• On an interior wall, in a frequently occupied space.
• Approximately 5 feet above oor.
• At least 18” from outside wall.
• Thermostat can be mounted to a vertical junction box.
Do not mount thermostat:
• Behind doors, in corners or other dead air spaces.
• In direct sunlight, near lighting xtures, or other appliances that give off heat.
• On an outside or unconditioned area wall.
• In the ow of a supply register, in stairwells, or near outside doors.
• On a wall with concealed pipes or ductwork.
32
Page 3
OUTDOOR TEMPERATURE SENSOR (INCLUDED)
O/B
I1
Outdoor temperature can be measured by attaching the included 8052 sensor to the T1 and T2
terminals. The outdoor sensor must be enabled in the installer setup menu.
Heat pump models can use the outdoor temperature to effectively utilize the heat pump:
• When the outdoor temperature is lower than the Low Balance Point, the heat pump will be
locked out and only auxiliary heating will be used to provide heating.
• When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will
be locked out and only the heat pump will be used to provide heating.
Indoor Air Quality functions can use the outdoor temperature sensor to:
• Control humidication set point based on outdoor temperature to prevent condensation.
• Lock out ventilation based on high and/or low outdoor temperatures.
• Display outdoor temperature on thermostat.
Outdoor temperature sensor should be mounted:
• On side of building out of direct sunlight (north side recommended).
• Above snow line.
• At least 3 feet away from exhaust vents and condensing lines.
• Using less than 300 feet of wire.
• Do not route wires along 120 VAC lines.
FIGURE 1 – OUTDOOR TEMPERATURE SENSOR WIRING
RH
RC
W
Y
G
C
L
W2
Y2
T2
T1
I2
90-2 561
54
Page 4
REMOTE TEMPERATURE SENSOR (OPTIONAL)
O/B
I1
A remote temperature sensor can be used for control if the thermostat is to be mounted in a
concealed location or a remote sensor can be averaged with the thermostat sensor to control
a large space. An 8051 ush mount or 8053 surface mount remote temperature sensor can be
attached to the T1 and T2 terminals and mounted in a recommended area. The remote sensor
must be enabled in the installer set-up menu, and once enabled will override or be averaged
with the thermostat’s internal temperature sensor, based on the setting.
Remote temperature sensor should be mounted:
• On an interior wall, in a frequently occupied space.
• Approximately 5 feet above oor.
• At least 18” from outside wall.
• Using less than 300 feet of wire.
Do not mount remote sensor:
• Behind doors, in corners or other dead air spaces.
• In direct sunlight, near lighting xtures, or other appliances that give off heat.
• On an outside or unconditioned area wall.
• In the ow of a supply register, in stairwells, or near outside doors.
• On a wall with concealed pipes or ductwork.
• Near 120 VAC lines.
FIGURE 2 – REMOTE TEMPERATURE SENSOR WIRING
RH
RC
W
Y
G
C
L
W2
Y2
T2
T1
I2
90-2 562
76
Page 5
WIRELESS SENSORS
THERMOSTAT MOUNTING
This thermostat is compatible with the following AprilAire wireless sensors:
• Model Z10IDT Indoor Temperature and Humidity Sensor
Up to eight of these sensors can be connected to the thermostat. Connected sensors will
automatically be averaged, or individual sensors can be selected for scheduled events.
• Model Z10ODT Outdoor Temperature and Humidity Sensor
One sensor can be connected to the thermostat.
The wireless sensor settings can be found under the thermostats’ installer settings. See the
sensors instruction manual for mounting and connecting details.
1. Remove the rear mounting plate
from the thermostat.
2. Pull wires through the opening on
the back of the rear mounting plate.
3. Position and level the mounting
plate of the thermostat on wall
and mark the hole locations with a
pencil.
4. Insert and tighten supplied self-
drilling anchors (drywall only).
5. Place mounting plate over anchors,
insert and tighten screws.
6. Seal wire entry holes to prevent
drafts affecting temperature
readings.
FIGURE 3 – THERMOSTAT MOUNTING
90-2 563
98
Page 6
POWER AND RESET OPTIONS
The thermostat is powered from 24VAC. In the case of power loss, the thermostat will maintain
the clock for 2 hours. The thermostat has a memory backup that saves the thermostat settings
in case of power interruption. The thermostat can be set back to factory defaults from the
installer settings menu. See Installer System Settings section for details.
