AT&T D-10000, D-320 User Manual

107 W. Main Street
Worthington, PA 16262
Phone: 724.297.3416 Fax: 724.297.5189
http://www.airtak.com
OPERATING INSTRUCTIONS
Refrigerated Air Dryers Models D-320 through D-10,000
Contents
A. INTRODUCTION B. RECEIVING C. LOCATION D. FOUNDATION E. PIPING F. ELECTRICAL G. COMPRESSED AIR CIRCUIT
1. Air to Air Heat Exchanger
2. Air to Refrigerant Heat Exchanger (Evaporator)
3. Drain Traps
H. REFRIGERANT CIRCUIT
1. Refrigerant Compressor
2. Air-Cooled Condenser and Condenser Fan Cycling Control (Low Ambient)
3. Air to Refrigerant Heat Exchanger (Evaporator)
4. Expansion Valves
5. Hot Gas Bypass Valve (D-320 and Larger)
6. Low Pressure Switch
7. High Pressure Switch
8. Crankcase Heater (D-320-A thru D-2000-A and D-400-W thru D-1000-W)
9. Automatic Water Regulating Valve
10. Oil Sightglass
11. Refrigerant Liquid Line Filter Dryer
12. Water Pressure Switch
13. Desuperheating Valve (D-1600 and Larger)
14. High Temperature Control
15. Start Timer
I. START-UP J. DESIGN CONDITIONS K. SHUTDOWN L. WATER-COOLED MODELS: Cooling Water Requirements M. MAINTENANCE
1. Drain Valves
2. Refrigeration Condenser
3. Condenser Fans
N. REMOTE CONDENSER INSTALLATION (OPTIONAL)
TROUBLESHOOTING GUIDE
WARRANTY PROCEDURES
OTHER AIR/TAK PRODUCTS
2
A. INTRODUCTION
AIR/TAK Refrigerated Compressed Air Dryers are of the high-efficiency type, designed to effectively remove moisture from compressed air by means of a refrigeration process. The compressed air pressure dewpoint is reduced to 38°F and then reheated to prevent in-plant air lines from sweating. The 38°F dewpoint can be maintained under varying conditions from zero load to 100% of the design conditions.
AIR/TAK dryers are completely automatic in all respects. As with all AIR/TAK products, only a minimum of maintenance is required. It is our recommendation that this manual be followed for any maintenance that might be required. Any, and all service should be performed by a qualified refrigeration engineer who is trained in the service of refrigerated air dryers.
B. RECEIVING
Upon receiving your air dryer:
1. Inspect the shipping carton for any apparent damage.
2. After removing the crate, inspect the unit for any hidden damage.
3. Report any damage immediately to the carrier and notify your supplier.
C. LOCATION
Air cooled dryers must have cool ambient air made available to prevent a heat build-up in the area where the dryer is installed. An exhaust system is recommended to avoid recirculation of hot condenser air.
Ambient temperature at the selected location should not exceed 100°F (38°C), 60 HZ; or 77°F (25°C), 50 HZ; and should not be lower than 50°F (10°C). High ambient temperature can affect the efficiency of the dryer. Every 10°F increase in ambient temperature above 100°F (38°C) will result in a 6% decrease in air cooled dryer performance, resulting in higher dewpoints and increased operating costs.
To assure an unrestricted flow of cool air through the refrigeration condenser, a minimum distance from the cabinet to the nearest wall of 24 inches must be maintained.
All outside installations must have weather protection. Minimum protection should include a shed roof. Air-cooled units must be protected against the wind.
Ambient temperatures should not exceed 100°F (38°C) and should not be lower than 50°F (10°C) where a standard unit is to be located. If ambient temperatures below 50°F (10°C) are anticipated, the dryer should be equipped with an optional ultra-low ambient package.
D. FOUNDATION
All dryers are completely free-standing units. Any reasonably level floor that has sufficient strength will serve as a foundation.
E. PIPING
When piping the main air lines to the dryer, the use of flexible connections or union joints is recommended to avoid piping stress and vibration when used with reciprocating compressors. Bypass piping and valves are recommended. The bypass will permit isolation of the dryer for servicing and will eliminate the need to shut down the complete compressed air system. The bypass must be provided and installed by the customer.
3
In keeping with good compressed air piping design, the air dryer should be installed on the downstream side of the air receiver and aftercooler. An AIR/TAK prefilter(s) for oil and dirt removal installed at the inlet of the dryer is recommended. Contamination can be present in a compressed air system and can reduce the ability of the dryer heat exchangers to achieve the proper heat transfer. AIR/TAK recommends the use of afterfilter(s) to remove final trace contaminates.
All water cooled dryers are factory piped for cooling tower water, unless ordered otherwise. A dryer that is piped for city water cannot be used on cooling tower water without necessary piping changes because of: the higher water temperature, lower water pressure and the increased water flow needed. All water cooled dryers are supplied with a factory mounted automatic water regulating valve which is designed to maintain the proper working refrigerant head pressure under all dryer load conditions. No adjustment will be necessary. (Full water pressure and flow should be supplied to the water line inlet. Refer to Section L for water cooled water requirements.)
All dryers are supplied with automatic drain valves. On models D-320 to D-2000, an isolation valve/strainer and solenoid drain valve is provided for the outlet of the air to-refrigerant heat exchanger. Models D-2500 to D-7500 dryers are supplied with two drain outlets with zero air loss valve provided for each outlet. Models D-8000 and larger are supplied with four drain outlets and two zero air loss drain valves. Solenoid drain valves with isolation
valve/strainer and zero air loss drain valves are to be installed at destination.
F. ELECTRICAL
The dryer is completely wired at the factory. A terminal box at the rear of the dryer, or a control box on the side of the dryer is provided for the main power connection. Power connections can be made through any knock-out on the terminal box or through the side or top of the control box. The dryer dataplate must be checked to verify voltage, phase and cycle. Connect the power leads to the terminal block which is conveniently located within the box. Always be sure adequate power is available to maintain efficient operation of your dryer.
A properly sized fused main disconnect switch (supplied by the installer) must be located near the dryer. Check the wiring diagram supplied with the dryer for the recommended fuse size. The use of fusetron time-delay fuses will permit smaller fuse sizes and, in some instances, a smaller fused disconnect switch may be used.
The dryer wiring must be independent of the air compressor so as not to cycle along with the air compressor.
Fan rotation must be checked to assure proper air flow. Air must be drawn through the finned condenser and exit through the fan guard. To change fan rotation, switch any two hot power leads on the terminal block located in the box.
Dryers with scroll compressor(s) need to be checked for proper rotation by making sure the discharge pressure is greater than the suction pressure. To change rotation, switch inlet power leads L1 and L3. If you have any question or problems, please consult factory.
Dryers with pre-wired solenoid drain valves need to have the DIN connector attached to the drain valve after the drain is installed on the dryer.
On units supplied with crankcase heaters, the crankcase heaters are pre-wired at the factory to be energized when power is supplied to the dryer. It is important that the crankcase heaters be energized at least 24 hours before initial start-up or after prolonged shut-down. (See Start-Up).
4
Loading...
+ 9 hidden pages