Autonics ATS8P Series Catalog Page

ATS8P Series
Power-OFF Delay Timer, Compact Size W38×H42mm
Features
● Control time range (ATS8P-
● Direct reading for time setting and time range with easy adjustment
● Power supply: 100-120VAC50/60Hz, 200-240VAC 50/60Hz,
● Close and DIN rail mounting with the dedicated socket (PS-M8) width 41mm
● Easy mounting and installation/maintenance with the dedicated bracket for DIN 48×48mm
● Application : Protection circuit when momentary power failure and start it again
t.=I
&:___
Ordering Information
~
ATS
Item
Specifications
~
Model ATS8P- Function Power OFF Delay Control time setting range※10.1 to 10 sec 0.1 to 10 min Power supply •100-120VAC 50/60Hz •200-240VAC 50/60Hz •24VAC 50/60Hz, 24VDC universal Allowable voltage range 90 to 110% of rated voltage
Power consumption
Timing operation Power OFF Start
Control output
Relay life cycle
Repeat error Max. ±0.2% ±10ms SET error Max. ±5% ±50ms Voltage error Max. ±0.5% Temperature error Max. ±2% Insulation resistance Over 100 (at 500VDC megger) Dielectric strength 2,000VAC 50/60Hz for 1 min Noise immunity ±2kV the square wave noise (pulse width: 1㎲) by noise simulator
Vibra ion
Shock
Environ­ment
Approval Accessory Bracket Unit weight Approx. 80g Approx. 85g
1: Refer to time specications for control time setting range by model.
Environment resistance is rated at no freezing or condensa ion.
S: 0.1 to 10 sec, ATS8P- M: 0.1 to 10 min)
24VAC 50/60Hz, 24VDC universal
Please read “Safety Considerations” in the instruction manual before using.
____
8
-
P 2 S
Time operation
Number of plug pins
y
Time unit
Power supply
S ATS8P- M
_____.I
(
E:
c
'i\lus
S SEC
M MIN
I I I
2 24VAC 50/60Hz, 24VDC type
5 200-240VAC 50/60Hz
6 100-120VAC 50/60Hz
P Power OFF Delay
8 8-pin plug type
ATS Compact Analog Timer
8-pin socket (PG-08, PS-08(N), PS-M8) is sold separately.
I
I
•Max. 1.5VA (100-120VAC 50/60Hz) •Max. 1 5VA (200-240VAC 50/60Hz)
•Max. 0.2VA (24VAC 50/60Hz), Max. 0.2W (24VDC)
Contact type Time limit DPDT (2c) Contact capacity Mechanical Min. 10,000,000 operations Electrical Min. 100,000 operations (250VAC 3A resistive load)
Mechanical 0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direc ion for 1 hour Malfunction 0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min Mechanical 300m/s Malfunction 100m/s Ambient temp. -10 to 55, storage: -25 to 65 Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
250VAC 3A, 30VDC 3A resistive load
2
(approx. 30G) in each X, Y, Z direction 3 times
2
(approx. 10G) in each X, Y, Z direction 3 times
ᜢ ᜧ
I
N-58
Autonics
Connections
CONTACT OUT: 250VAC 3A, 30VDC 3A RESISTIVE LOAD
Compact Power OFF Delay Analog Timer
4
5
a
b
(Time limit 1c)
3
2
1
6
a
7
8
(Time limit 1c)
CONTACT OUT: 250VAC 3A,
b
30VDC 3A RESISTIVE LOAD
SENSORS
CONTROLLERS
MOTION DEVICES
+
-
SOURCE: •100-120VAC 50/60Hz
•200-240VAC 50/60Hz
•24VAC 50/60Hz, 24VDC
Dimensions
8
38
75.5
62
●Panel cut-out
Min. 55
I'
42
1
Min. 62
[
·1
45
(unit: mm)
0.6
0
0.6 0
45
J
● Bracket
48
1
8-pin socket (PG-08, PS-08(N), PS-M8) is sold separately. Refer to the '(I)Connectors/Connector Cables/Sensor Distribution Boxes/Sockets's.
10 81.5
54
41
8-pin socket
Unit Description
Power indicator
1
Time range display part
Time range switching SW
●Time specifications
Model Time range Time unit Time setting range
ATS8P-
ATS8P-
1
S
10 1 to 10 sec
1
M
10 1 to 10 min
SEC
MIN
0.1 to 1 sec
0.1 to 1 min
Operation
When supplying the power, 'a' contact turns ON at the same time. When turning OFF the power, 'a' contact turns OFF after the setting time (T).
Power
Time limit a contact
Time limit b contact
Power LED operation
②-⑦
⑧-⑥ ①-③
⑧-⑤ ①-④
T
T: setting time
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers
(M) Counters
(N) Timers
(O) Digital Panel Meters
(P) Indicators
(Q) Converters
(R) Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
(U) Recorders
(V) HMIs
(W) Panel PC
(X) Field Network Devices
Autonics