Atag MadQ/2 Installation Manual

8G.51.10.00/10.05
INSTALLATION MANUAL
MadQ/2
MadQ/2 Controller
GB English
Contents
General safety instructions..............................................................................GB-4
Safety measures for EMC - compliant installation.........................................GB-4
Installation of the control unit.........................................................................GB-6
Mounting instructions .................................................................................... GB-6
Electrical installation...................................................................................... GB-6
Electrical connection ..................................................................................... GB-7
Installation set MadQ .................................................................................... GB-8
Wall-mounting case .......................................................................................GB-9
Assembly and electric installation .................................................................. GB-9
Electrical connections ................................................................................. GB-10
Thermostats (for remote- control) .............................................................. GB-11
Mounting Location....................................................................................... GB-11
Mounting instructions .................................................................................. GB-11
Electrical connection ................................................................................... GB-12
Electrical connection at control unit ............................................................ GB-12
Data bus allocation...................................................................................... GB-12
Accessories ..................................................................................................GB-14
Outdoor sensor ........................................................................................... GB-14
Tank sensor ................................................................................................ GB-15
Flow sensor................................................................................................. GB-15
Resistance values of sensors depending on temperature.......................... GB-16
Commissioning the control unit .................................................................GB-17
Code input................................................................................................... GB-17
Automatic setting function..........................................................................GB-18
Alarm messages...........................................................................................GB-19
Plant information ..........................................................................................GB-20
Parameter synoptic ......................................................................................GB-23
Overview of installer parameters and adjustment options.......................... GB-25
Appendix ................................................................................................................ I
GB
General safety instructions
All electrical connections and safety measures have to be carried out by a specialist in due consideration of valid standards and VDE-guidelines as well as the local regulations.
The electrical connection must be a permanent connection in accordance with VDE 0100).
The electrical connection must be in compliance with the specifications of the ATAG boiler.
Important! Deenergize the boiler or wall-mounting
case before opening. Unprofessional plugging attempts under voltage may damage the control or cause dangerous electrical shocks.
Safety measures for EMC ­compliant
installation
1. Cables with mains voltage must be
generally routed separately from sensor lines and data bus cables. A minimum distance of 2 cm between the lines is mandatory. Crossing of lines is permitted.
2. For control units with their own mains connections, ensure the power-, sensor- and bus lines are routed separately. If cable ducts are in use, they must be equipped with separators.
3. When installing the control units or thermostats, a minimum distance of 40 cm must be maintained to other electrical utilities with electromagnetic emissions, such as radio`s, motors, transformers, dimmer switches, microwave ovens and televisions, loudspeakers, computers, radiophones etc.
4. A minimum distance of 40 cm between the thermostats and control units is mandatory. Several control units in a data bus connection may be installed directly side by side.
Fig. 1: Minimum distances during electrical
installation
Fig. 2: Minimum distance to other electric
instruments
40 cm
15 cm
Mains
230 V~
Data bus line 12 V
2c
m
GB
5. The main connection for the heating system (i.e. boiler control panel ­control unit) must be designed as an independent electrical circuit. There should no fluorescent lamps or other machines, which may be sources of disturbance, be connected and even the possibility of such connections should be ruled out.
6. The outside sensor may not be
installed close to transmitting or receiving equipment (on garage walls close to receivers for radio-controlled garage door openers, amateur radio antennas, radio controlled alert systems or close to large scale radio transmission equipment).
Recommended cable cross-sections and maximum permitted cable lengths:
For all cables with mains voltage (power supply, burner, pumps, actuators)
1.5 mm
2
Maximum length: Unlimited cable length within house installation.
All low voltage cables (sensors, external switches due to demands via contact points, modem connection cables, analogue signal cables etc.): 0.5 mm
2
Maximum length: 100 m (duplicate wire)
Longer connecting cables should be avoided in order to reduce the risk of interfering radiation.
Data bus line: 0.6 mm Ø Maximum length: 50 m (duplicate wire) Longer connecting cables should be avoided in order to reduce the risk of interfering radiation.
Fuse 16 A
Heating room emergency switch
Only connect heating room lighting and sockets on separate power circuit!
