AprilAire S86W MUPR Installation Manual

Page 1
Thermostats
70
HEATING
SAFETY & INSTALLATION INSTRUCTIONS
Model S86W MUPR
Wi-Fi Thermostat with IAQ
READ AND SAVE THESE INSTRUCTIONS
Page 2
TABLE OF CONTENTS
INSTALLATION
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation Location Recommendations . . .3
Outdoor Temperature Sensor (included) . . .4 Remote Temperature Sensor (optional). . . 6
Wireless Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Thermostat Mounting . . . . . . . . . . . . . . . . . . . . . . 9
Power and Reset Options . . . . . . . . . . . . . . . . . 10
Wiring Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Single & Multi Stage Heat/Cool,
One Transformer. . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Single & Multi Stage Heat/Cool,
(Ex: Boiler) Two Transformer . . . . . . . . . . . . . . . 13
Single & Multi Stage Heat Pump,
One Transformer. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Radiant & Heat/Cool, One Transformer. . . .15
Radiant & Heat Pump, One Transformer. . .16 Indoor Air Quality Equipment
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . .17
SETUP AND TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Installer Setup Wizard and
Installer Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
HVAC Installer System Settings Table. . . . . 19
TABLE 1 – HVAC Installer System Settings . . .19 Indoor Air Quality System
Settings Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
TABLE 2 – Humidier System Settings. . . . .26
TABLE 3 – Dehumidier System Settings. .30 TABLE 4 – Air Cleaning System Settings. . . 32 TABLE 5 – Fresh Air Ventilation System
Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
System Test Menu . . . . . . . . . . . . . . . . . . . . . . . . .38
Wi-Fi Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
QUICK REFERENCE TO CONTROLS
AND DISPLAY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Error Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
THERMOSTAT F EATUR ES . . . . . . . . . . . . . . . . . . . . . . .45
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
INSTALLATION LOCATION RECOMMENDATIONS
Thermostat should be mounted:
• On an interior wall, in a frequently occupied space.
Approximately 5 feet above oor.
• At least 18” from outside wall.
• Thermostat can be mounted to a vertical junction box.
Do not mount thermostat:
• Behind doors, in corners or other dead air spaces.
In direct sunlight, near lighting xtures, or other appliances that give off heat.
• On an outside or unconditioned area wall.
In the ow of a supply register, in stairwells, or near outside doors.
• On a wall with concealed pipes or ductwork.
32
Page 3
OUTDOOR TEMPERATURE SENSOR (INCLUDED)
O/B
I1
Outdoor temperature can be measured by attaching the included 8052 sensor to the T1 and T2 terminals. The outdoor sensor must be enabled in the installer setup menu.
Heat pump models can use the outdoor temperature to effectively utilize the heat pump:
• When the outdoor temperature is lower than the Low Balance Point, the heat pump will be locked out and only auxiliary heating will be used to provide heating.
• When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will be locked out and only the heat pump will be used to provide heating.
Indoor Air Quality functions can use the outdoor temperature sensor to:
Control humidication set point based on outdoor temperature to prevent condensation.
• Lock out ventilation based on high and/or low outdoor temperatures.
• Display outdoor temperature on thermostat.
Outdoor temperature sensor should be mounted:
• On side of building out of direct sunlight (north side recommended).
• Above snow line.
• At least 3 feet away from exhaust vents and condensing lines.
• Using less than 300 feet of wire.
• Do not route wires along 120 VAC lines.
FIGURE 1 – OUTDOOR TEMPERATURE SENSOR WIRING
RH RC
W
Y G C
L
W2
Y2 T2
T1 I2
90-2 561
54
Page 4
REMOTE TEMPERATURE SENSOR (OPTIONAL)
O/B
I1
A remote temperature sensor can be used for control if the thermostat is to be mounted in a concealed location or a remote sensor can be averaged with the thermostat sensor to control
a large space. An 8051 ush mount or 8053 surface mount remote temperature sensor can be
attached to the T1 and T2 terminals and mounted in a recommended area. The remote sensor must be enabled in the installer set-up menu, and once enabled will override or be averaged with the thermostat’s internal temperature sensor, based on the setting.
Remote temperature sensor should be mounted:
• On an interior wall, in a frequently occupied space.
Approximately 5 feet above oor.
• At least 18” from outside wall.
• Using less than 300 feet of wire.
Do not mount remote sensor:
• Behind doors, in corners or other dead air spaces.
In direct sunlight, near lighting xtures, or other appliances that give off heat.
• On an outside or unconditioned area wall.
