Ariston A23 MFFI, A27 MFFI Servicing Instructions

A/23 MFFI - A/27 MFFI
G.C.N. 47-116-10 / 47-116-12 Servicing Instructions Type C Boilers
LEA VE THESE INSTRUCTIONS ADJACENT T O THE GAS METER
2
Page No.
1. SERVICING INSTRUCTIONS
1.1 Replacement of Parts 3
1.2 To Gain General Access
- Removing the Front Panel 3
- Removing the Side Panels 4
- To Lower the Control Panel 4
1.3 Access to the Combustion Chamber
- Removing the Sealed Combustion Chamber 5
- Removing the Burner and Injectors 5
- Removing the Electrodes 6
- Removing the Main Heat Exchanger 7
- Removing the Air Pressure Switch 7
- Removing the Venturi Device 8
- Removing the Fan 8
1.4 Servicing and Removal of the Gas Valve
- Setting Gas Pressure 9
- Removing the Spark Ignitor 11
- Removing the Gas Valve 12
1.5 Access to the Hydraulic Circuit
- Removing the D.H.W. (Secondary) Exchanger 12
- Removing the Safety Valve 13
- Removing the Automatic Air Vent 13
- Removing the Main Flow Circuit Switch 13
- Removing the Pump 14
- Removing the Pressure Gauge 14
- Removing the Expansion Vessel 15
- Removing the Overheat Ther mostat 15
- Removing the Heating Temperature Sensor (N.T.C.) 15
1.6 Access to the Control System
- Checking the Fuses 16
- Removing the Time Clock 16
- Removing the P.C.B.s 17
2. FAULT FINDING
2.1 Fault Finding Guide (Flow-chart) 18
2.2 Fault Finding Using the Total Check System 23
3. ELECTRICAL DIAGRAMS
3.1 Electrical Connection 24
3.2 Functional Flow Connection 25
4. SHORT SPARE PARTS LIST
26
TABLE OF CONTENTS
3

1. SERVICING INSTRUCTIONS

The life of individual components vary and they will need servicing or replacing as and when faults develop. The fault finding sequence chart in chapter 2 will help to locate which component is the cause of any malfunction, and instructions for removal, inspection and replacement of the individual parts are given in the following pages.

1.1 Replacement of Parts

1.2 To Gain General Access

All testing and maintenance operations on the boiler require the control panel to be lowered.This will also require the removal of the casing.
To dismantle the front part of the casing, proceed as follows:
1.
Remove screw “A”
(see fig. 1.1)
;
2.
Lift the front panel up and forward
(see fig. 1.2)
.
A
Fig. 1.2
Fig. 1.1
To ensure efficient safe operation, it is recommended that the boiler is serviced annually by a competent person.
Before starting any servicing work, ensure both the gas and electrical supplies to the boiler are isolated and the boiler is cool.
Before and after servicing, a combustion analysis should be made via the flue sampling point (please refer to the Installation Manual for further details).
After servicing, preliminary electr ical system checks must be carried out to ensure electrical safety (i.e. polar ity, earth continuity, resistance to earth and short circuit).
4
Removing the side panels
1.
Remove the screws “B”;
2.
Pull the panel away from the boiler, then lift the panel up and away from the boiler
(see fig. 1.2).
To lower control panel
1.
Remove the screws “B”
2.
Push the two side panels outward slightly
(fig. 1.5)
;
3.
Rotate the control panel forward and down.
Fig. 1.4
B
Fig. 1.5
B
C
Fig. 1.7
Fig. 1.6
C
To access the areas where the adjustment and control devices are located, simply remove the plugs by pressing from the inside, unscrew the screws “C” and remove the bottom part of the instrument panel, rotating it upwards.
Fig. 1.3
B
1.
Remove the side panels of sealed chamber
(fig. 1.10)
;
2.
Remove the screws “F” of the burner
(see fig. 1.11)
;
3.
Remove the burner
(see fig. 1.12)
;
4.
Remove the injectors using a No. 7 socket spanner;
5.
Replace in reverse order.
Removing the burner and the injectors
5
Removing the sealed chamber
frontal cover
1.3