Thermostat(s
)
ATAG - burner
Fig. 3: Electric routing in heating room
GB
Installation of the control unit
Mounting instructions
Parts necessary for the installation into the boiler control unit:
- MadQ control unit 23BC or 233BVVC
- MadQ installation set for 23BC or
233BVVC
Parts necessary for the installation into the wall-mounting case:
- MadQ control unit 23BC or 233BVVC
- MadQ wall-mounting case
All control units can be built into the corresponding ATAG boiler control unit or wall-mounting case after the electrical connections have been made. They should be fastened with quick­clamping devices (1) by turning them clockwise. The removal is done in reverse order. See the assembly instructions that belong to the MadQ installation set and the MadQ wall-mounting case.
Electrical installation
The electrical connection and the further routing to the control units is done on the back of the unit with the four
terminal strips X1, X2, X3 and X4 in the boiler control unit, corresponding to the designations in the coloured terminal fields.
The routing in the wall-mounting case is prepared in the factory.
All terminal clamps inside the blue fields (X1) carry low voltage and may not get into contact with the mains voltage! Ignoring this will inevitably lead to the destruction of the control unit and to the loss of the basis for warranty claims!
The terminal clamps in the red fields (X2...X4), depending on the operation mode, generally carry mains voltage.
Terminal occupation, see next page.
Note:
When routing the unit, ensure that sensor­, data bus- and mains lines are routed
separately. Mutual routing inside one cable is prohibited. Sensor- and data bus
lines may not be routed with mains lines that supply electrical units that are not interference suppressed according to EN 60555-2.
230 V~
GB
Electrical connection
Mains connection
1 - Do not use 2 - Do not use 3 - Unmixed circuit pump 4 - Do not use 5 - Charge pump 6 - L 1 / 230 V 7 - Mixing valve 1 OPEN 8 - Mixing valve 1 CLOS 9 - Mixed circuit pump 1 10 - Variable output 1 11 - Variable output 2 12 - L 1 / 230 V 13 - Mixing valve 2 OPEN 14 - Mixing valve 2 CLOS 15 - Mixed circuit pump 2 16 - Do not use 17 - Do not use 18 - Do not use 19 - Do not use 20 - Do not use 21 - N / 230 V 22 - L 1 / 230 V
Sensor-/data bus connection
23 - GND for sensor 24 - Data bus connection A 25 - Data bus connection B 26 - Outside sensor ARV20 Mad 27 - Do not use 28 - Tank sensor 29 - Flow sensor mixed circuit 1 30 - Variable input 1 31 - Variable input 2 32 - Variable input 3 33 - Flow sensor mixed circuit 2 34 - Do not use 35 - Do not use 36 - Impulse input 37 - Boiler control unit-data bus A 38 - Boiler control unit-data bus B
GND for sensor
} Mains connection
GB
When building in a MadQ controller into a boiler a data bus connection is made between the boiler and the controller through the cable loom. In case of a Cascade installation the positions 20 and 21 of the connection block of each boiler have to be connected to each other. Adjust Parameter 89 of each boiler to their individual bus address: Boiler 1 = 00, boiler 2 = 01, etc. See also example 17 on page XXXIV.
Installation set MadQ
GB
Cable harness for the installation of a control unit in the boiler control unit
MC-1 MC-2
MC-1
MC-2
Sensor
Sensor
DHW
VO1 VO2
USPSPS
OS
ARV12
Wall-mounting case
Application:
The wall-mounting case serves as a case for the control unit.
Design
The wall-mounting case is only suitable for use as a case and for the connections of the control unit. The control unit is ready for use after it has been fastened to the motherboard and after the output cables have been routed.
Assembly and electric installation
1- Push out the cable inlets at the pre-
stamped locations at the top or bottom according to the size and number of the cable ducts.
Note: If no cable duct is used, a suitable strain relief for the cables must be ensured during installation.
2- Place locking bolts (1) horizontally and
pull off the connection covers (2) to one side.
3- Install the wall-mounting case with the
supplied bolts and dowel pins on a flat surface without distorting it. Use the enclosed drilling jig.