In the ow of a supply register, in stairwells, or near outside doors.
• On a wall with concealed pipes or ductwork.
• Near 120 VAC lines.
FIGURE 2 – REMOTE TEMPERATURE SENSOR WIRING
RH RC
W
Y G C
L
W2
Y2
T2
T1 I2
90-2 562
76
Page 5
WIRELESS SENSORS
THERMOSTAT MOUNTING
This thermostat is compatible with the following AprilAire wireless sensors:
Model Z10IDT Indoor Temperature and Humidity Sensor
Up to eight of these sensors can be connected to the thermostat. Connected sensors will automatically be averaged, or individual sensors can be selected for scheduled events.
Model Z10ODT Outdoor Temperature and Humidity Sensor
One sensor can be connected to the thermostat.
The wireless sensor settings can be found under the thermostats’ installer settings. See the sensors instruction manual for mounting and connecting details.
1. Remove the rear mounting plate
from the thermostat.
2. Pull wires through the opening on
the back of the rear mounting plate.
3. Position and level the mounting
plate of the thermostat on wall and mark the hole locations with a pencil.
4. Insert and tighten supplied self-
drilling anchors (drywall only).
5. Place mounting plate over anchors,
insert and tighten screws.
6. Seal wire entry holes to prevent
drafts affecting temperature readings.
FIGURE 3 – THERMOSTAT MOUNTING
90-2 563
98
Page 6
POWER AND RESET OPTIONS
The thermostat is powered from 24VAC. In the case of power loss, the thermostat will maintain the clock for 2 hours. The thermostat has a memory backup that saves the thermostat settings in case of power interruption. The thermostat can be set back to factory defaults from the installer settings menu. See Installer System Settings section for details.
The factory reset does not clear thermostat account information from the AprilAire Wi-Fi Thermostat App. To clear this information, remove the thermostat from the app or use the unregister option from the thermostat’s Wi-Fi settings.
WIRING TERMINAL
WIRE SPECIFICATIONS:
• 18-24 gauge thermostat wire
INSTALLATION NOTES:
• Ensure power at the HVAC equipment is off.
• Loosen screw terminals, insert stripped wire and re-tighten.
• Push the excess wire back into the opening and plug the wall opening to prevent drafts.
RH 24VAC supply heating*
RC 24VAC supply cooling*
W
Y
G Fan
C Common
O/B Reversing valve
L
W2
Y2
T1 & T2 Outdoor/remote temperature sensor
I1 & I2 Indoor Air Quality control output
* Jumper between RC & RH is used in single
transformer systems (see wiring diagrams).
First stage heat (conventional) / First stage auxiliary (heat pump)
First stage cooling (conventional) / First stage compressor (heat pump)
System fault indicator (optional) (heat pump only)
Second stage heat (conventional) / Second stage auxiliary (heat pump)
Second stage cooling (conventional) / Second stage compressor (heat pump)
FIGURE 4 – WIRING TERMINALS
90-2 564
1110
Page 7
O/B
I1
FIGURE 5 – SINGLE & MULTI
O/B
I1
STAGE HEAT/COOL, ONE TRANSFORMER
NOTE: Dashed lines represent wiring for multi stage systems only.
WIRING DIAGRAMS
RH RC
W
Y G C
L
W2
Y2 T2
T1 I2
JUMPER
ODT/REMOTE
TEMP SENSOR
R
W
Y
G
C
FURNACE
W2
Y2
Y2
AIR
C
CONDITIONER
Y
FIGURE 6 – SINGLE & MULTI STAGE HEAT/COOL, (EX: BOILER) TWO TRANSFORMER
NOTE: Dashed lines represent wiring for multi stage systems only.
RH RC
W2
Y2 T2
(REMOVE JUMPER)
W
Y G C
L
ODT/REMOTE
T1
TEMP SENSOR
I2
90-2 566
R
HEAT SOURCE
(EX: BOILER)
W
Y G
AIR
HANDLER
C
R
Y2
Y2
AIR
C
CONDITIONER
Y
90-2 565
1312
Page 8
FIGURE 7 – SINGLE
O/B
JUMPER
O/B
I1
& MULTI STAGE HEAT PUMP, ONE TRANSFORMER
NOTE: Dashed lines represent wiring for multi stage systems only.