The factory reset does not clear thermostat account information from the AprilAire Wi-Fi Thermostat App. To clear this information, remove the thermostat from the app or use the
unregister option from the thermostat’s Wi-Fi settings.
WIRING TERMINAL
WIRE SPECIFICATIONS:
• 18-24 gauge thermostat wire
INSTALLATION NOTES:
• Ensure power at the HVAC equipment is off.
• Loosen screw terminals, insert stripped wire and re-tighten.
• Push the excess wire back into the opening and plug the wall opening to prevent drafts.
RH 24VAC supply heating*
RC 24VAC supply cooling*
W
Y
G Fan
C Common
O/B Reversing valve
L
W2
Y2
T1 & T2 Outdoor/remote temperature sensor
I1 & I2 Indoor Air Quality control output
* Jumper between RC & RH is used in single
transformer systems (see wiring diagrams).
First stage heat (conventional) /
First stage auxiliary (heat pump)
First stage cooling (conventional) /
First stage compressor (heat pump)
System fault indicator (optional)
(heat pump only)
Second stage heat (conventional) /
Second stage auxiliary (heat pump)
Second stage cooling (conventional) /
Second stage compressor
(heat pump)
FIGURE 4 – WIRING TERMINALS
90-2 564
1110
Page 7
O/B
I1
FIGURE 5 – SINGLE & MULTI
O/B
I1
STAGE HEAT/COOL, ONE
TRANSFORMER
NOTE: Dashed lines
represent wiring for multi
stage systems only.
WIRING DIAGRAMS
RH
RC
W
Y
G
C
L
W2
Y2
T2
T1
I2
JUMPER
ODT/REMOTE
TEMP SENSOR
R
W
Y
G
C
FURNACE
W2
Y2
Y2
AIR
C
CONDITIONER
Y
FIGURE 6 –
SINGLE & MULTI STAGE
HEAT/COOL, (EX: BOILER)
TWO TRANSFORMER
NOTE: Dashed lines
represent wiring for multi
stage systems only.
RH
RC
W2
Y2
T2
(REMOVE JUMPER)
W
Y
G
C
L
ODT/REMOTE
T1
TEMP SENSOR
I2
90-2 566
R
HEAT SOURCE
(EX: BOILER)
W
Y
G
AIR
HANDLER
C
R
Y2
Y2
AIR
C
CONDITIONER
Y
90-2 565
1312
Page 8
FIGURE 7 – SINGLE
O/B
JUMPER
O/B
I1
& MULTI STAGE
HEAT PUMP, ONE
TRANSFORMER
NOTE: Dashed lines
represent wiring for
multi stage systems
only.
RH
RC
W2
Y2
T2
JUMPER
W
Y
G
C
L
ODT/REMOTE
T1
TEMP SENSOR
I2
I1
90-2 567
R
W
Y
G
C
HANDLER
W2
Y2
Y2
C
Y
OUTDOOR
W
R
O/B
L
AIR
UNIT
FIGURE 8 – RADIANT
& HEAT/COOL, ONE
TRANSFORMER
RH
RC
W
Y
G
C
L
W2
Y2
T2
T1
I2
90-2 677
24V
COM
E/W2
ODT/REMOTE
TEMP SENSOR
NO(1)
AA
8024
COM(3)
R
RADIANT
FLOOR
W
Y
G
C
FURNACE
R
W
C
AIR
CONDITIONER
Y
1514
Page 9
FIGURE 9 –
O/B
DUCT MOUNTED EVAPORATIVE HUMIDIFIERS
I2
I1
STANDALONE OR RESIDENTIAL STEAM HUMIDIFIER
I2
I1
DEHUMIDIFIER
I2
I1
I2
I1
RADIANT &
HEAT PUMP, ONE
TRANSFORMER
RH
RC
W
Y
G
C
L
W2
Y2
T2
T1
I2
I1
90-2 678
JUMPER
ODT/REMOTE
TEMP SENSOR
24V
COM
E/W2
Y
AA
8024
NC(2)
COM(3)
NO(4)
COM(6)
R
W
G
C
R
O/B
W
Y
Y
W
O/B
R
C
L
RADIANT
FLOOR
AIR
HANDLER
OUTDOOR
UNIT
FIGURE 10 - INDOOR AIR QUALITY EQUIPMENT WIRING DIAGRAMS
(APRILAIRE SERIES 400, 500, 600, 700)
TRANSFORMER
HUMIDIFIER
SOLENOID
90-2 570
(APRILAIRE SERIES 300, 800)
HUMIDIFIER
DRY CONTACT INPUT
90-2 680
(APRILAIRE SERIES 1800, e-SERIES)
DEHUMIDIFIER
DRY CONTACT INPUT
VENTILATION
(APRILAIRE SERIES 8100)
TRANSFORMER*
V
DAMPER
*If required by ventilation accessory.