4- Carry out the electric routing according
to the unit version and the connection diagram (see reverse).
The terminal clamps of the terminal blocks X5 and X6 in the left connection
area carry low voltage and may not come into contact with the mains voltage! Ignoring this will inevitably lead to the destruction of the control unit and to the loss of the basis for warranty claims!
The terminal clamps of the terminal blocks X7 to X10 in the right connection area carry mains voltage, depending on the operation mode. When connecting the electric cables, the cables with a solid core can be placed directly into the clamp. The twisted core must carefully be lead in by pressing the locking device
5- Slide clamp covers onto the wall-
mounting case and fasten them.
6- Slide the control unit into the wall-
mounting unit and let it engage under evenly distributed pressure. The electric connection is made via the socket strip on the motherboard. Tighten the control unit and both quick­clamping devices clockwise.
Note:
When routing the control unit, ensure that sensor-, data bus- and mains lines are routed separately. Mutual routing inside one cable is prohibited. Use cable ducts equipped with separators, if necessary.
230 V~
1
2
GB
GB-10
Electrical connections
X5 X6 Sensor- and data bus lines (X5-X6)
1 1 B – Data bus - A (T2B) 2 2 Outdoor sensor ARV20 Mad 3 3 Do not use 4 4 Tank sensor 5 5 Flow sensor mixed circuit 1 6 6 Variable input 1 7 7 Variable input 2 8 8 Variable input 3
9 9 Flow sensor mixed circuit 2 10 10 Do not use 11 11 Do not use 12 12 Do not use
////1
11
1
X7 X10 X10 Mains connections (X7)

L1 (230V)
X8 X9 X10 Pumps and mixing valve engines (X8, X9, X10)

Unmixed circuit pump

Charge pump
4 5 5 Engine mixing valve 1 (OPEN)
5 Engine mixing valve (CLOS)
6 7 7 Mixed circuit pump 1 7 8 8 Variable output 1 8 9 9 Variable output 2 9 10 10 Engine mixing valve 2 (OPEN)
10 Engine mixing valve 2 (CLOS)
11 12 12 Mixed circuit pump 2
X11 Data bus boiler control unit (X11)
A
Data bus boiler control unit A
B Data bus boiler control unit B
Here, only connect the first MadQ of the data bus connection!
Only connect the A-B data bus boiler control unit (RS485) of the boiler control unit after the first MadQ control unit from position 20-21 in the boiler to position A-B on X11 in the wall-mounting case. Every following MadQ control unit (up to 5) must be connected to the A-B data bus (T2B) from position 1 to X6 and X5.
GB
GB-11
Thermostats (for remote­control)
Mounting Location
a – for applications without room sensor
If the internal room sensor is not to be activated the unit may be mounted at any location indoors.
b – for applications with room sensor
The activated room sensor should be fixed at a height of approx.1.20 – 1.50 m at a place most representative of all rooms. It is recommended to chose a partition wall in the coolest day room. In order to ensure sufficient air circulation at the room station, it must be mounted to the wall with a gap inbetween.
The thermostat must not be mounted:
– at locations subjected to direct solar
radiation (consider the position of the sun during winter).
– close to heat-generating appliances,
such as televisions, refrigerators, wall lamps, radiators etc.
– on walls with heating or domestic hot
water pipes or chimneys behind.
– on non-insulated outside walls
– in corners or wall recesses, shelves or
behind curtains (insufficient ventilation)
– close to doors of unheated rooms
(influence of low temperatures)
– on unsealed flush-type boxes
(influence of external low temperatures due to the chimney effect of installation tubes)
– in rooms with radiators controlled by
thermostatic valves (mutual influence).
Mounting instructions
After removing the front panel by pressing the locating lug the wall mounting base can be taken off and mounted at the desired location using the enclosed dowel pins and screws. The data bus line must thereby be routed through the bottom cable gland.
Recommended connecting cable:
2x0.6 max. cable length: 50 m.
Note: For new installations use a
flush-mounting switch box to ensure perfect routing of cable.