RH RC
W2
Y2 T2
JUMPER
W
Y G C
L
ODT/REMOTE
T1
TEMP SENSOR
I2
I1
90-2 567
R
W
Y
G
C
HANDLER
W2
Y2
Y2 C Y
OUTDOOR
W R
O/B L
AIR
UNIT
FIGURE 8 – RADIANT & HEAT/COOL, ONE TRANSFORMER
RH RC
W
Y G C
L
W2
Y2 T2
T1 I2
90-2 677
24V COM
E/W2
ODT/REMOTE
TEMP SENSOR
NO(1)
AA
8024
COM(3)
R
RADIANT
FLOOR
W
Y
G
C
FURNACE
R
W
C
AIR
CONDITIONER
Y
1514
Page 9
FIGURE 9 –
O/B
DUCT MOUNTED EVAPORATIVE HUMIDIFIERS
I2
I1
STANDALONE OR RESIDENTIAL STEAM HUMIDIFIER
I2
I1
DEHUMIDIFIER
I2
I1
I2
I1
RADIANT & HEAT PUMP, ONE TRANSFORMER
RH RC
W
Y G C
L
W2
Y2 T2
T1 I2
I1
90-2 678
JUMPER
ODT/REMOTE
TEMP SENSOR
24V COM
E/W2
Y
AA
8024
NC(2)
COM(3)
NO(4)
COM(6)
R
W
G
C
R
O/B
W
Y
Y
W
O/B R
C
L
RADIANT
FLOOR
AIR
HANDLER
OUTDOOR
UNIT
FIGURE 10 - INDOOR AIR QUALITY EQUIPMENT WIRING DIAGRAMS
(APRILAIRE SERIES 400, 500, 600, 700)
TRANSFORMER
HUMIDIFIER
SOLENOID
90-2 570
(APRILAIRE SERIES 300, 800)
HUMIDIFIER
DRY CONTACT INPUT
90-2 680
(APRILAIRE SERIES 1800, e-SERIES)
DEHUMIDIFIER
DRY CONTACT INPUT
VENTILATION
(APRILAIRE SERIES 8100)
TRANSFORMER*
V
DAMPER
*If required by ventilation accessory.
90-2 569
O
A
N
T
T
L
E
I
I
90-2 571
NOTE: The I1/I2 output is a dry contact closure. The HUMIDIFIER wiring diagram assumes the control is powering a solenoid valve. The DEHUMIDIFIER wiring diagram is for a normally open dry contact input. The VENTILATION wiring diagram assumes the control is for a normally closed
damper. Refer to the individual humidier, dehumidier or ventilation installation instructions for product specic wiring details.
N
1716
Page 10
SETUP AND TESTING
INSTALLER SETUP WIZARD AND INSTALLER SETTING
The rst time the thermostat is powered
up (or after a factory reset) it will enter the Installer Setup Wizard. All Installer Settings can be set through this process. The Installer Settings are also accessible in the
Installer Menu.
HOW TO ENTER THE INSTALLER MENU:
1. Press Select to enter the Main Menu.
2. Use
3. Press and hold
4. Use
or to navigate to Settings,
press SELECT.
and for 3 seconds
to unlock the Installer option.
or to navigate to Installer,
press SELECT. Refer to the chart at right for options.
INSTALLER MENU OPTIONS DESCRIPTION
HVAC Settings
HVAC Advanced
IAQ Settings
Wireless Sensor
Test
Reset
Essential HVAC equipment (equipment type, stages, etc.)
Advanced HVAC control (effsets, deadbands, staging, protection, etc.)
Humidier, Dehumidier,
Air Cleaner, and
Ventilation conguration
Connect/disconnect wireless indoor and outdoor sensors
Installer test for
congured equipment
relay outputs
Reset all settings to factory default
HVAC INSTALLER SYSTEM SETTINGS TABLE
The following table contains the system settings and their details. Default settings are shown in bold. The availability of some settings is dependent upon the value of other settings.
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
Factory default setting (bold)
System setting Description
Equipment Type
O/B Energized For?
Control Setup
Heat Pump Auxiliary Type
Fan Control in Heating
NOTE: Equipment Type related settings will return to defaults if this is changed.
Selects O or B reversing valve operation. (Heat Pump mode only.)
Used to lockout heating or cooling outputs. (Heat/Cool mode only).
Selects auxiliary type. (Heat Pump mode only.)
Selects thermostat or equipment to control the fan in heating. (Heat/Cool mode only.)
and setting range
Heat/C ool
Heat Pump
Cooling Heating
Heat & Cool
Heat Only Cool Only
Gas/Oil Heat
Electric Heat
Gas/Oil Heat
Electric Heat
1918
Page 11
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System setting Description
Number of Compressor Stages
Number of Auxiliary Heat Stages
Number of Stages of Heat
Number of Stages of Cool
Programmable
Wired Temperature Sensor Installed?