90-2 569
O
A
N
T
T
L
E
I
I
90-2 571
NOTE: The I1/I2 output is a dry contact closure. The HUMIDIFIER wiring diagram assumes the
control is powering a solenoid valve. The DEHUMIDIFIER wiring diagram is for a normally open
dry contact input. The VENTILATION wiring diagram assumes the control is for a normally closed
damper. Refer to the individual humidier, dehumidier or ventilation installation instructions for
product specic wiring details.
N
1716
Page 10
SETUP AND TESTING
INSTALLER SETUP WIZARD AND
INSTALLER SETTING
The rst time the thermostat is powered
up (or after a factory reset) it will enter the
Installer Setup Wizard. All Installer Settings
can be set through this process. The
Installer Settings are also accessible in the
Installer Menu.
HOW TO ENTER THE INSTALLER MENU:
1. Press Select to enter the Main Menu.
2. Use
3. Press and hold
4. Use
or to navigate to Settings,
press SELECT.
and for 3 seconds
to unlock the Installer option.
or to navigate to Installer,
press SELECT. Refer to the chart at right for
options.
Advanced HVAC control
(effsets, deadbands,
staging, protection, etc.)
Humidier, Dehumidier,
Air Cleaner, and
Ventilation conguration
Connect/disconnect
wireless indoor and
outdoor sensors
Installer test for
congured equipment
relay outputs
Reset all settings to
factory default
HVAC INSTALLER SYSTEM SETTINGS TABLE
The following table contains the system settings and their details. Default settings are shown in
bold. The availability of some settings is dependent upon the value of other settings.
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
Factory default setting (bold)
System settingDescription
Equipment Type
O/B Energized For?
Control Setup
Heat Pump
Auxiliary Type
Fan Control in
Heating
NOTE: Equipment Type related
settings will return to defaults if this is
changed.
Selects O or B reversing valve
operation. (Heat Pump mode only.)
Used to lockout heating or cooling
outputs. (Heat/Cool mode only).
Selects auxiliary type. (Heat Pump
mode only.)
Selects thermostat or equipment to
control the fan in heating. (Heat/Cool
mode only.)
and setting range
Heat/C ool
Heat Pump
Cooling
Heating
Heat & Cool
Heat Only
Cool Only
Gas/Oil Heat
Electric Heat
Gas/Oil Heat
Electric Heat
1918
Page 11
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System settingDescription
Number of
Compressor
Stages
Number of Auxiliary
Heat Stages
Number of Stages
of Heat
Number of Stages
of Cool
Programmable
Wired Temperature
Sensor Installed?
Select number of compressor stages.
(Heat Pump mode only.)
Select number of auxiliary heat
stages. (Heat Pump mode only.)
Select number of heat stages. (Heat/
Cool mode only.)
Select number of cool stages. (Heat/
Cool mode only.)
Non Programmable hides all
scheduling features.
Selects how the external temperature
sensor terminals (T1 & T2) are being
used. Choose Outdoor for a wired
outdoor sensor or Remote/Remote
Average for a wired indoor sensor.
Factory default setting (bold)
and setting range
One
Two
One
Two
One
Two
One
Two
Programmable
Non Programmable
Outdoor
Remote
(Onboard sensor disabled)
Remote Average
(Average with onboard sensor)
No
(No external sensor connected)
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System settingDescription
Outdoor
Temperature Data
Provided From?
Advanced HVAC
Settings?
Connection Type
Progressive
Recovery
Display Heat Blast?
Heat Blast Offset
Select where the outdoor temperature
data comes from. (This option is not
available if you are using the wired
outdoor temperature sensor.)
Select No to skip the rest of the
thermostat settings.
Selects if the thermostat connects
with an automation system or an
AprilAire account.
Enables or disables progressive
recovery.
Select if the Heat Blast option is
displayed.
Amount of heating when Heat Blast is
initiated.