Locating lug
GB
GB-12
Electrical connection
The 2-strand data bus cable is connected to terminals A and B of the 2-pole terminal strip on the bottom plate. The connections are not interchangeable and must be connected in compliance with the identification A/B on the base. If the two connecting lines are mixed up by mistake the display will be out of function.
Once the electrical connection is completed the thermostat is hooked in flush at the top and folded down, as shown in the picture, until it audibly engages into the wall-mounting base.
Electrical connection at control unit
See assembly instructions of the controll unit.
Data bus allocation
The connection of one or more thermostats to the control unit occurs via a two-core data bus line. Because this connection is always carried out parallel in the same line, a separate bus address must be allocated to every thermostat.
Likewise, a separate bus address must be allocated to every control unit (if there is more than one, e.g. when the heating circuit is extended).
Bus address (control unit)
If there is only one control unit, it should have bus address 10. If there is more than one control unit in the network (max.: five), the leading control unit that controls the boiler control unit, has bus address 10, the others are allocated in sequence with bus addresses 20, 30, 40 and 50.
Setting the bus address in the control unit
The setting of the bus address is carried out after entering the installer code in the data bus level of the corresponding control unit (see commissioning of the control unit).
Bus address (thermostat)
The allocation of the bus addresses of the control units and the bus addresses of the thermostats must be carried out according to the enclosed table.
Setting the bus address in the thermostat
A- Commissioning
After completing the electrical installation and commissioning the plant, all available segments appear in the display.
Control unit Thermostat
Function
Bus
address
Heating circuit
Bus
address
Control unit 1 10
Unmixed circ. Mixed circ. 1 Mixed circ. 2
11 12 13
Control unit 2 20
Unmixed circ. Mixed circ. 1 Mixed circ. 2
21 22 23
Control unit 3 30
Unmixed circ. Mixed circ. 1 Mixed circ. 2
31 32 33
Control unit 4 40
Unmixed circ. Mixed circ. 1 Mixed circ. 2
41 42 43
Control unit 5 50
Unmixed circ. Mixed circ. 1 Mixed circ. 2
51 52 53
¾ ¿ À Á Ä
°C KWh Min %
°C KWh Min %
0 2 4 6 8 10 12 14 16 18 20 22 24
Fffff
ffff
Segment test
GB
GB-13
Subsequently, the unit identification and the data bus address will appear.
After setting the bus address using the rotary pushbutton and confirming this by pressing it, the allocation determined by the address will appear automatically.
Attention:
Double allocation of bus addresses is not permitted and inevitably lead to faults in data transfer and therefore to faulty control of the heating system.
B - Changing bus addresses
If a bus address has to be changed afterwards, then carry out the following procedure:
1 - By pressing the bottom locking device,
remove the thermostat from the ground board (the bus is disconnected).
2 - Place the thermostat again while
keeping the rotary pushbutton depressed until the address setting appears.
3 - Set and confirm a new bus address.
RS-2
15.05.
V1.2
BUS ADDRES
11
Instrument identification
Device type Software date Software version
Address settings
see table above
BUS
HC
AU-1
Data bus address
Unmixed circ. MadQ control unit 1 (=AU1), MadQ control unit 2 (=AU2), etc.
GB
GB-14
Accessories
Outdoor sensor
Mounting Location
The outdoor sensor should be mounted on the most exposed and coldest side of the building (north or north-east) at a height of min. 2 m above ground.
Exception: If the preferential living
area is facing another direction, the corresponding side of the building should be chosen.
When mounting the sensor mind external heat sources (heated chimneys, war hot air from air shafts, installation on black surfaces, thermal bridges in the wall, etc.) which could falsify the measuring value. The cable outlet must always be directed downwards in order to avoid the penetration of moisture.
The outside sensor may not be installed close to transmitting or receiving equipment (on garage walls close to receivers for garage door openers, amateur radio antennas, radio controlled alarm systems or close to large scale radio transmission equipment etc.).
Electrical connection
For the electrical installation preferably use a 2-strand cable with a minimum cross-section of 0,6mm
2
. The connection is made at the 2 screw terminals inside the sensor case and may be interchanged.
Mounting instructions
1– Route the sensor cable to the
mounting location
2– Loosen lid screws from sensor case
and remove top
3– Mount sensor base with enclosed
central fastening screw. Use sealing ring! Cable outlet must be directed downwards!