Access to the Combustion Chamber

Remove the screws “D”
Remove the screws “E”
Removing the combustion cover
E
E
E
E
E
E
E
Fig. 1.8
Fig. 1.9
D
D
D
D
Fig. 1.10
Fig. 1.11
Fig. 1.12
F
push
push
6
Removing the electrodes 1.
Remove rubber gasket “G”
(see fig. 1.13)
;
2.
Disconnect ignition leads by pulling downward
(see fig. 1.14)
;
3.
To remove the flame sensor, disconnect the cable at its only connection point close to the P.C.B.
(see fig. 1.15)
;
5.
Remove screw “H” using a Philips No.2 star tip screwdriver
(see fig. 1.16)
;
6.
Slide the electrode gently downward
(see fig. 1.17).
To replace, repeat the steps in reverse order , pa ying particular attention to the following:
a
-Centre the electrode in the positioning hole carefully, otherwise the electrode may break;
b
-Check that the cables have been connected correctly;
c
-Check that the rubber gasket covers the cable/electrode connection
point completely.
Fig. 1.13
G
Fig. 1.14
Fig. 1.15
Fig. 1.16
Fig. 1.17
H
1.
Disconnect the electrical connections “K” and silicone pipes “L” from their connection points
(see fig. 1.20)
;
2.
Remove screws “J” on the top of the sealed chamber
(see fig. 1.21)
;
Use a No.2 star tip screwdriver to remove the switch from the plate.
Fig. 1.21
Fig. 1.20
7
1.
Drain the boiler of water;
2.
Release the two connection nuts “I” connecting the exchanger to the flow and return pipes
(see fig. 1.18)
;
3.
Pull it straight out
(see fig. 1.19).
Removing the main heat exchanger
Removing the air pressure switch
Fig. 1.18
I
Fig. 1.19
L
L
K
J
J
8
1.
Disconnect the silicone pipes “M” and remove the screw “N”
(see fig. 1.22)
;
2.
Extract the venturi
(see fig. 1.23)
.
Removing the venturi device
1.
Disconnect electrical connections and remove screws “O” using a No. 2 star tipped screwdriver
(see fig.1.24)
;
2.
Pull fan to the right, forward and remo ve (
see fig.1.25)
;
3.
Remove fan from mounting plate;
4.
Remove screws “P”
(see fig.1.26)
.
Removing the fan
M
N
Fig. 1.22
Fig. 1.23
Fig. 1.24
Fig. 1.25 Fig. 1.26
O
O
P
P
9
1.4