Select number of compressor stages.
(Heat Pump mode only.)
Select number of auxiliary heat
stages. (Heat Pump mode only.)
Select number of heat stages. (Heat/
Cool mode only.)
Select number of cool stages. (Heat/
Cool mode only.)
Non Programmable hides all
scheduling features.
Selects how the external temperature
sensor terminals (T1 & T2) are being
used. Choose Outdoor for a wired
outdoor sensor or Remote/Remote
Average for a wired indoor sensor.
Factory default setting (bold) and setting range
One
Two
One
Two
One
Two
One
Two
Programmable Non Programmable
Outdoor Remote
(Onboard sensor disabled) Remote Average
(Average with onboard sensor) No
(No external sensor connected)
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System setting Description
Outdoor Temperature Data Provided From?
Advanced HVAC Settings?
Connection Type
Progressive Recovery
Display Heat Blast?
Heat Blast Offset
Select where the outdoor temperature data comes from. (This option is not available if you are using the wired outdoor temperature sensor.)
Select No to skip the rest of the thermostat settings.
Selects if the thermostat connects with an automation system or an AprilAire account.
Enables or disables progressive recovery.
Select if the Heat Blast option is displayed.
Amount of heating when Heat Blast is initiated.
Factory default setting (bold) and setting range
Web
Automation
(for home automation cong only)
None Wireless
(Wireless outdoor sensor)
No
Yes
AprilAire Cloud
Automation System
Disabled
Enabled
No
Yes
3° F (1. 5°C)
4° F (2°C) 5°F (2.5°C)
2120
Page 12
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System setting Description
Extended Fan – Heat
Extended Fan – Cool
Auto Changeover
DeadBand Auto Changeover mode deadband.
Auto Changeover Time
Temp Sensor Offset
RH Sensor Offset
Equipment Minimum On Time
Extends fan operation 90 seconds
after heat call ends. NOTE: Only
available with electric heat.
Extends fan operation 90 seconds
after cool call ends.
Enable or disable Auto Changeover
mode.
Minimum time between heating and
cooling calls.
Field adjustment of controlling
temperature sensors.
Internal RH sensor. Increases or
decreases displayed RH%.
Minimum on time for heating and
cooling.
Factory default setting (bold) and setting range
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
3° F (1. 5°C)
2 to 9°F (1 to 4.5°C)
4 Minutes
1 to 5 Minutes
0°F (0°C)
-4 to 4°F (-2 to +2°C)
0
-5 to 5
2 Minutes
1 to 5 Minutes
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System setting Description
Heating Minimum Off Time
Compressor Minimum Off Time
Outdoor Temperature High Balance Point
High Balance Point Temperature
Outdoor Temperature Low Balance Point
Low Balance Point Temperature
Minimum off time for heating.
Minimum off time for compressor protection.
Enable or disable high balance point. (Available if an ODT is installed.)
If outside temperature is above the high balance point the aux heat operation is not allowed. (Available if high balance point is enabled.)
Enable or disable low balance point. (Available if an ODT is installed.)
If outside temperature is below the low balance point the compressor operation is not allowed. (Available if low balance point is enabled.)
Factory default setting (bold) and setting range
2 Minutes
1 to 5 Minutes
5 Minutes
1 to 5 Minutes
Enabled
Disabled
65°F (14.5°C)
0 to 80°F (-18 to 22°C)
Enabled
Disabled
20 °F (- 8°C)
0 to 60°F (-18 to 12°C)
2322
Page 13
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System setting Description
Stage Rate
Stage Rate Factor
First Stage Differential
Second Stage Differential
Third Stage Differential
Fourth Stage Differential
Service HVAC Reminder
Accumulation of difference from
setpoint over time in staging
determination.
1 = more rapid staging of equipment
(comfort),
5 = slower staging of equipment
(economy).
First stage differential.
Second stage differential.
Third stage differential.
Fourth stage differential.
Enable or disable the HVAC Service
reminder message.
Factory default setting (bold) and setting range
Enabled
Disabled
2
1 to 5
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
Disabled
Enabled
TAB LE 1 – HVAC INSTALLER SYSTEM SETTINGS
System setting Description
Recurrence
Max Heat Setting
Min Heat Setting
Max Cool Setting
Min Cool Setting
Select number of months between HVAC Service reminder messages.
Select the maximum heating set point temperature allowed.
Select the minimum heating set point temperature allowed.
Select the maximum cooling set point temperature allowed.
Select the minimum cooling set point temperature allowed.