4– Insert the sensor cable so that the
cable jacket is fully enclosed by the sealing lip.
5– Electrical connection on terminal block
boiler control unit position 18-19.
6– Attach the lid again an and screw it
firmly onto the base. Ensure correct fit
of sealing ring. In situations when the control unit has to be controlled via its own outside sensor, ARV20 (white) must be used. Connection to the control unit.
Outside sensor ARV12
GB
GB-15
Tank sensor
Versions:
AVB06 Cable length 5 m Application: Tank sensor (for nearby hot
water generators, buffer tanks etc.)
Mounting location:
In the designated immersion sleeve of the corresponding application.
Mounting in DHW- or buffer tanks
Bend the pressing spring towards the sensor tip and slide the sensor into the dry immersion sleeve of the corresponding tank.
Electrical connection
Clamp the sensor to the appropriate terminal clamps of the respective control unit (see corresponding connection diagram). The two-strand connection is interchangeable.
Flow sensor
Flow sensor VF20
Versions:
VF 20 Cable length 4 m
S4363400
Application: As a flow sensor for unmixed
circuits and mixed circuits of heating circuits
Mounting location:
Behind the mixer pump at a distance of at least 50 cm.
Mounting:
Polish the flow pipe and apply heat conductive paste. Fasten the sensor to the contact location with a tensioning belt so that it is flush with the pipe's surface. Ensure a tight fitting!
Electrical connection
Clamp the sensor to the appropriate terminal clamps of the respective control unit (see corresponding connection diagram). The two­strand connection is interchangeable.
Tank sensor AVB06
GB
GB-16
Resistance values of sensors depending on temperature
temperature
°°°°Celsius
PTC 2K
(2kΩΩΩ/25°°°°C)
Flow sensor VF20
Outside sensor ARV20
Tank sensor AVB06
NTC 12K
(12kΩΩΩ/25°°°°C)
Outside sensor ARV12
-20 1.387 98.900
-18
-16
-14
-12
-10
1.413
1.438
1.463
1.488
1.513
98.950
80.100
72.200
65.150
58.900
-8
-6
-4
-2 0
1.540
1.566
1.593
1.619
1.646
53.300
48.250
43.750
39.750
36.150 2 4 6 8
10
1.673
1.700
1.728
1.756
1.783
32.900
29.950
27.350
24.950
22.800
12 14 16 18 20
1.812
1.841
1.869
1.898
1.927
20.850
19.100
17.500
16.100
14.750
22 24 26 28 30
1.957
1.986
2.016
2.046
2.077
13.600
12.500
11.500
10.600
9.800 32 34 36 38 40
2.107
2.128
2.169
2.200
2.232
9.100
8.350
7.750
7.200
6.650 45 50
2.311
2.393
5.525
4.600 55 60
2.475
2.559
3.850
3.250 70 2.732 2.325 80 2.910 1.700 90 3.093 1.275
100 3.283 950
GB
GB-17
Commissioning the control unit
Segment test and identification
During the first activation of the control unit or with each return of voltage after a power failure all segments available in display will appear:
This is followed by the equipment version with type code and current version number of software status
If there is no alarm at present, the standard display with date, time and current flow temperature will appear afterwards.
An active summer switch-off is represented by a sunshade symbol (À).
An active frost protection function is represented by a ice crystal symbol (Á).
Code input
Installer code
After entering the installer code all parameters determined for the heating specialist are released and can be edited in accordance with the syst version.
Code input
In order to enter the installer code, the keys
¥
and
§
must be pressed
simultaneously for approx. three seconds, until the code input appears in the display.
¥
+
§
Each flashing digit is set by using the rotary pushbutton in accordance with the code number and is confirmed by pressing the button. All other digits are edited in the same way.
After the code has been entered correctly, the acknowledgement INSTALLER OK will appear upon confirmation of the last digit, after a wrong entry, the message CODE ERROR will appear.
The factory set consumer code is: 1 2 3 4
The factory set installer code is : 0 1 2 3 Note: If the code is not accepted, you
should consult the supplier!