Servicing and Removal of the Gas Valve

1
2
3
4
A
B
C
E
F
D
SIT TANDEM
SIT SIGMA
1
2
3
4
A
B
C
E
F
D
10
Setting the minimum and the maximum power of the boiler
1. Check that the supply pressure to the gas valve is a minimum of 20 mbar
for natural gas.
2. To do this, remove the screw “A”. Fit the pipe of the pressure gauge to the pressure connection of the gas valve “B”. When you have completed this operation, replace the screw “A” securely into its housing to seal off the gas.
3. To check the pressure supplied by the gas valve to the burner, remove the screw “C”. Fit the pipe of the pressure gauge to the pressure outlet of the gas valve “D”. Disconnect the compensation pipe either from the gas valve or from the sealed chamber.
4. Set the On/Off button to position < I > and the "summer/winter" switch to the winter position. To set the maximum power, turn on the hot water tap and allow the hot water tap to run at a rate of about 8 litres/minute so that the main burner lights. Adjust nut “E” on the modureg to set the gas pressure (displayed on the pressure gauge) corresponding to the maximum power (see table “A”page 11).
5. T o set the minim um pow er, disconnect a supply terminal from the modureg and adjust screw “F”. Turn the screw clockwise to increase the pressure and coun­ter-clockwise to decrease the pressure (displayed on the pressure gauge) corresponding to the minimum power (see table “A” page
11).
6. When you have completed the above operations, turn off the hot water tap, re-connect the supply terminal to the modureg on the gas valve and replace the cap on the screw of the modureg.
Setting the maximum heating circuit power
7. To set the maximum heating circuit power, place the
On/Off button to position < I > and the "summer/winter" switch to winter position. Turn the knob of the heating ther mostat clockwise to maximum;
8. Remove the left hand inspection panel of the P.C.B. and fit a small
cross-head screwdriver in to the right hand potentiometer.Turn clockwise to increase the pressure or counter-clockwise to reduce the pressure. Adjust the setting to the required heating pressure value (displayed on the pressure gauge), as indicated in the diagrams shown in page 11.
9. Turn off the boiler by placing the main switch to the "Off" position.
Setting pressure for soft ignition.
Disconnect the detection electrode connection from the P.C.B. (see fig.
1.13). Start the boiler and during the ignition sequence adjust the centre potentiometer until the gas pressure reads the required gas pressure as per the table below. Once the gas pressure is set turn off the boiler and reconnect the connection to the P.C.B. NB.:It may be necessary to reset the flame failure reset a number of times during this operation.
Setting gas pressures
Recommended pressure for slow ignition
NATURAL GAS (G20) BUTANE GAS (G30) PROPANE GAS (G31)
5 mbar - 1.95 in w.g.
18 mbar - 7.0 in w.g. 19 mbar - 7.4 in w.g.
11
Regulating the heating power for
natural gas (G20)
Regulating the heating power for
butane gas (G30)
Regulating the heating power for
propane gas (G31)
T ABLE “A”
model 23 model 27
model 23 model 27
GAS REQUIREMENTS
Gas rate Gas rate
Inlet pressure Burner pressure Burner pressure Burner injectors
40 38 36 34
model 23 model 27
NATURAL GAS (G20) BUTANE GAS (G30) PROPANE GAS (G31)
max min
3
/h
3.0 m 106.0 ft
3
/h 42.3 ft
1.2 m
3
3
/h
20 mbar 7.8 in w.g. max 12.3 mbar 4.8 in w.g. min
2.0 mbar 0.8 in w.g.
13 x 1.25
/h
3
0.88 m 31.1 ft
/h
3
0.35 m
/h 12.3 ft
28 mbar 10.9 in w.g.
28 mbar 10.9 in w.g.
5.1 mbar 2.0 in w.g.
13 x 0.72
3
/h
1.15 m3/h 40.6 ft3/h
3
/h
0.46 m3/h 16.2 ft3/h 37 mbar
37 mbar 14.4 in w .g.
7.0 mbar 2.7 in w.g.
13 x 0.72
14.4 in w .g.
12
10. Remove the pipe from the pressure gauge and connect screw “C” to the pressure outlet in order to seal off the gas.
11.Carefully check the pressure outlets for gas leaks (valve inlet and outlet).
IMPORTANT!
Whenever you disassemble and reassemble the gas connections, always check for leaks using a soap and water solution.
Setting the anti-cycling device
This appliance is equipped with a potentiometer which delays the ignition of the heating control and is situated on the P.C.B .(see the electrical diagrams). By adjusting the potentiometer, it is possible to change the time interval between the burner shutting down and its next ignition. It is preset at 1 minute and can be adjusted from 0 to 2 minutes. Use this control in particular situations where continuous shutting down and ignition of the main burner occurs.
40 50 60 70 80
Anti-cycling
Device
Soft-light
Adjustment
Max. Heating
Adjustment
Removing the spark generator (SIT Sigma gas valve)
1.
Disconnect ignition leads “Q” by pulling upwards
(see fig. 1.27)
;
2.
Remove the screws “R”
(see fig. 1.28)
with a Pozidrive
No.2 star tip screwdriver;
3.
Remove the spark generator.
Fig. 1.27
Fig. 1.28 Fig. 1.29
Q
R
C C
13
Removing the spark generator (SIT Tandem gas valve)
1.
Disconnect ignition leads “Q1” by pulling upwards
(see fig. 1.30)
;
2.
Remove the screws “R1”
(see fig.1.31)
with a Pozidrive
No.2 star tip screwdriver;
3.
Remove the spark generator.
Fig. 1.30
Fig. 1.31 Fig. 1.32
Q1
R1
R1
14
1.5