Factory default setting (bold) and setting range
12 Months
1 to 12 Months
90 °F (32°C)
40 to 90°F (4.5 to 32°C)
40 °F (4 .5°C)
40* to 90°F (4.5 to 32°C)
99 °F (37°C)
50 to 99°F (10 to 37°C)
50° (10°C)
50 to 99°F (10 to 37°C)
2524
Page 14
INDOOR AIR QUALITY SYSTEM SETTINGS TABLES
The following tables contain the Indoor Air Quality system settings and their details. Default settings are shown in bold. The availability of some settings is dependent upon the value of other settings. The use of outdoor temperature data enables additional Indoor Air quality functionality. While the outdoor temperature sensor option was presented in the HVAC installer settings, it is also available in the Indoor Air Quality settings.
Please refer to the Owner’s Manual for further information about thermostat features.
TAB LE 2 – HUMIDIFIER SYSTEM SETTINGS
Factory default setting (bold)
System setting Description
and setting range
NOTE: A humidier can only be installed if ventilation is not installed and dehumidier control is not set to Whole Home.
Selects whether a humidier is installed.
Yes/On HVAC is used for applications
Humidier
Installed?
where the humidier is installed on the
HVAC duct. Yes/Standalone is used for
applications where the humidier is
independent from the HVAC system. (If set to No, no other humidier settings will be available.)
No
Yes/O n HVAC Yes/Standalone
TAB LE 2 – HUMIDIFIER SYSTEM SETTINGS
System setting Description
Wired Temperature Sensor Installed?
Outdoor Temperature Data Provided From?
Humidier Mode
Selects how the external temperature sensor terminals (T1 & T2) are being used. Choose Outdoor for a wired outdoor sensor or Remote/Remote Average for a wired indoor sensor.
Select where the outdoor temperature data comes from. (This option is not available it you are using the wired outdoor temperature sensor)
Selects auto or manual mode. Auto mode controls humidity based on the humidity setting and outdoor temperature. Manual mode controls humidity based on the %RH setpoint. (Auto mode is only available if an outdoor sensor option is enabled.)
Factory default setting (bold) and setting range
Outdoor Remote
(Onboard sensor disabled) Remote Average
(Average with onboard sensor) No
(No external sensor connected)
Web
Automation
(for home automation cong only)
None Wireless
(Wireless outdoor sensor)
Auto
Manual
2726
Page 15
TAB LE 2 – HUMIDIFIER SYSTEM SETTINGS
Factory default setting (bold)
System setting Description
Selects when humidication is allowed
to occur relative to heating and fan
Allowed
Humidier
Operation
operation. NOTE: Without Fan is only
available when Humidier Installed
is set to Yes/Standalone. It allows
humidication to occur without
activating an HVAC fan and should only
be used when the humidier is mounted
independently of any HVAC system.
and setting range
Heat Only Heat or Fan
Forces Fan
Without Fan
CAUTION
When Humidier Operation is set to Without Fan the thermostat will turn on humidication without energizing the HVAC fan. Do not select this option when the humidier is installed on the HVAC duct. Without airow moisture can accumulate in the duct resulting in signicant damage.
TAB LE 2 – HUMIDIFIER SYSTEM SETTINGS
System setting Description
Humidier
Reminder
Single or First Reminder Appears
Second Reminder Appears
Selects when the “Change Water Panel” message is displayed.
Determines the month the rst (or only)
“Change Water Panel” message is displayed.
Determines the month the second “Change Water Panel” message is displayed. (Only available when 2 reminders per season is selected.)
Factory default setting (bold) and setting range
Off
150h Valve 300h Valve 600h Valve 1 per season 2 per season
October
November December January February March
October November December
January
February March
April May June July August September
April May June July August September
2928
Page 16
TAB LE 3 – DEHUMIDIFIER SYSTEM SETTINGS
Factory default setting
System setting Description
(bold) and setting range
NOTE: Dehumidier control can only be set to Whole Home if ventilation and humidication
are not enabled.
Selects if a dehumidier is installed. (If set to
Dehumidier Type
Installed?
Disable
Dehumidication
During Cooling?
Dehumidier Forces
Fan?
Dehumidier
Overcool Limit
None, no other dehumidier settings will be
available.) AC w/ IAQ selects overcooling, I1 and I2 terminals energize during overcooling. AC w/o IAQ selects overcooling, I1 and I2 terminals are not used.
Selects if dehumidication is disabled
during a cooling call.
Selects if dehumidication can turn on the
HVAC system fan.