Factory default setting (bold)
and setting range
Web
Automation
(for home automation cong only)
None
Wireless
(Wireless outdoor sensor)
No
Yes
AprilAire Cloud
Automation System
Disabled
Enabled
No
Yes
3° F (1. 5°C)
4° F (2°C)
5°F (2.5°C)
2120
Page 12
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System settingDescription
Extended Fan –
Heat
Extended Fan –
Cool
Auto Changeover
DeadBandAuto Changeover mode deadband.
Auto Changeover
Time
Temp Sensor Offset
RH Sensor Offset
Equipment
Minimum On Time
Extends fan operation 90 seconds
after heat call ends. NOTE: Only
available with electric heat.
Extends fan operation 90 seconds
after cool call ends.
Enable or disable Auto Changeover
mode.
Minimum time between heating and
cooling calls.
Field adjustment of controlling
temperature sensors.
Internal RH sensor. Increases or
decreases displayed RH%.
Minimum on time for heating and
cooling.
Factory default setting (bold)
and setting range
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
3° F (1. 5°C)
2 to 9°F (1 to 4.5°C)
4 Minutes
1 to 5 Minutes
0°F (0°C)
-4 to 4°F (-2 to +2°C)
0
-5 to 5
2 Minutes
1 to 5 Minutes
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System settingDescription
Heating Minimum
Off Time
Compressor
Minimum Off Time
Outdoor
Temperature High
Balance Point
High Balance Point
Temperature
Outdoor
Temperature Low
Balance Point
Low Balance Point
Temperature
Minimum off time for heating.
Minimum off time for compressor
protection.
Enable or disable high balance point.
(Available if an ODT is installed.)
If outside temperature is above the
high balance point the aux heat
operation is not allowed. (Available if
high balance point is enabled.)
Enable or disable low balance point.
(Available if an ODT is installed.)
If outside temperature is below the
low balance point the compressor
operation is not allowed. (Available if
low balance point is enabled.)
Factory default setting (bold)
and setting range
2 Minutes
1 to 5 Minutes
5 Minutes
1 to 5 Minutes
Enabled
Disabled
65°F (14.5°C)
0 to 80°F (-18 to 22°C)
Enabled
Disabled
20 °F (- 8°C)
0 to 60°F (-18 to 12°C)
2322
Page 13
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System settingDescription
Stage Rate
Stage Rate Factor
First Stage
Differential
Second Stage
Differential
Third Stage
Differential
Fourth Stage
Differential
Service HVAC
Reminder
Accumulation of difference from
setpoint over time in staging
determination.
1 = more rapid staging of equipment
(comfort),
5 = slower staging of equipment
(economy).
First stage differential.
Second stage differential.
Third stage differential.
Fourth stage differential.
Enable or disable the HVAC Service
reminder message.
Factory default setting (bold)
and setting range
Enabled
Disabled
2
1 to 5
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
Disabled
Enabled
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System settingDescription
Recurrence
Max Heat Setting
Min Heat Setting
Max Cool Setting
Min Cool Setting
Select number of months between
HVAC Service reminder messages.
Select the maximum heating set point
temperature allowed.
Select the minimum heating set point
temperature allowed.
Select the maximum cooling set point
temperature allowed.
Select the minimum cooling set point
temperature allowed.
Factory default setting (bold)
and setting range
12 Months
1 to 12 Months
90 °F (32°C)
40 to 90°F (4.5 to 32°C)
40 °F (4 .5°C)
40* to 90°F (4.5 to 32°C)
99 °F (37°C)
50 to 99°F (10 to 37°C)
50° (10°C)
50 to 99°F (10 to 37°C)
2524
Page 14
INDOOR AIR QUALITY SYSTEM SETTINGS TABLES
The following tables contain the Indoor Air Quality system settings and their details. Default
settings are shown in bold. The availability of some settings is dependent upon the value of
other settings. The use of outdoor temperature data enables additional Indoor Air quality
functionality. While the outdoor temperature sensor option was presented in the HVAC installer
settings, it is also available in the Indoor Air Quality settings.
Please refer to the Owner’s Manual for further information about thermostat features.
TAB LE 2 – HUMIDIFIER SYSTEM SETTINGS
Factory default setting (bold)
System settingDescription
and setting range
NOTE: A humidier can only be installed if ventilation is not installed and dehumidier control is not set to Whole Home.
Selects whether a humidier is installed.