Access to the Hydraulic Circuits

Fig. 1.37
U
U
Removing the D.H.W. (secondary) exchanger
1.
Remove the screw “U”
(see fig. 1.37)
;
2.
Push the exchanger towards the rear of the boiler, lift upwards and remove out of the front of the boiler;
3.
Before replacing the exchanger ensure that the O-rings are in good condition and replace if necessary.
Important!
Before any component is removed, the boiler
must be drained of all water.
Removing the gas valve
1.
Disconnect all the cables from the solenoid and modureg;
2.
Remove the spark generator;
3.
Release the top nut “S” using a 30 mm open ended spanner
(see fig. 1.31)
;
4.
Remove the screws “T” from the bottom of the gas valve pipe
(see fig. 1.32)
.
Attention!!
The gas valve is connected with the two pipes
(as shown) with an O-ring connection.
Fig. 1.33
Fig. 1.34
Fig. 1.35
S
T
T
Fig. 1.36
15
Removing the safety valve
1.
Loosen nut “V”
(see fig. 1.38);
2.
Remove the valve.
Removing the automatic air vent
1.
Unscrew valve “W”
(see fig. 1.39)
.
Removing the main circuit flow switch
1.
Remove the cable of the main circuit flow switch “Y”;
2.
Remove the screws “Y1”
(see fig. 1.40);
3.
Remove the main circuit flow switch.
Fig. 1.38
Fig. 1.39
Fig. 1.40
V
W
Y
Y1
Y1
16
Removing the pump
1.
Unscrew “Z” and remove the electrical connection
(see fig. 1.41)
;
2.
Release the nuts “A1” and remove the pump
(see fig. 1.42)
.
Removing the pressure gauge
1.
Remove the inspection panel
(see fig. 1.6 - 1.7)
;
2.
Release coupling “A2” using a 14 mm open ended spanner
(see fig. 1.43)
;
3.
Push the pressure gauge through the control panel from the rear
(see fig. 1.44)
.
A1
A1
Z
A2
Fig. 1.41
Fig. 1.42
Fig. 1.43
Fig. 1.44
17
Removing the expansion vessel
1.
Remove nut “A3” away from the expansion vessel
(see fig. 1.45)
;
2.
Remove nut “A4”
(see fig. 1.46)
;
3.
Remove expansion vessel
(see fig. 1.47)
.
Removing the overheat thermostat
1.
Remove the electrical connection from the overheat thermostat
(see fig. 1.48)
;
2.
Then remove the thermostat from the pipe by releasing its securing clip.
Removing the heating temperature sensor (N.T.C.)
1.
Remove the electrical connector by pulling off the thermostat connections and unscrewing the sensor probe with a 14 mm open ended spanner
(see fig.
1.49)
.
A3
A4
Fig. 1.45
Fig. 1.46
Fig. 1.48
Fig. 1.49
Fig. 1.47
18
Checking fuse
1.
Remove the inspection panel
(see fig. 1.6 - 1.7)
;
2.
Remove fuse
(see fig. 1.50)
.
1.6

Access to the Control System

Removing the time clock
1.
Remove the inspection panel
(see fig. 1.6 - 1.7)
;
2.
Remove electrical connection of the clock “A5”
(see fig. 1.51)
;
3.
Unclip the clock from the panel and remove
(see fig. 1.52)
.
Fig. 1.50
Fig. 1.51
Fig. 1.52
A5
19
Removing the P.C.B.s
1.
Isolate electricity;
2.
Remove the front cover of the boiler;
3.
Remove the inspection panel
(see fig. 1.6-1.7
);
5.
Remove the mounting screws “A6’
(see fig. 1.53)
;
6.
Disconnect the connection cable”A7”
(see fig. 1.54)
;
7.
To remove the 24V P.C.B.: remove the electrical plug connectors and screws “A8”
(see fig. 1.55)
;
8.
To remove the 240V P.C.B.: remove the electrical plug connectors and screws “A9”
(see fig. 1.56)
;
9.
Replace either P.C.B. in reverse order.
Fig. 1.53
Fig. 1.54
Fig. 1.55
Fig. 1.56
A6
A6
A6
A6
A7
A7
A8
A8
A9
A9
N.B. It is possible to by-pass the time clock in the event of failure by simply unplugging the electrical connection from the P.C.B.
(see fig. 1.48
). This will revert control of the central heating to the room stat connection on the rev erse of the control panel.
20