Selects the amount of overcooling that can
occur for dehumidication. (Only available if dehumidier type is set to Overcool.)
None
Whole Home AC w/ IAQ AC w/o IAQ
Yes
No
Yes
No
1°F (0.5°C)
2° F (1° C) 3° F (1.5° C)
TAB LE 3 – DEHUMIDIFIER SYSTEM SETTINGS
System setting Description
Dehumidier
Reminder
Recurrence
Dehumidify in Vacation Hold?
Vacation Hold Low Temperature Limit
Humidity Deadband
Enable or disable the Dehumidier Service
reminder message.
Select number of months between
Dehumidier Service reminder messages.
Selects if dehumidication with the air
conditioner is done in vacation mode.
Sets the lowest temperature the air conditioner will cool to, to meet RH setpoint in Vacation Mode. (Only available if dehumidier type is set to Overcool.)
Select the minimum difference between
the humidier and dehumidier setpoints. (Only available if both Humidier and Dehumidier are enabled.)
Factory default setting (bold) and setting range
Disabled
Enabled
12 Months
1 to 12 Months
No
Yes
75°F (24°C)
70 to 85°F (21 to 29.5°C)
10%
10 to 20%
3130
Page 17
TAB LE 4 – AIR CLEANING SYSTEM SETTINGS
System setting Description
Air Cleaner Installed?
Air Cleaner Reminder
Recurrence
Selects if an air cleaner is installed. (If set to No, no other air cleaner settings will be available.)
Enable or disable the Change Air Filter message.
Select number of months between Change Air Filter messages.
Factory default setting (bold) and setting range
No
Yes
Disabled
Enabled
12 Months
1 to 12 Months
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
Factory default setting (bold)
System setting Description
and setting range
NOTE: Ventilation can only be installed if humidication is not enabled and dehumidier control is not set to Whole Home.
Fresh Air Vent Installed?
Fresh Air Setup Type
Number of Bedrooms
Square Footage
Measured CFM
Selects if ventilation is installed. (If set to No, no other ventilation settings will be available.)
Selects if ventilation is congured through
the Code setup or Comfort. Comfort setup has more lockout options. Code setting ensures time missed due to lockouts is made up.
Selects the number of bedrooms to be used for the Calculated Minutes per Hour.
Selects the size of the home to be used for the Calculated Minutes per Hour.
Selects the ventilation CFM to be used for the Calculated Minutes per Hour.
No
Yes
Comfort
Code
3 Bedrooms
1 to 10 Bedrooms
2500 SQ FT
500 to 7500 SQ FT
110 CFM
30 to 250 CFM
3332
Page 18
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
System setting Description
Calculated Minutes Per Hour
Override
Wired Temperature Sensor Installed?
Outdoor Temperature Data Provided From?
Displays the Fresh Air Time calculated.
Manual adjustment of Calculated Minutes per Hour.
Selects how the external temperature sensor terminals (T1 & T2) are being used. Choose Outdoor for a wired outdoor sensor or Remote/Remote Average for a wired indoor sensor.
Select where the outdoor temperature data comes from. ( This option is not available it you are using the wired outdoor temperature sensor)
Factory default setting (bold) and setting range
None
Range 6 to 60 Minutes
(Calculated Minutes per Hour)
Range 6 to 60 Minutes
Outdoor Remote
(Onboard sensor disabled) Remote Average
(Average with onboard sensor) No
(No external sensor connected)
Web
Automation
(for home automation cong only)
None Wireless
(Wireless outdoor sensor)
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
System setting Description
High Vent RH Limit
High Vent RH Limit
Low Vent RH Limit
Low Vent RH Limit
High Vent Temperature Limit
Selects if ventilation is disabled when the indoor RH exceeds the indoor RH limit. (Only available if Fresh Air Setup is set to Comfort.)
Sets the ventilation indoor RH lockout limit. (Only available if High Vent RH Limit is set to Enabled.)
Selects if ventilation is disabled when the indoor RH exceeds the indoor RH limit. (Only available if Fresh Air Setup is set to Comfort.)
Sets the ventilation indoor RH lockout limit. (Only available if Low Vent RH Limit is set to Enabled.)
Enables high ventilation temperature lockout limit. (Only available if an outdoor sensor option is enabled.)
Factory default setting (bold) and setting range
Disabled
Enabled
55%
45% to 70%
Disabled
Enabled
20%
10% to 30%
Disabled
Enabled
3534
Page 19
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
System setting Description
High Vent Temperature Limit
Low Vent Temperature Limit
Low Vent Temperature Limit
HVAC Fan with Vent?
