Autonics DPU1 Series, DPU3 Series Catalog Page

DPU1/DPU3 Series
Digital Power Controllers
Features
• High speed and high accuracy by digital control using high speed CPU
• Various controls
- Phase control, feedback control (constant voltage/constant current/constant power)
- Zero crossing cycle control (xed/variable cycles)
• Improved maintainability with built-in fast-acting fuse and easy fuse replacement
• Communication output model: RS485 (Modbus RTU)
• Various control inputs and DI inputs
- control input: analog (current, voltage), ON/OFF (voltage pulse, no voltage), communication (RS485), potentiometer
- DI input: AUTO/MAN switching, RUN/STOP switching, Reset, output holding, SP designation (6 setting points can be customized)
• Various alarm output
- Overcurrent, overvoltage, fuse break, heat sink overheat, device fault, heater break alarm (partial heater break detection)
• Improved convenience by separating operation part
• Applicable load
- Supercantal, platinum, molybdenum, carbon, halogen lamps, chrome, nickel, etc.
Ordering Information
I I
(Q)
Size type
DPU1 Series DPU3 Series
Size
A 0 to 70 A 97 260 170 82 150 Min. AWG 4 B 80 to 200 A 140 280 174 127 150 Min. AWG 4/0 C 250 to 350 A 213 338 179 193 200 Min. AWG 300MCM D 400 to 600 A 278 418 212 261 200 Min. AWG 500MCM
L-28
1 2 ADPU 025 R
Power supply
Control phase
Item
Current capacity
W H D P1 P2
Size
-
(unit: mm)
Option
9
Rated load current
Allowable cable thickness
R RS485 communication
D Remote Display Unit
A Remote Display Unit + RS485 communication
N No option
I I I
025 25A 180 180A
040 40A 200 200A
050 50A 250 250A
070 70A 350 350A
080 80A 400 400A
100 100A 500 500A
120 120A 600 600A
150 150A
A 0 to 70A 0 to 50A
B 80 to 200A 70 to 200A
C 250 to 350A
D 400 to 600A
E Option
1 110VAC
2 220VAC
3 380VAC
4 440VAC
1 Single-phase
3 3-phase
DPU Digital Power Controller
Size
A 0 to 50A 140 306 200 127 150 Min. AWG 4 B 70 to 200A 213 365 217 195 200 Min. AWG 4/0 C 250 to 350A 278 450 D 400 to 600A 427 528
I I I I I I I I I
Autonics
Please read “Safety Considerations” in the instruction manual before using.
Single-phase 3-phase
Current capacity
(unit: mm)
W H D P1 P2
227 5
261 200 Min. AWG 300MCM
275 5
405 330 Min. AWG 500MCM
ICE:
Allowable cable thickness
Digital Power Controllers
Specifications
Series DPU1 DPU3
Control phase Single-phase 3-phase Power supply 110VAC / 220VAC / 380VAC / 440VAC (FAN and control power 220VAC 50/60Hz separately)
Allowable voltage range 90 to 110% of rated voltage 85 to 115% of rated voltage
Rated frequency 50/60Hz (auto recognition), allowable frequency range: ±2Hz
Min. load current 1A
Output range Phase control: 5 to 98%, Z.C. control: 0 to 100%
• Phase control: Normal control (non-Feedback), constant voltage/constant current/constant power
Control method
Applied load
Power consumption Max. 7W (except FAN operation power) Max. 10W (except FAN operation power)
Display method
Output accuracy
Set method By front keys, By communication
Control input
Digital input (DI) AUTO/MAN switching, RUN/STOP switching, RESET, Output holding, SP setting (SP1 to 6)
Display content Control input, load voltage, load current, load power, load resistance, power supply frequency
Min. display output Min. 2.5% of rated voltage/current
Option output RS485 communication output (Modbus RTU method), [max. 32 units]
Dielectric strength 2,000VAC 50/60Hz for 1 min (between input terminal and power terminal)
Vibration 0.75mm amplitude at frequency of 5 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
Insulation resistance Over 200MΩ (at 500VDC megger)
Noise immunity ±2kV the square wave noise (pulse width 1) by the noise simulator
Environ­ment
Approval
Weight
1. Variable cycle control is only for single-phase model.
The weight includes packaging. The weight in parenthesis is for unit only.
2.
Environment resistance is rated at no freezing or condensation.
1
Ambient temp.
I
Ambient humi.
I
2
control (Feedback)
• Cycle control (Z.C.): Fixed cycle control, Variable cycle control
• ON/OFF control (Z.C.)