Yes/On HVAC is used for applications
Humidier
Installed?
where the humidier is installed on the
HVAC duct. Yes/Standalone is used for
applications where the humidier is
independent from the HVAC system. (If
set to No, no other humidier settings will
be available.)
No
Yes/O n HVAC
Yes/Standalone
TAB LE 2 – HUMIDIFIER SYSTEM SETTINGS
System settingDescription
Wired
Temperature
Sensor
Installed?
Outdoor
Temperature
Data Provided
From?
Humidier Mode
Selects how the external temperature
sensor terminals (T1 & T2) are being used.
Choose Outdoor for a wired outdoor
sensor or Remote/Remote Average for a
wired indoor sensor.
Select where the outdoor temperature
data comes from. (This option is not
available it you are using the wired
outdoor temperature sensor)
Selects auto or manual mode. Auto mode
controls humidity based on the humidity
setting and outdoor temperature. Manual
mode controls humidity based on the
%RH setpoint. (Auto mode is only available
if an outdoor sensor option is enabled.)
Factory default setting (bold)
and setting range
Outdoor
Remote
(Onboard sensor disabled)
Remote Average
(Average with onboard sensor)
No
(No external sensor connected)
Web
Automation
(for home automation cong only)
None
Wireless
(Wireless outdoor sensor)
Auto
Manual
2726
Page 15
TAB LE 2 – HUMIDIFIER SYSTEM SETTINGS
Factory default setting (bold)
System settingDescription
Selects when humidication is allowed
to occur relative to heating and fan
Allowed
Humidier
Operation
operation. NOTE: Without Fan is only
available when Humidier Installed
is set to Yes/Standalone. It allows
humidication to occur without
activating an HVAC fan and should only
be used when the humidier is mounted
independently of any HVAC system.
and setting range
Heat Only
Heat or Fan
Forces Fan
Without Fan
CAUTION
When Humidier Operation is set to Without Fan the thermostat will turn on
humidication without energizing the HVAC fan. Do not select this option when the
humidier is installed on the HVAC duct. Without airow moisture can accumulate in the
duct resulting in signicant damage.
TAB LE 2 – HUMIDIFIER SYSTEM SETTINGS
System settingDescription
Humidier
Reminder
Single or First
Reminder
Appears
Second
Reminder
Appears
Selects when the “Change Water Panel”
message is displayed.
Determines the month the rst (or only)
“Change
Water Panel” message is displayed.
Determines the month the second
“Change Water
Panel” message is displayed. (Only
available when 2 reminders per season
is selected.)
Factory default setting (bold)
and setting range
Off
150h Valve
300h Valve
600h Valve
1 per season
2 per season
October
November
December
January
February
March
October
November
December
January
February
March
April
May
June
July
August
September
April
May
June
July
August
September
2928
Page 16
TAB LE 3 – DEHUMIDIFIER SYSTEM SETTINGS
Factory default setting
System settingDescription
(bold) and setting range
NOTE: Dehumidier control can only be set to Whole Home if ventilation and humidication
are not enabled.
Selects if a dehumidier is installed. (If set to
Dehumidier Type
Installed?
Disable
Dehumidication
During Cooling?
Dehumidier Forces
Fan?
Dehumidier
Overcool Limit
None, no other dehumidier settings will be
available.) AC w/ IAQ selects overcooling,
I1 and I2 terminals energize during
overcooling. AC w/o IAQ selects overcooling,
I1 and I2 terminals are not used.
Selects if dehumidication is disabled
during a cooling call.
Selects if dehumidication can turn on the
HVAC system fan.
Selects the amount of overcooling that can
occur for dehumidication. (Only available
if dehumidier type is set to Overcool.)
None
Whole Home
AC w/ IAQ
AC w/o IAQ
Yes
No
Yes
No
1°F (0.5°C)
2° F (1° C)
3° F (1.5° C)
TAB LE 3 – DEHUMIDIFIER SYSTEM SETTINGS
System settingDescription
Dehumidier
Reminder
Recurrence
Dehumidify in
Vacation Hold?
Vacation Hold Low
Temperature Limit
Humidity Deadband
Enable or disable the Dehumidier Service
reminder message.
Select number of months between
Dehumidier Service reminder messages.
Selects if dehumidication with the air
conditioner is done in vacation mode.
Sets the lowest temperature the air
conditioner will cool to, to meet RH setpoint
in Vacation Mode. (Only available if
dehumidier type is set to Overcool.)