High Mixing Temperature
High Mixing Temperature
Sets high ventilation temperature lockout limit. (Only available if High Vent Temperature Limit is set to Enabled.)
Enables low ventilation temperature lockout limit. (Only available if an outdoor sensor option is enabled.)
Sets low ventilation temperature lockout limit. (Only available if Low Vent Temperature Limit is set to Enabled.)
Selects if ventilation forces the fan on. (Yes with high and low limits is only available if an outdoor sensor option is enabled.)
Enables high mixing temperature. (Only available is HVAC Fan with Vent is set to Yes with high and low limits.)
Sets the high mixing temperature. (Only available if High Mixing Temperature is set to Enabled.)
Factory default setting (bold) and setting range
10 0°F (38° C)
85°F to 105°F (29°C to 41°C)
Disabled
Enabled
10 °F (-12°C)
-10°F to 40°F (-24°C to 6°C)
Yes
Yes with high and low limits No
Disabled
Enabled
80°F or (26°C)
60°F to 105°F (14°C to 41°C)
TAB LE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS
System setting Description
Low Mixing Temperature
Low Mixing Temperature
Fresh Air Reminder
Recurrence
Enables low mixing temperature. (Only available is HVAC Fan with Vent is set to Yes with high and low limits.)
Sets the Low mixing temperature. (Only available if Low Mixing Temperature is set to Enabled.)
Enable or disable the Service Fresh Air message.
Select number of months between Service Fresh Air messages.
Factory default setting (bold) and setting range
Disabled
Enabled
40 °F (6°C)
0°F to 50°F (-18°C to 12°C)
Disabled
Enabled
12 Months
1 to 12 Months
3736
Page 20
SYSTEM TEST MENU
HP: Heat Stage
1, Gas
Next
W
70
72
HEATING
AWAY
The system test menu is used to test a system after installation. The Installer Test can be accessed
from the Installer Menu. All equipment outputs that are congured in the installer settings can be
turned on and off for testing equipment. Minimum on and off times are not enforced while in this mode. The instructions below show how to enter the test mode and turn outputs on and off.
QUICK REFERENCE TO CONTROLS & DISPLAY
HOME SCREEN
ENTER THE SYSTEM TEST MENU
1. Press Select to enter the Main Menu.
2. Use
3. Press and hold and
4. Use
5. Use or to select System
WI-FI SETUP
For detailed instructions for connecting the thermostat to a Wi-Fi network and registering it to an AprilAire account, refer to the Wi-Fi Quick Start Guide included in the box.
or to navigate to
Settings, press Select.
for 3 seconds to unlock the Installer option.
or to select
Installer Settings, press Select.
Test, press Select.
SYSTEM TEST STEPS
1. Heating equipment
test.
2. Cooling equipment
test.
3. Fan equipment test.
4. Humidication
equipment test.
5. Dehumidication
equipment test.
6. Ventilation
equipment test.
EQUIPMENT STATUS
ROOM TEMPERATURE
ROOM TEMPERATURE SETTING
EVENT STATUS
UP ARROW
BACK
SELECT (OPENS MENU FROM HOME SCREEN)
DOWN ARROW
3938
Page 21
MAIN MENU
Main Menu
Mode
Fan
Schedule
Hold
Heat Blast
Main Menu
Mode
Fan
Schedule
Hold
Heat Blast
Humidifier
Ventilation
Away
Dehumidifier
Air Cleaning
Vacation
Settings
70
11:11 AM
84°
55%
Indoor RH
Outside
Item availability based on installed options.
SCREEN SAVER
Starts 45 seconds after inactivity, press any button to wake the screen.
CURRENT TIME
ROOM TEMPERATURE
INDOOR RH%
OUTDOOR TEMPERATURE
4140
Page 22
TROUBLESHOOTING
DISPLAY IS BLANK
• Check circuit breaker and reset if
necessary.
• Make sure power switch at heating &
cooling system is on.
• Make sure furnace door is closed securely.
HEATING SYSTEM DOES NOT RESPOND (“HEATING” APPEARS ON SCREEN)
• Check for 24VAC at the equipment on the
secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to
nd the cause of the problem.
• Check for 24VAC between the heat terminal
(W) and the transformer common. If 24VAC is present, the thermostat is functional.
Check the heating equipment to nd the
cause of the problem.
• Check for loose or broken wires between
the thermostat and the heating equipment.
TEMPE RATURE S ETTIN GS DO NOT C HANG E
• Make sure heating and cooling temperatures are set to acceptable ranges:
Heat: 40° to 90°F (4° to 32°C).
