Aprilaire 6303 User Manual

ZONED COMFORT CONTROL SYSTEM
WARNING
1. 120 Volts may cause serious injury from electrical shock. Sudden operation may cause serious injury from moving parts. Leave power disconnected until installation is complete.
2. Sharp edges may cause serious injury from
3. The Aprilaire Zoned Comfort Control System is
designed for indoor use only. Do not expose any component of the zone control system to moisture. Do not mount any Aprilaire Zoned Comfort Control equipment where it may be accessible to children.
CAUTION
1. Installation must be done in accordance with all applicable codes.
2. Installer should touch a grounded metal object before handling the Aprilaire control panel to avoid potential loss of internal computer programs due to static discharge.
3. A zoned comfort control system may not control temperature properly unless the heating and cooling system is
properly sized
and balanced.
4. Insufficient air flow or excessive temperatures through the heating and cooling system could result in equipment damage. Refer to the manufacturer’s recommendations for minimum safe airflow and temperature requirements.
5. Excessive pressure across a bypass evaporative type humidifier may cause high air velocity in the humidifier, resulting in water being blown into the ductwork. Refer to Design Guide for humidifier installation instructions.
6. Install an outdoor thermostat to prevent non­seasonal equipment starts if using auto changeover thermostats.
7. Do not mount the control panel on any part of the heating/cooling equipment or ductwork.
8. Do not install control panel where temperatures exceed 158°F (70°C).
Read this Installation Manual before beginning installation of the Aprilaire Zoned Comfort Control System.
For questions call Research Products Corporation at (800) 334-6011.
SAFETY INSTRUCTIONS
CAUTION: Installer must touch a grounded metal object before handling the Aprilaire Zoned Comfort Control panel to avoid potential loss of programs due to static discharge.
1. MOUNT THE CONTROL PANEL
Four holes are provided on the back of the unit for mounting. (See Figure 1)
• Mount indoors using #8 or #10 screws (field supplied).
• Mount in location where the temperature will
not exceed 158°F and will not drop below freezing (32°F).
• Do not mount on foundation walls, or on the
HVAC equipment or ductwork. These locations can cause the enclosure to become cooler than the surrounding air, which can cause moisture to condense on the enclosure.
6303
INSTALLATION
MANUAL
INSTALLATION
FIGURE 1
MOUNTING HOLE
2 PLACES
E-H
ON
E-H
E
A
T
ON
OFF
ENCLOSURE BASE
CONTROL BOARD
MOUNTING HOLE
2 PLACES
“THROUGH-THE-WALL”
E
A
T
OFF
#8 SCREWS (Field Supplied)
WIRING HOLE,
2 PLACES
ENCLOSURE
COVER
2. MOUNT THE 8052 PLENUM TEMPERATURE SENSOR (provided)
IMPORTANT: Do not mount the sensor in direct line-of-sight of the heat exchanger, cooling coils, or UV lights as they may cause the sensor to report false temperature readings.
• Locate the sensor in the supply trunk, after the heat exchanger and cooling coils and before the zone dampers (shaded areas). (See Figure 2)
• Mount the 8052 Sensor according to Installation Instructions provided with the sensor.
• Wire the 8052 Sensor to the Plenum Sensor terminals on the zoned comfort control panel
before power is applied to control panel.
• Measure the resistance across the Plenum Sensor terminals (before power is applied to
the panel) and confirm that it roughly corresponds to the ambient temperature values listed in the table below.
NOTE: In order for the control panel to recognize a sensor, it must be wired to the panel before power is applied.
3. PROVIDE CONTROL SYSTEM POWER
Install a transformer, separate from the transformer provided for the HVAC equipment, to provide power for the control panel, thermostats and dampers. The size of the transformer depends on the greatest number of dampers that will be energized at any given time. If more than 6 dampers could be powered at one time, install dedicated damper transformers and a Model 8028 Damper Power Distribution Panel. Use the table below to size the added transformer(s). Aprilaire Flexible Link Dampers require 12 VA per damper. Multiply the number of dampers by 12 and select a transformer that meets or exceeds this value. The table below illustrates.
4. SET UP THE CONTROL PANEL FOR THE APPLICATION
Z1 HC/Z1 HP is set according to the type of thermostat installed in Zone 1. If a heat/cool thermostat is used in Zone 1, place the pin jumper block on the left two pins (Z1 HC). While set as Z1 HC, emergency heat can only be controlled with the on board E-HEAT switch. If a heat pump thermostat is used in Zone 1, place the pin jumper block on the right two pins (Z1 HP). Using a heat pump thermostat in Zone 1 allows for emergency heat control from the Zone 1 thermostat.
GAS/ELECTRIC refers to the auxiliary heat source. If gas (or propane or oil) heat is to be used, place the pin jumper block on the left two pins
(GAS). This will allow the auxiliary heating equipment to control the fan operation through the use of a plenum switch. If electric heat is to be used, place the pin jumper block on the right two pins (ELECTRIC).
PURGE/NO PURGE determines whether the zone control panel or the equipment will control the fan purge. If set to PURGE, pin jumper block on left two pins, the G terminal and any energized damper terminals will remain energized for a one-minute purge delay following the completion of a cool call, regular heat call or an electric auxiliary heat call. If set to NO PURGE, pin jumper block on right two pins, the G terminal will de­energize immediately and any energized damper will remain energized for 3.5 minutes following the completion of a call. The NO PURGE setting is designed for use with systems where the equipment has a built-in fan purge.
HT-160/120: If using a plenum temperature sensor, this jumper controls the temperature at which the heating equipment will cut out to prevent
overheating. Set the high limit temperature that is appropriate for the equipment being used. For a high limit temperature of 160°F, place the pin jumper block on the left two pins (HT-160). For a high limit temperature of 120°F, place the pin jumper block to the right two pins (120).
CL-45/40: If using a plenum temperature sensor, this jumper controls the temperature at which the cooling equipment will cut out to prevent freezing the indoor coil. For a low limit temperature of 45°F, place the pin jumper block on the left two pins (CL-45). For a low limit temperature of 40°F, place the pin jumper block to the right two pins (40).
5.WIRE THE SYSTEM
Use standard 18 or 20 gauge thermostat wire, color coded wherever possible to simplify troubleshooting. The wiring diagram and the THERMOSTAT SELECTION guide below are to be used to guide you through wiring the system.
Highest Number of Powered Dampers
3 or Less
4 5 6
7 or More
VA Required
36 VA or less
48 VA 60 VA 72 VA
No. of Dampers* 12
Select Transformer
40 VA 50 VA 75 VA 75 VA
75 VA + 40 VA / 3 Dampers
Ambient Temperature (°F)
30 40 50 60 70 80 90
100
Resistance (kΩ)
7.8
7.2
6.6
6.0
5.4
4.8
4.2
3.6
ZONED COMFORT CONTROL:
MOUNT PLENUM SENSOR IN
SHADED AREA
ZONE DAMPERS
UPFLOW
FURNACE
FIGURE 2
90-690