Select the minimum difference between
the humidier and dehumidier setpoints.
(Only available if both Humidier and
Dehumidier are enabled.)
Factory default setting
(bold) and setting range
Disabled
Enabled
12 Months
1 to 12 Months
No
Yes
75°F (24°C)
70 to 85°F (21 to 29.5°C)
10%
10 to 20%
3130
Page 17
TAB LE 4 – AIR CLEANING SYSTEM SETTINGS
System settingDescription
Air Cleaner Installed?
Air Cleaner Reminder
Recurrence
Selects if an air cleaner is installed.
(If set to No, no other air cleaner settings
will be available.)
Enable or disable the Change Air Filter
message.
Select number of months between
Change Air Filter messages.
Factory default setting
(bold) and setting range
No
Yes
Disabled
Enabled
12 Months
1 to 12 Months
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
Factory default setting (bold)
System settingDescription
and setting range
NOTE: Ventilation can only be installed if humidication is not enabled and dehumidier control is not set to Whole Home.
Fresh Air Vent
Installed?
Fresh Air Setup
Type
Number of
Bedrooms
Square Footage
Measured CFM
Selects if ventilation is installed. (If set to
No, no other ventilation settings will be
available.)
Selects if ventilation is congured through
the Code setup or Comfort. Comfort
setup has more lockout options. Code
setting ensures time missed due to
lockouts is made up.
Selects the number of bedrooms to be
used for the Calculated Minutes per Hour.
Selects the size of the home to be used
for the Calculated Minutes per Hour.
Selects the ventilation CFM to be used for
the Calculated Minutes per Hour.
No
Yes
Comfort
Code
3 Bedrooms
1 to 10 Bedrooms
2500 SQ FT
500 to 7500 SQ FT
110 CFM
30 to 250 CFM
3332
Page 18
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
System settingDescription
Calculated
Minutes Per
Hour
Override
Wired
Temperature
Sensor
Installed?
Outdoor
Temperature
Data Provided
From?
Displays the Fresh Air Time calculated.
Manual adjustment of Calculated Minutes
per Hour.
Selects how the external temperature
sensor terminals (T1 & T2) are being used.
Choose Outdoor for a wired outdoor
sensor or Remote/Remote Average for a
wired indoor sensor.
Select where the outdoor temperature
data comes from. ( This option is not
available it you are using the wired
outdoor temperature sensor)
Factory default setting (bold)
and setting range
None
Range 6 to 60 Minutes
(Calculated Minutes per Hour)
Range 6 to 60 Minutes
Outdoor
Remote
(Onboard sensor disabled)
Remote Average
(Average with onboard sensor)
No
(No external sensor connected)
Web
Automation
(for home automation cong only)
None
Wireless
(Wireless outdoor sensor)
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
System settingDescription
High Vent RH
Limit
High Vent RH
Limit
Low Vent RH
Limit
Low Vent RH
Limit
High Vent
Temperature
Limit
Selects if ventilation is disabled when the
indoor RH exceeds the indoor RH limit.
(Only available if Fresh Air Setup is set to
Comfort.)
Sets the ventilation indoor RH lockout
limit. (Only available if High Vent RH Limit
is set to Enabled.)
Selects if ventilation is disabled when the
indoor RH exceeds the indoor RH limit.
(Only available if Fresh Air Setup is set to
Comfort.)
Sets the ventilation indoor RH lockout
limit. (Only available if Low Vent RH Limit is
set to Enabled.)
Enables high ventilation temperature
lockout limit. (Only available if an outdoor
sensor option is enabled.)
Factory default setting (bold)
and setting range
Disabled
Enabled
55%
45% to 70%
Disabled
Enabled
20%
10% to 30%
Disabled
Enabled
3534
Page 19
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
System settingDescription
High Vent
Temperature
Limit
Low Vent
Temperature
Limit
Low Vent
Temperature
Limit
HVAC Fan with
Vent?
High Mixing
Temperature
High Mixing
Temperature
Sets high ventilation temperature
lockout limit. (Only available if High Vent
Temperature Limit is set to Enabled.)
Enables low ventilation temperature
lockout limit. (Only available if an outdoor
sensor option is enabled.)
Sets low ventilation temperature
lockout limit. (Only available if Low Vent
Temperature Limit is set to Enabled.)
Selects if ventilation forces the fan on.