2. FAULT FINDING

It is possible to detect and correct any defect by using the standard fault finding diagrams described in this chapter.
2.1
Fault Finding Guide (Flow-chart)
Preliminary Checks
Makesure that:
1) Thereis sufficient water i nthesys tem
2) Thegas is turned on
3) Theelectr icitytothe
boiler is on
Press the
On /Off Button
HAS
THE LIGHT fOR
THE POWER SUPPLY
COME ON?
YES
NO
1)Checkthefuses
2)Check thepower supply cord, plug and outlet
3)Check/replacethepower supply PCB
NO
SUMMER
ISHOT
WATERBEING
DEMANDED?
NO
FOR BOILERS
EQUIPPED WITHAN
ELEC T R ONICANT -FREEZE
SYST EM :HASTHESAFETYBEEN
TRIGGERED TO ACTIVATE
TH EDEVIC E?
(Tsensor <5°C)
SETTING
FOR THE OPERATING
MODE
FUME DISCHARGE TEST
YES
YES
A
YES
WIN TER
YES
ISHOT
WATERBEING
DEMANDED?
NO
DO THE
PROGRAMMING
TIMERAND/OREXTERNAL
TH ERM OS T ATNEED
TO BE ACTIVATED
NO
FOR BOILERS
EQUIPPED WITHAN
ELEC T R ONICANT -FREEZE
SYST EM :HASTHESAFETYBEEN
TRIGGERED TO ACTIVATE
TH EDEVIC E?
(Tsensor <5°C)
21
A
DOES THE
CIRCULATIONPUMP
COME ON?
YES
NO
1)Checkfor air in the system
2)Checkthepressureswitch foractivatingpump
3)Check/replace water gaug eandre fill the thesyste mproperly
1)Turn the boiler off
and thenbackon again (safe tyreset)
YES
DOES THE
INS UFFICI ENT WATER
INDIC ATORLIG H TCOME
ON?(wi thi n
40sec.)
NO
B
POWER TO THE PUMP ?
YES
1)Check to see if pump is stuck
2)Replacecirculationpump
NO
1) Check wiring
2) Check/replace wire toP CB
3) Replace power supply PCB
4) Replace control PCB
5) Check micro­switch when hot water isrequested.
22
B
DOESTHE FAN
COME ON?
YES
C
NO
BOILER
SHUT D OWN ?
NO
PUMP
SAFETYDEVICE
ACTIVATED?
NO
INTERNAL
SAFETYDEVICE
FOR PCB
ACTIVATED?
NO
ISTHEREPOWER
TO THE FAN?
YES
YES
YES
YES
NO
1)Reset the boiler
1)Check/replacediffere ntial pressureswitch for pump
2)Check/replace wiring
3)Check/replacePCB wire
4)Check/replace power supply P CB
5)Check/replace control
PCB
1)
Check/replaceair
pressureswitch/wiring
2)Check whether reset button isstuck
3)
Check/replace flame
dete cti onele ctrod e
1)
Check/replace wiring
2)
Check/replacePCB wire
3)Check/replacepower supply PCB
4)
Check/replace control
PCB
5)
Check/replace air
pressureswitch
1)Replacefan
23
C
IS
THEAIR PRESSURE
SWITCH ACTIVATED?
YES
ARETHE
FUMES DISCHARGED
CORRECTLY?
YES
DOESTHE
BURN ERLIGH T ?
YES
SAFETY
SHUT D OWNOFTHE
BOILER ACTIVATED?
NO
NO
NO
NO
YES
1) Check flue discharge
2) Check venturi & small pipes
3) Check wire for air press.switch
4) Check/replace air press. switch
5) Check/replace PCB wire
6) Check/replace power PCB
7) Check/replace control PCB
1)Check/replaceigniterplugs
2)Check wiring
3)Check starter
4)Check small wire
5)Check power supply PCB
6)Checkcontrol P C B
1)Checksupplyofgasto gas valve
2)Check power supply PCB
3)Checkcontrol P C B
4)Checkfunct i o na lityofthe valve
1)Check whether flame
dete cti onele ctrodeis hitbythefla me
2)Check theelectrode
3)Check thepowerPCB
4)Checkthecontrol PCB
D
NO
WASTHE
RESET SWITCH
PRESSED?
YES
Shutdown LEDoff
Res tartofthefan
24
D
THERE STILL A
IS
PROBLEM?
YES
NO
FUNCTIONS
NORMALLY
LISTOFMALF UNCT ION S
De live ryofhot wate rfordomes ti cuse :
De live ryofhot wate rfordomes ti cuse :
1
whenthetapisturnedon,theburnergoe sout.
whenthetapisturnedon,theburnergoe sout.
2
De live ryofhot wate rfordomes ti cuse :
De live ryofhot wate rfordomes ti cuse :
theradia tore sareheatedin summe rmode.
theradia tore sareheatedin summe rmode.
De live ryofhot wate rfordomes ti cuse :
De live ryofhot wate rfordomes ti cuse :
3
watertempe ra tureisnot satis f actory .
watertempe ra tureisnot satis f actory .
4
De live ryofhot wate rfordomes ti cuse :
De live ryofhot wate rfordomes ti cuse :
noisyopera tion.
noisyopera tion.
POSSIBLE CAUSES
- Airinthese c ondaryexchange r
- Airinthese c ondaryexchange r
- Hot water pressureswitch isdefective
- Hot water pressureswitch isdefective
- 3-way valve isdefective
- 3-way valve isdefective
- 3-way valve isdefective
- 3-way valve isdefective
- Checkhe a t i ngsensor s
- Checkhe a t i ngsensor s
- Checkgasset t i ngsandregula t ion
- Checkgasset t i ngsandregula t ion
- Checkwaterflowra t e
- Checkwaterflowra t e
- Check exchanger for domes tichot water
- Check exchanger for domes tichot water
- Primaryexchanger isdefective
- Primaryexchanger isdefective
- Low waterpressurein heatingsys tem
- Low waterpressurein heatingsys tem
- Checkgasset t i ngsandregula t ion
- Checkgasset t i ngsandregula t ion
5
Drop/increasein pre ss urein primarycircuit.
Drop/increasein pre ss urein primarycircuit.
6
Repeatedshutdowns.
Repeatedshutdowns.
7
Safe ty therm os ta tistrigge re drepe a te d ly.
Safe ty therm os ta tistrigge re drepe a te d ly.
8
Whenthecold watertapisturne doff,the
Whenthecold watertapisturne doff,the
boiler comeson.
boiler comeson.
9
Tempe rature of radiatorsnot s atisfactory.
Tempe rature of radiatorsnot s atisfactory.
- Checkfor leaksin heatingcircuit
- Checkfor leaksin heatingcircuit
- Defe ctivewater supplyinlet valve
- Defe ctivewater supplyinlet valve
- Secondary exchanger isdefective
- Secondary exchanger isdefective
- Expansion vessal is empty
- Expansion vessal is empty
- Detection electrodes are defective
- Detection electrodes are defective
- Checkgasset t i ngsandregula t ion
- Checkgasset t i ngsandregula t ion
- Checkelectrical circuit for f lamedetection
- Checkelectrical circuit for f lamedetection
- F a ulty(contacts)ntcheating sensors-
- F a ulty(contacts)ntcheating sensors-
- Defective (poorlycalibrated)safety thermostat
- Defective (poorlycalibrated)safety thermostat
- Pres e nceofair in theprimary watercircuit
- Pres e nceofair in theprimary watercircuit
- Dropin pre ss urein thewater mains,resulting
- Dropin pre ss urein thewater mains,resulting
in waterhammering
in waterhammering
- Checkntcheati ng s ensor
- Checkntcheati ng s ensor
- Check by-pass
- Check by-pass
- Checkgasset t i ngsandregula t ion
- Checkgasset t i ngsandregula t ion
25
Signalling
Boiler Off Auto diagnostic state Spark ignition state Boiler functioning normally Lockout Boiler thermostat satisfied Room thermostat/clock no demand or selector in summer setting
Malfunction
Faulty ventilation system Air pressure switch stuck in N.O. position Faulty reset switch Faulty main circuit flow switch
Faulty flame detection Faulty overheat ther mostat Faulty exhaust fumes sensor Faulty heating sensor (N.T.C.) Faulty D.H.W.sensor (N.T.C.)
A b
C
d
E F
G
I
m
1 2 3 4 5 6
2.2
Fault Finding Using the Total Check System
Pump fed
Main flow switch closed
Air pressure switch N.O.
Flame detected
Water at required temperature
Room thermostat/clock no demand or selector in summer setting
Auto diagnostics faulty
Heating temperature control
D.H.W. temperature control
Heating circuit efficiency control
D.H.W.exchanger efficiency control
26