• Phase control: resistance load, inductive load
• ON/OFF, Cycle control: resistance load
• Display value and SV display: 7-segment 4-digit
• Status display: 4 LED
• Display value percentage display: 11 LED Bar
• Constant voltage feedback control: Within ±3% F.S. of rated voltage
• Constant current feedback control: Within ±3% F.S. of rated voltage
• Constant power feedback control: Within ±3% F.S. of rated voltage
• Normal control: within ±10% F.S. of rated voltage
• Auto: 4-20mA / 0-20mA / 0-5VDC / 1-5VDC / 0-10VDC / voltage pulse (0/12VDC(24VDC)) /
no-voltage input (ON/OFF) / communication input (RS485)
• Manual: inside 10kΩ adjuster, outside 3 to 10kΩ adjuster (min. 2W)
-
10 to 50, storage: -20 to 80
5 to 90%RH, storage: 5 to 90%RH
• A size
: approx. 3.2kg (approx. 3.0kg)
• C size
: approx. 12.1kg (approx. 11.0kg)
• B size
• D size
(within variable ±10% F.S. of rated voltage)
(within variable 1 to 10 times of rated resistance)
( within variable ±10% F.S. of rated voltage and within variable 1 to 10
times of rated resistance)
: approx. 5.6kg (approx. 3.0kg)
: approx. 19.3kg (approx. 11.0kg)
• Display value and SV display: 7-segment 4-digit
• Status display: 6 LED
• Display value percentage display: 11 LED Bar
• A size
: approx. 7.6kg (approx. 6.5kg)
• C size
: approx. 21.1kg (approx. 20.0kg)
• B size
: approx. 13.0kg (approx. 11.5kg)
• D size
: approx. 35.7kg (approx. 30.8kg)
L-29
DPU1/DPU3 Series
Connections
DPU1 Series
A Size B Size C Size D Size
R S U
F.G.
Voltage input
~
1-5V 0-5V 0-10V
------=----.
Internal adjuster (10kΩ)
3-level slide switch
~
Jul_
Voltage
ON/OFF
-----=-----
R S U
ON/OFF
External
VR
Input
F.G.
R SU
F.G.
R S U
F.G.
250VAC
1A
RESISTIVE
R
>---------1
AC POWER IN
S>---------------<1~-----~
Do not mix noise to input cable. It is recommended to use shield cable, twisted cable as input cable for e󰀨ective noise.
If there is possible to a󰀨ect inductive noise, it is recommended to use shielded cable at high-frequency power for e󰀨ective noise.
DI input switch should be for low current and ON resistance should be max. 20Ω (including cable resistance).
DI input terminals are COM, DI-1 to 3, RUN, AUTO.
For remote display unit option model, use connection cable as our standard cable.
When connecting ⑥, ⑪ , it operates as MANUAL. When connecting, ⑥, ⑦, ⑪, it operates AUTO.
L-30
~----is
Autonics
i---~
1a
LOAD
Load
Digital Power Controllers
DPU3 Series
A Size B Size C Size D Size
L1
(R)L2 (S)L3 (T)
F.G.
Internal adjuster (10kΩ)
3-level slide switch
U
V W
L1
(R)L2 (S)L3 (T)
U
V W
F.G.
L1
(R)L2 (S)L3 (T)
U
V W
F.G.
L1
(R)
(S)
L2
(T)
L3
F.G.
~
1-5V 0-5V 0-10V
Voltage input
------=---.
~
J1.fL
Voltage
ON/OFF
-----=-----
External
VR
Input
Load
Load
U
V W
Load
Do not mix noise to input cable. It is recommended to use shield cable, twisted cable as input cable for e󰀨ective noise.
If there is possible to a󰀨ect inductive noise, it is recommended to use shielded cable at high-frequency power for e󰀨ective noise.
DI input switch should be for low current and ON resistance should be max. 20Ω (including cable resistance).
DI input terminals are COM, DI-1 to 3, RUN, AUTO.
For remote display unit option model, use connection cable as our standard cable.
When connecting ⑥, ⑪ , it operates as MANUAL. When connecting, ⑥, ⑦, ⑪, it operates AUTO.
L-31
DPU1/DPU3 Series
Dimensions
DPU1 Series
● A Size: DPU1
25A, 40A, 50A are not attached a fan.
A-025/040/050/070
60
(unit: mm)
Fixed 4-M5
● B Size: DPU1
120
30
40
260
150 (P2)
82 (P1)
97
B-080/100/120/150/180/200
30
50150 (P2)
3
I
I_
Jj
Ii
l
209.5
135°
135°
222
154
120
80
170
147
110
L-32
Fixed 4-M5
127 (P1)
140
280
3
t
I~
~
~
I I
11-1
mom
~
241.5
121.5
151
174
Digital Power Controllers
● C Size: DPU1
Fixed 4-M6
193 (P1)
213
● D Size: DPU1
C-250/350
@)
D-400/500/600
40200 (P2)
50200 (P2)
T
J
j
l:
mmm
tr
179
II
~
I
38
365
160°
••
338
300
163
132
4
38
I
494
160°
213
• I
418
280
~
Fixed 4-M6
©
tr
immmmim
261 (P1)
278
(Q)
In case of remote display unit + RS485 communication option
102
55
I.
212
55
• I
345
·-
90
102
4
250
278
● Panel cut-out of the display model
156
0
+ 0.5
100.5
195
0
It is recommended for remote panel cable to use max. 5 m to prevent noise. (Check the length when ordering it.)
I.
53.5
+ 0.5
0
. I
L-33
DPU1/DPU3 Series
DPU3 Series
● A Size: DPU3
Fixed 4-M5
127 (P1)
140
● B Size: DPU3
A-025/040/050
306
150 (P2)63.526
B-070/080/100/120/150/180/200
(unit: mm)
235.6
160°
239
200
138
182
364
160°
280
200 (P2) 40
Fixed 4-M6
195 (P1)
213
In case of remote display unit + RS485 communication option
<O
365
43.1
199 183
● Panel cut-out of the display model
102
55
0.5
53 5
0
0.5
176
0
100.5
It is recommended for remote panel cable to
use max. 5m to prevent noise. (Check the
length when ordering it.)
278
217
L-34