(Yes with high and low limits is only
available if an outdoor sensor option is
enabled.)
Enables high mixing temperature. (Only
available is HVAC Fan with Vent is set to
Yes with high and low limits.)
Sets the high mixing temperature. (Only
available if High Mixing Temperature is set
to Enabled.)
Factory default setting (bold)
and setting range
10 0°F (38° C)
85°F to 105°F (29°C to 41°C)
Disabled
Enabled
10 °F (-12°C)
-10°F to 40°F (-24°C to 6°C)
Yes
Yes with high and low limits
No
Disabled
Enabled
80°F or (26°C)
60°F to 105°F (14°C to 41°C)
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
System settingDescription
Low Mixing
Temperature
Low Mixing
Temperature
Fresh Air
Reminder
Recurrence
Enables low mixing temperature. (Only
available is HVAC Fan with Vent is set to
Yes with high and low limits.)
Sets the Low mixing temperature. (Only
available if Low Mixing Temperature is set
to Enabled.)
Enable or disable the Service Fresh Air
message.
Select number of months between
Service Fresh Air messages.
Factory default setting (bold)
and setting range
Disabled
Enabled
40 °F (6°C)
0°F to 50°F (-18°C to 12°C)
Disabled
Enabled
12 Months
1 to 12 Months
3736
Page 20
SYSTEM TEST MENU
HP: Heat Stage
1, Gas
Next
W
70
72
HEATING
AWAY
The system test menu is used to test a system after installation. The Installer Test can be accessed
from the Installer Menu. All equipment outputs that are congured in the installer settings can be
turned on and off for testing equipment. Minimum on and off times are not enforced while in this
mode. The instructions below show how to enter the test mode and turn outputs on and off.
QUICK REFERENCE TO CONTROLS & DISPLAY
HOME SCREEN
ENTER THE SYSTEM TEST MENU
1. Press Select to enter the Main
Menu.
2. Use
3. Press and hold and
4. Use
5. Use or to select System
WI-FI SETUP
For detailed instructions for connecting the thermostat to a Wi-Fi network and registering it to an
AprilAire account, refer to the Wi-Fi Quick Start Guide included in the box.
or to navigate to
Settings, press Select.
for 3 seconds to unlock the
Installer option.
or to select
Installer Settings, press Select.
Test, press Select.
SYSTEM TEST STEPS
1. Heating equipment
test.
2. Cooling equipment
test.
3. Fan equipment test.
4. Humidication
equipment test.
5. Dehumidication
equipment test.
6. Ventilation
equipment test.
EQUIPMENT
STATUS
ROOM
TEMPERATURE
ROOM
TEMPERATURE
SETTING
EVENT
STATUS
UP ARROW
BACK
SELECT (OPENS
MENU FROM
HOME SCREEN)
DOWN ARROW
3938
Page 21
MAIN MENU
Main Menu
Mode
Fan
Schedule
Hold
Heat Blast
Main Menu
Mode
Fan
Schedule
Hold
Heat Blast
Humidifier
Ventilation
Away
Dehumidifier
Air Cleaning
Vacation
Settings
70
11:11 AM
84°
55%
Indoor RH
Outside
Item availability based
on installed options.
SCREEN SAVER
Starts 45 seconds after inactivity, press any button to wake the screen.
CURRENT
TIME
ROOM
TEMPERATURE
INDOOR RH%
OUTDOOR
TEMPERATURE
4140
Page 22
TROUBLESHOOTING
DISPLAY IS BLANK
• Check circuit breaker and reset if
necessary.
• Make sure power switch at heating &
cooling system is on.
• Make sure furnace door is closed securely.
HEATING SYSTEM DOES NOT RESPOND
(“HEATING” APPEARS ON SCREEN)
• Check for 24VAC at the equipment on the
secondary side of the transformer between
power and common. If voltage is not
present, check the heating equipment to
nd the cause of the problem.
• Check for 24VAC between the heat terminal
(W) and the transformer common. If 24VAC
is present, the thermostat is functional.
Check the heating equipment to nd the
cause of the problem.
• Check for loose or broken wires between
the thermostat and the heating equipment.
TEMPE RATURE S ETTIN GS DO NOT C HANG E
• Make sure heating and cooling
temperatures are set to acceptable ranges:
− Heat: 40° to 90°F (4° to 32°C).
− Cool: 50° to 99°F (10° to 37°C).