3. ELECTRICAL DIAGRAMS

Legend:
AT = High V oltage P.C.B . BT = Low Voltage P.C .B . B = Flame Failure L.E.D. C = Insufficient Water Pressure L.E.D. D = Water Temperature Indicator L.E.D.s E = Overheat Thermostat Warning L.E.D. F = System Reset Button G = Selector Knob for Operating Mode H = Domestic Hot Water Temp. Adjustment I = Central Heating Temp.Adjustment J = Wire Connector for Room Thermostat K = Connector for Total Check System M = Anti-cycling Device Adjustment for Heating N = Soft-light Adjustment O = Max Heating Temperature Adjustment P = Time Clock Connection Q = On/Off L.E.D. R = On/Off Switch S = Interface Wire for P.C.B.s T = Relay Motorised Valve U = Ignitor Relay V = Gas Valv e Relay W = Fan Relay X = Circulation Pump Relay Y = Selector TCS2 Aa = Adaptor (British Gas use only)
A01= Air Pressure Switch A02= Fan A03= Gas Valve A04= Ignitor A05= Motorised Valv e A06= Circulation Pump A07= Flame Detector A08= Earth T erminal A09= Flame Detection Circuit A10= Flame Indicator L.E.D. A11= Transformer A12= Filter
B01= Over Heat Thermostat B02= Room Thermostat B03= Gas Valve Modulator B05= Heating Sensor B06= Pressure Switch for Heating Circuit B07= Microswitch for Diverter Valve B08= Time Clock
Colours
Gry = Grey Rd = Red Bl = Blue Grn/Yll = Yellow/Green Wh = White Brn = Brown Blk = Black Wh/Rd = White/Red
27
A/23 MFFI - A/27 MFFI
EX C-MI/FFI
8
28