Cool: 50° to 99°F (10° to 37°C).
COOLING SYSTEM DOES NOT RESPOND (“COOLING” APPEARS ON SCREEN)
• Check for 24VAC at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment to
nd the cause of the problem
• Check for 24VAC between the cooling terminal (Y) and the transformer common. If 24VAC is present, the thermostat is functional. Check the cooling system to
nd the cause of the problem.
• Check for loose or broken wires between the thermostat and the cooling equipment.
FAN DOES NOT T URN ON I N A CALL FOR HE AT
• Check System Setting (Fan Control in Heating), to make sure the fan control is properly set to match the type of system (see page 19).
HEAT PUMP ISSUES COOL AIR IN HEAT MODE, OR WARM AIR IN COOL MODE
• Check System Setting (O/B Operation) to make sure the reversing valve operation matches the heat pump.
HEAT/COOL BOTH ON AT SAME TIME
• Check System Setting (Equipment Type), to make sure it is set to match the installed heating/cooling equipment (see page 19).
• Check to make sure heating and cooling wires are not shorted together.
HEATING EQUIPMENT IS RUNNING IN COOL MODE
• Check System Setting (Equipment Type), to make sure it is set to match the installed heating/cooling equipment (see page 19).
“HEATING” IS NOT DISPLAYED
• Check System Setting (Control Setup) is set correctly.
• Change the System Mode to Heat, and set the temperature level above the current room temperature.
“COOLING” IS NOT DISPLAYED
• Check System Setting (Control Setup) is set correctly.
• Change the System Mode to Cool, and set the temperature level below the current room temperature.
HUMIDIFIER DOES NOT OPERATE IN AUTO MODE
• Check Installer System Setting number (Outdoor Sensor) is set to Yes.
• Verify that the outdoor sensor is functioning correctly. If the sensor is functioning correctly the outdoor temperature will display in the outdoor temperature location (see SCREEN SAVER on page 42 for the location).
4342
Page 23
ERROR CODES
THERMOSTAT FEATURES
If the thermostat enters an error mode, all outputs are turned off. The thermostat attempts to recover every 10 minutes.
Error Code Message Error Description
E01 Sensor Error Internal temperature & RH sensor failure
E03 EEPROM Error Error in permanent memory
E06 Remote Sensor Error Open remote temperature sensor circuit
E07 Remote Sensor Error Shorted remote temperature sensor circuit
• Remote access and control over Wi-Fi.
• Indoor air quality control.
− Humidication automatic or manual control.
− Dehumidication.
− Event-Based™ air cleaning.
− Ventilation with temperature and humidity limits.
• Heat Blast® raises the room temperature 3°F to 5°F.
• Easy to read, color graphical display.
• Easy to use installer settings, no codes.
• 7 day programmability.
• Displays room temperature, room humidity, temperature setting, and outdoor temperature.
Air lter, humidier, dehumidier, and HVAC service reminders.
• Programmable fan control with fan circulation mode.
• Easy to use temperature control can override program schedule at any time.
• Progressive recovery ensures proper room temperature at the start of a program event.
• Built in compressor protection prevents damage to your equipment.
• System test mode.
• Optional wireless indoor and outdoor sensors.
• Sensor averaging and the ability to assign a sensor to a scheduled event.
• Installer adjustable set point limits.
4544
Page 24
SPECIFICATIONS
ENVIRONMENT
Temperature
Relative humidity Operating: 5% to 90% R.H. (non-condensing)
ELECTRICAL
Operating voltage 24VAC (18–30VAC)
Current
THERMAL
Outdoor & Remote temperature sensor Maximum distance: 300 feet
Room temperature measurement Display range: 32° to 99°F (0° to 40°C)
Outdoor temperature measurement Display range: -40° to 130°F (-40° to 55°C)
Setpoint temperature range
Setpoint humidity range
46
Operating: 32° to 120°F (0° to 48.9°C) Shipping: -30° to 150°F (-34.4° to 65.5°C)
Maximum: 2.5A (total), 1.0A (single output) Maximum surge current: 5A
Heat: 40° to 90°F (4° to 32°C) Cool: 50° to 99°F (10° to 37°C)
Humidication: 10% to 50% R.H. Dehumidication: 40% to 90% R.H.
Page 25
B2208826C • 61001878 • 7.22 © 2022 AprilAire | aprilairepartners.com | 800.334.6011
U.S. Patent Numbers 8,146,376, 8,596,078, 9,874,366 and other patents pending.
AprilAire reserves the right to change specications without notice.
Loading...