRngeThe target is out of range, too dark, or the
Power LED is flashing
green
Power LED is flashing
red
SPtx
< Near
or
SPtx
> Far
Type
Sync Slave
The TEACH failed. The target is in range but
the offset value caused the setpoint(s) to
be out of range.
The adjusted or taught window size is too
small; the minimum window size is
displayed.
sensor is not measuring.
The sensor input is set to laser enable and
the input is not active.
The laser shut off, the Power LED flashes
red and Output LEDs flash amber at 1Hz,
and the display is blank.
The laser has experienced a fault.
One of the switch points is located outside
the sensor's range, either too close to the
sensor or too far away.
The slave mode sensor does not see the
master's pulse.
Adjust the offset value or target distance to keep
the setpoint(s) within the measurement range.
The sensor automatically adjusts the window size
to maintain the minimum window size and
completes the adjust or TEACH operation.
Move the target within the measurement range.
See Input Type on page 21.
Contact Banner Engineering to resolve.
The desired window size is maintained, but the
usable portion of the window is restricted to be
within the sensor's range.
Verify the master mode sensor is configured and
functioning properly. Check the input wire
connection between the master and slave.
32www.bannerengineering.com - Tel: 763.544.3164
OffDly 0 ms
Off1Sho 0 ms
OnDly 0 ms
On1Sho 0 ms
TchSPt1 100 mm
TchSPt2 1000 mm
Tch2Pt TchSPt2
Tch2Pt TchSPt1
Mode Health
Mode Alarm
Timer On1Sho
Timer OffDly
Mode Swtch
Mode Swtch
Mode Wnd
Mode Wnd
Timer Off1Sho
Timer OnDly
AdjSPt2 1000 mm
AdjSPt1 100 mm
D2_OUT Tch2Pt
D2_OUT TchMid
D2_OUT Mode
D2_OUT Timer
D2_OUT AdjSPt1
D2_OUT AdjSPt2
Run
Mode
Enter Quick Menu Loop
(see Quick Menu diagram)
MENU D1_OUT
MENU D2_OUT
MENU INPUT
LE Series User Interface
Enter
Top Menu
(Continued on right side)
(Continued from left)
Top Menu
MENU MEASURE
MENU DISPLAY
MENU INFO
MENU RESET
Sub Menus
Top MenuSub Menus
or
or
Go Back to Parent Menu
Select Menu Item
Press to Save Setting
Press and Hold to Go Back
to Run Mode
OffDly 0 ms
Off1Sho 0 ms
OnDly 0 ms
On1Sho 0 ms
TchSPt1 100 mm
TchSPt2 1000 mm
Tch2Pt TchSPt2
Tch2Pt TchSPt1
WndSize 300 mm
TchMdPt 500 mm
TchMid TchMdPt
TchMid WndSize
Mode Health
Mode Alarm
Timer On1Sho
Timer OffDly
Mode Swtch
Mode Swtch
Mode Wnd
Mode Wnd
Type LasrEnbl
Type Teach
Type SyncMstr
Type SyncSlve
Type Disabled
Speed Standard
Speed Fast
Speed Medium
Speed Slow
Timer Off1Sho
Timer OnDly
AdjSPt2 1000 mm
AdjSPt1 100 mm
Sleep 1min
Sleep Disabled
Units in
Units mm
View Invert
View Normal
Sleep 5min
Sleep 15min
Sleep 60min
Version 1.0.0
Model LE550K
P/N 97761
S/N F..S..P..D..
D1_OUT Tch2Pt
D1_OUT TchMid
D1_OUT Mode
D1_OUT Timer
INPUT Type
MEASURE Speed
D1_OUT AdjSPt1
D1_OUT AdjSPt2
DISPLAY Sleep
DISPLAY Units
DISPLAY View
INFO Version
INFO Model
INFO P/N
INFO S/N
RESET No
RESET Yes
Default Setting
SPtRef Object
SPtRef Custom
(in Swtch mode only)
(in Swtch mode only)
Offset 0 mm
TchMid Offset
DISPLAY Zero
Zero Near
Zero Far
DISPLAY Shift
Shift Off
Shift SetZero
Shift AutoSet
WndSize 300 mm
TchMdPt 500 mm
TchMid TchMdPt
TchMid WndSize
Offset 0 mm
TchMid Offset
Offset 0 mm
D2_OUT Offset
SPtRef Backgrnd
(available only when
SPtRef Custom is
selected)
(available only when
SPtRef Custom is
selected)
D2_OUT SPtRef
SPtRef Object
SPtRef Custom
Offset 0 mm
D1_OUT Offset
SPtRef Backgrnd
D1_OUT SPtRef
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
8 Sensor Menu Full Map
www.bannerengineering.com - Tel: 763.544.316433
NOTE: See Remote Input on page 10 for remote input options.
44 Typ.
ø 14.5
M12 x 1
2
3
4
1
5
32 Typ.
[1.26"]
30 Typ.
[1.18"]
ø 14.5 [0.57"]
M12 x 1
65
68
64
A
C
B
A
B
C
65
75
28
A
56
60
45
85
134
6X Ø3.5
2X Ø4.5
Ø4.5
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
9 Accessories
9.1 Cordsets
All measurements are listed in millimeters, unless noted otherwise.
5-Pin Threaded M12/Euro-Style Cordsets—with Shield
ModelLengthStyleDimensionsPinout (Female)
MQDEC2-5061.83 m (6 ft)
MQDEC2-5154.57 m (15 ft)
MQDEC2-5309.14 m (30 ft)
MQDEC2-55015.2 m (50 ft)
MQDEC2-506RA1.83 m (6 ft)
MQDEC2-515RA4.57 m (15 ft)
MQDEC2-530RA9.14 m (30 ft)
MQDEC2-550RA15.2 m (50 ft)
Straight
Right-Angle
1 = Brown
2 = White
3 = Blue
4 = Black
5 = Gray
9.2 Brackets
All measurements are listed in millimeters, unless noted otherwise.
SMBLEU
•Enclosed bracket
•12 gauge stainless steel
Hole size: A = ø 5 with 20° adjustability, B = ø 4.5, C = ø 4.5 with 10°
adjustability
SMBLEFA
•Swivel plate bracket
•12 gauge stainless steel
Hole size: A = 4x ø 4.5
SMBLEL
Hole size: A = ø 4.5 with 20° adjustability, B = ø 4.5, C = ø 5.7 with
20° adjustability
SMBAMSLTFP
•Right-angle bracket
•12 gauge stainless steel
•AMS mounting pattern
•12 gauge stainless steel
34www.bannerengineering.com - Tel: 763.544.3164
L-GAGE® LE250/550 IO-Link Laser Gauging Sensors
10 Banner Engineering Corp. Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp.
will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty
period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION,
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE
OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE
LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER
ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product
previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection
applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval
by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product
specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most
recent version of any documentation, refer to: www.bannerengineering.com.
www.bannerengineering.com - Tel: 763.544.316435
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.