4. SHORT SPARE PARTS LIST

A/23 MFFI - A/27 MFFI (SIT Sigma Gas Valve)
2
72
1
2
3
4
5
4
6
7 8 9
10
11
12
13 14
11 15
87
73
74
4
4
7
88
89
86
90
91
94
92
93
75
63
79
81
84
87
85
86
90
92
96
68 60 57
67 59 5861
66 64676669706471
75
76
77
78
80
82
11
83
104
103 100
102
98
101
100
97
85
95
23
6365
62
75
125
121
120
105
106
108
99
124
123
122
119
126
107
82
118
109
111
110
117
112
4
301 4 302 301
116
115
114
113
49
52
45
45
41
39
4
4
56
55
54
53 52 51 50 49 48 47 46
45 44
43 42
41 29 40 39
38
34
17 18 19 2320 21 22 24 2625
16
102 16
364
361
362
27
28
343332 35
3631
37
29 30
363
321
17
371
372
373
374
375
311
22
A 23/27 MFFI
29
573294 573520 997206 573224 569236 573340 573528 573727 573172 571649 997208 953730 952981 952610 572989 572990 573343 573314 571651 571652 570717 564254 569387 571449 571646 573295 573825 571807 573521 997150 997151 571965 574279 574232 574233 573441 569390 569560 569561 572271 572277 572343 572372 572749 572835 571993 571444 997029 571443 571442 571447 571446 571547 571772 571771 571770 573138 569281 569282
Key
no.
G.C. part
no.
ARISTON
Part No.
Description
1 11 14 17 18 19 23 24 25 28 32 45 46 47
57AB 57CD
58 61
72AB 72CD
75 84 85 87
89AB 89CD
90 92 96
98AB 98CD
100 101 102 108 112 116 118
119 120A 120B 120C 120D
121AB 121CD
301
311
321
361
362
363
364
371
372
373
374
375
381
382
379816
164 225
164 338 164 229
378 814
E03 818 E02 071
379 079 164 230
164 282
379 981 164 261 379 979 379 980 E02 026
E02 078
164 311
Expansion vessel Gasket 3/4"
Overheat thermostat Main flow Switch Temp probe (C.H.W.) Microswitch for 3-way/main flow group Gasket 1/2" Manual vent cock Safety valve 3 bar 1/2" Pressure gauge Time clock P.C.B. EX C-MI/FFI P.C.B. EI A-MFFI P.C.B. cable Fan Fan Fan inlet gasket Venturi (exhaust manifold/header) Air pressure switch Air pressure switch Fastening spring Automatic air release valve Gasket 1" O-ring Secondary exchanger (plate-type) exchanger 23kW Secondary exchanger (plate-type) exchanger 27kW O-ring (secondary exchanger) 20-18 O-ring Gasket 3/8" Pump Pump O-ring (13) Gasket Gas valve (SIT Sigma) Spark generator Detection electrode Gasket 1/4" Ignition electrode (R.H.) Ignition electrode (L.H.) Main burner Main burner Main burner Main burner Main exchanger Main exchanger Front panel runner kit D.H.W. actuator kit SIT Sigma gas valve operator coils Heating by-pass kit D.H.W. pressure switch kit 3-way spring kit D.H.W. diaphram valve Main flow switch diaphram Main flow switch magnet Main flow switch spring Main flow switch top cap Main flow switch reed system Burner jet 1.25 full kit (Natural gas) Burner jet 0.72 full kit (LPG)
1 1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
A/23 MFFI - A/27 MFFI (SIT Sigma Gas Valve)
30
A/23 MFFI - A/27 MFFI (SIT Tandem Gas Valve)
Key
no.
1 11 14 17 18 19 23 24 25 28 31 44 46 47
57AB
57CD
58 61
72AB 72CD
75 84 85 87
89AB 89CD
90 92 96
98AB 98CD
101
103 106 114 118 120 121
122A 122B 122C 122D
123AB
123CD
311 321 322 323 361 362 363 364 371 372 373 374 375 381 382
G.C. part
no.
379816
164 225
164 338 164 229
378 814
E03 818 E02 071
379 079 164 230
164 282
379 976
379 981 164 261 379 979 379 980 E02 026
E02 078
378 978 378 815 164 303
164 311
Description