Attention: Enabled installer parameters will
be blocked again if no further action takes place over a period of ten minutes. In this case the installer code must be entered again.
¾ ¿ À Á Ä
°C KWh Min %
°C KWh Min %
0 2 4 6 8 10 12 14 16 18 20 22 24
Fffff
ffff
À
°C
;
1632
63.5
°C
;
1632
63.5
Segment test
Standard displa
y
Wednesday, June 25
th
2003 16:32 hrs Temp. 63.5°C
Summer shutdown
active
Á
°C
;
1632
635
Plant frost protection
active
N
VV
18
V2.0
Device type
Version number
Type code
CODE
0
000
I
OK
GB
GB-18
Automatic setting function
This function can switch off control circuits that are not needed or are only needed later.
The control circuits are registered automatically when their corresponding sensors are connected and transfer permitted measuring values. Control circuits without sensor circuits are automatically switched off without displaying an alarm.
The AUTO-SET function is activated every time the mains voltage is switched on.
Automatic activation
If the AUTO-SET function is switched on by parameter 14 in the SYSTEM level and the commissioning date has not yet been saved, then the sensors that are connected or clamped off are registered automatically every time the control unit is switched on. During this period, the error messages of the sensors (short circuit interruption) are suppressed. If the commissioning date was saved, a changed sensor configuration can only be confirmed via manual activation.
Manual activation
The AUTO-SET function can be activated manually at any time. To do this, press the rotary pushbutton when switching on the control unit while the version is being displayed. Keep the button depressed until the AUTO-SET function in the display is quit.
The AUTO-SET function serves the following sensor inputs: – Outdoor sensor – Flow sensor 1 – Flow sensor 2 – Tank sensor
Apart from that, the AUTO-SET function is only carried out if the circuits in the following levels that are allocated to the sensors were parameterised accordingly.
For the tank sensor:
HYDRAULIC Level
Parameter 2 - DHW-charge pump function set value OFF or 1 (DHW-charge pump)
For flow sensor 1:
HYDRAULIC Level
Parameter 3 – mixed circuit function 1 set value OFF or 3 (mixed circuit)
For flow sensor 2:
HYDRAULIC Level
Parameter 4 – mixed circuit function 2 set value OFF or 3 (mixed circuit)
Because a parameter setting is not changed by the AUTO-SET function, the current settings are checked beforehand. A change is only made if one of the settings above is changed. This means that the deeper system configuration can never be changed by the AUTO-SET function.
N
VV
18
V2.0
T
T
Standard display
GB
GB-19
Alarm messages
In order to be able to perform an exact diagnose in case of a problem the control system is equipped with a comprehensive fault alarm system. An alarm is thereby always displayed and saved on the corresponding control unit.
There are five different categories of error messages:
1 - Sensor error messages
Sensor measuring values that are not inside the measuring range are valued as errors. They appear with an error message according to their use.
2 - Error messages of the boiler control
unit
These error messages evaluate the respective control status. They appear with the corresponding error message, depending on the version and allocation.
3 - Logical error messages
The error messages evaluate the expected control result. They appear with the corresponding error message, depending on the version and allocation.
4 - Bus error messages
These error messages relate to address errors such as double allocation or unrecognised address settings inside the data bus. They appear with the corresponding error message, depending on the version and allocation.
5 - Alarms from the boiler control
These error messages come from the boiler control and are divided into permanent faults (permanent locking) with error code E-XX (MCBA-code) or temporary faults (self-eliminating locking) with fault code B-XX (MCBA-code).
The display and further processing of logical error messages can be suppressed by a corresponding parameter setting (see parameter 13 – SYSTEM level – logical error message)
Further processing of errors:
– Errors appear in the standard display of the
control
– System errors appear in the info-level at the
corresponding info-value
– If necessary, errors are transferred into the
error message level (see description below)
– At the corresponding parameter settings,
errors activate an error notification output for connecting an optical or acoustic signal transmitter.
– Errors are transferred to the corresponding
gateways via the data bus.