COOLING SYSTEM DOES NOT RESPOND
(“COOLING” APPEARS ON SCREEN)
• Check for 24VAC at the equipment on the
secondary side of the transformer between
power and common. If voltage is not
present, check the cooling equipment to
nd the cause of the problem
• Check for 24VAC between the cooling
terminal (Y) and the transformer common.
If 24VAC is present, the thermostat is
functional. Check the cooling system to
nd the cause of the problem.
• Check for loose or broken wires between
the thermostat and the cooling equipment.
FAN DOES NOT T URN ON I N A CALL FOR HE AT
• Check System Setting (Fan Control in
Heating), to make sure the fan control is
properly set to match the type of system
(see page 19).
HEAT PUMP ISSUES COOL AIR IN HEAT MODE,
OR WARM AIR IN COOL MODE
• Check System Setting (O/B Operation) to
make sure the reversing valve operation
matches the heat pump.
HEAT/COOL BOTH ON AT SAME TIME
• Check System Setting (Equipment Type), to
make sure it is set to match the installed
heating/cooling equipment (see page 19).
• Check to make sure heating and cooling
wires are not shorted together.
HEATING EQUIPMENT IS RUNNING IN
COOL MODE
• Check System Setting (Equipment Type), to
make sure it is set to match the installed
heating/cooling equipment (see page 19).
“HEATING” IS NOT DISPLAYED
• Check System Setting (Control Setup) is set
correctly.
• Change the System Mode to Heat, and set
the temperature level above the current
room temperature.
“COOLING” IS NOT DISPLAYED
• Check System Setting (Control Setup) is set
correctly.
• Change the System Mode to Cool, and set
the temperature level below the current
room temperature.
HUMIDIFIER DOES NOT OPERATE IN AUTO MODE
• Check Installer System Setting number
(Outdoor Sensor) is set to Yes.
• Verify that the outdoor sensor is functioning
correctly. If the sensor is functioning
correctly the outdoor temperature will
display in the outdoor temperature
location (see SCREEN SAVER on page 42 for
the location).
4342
Page 23
ERROR CODES
THERMOSTAT FEATURES
If the thermostat enters an error mode, all outputs are turned off. The thermostat attempts to
recover every 10 minutes.
Error CodeMessageError Description
E01Sensor ErrorInternal temperature & RH sensor failure
E03EEPROM ErrorError in permanent memory
E06Remote Sensor ErrorOpen remote temperature sensor circuit
E07Remote Sensor ErrorShorted remote temperature sensor circuit
• Remote access and control over Wi-Fi.
• Indoor air quality control.
− Humidication automatic or manual
control.
− Dehumidication.
− Event-Based™ air cleaning.
− Ventilation with temperature and
humidity limits.
• Heat Blast® raises the room temperature
3°F to 5°F.
• Easy to read, color graphical display.
• Easy to use installer settings, no codes.
• 7 day programmability.
• Displays room temperature, room
humidity, temperature setting, and outdoor
temperature.
• Air lter, humidier, dehumidier, and HVAC
service reminders.
• Programmable fan control with fan
circulation mode.
• Easy to use temperature control can
override program schedule at any time.
• Progressive recovery ensures proper room
temperature at the start of a program
event.
• Built in compressor protection prevents
damage to your equipment.
• System test mode.
• Optional wireless indoor and outdoor
sensors.
• Sensor averaging and the ability to assign
a sensor to a scheduled event.
• Installer adjustable set point limits.
4544
Page 24
SPECIFICATIONS
ENVIRONMENT
Temperature
Relative humidityOperating: 5% to 90% R.H. (non-condensing)
ELECTRICAL
Operating voltage24VAC (18–30VAC)
Current
THERMAL
Outdoor & Remote temperature sensorMaximum distance: 300 feet
Room temperature measurementDisplay range: 32° to 99°F (0° to 40°C)
Outdoor temperature measurementDisplay range: -40° to 130°F (-40° to 55°C)
Setpoint temperature range
Setpoint humidity range
46
Operating: 32° to 120°F (0° to 48.9°C)
Shipping: -30° to 150°F (-34.4° to 65.5°C)
Maximum: 2.5A (total), 1.0A (single output)
Maximum surge current: 5A
Heat: 40° to 90°F (4° to 32°C)
Cool: 50° to 99°F (10° to 37°C)
Humidication: 10% to 50% R.H.
Dehumidication: 40% to 90% R.H.