Expansion vessel Gasket 3/4" Overheat thermostat Main flow Switch Temp probe (C.H.W.) Microswitch for 3-way/main flow group Gasket 1/2" Manual vent cock Safety valve 3 bar 1/2" Pressure gauge Time clock P.C.B. EX C-MI/FFI P.C.B. EI A-MFFI P.C.B. cable Fan Fan Fan inlet gasket Venturi (exhaust manifold/header) Air pressure switch Air pressure switch Fastening spring Automatic air release valve Gasket 1" O-ring Secondary exchanger (plate-type) exchanger 23kW Secondary exchanger (plate-type) exchanger 27kW O-ring (secondary exchanger) O-ring (20-18) Gasket 3/8" Pump Pump Gas valve (SIT Tandem) Spark generator O-ring (13) Detection electrode Gasket 1/4" Ignition electrode (R.H.) Ignition electrode (L.H.) Main burner Main burner Main burner Main burner Main exchanger Main exchanger D.H.W. actuator kit SIT Tandem gas valve operator coils SIT Tandem modureg coil Gas modulator cartridge Heating by-pass kit D.H.W. pressure switch kit 3-way spring kit D.H.W. diaphram valve Main flow switch diaphram Main flow switch magnet Main flow switch spring Main flow switch top cap Main flow switch reed system Burner jet 1.25 full kit (Natural gas) Burner jet 0.72 full kit (LPG)
ARISTON
Part No.
1 1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
573294 573520 997206 573224 569236 573340 573528 573727 573172 571649 997207 953730 952981 952610 572989 572990 573343 573314 571651 571652 570717 564254 569387 571449 571646 573295 573825 571807 573521 997150 997151 570732 573023 571965 573441 569390 569560 569561 572271 572277 572343 572372 572749 572835 571444 570712 573740 573745 571443 571442 571447 571446 571547 571772 571771 571770 573138 569281 569282
31
573294 573520 997206 573224 569236 573340 573528 573727 573172 571649 997207 953730 952981 952610 572989 572990 573343 573314 571651 571652 570717 564254 569387 571449 571646 573295 573825 571807 573521 997150 997151 570732 573023 571965 573441 569390 569560 569561 572271 572277 572343 572372 572749 572835 571444 570712 573740 573745 571443 571442 571447 571446 571547 571772 571771 571770 573138 569281 569282
Key
no.
G.C. part
no.
ARISTON
Part No.
Description
1 11 14 17 18 19 23 24 25 28 31 44 46 47
57AB 57CD
58 61
72AB 72CD
75 84 85 87
89AB 89CD
90 92 96
98AB 98CD
101 106
114 118 120
121 122A 122B 122C 122D
123AB
123CD
311
321
322
323
361
362
363
364
371
372
373
374
375
381
382
379816
164 225
164 338 164 229
378 814
E03 818 E02 071
379 079 164 230
164 282
379 976
379 981 164 261 379 979 379 980 E02 026
E02 078
378 978 378 815 164 303
164 311
Expansion vessel Gasket 3/4" Overheat thermostat Main flow Switch Temp probe (C.H.W.) Microswitch for 3-way/main flow group Gasket 1/2" Manual vent cock Safety valve 3 bar 1/2" Pressure gauge Time clock P.C.B. EX C-MI/FFI P.C.B. EI A-MFFI P.C.B. cable Fan Fan Fan inlet gasket Venturi (exhaust manifold/header) Air pressure switch Air pressure switch Fastening spring Automatic air release valve Gasket 1" O-ring Secondary exchanger (plate-type) exchanger 23kW Secondary exchanger (plate-type) exchanger 27kW O-ring (secondary exchanger) O-ring (20-18) Gasket 3/8" Pump Pump Gas valve (SIT Tandem) Spark generator O-ring (13) Detection electrode Gasket 1/4" Ignition electrode (R.H.) Ignition electrode (L.H.) Main burner Main burner Main burner Main burner Main exchanger Main exchanger D.H.W. actuator kit SIT Tandem gas valve operator coils SIT Tandem modureg coil Gas modulator cartridge Heating by-pass kit D.H.W. pressure switch kit 3-way spring kit D.H.W. diaphram valve Main flow switch diaphram Main flow switch magnet Main flow switch spring Main flow switch top cap Main flow switch reed system Burner jet 1.25 full kit (Natural gas) Burner jet 0.72 full kit (LPG)
1 1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1
1 1
1 1
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
103
A 23/27 MFFI (SIT Tandem Gas Valve)
Manufacturer: Merloni TermoSanitari SpA - Italy Commercial subsidiary: MTS (GB) LIMITED
MTS Building Hughenden Avenue, High Wycombe Bucks HP13 5FT Telephone: (01494) 755600 ­Fax:(01494) 459775
Technical Service Hotline: (01494) 539579
23 99 84 1268 000 - B029
Stampa BIEFFE Recanati
Loading...