Table of error messages:
Sensors and variable inputs:
Designation Error type Code Outdoor sensor Interruption 10-0 Outdoor sensor Short circuit 10-1 Flow sensor 1 Interruption 12-0 Flow sensor 1 Short circuit 12-1 Tank sensor Interruption 13-0 Tank sensor Short circuit 13-1 VI 2 Interruption 14-0 VI 2 Short circuit 14-1 VI 2 Error message 14-7 VI 3 Interruption 15-0 VI 3 Short circuit 15-1 VI 3 Error message 15-7 VI 1 Interruption 16-0 VI 1 Short circuit 16-1 VI 1 Error message 16-7 Buffer sensor Interruption 17-0 Buffer sensor Short circuit 17-1
Designation Error type Code Flow sensor 2 Interruption 18-0 Flow sensor 2 Short circuit 18-1
GB
GB-20
Temperatures:
Heat generator Not reached 50-4 Heat generator Exceeded 50-5 Domestic hot water
Not reached 51-4
Flow MC1 Not reached 52-4 Flow MC2 Not reached 53-4 Room HC Not reached 54-4 ROOM MC1 Not reached 55-4 ROOM MC2 Not reached 56-4
Data bus error
Address Address conflict 70-0 Activity No T2B-signal 70-1 EEPROM 71-0 EEPROM defective 71-1 Bus error Bus error 70-6
Fault in boiler control
Error Locking En: XX Error Blockage Bn: XX Explanation fault in boiler control:
En: XX
Alarm message register
The control unit is provided with an error message level, which is able to hold up to five alarms. The alarms are displayed with date, time, and nature of fault (error number), the errors are polled in the sequence of their occurrence in the level
ALARM
.
The latest (= up-to-date) alarm is prioritized at first position, alarms that have arrived before appear in the order of their occurrence. Upon arrival of a new alarm the fifth alarm will be deleted.
The alarm messages of the MCBA are a special case. Because they are external errors, they are not saved in the internal error message register of the control unit.
Plant information
Plants and system temperatures
After accessing the information level using the information key ¤ , all available plant- and system temperatures can be requested one by one by turning the rotary pushbutton clockwise.
If
set value
is displayed in the following table in the category "display value", it will appear when the rotary pushbutton is pushed. The following displays only appear under the specified display conditions. Some of the displays are not available for certain unit versions and are therefore skipped.
GB
Boiler error codes
(see boiler documentation)
Boiler
0 = Boiler 1 1 to 7 = Boiler 2 to 8 (Cascade)
E = Error
(B =Boiler blocking code)
GB-21
INFORMATION Display value Comments Application
Outside (1)
Mean value/ current value
Outside (1)
Min./max. value (0.00 to 24.00 h)
Outside 2
Mean value/ current value
Outside sensor 2 to var. input
Outside 2
Min./max. value (0.00 to 24.00 h)
Outside sensor 2 to var. input
External blockage
Blocked status ON/OFF
Ext. blockage to VI
Tank (1)
Set value/actual value
If there is a tank (..B..)
Tank 2
Set value/actual value
Tank sensor 2 to var. input (..B..)
DHW-thermostat
Charge status ON/OFF
Instead of tank sensor (..B..)
Demand via contact point (VI-1)
Demand ON/OFF Contact to var. input
Demand via contact point (VI-2)
Demand ON/OFF Contact to var. input
Demand via contact point (VI-3)
Demand ON/OFF Contact to var. input
Flow Mixed circ. 1
Set value/actual value
(..3..)
Flow Mixed circ. 2
Set value/actual value
(..33..)
Room temperature Unmixed circ.
Set value/actual value
Control unit required (..2..)
Room temperature Mixed circ. 1
Set value/actual value
Control unit required (..3..)
Room temperature Mixed circ. 2
Set value/actual value
Control unit required (..33..)
Thermostat function Unmixed circ.
THERMOSTAT HC
Room thermostat function active OFF = no room limit
(..2..)
Thermostat function Mixed circ. 1
THERMOSTAT MC-1
Room thermostat function active OFF = no room limit
(..3..)
Thermostat function Mixed circ. 2
THERMOSTAT MC-2
Room thermostat function active OFF = no room limit
(..33..)
GB
Loading...
+ 47 hidden pages