Aprilaire 600 Installation Manual

Return
Return
Supply
Supply
Supply
Drain Line
Floor Drain or Condensate Pump
Return
Supply
Floor Drain or
Model 600 Series Humidifier Template
ATTENTION INSTALLER
Read this installation template before installing humidifier. Warranty is void unless humidifier is installed by qualified heating and air conditioning contractor due to possible misapplication of product. This product must be installed in compliance with all local, state, and federal codes. Proper humidification and humidity control require that the home be constructed with local codes and good building practices.
ELECTRICAL SHOCK HAZARD. Disconnect power to the
furnace before installing humidifier.
CAUTION
SHARP EDGES. Use care when cutting and handling
ductwork.
HOT WATER CAN SCALD. Shut o hot water supply before tapping into hot water supply.
SPECIFICATIONS
Humidifier Dimensions:
Width (including solenoid valve): 15-3/8" Height (including drain spud): 15-3/4" Depth: 10-1/4"
Bypass Duct Opening: 6" diameter Plenum Opening: 10"W x 12-3/4"H Water Feed Rate: 3 gph Electrical Data: 24 VAC, 60 Hz, 0.5 Amp Water Panel®: Model 35
INSTALLATION OPTIONS (LEFT HAND DISCHARGE SHOWN)
Aprilaire® Model 600 and 600M can be installed on either the supply plenum or cold air return of a forced air handling system with right hand or left hand bypass duct connections. The humidifier dimensions and serviceability must be considered when selecting the best location for the humidifier.
Hot water is recommended (140°F max) to provide maximum evaporative capacity. It is also recommended when the Blower Activation Feature is used with an Automatic Digital Humidifier Control, or on a heat pump system. The humidifier functions with cold, hot, softened, or unsoftened water.
FURNISHED ITEMS
• Humidifier with built-in bypass damper
• 24 VAC transformer
• Automatic Digital Humidifier Control and Outdoor Temperature Sensor (Model 600 only)
• Manual Humidifier Control (Model 600M only)
• Humidifier Control Installation Instructions
• Saddle valve
• Humidifier Installation Template
Supply
ITEMS NOT FURNISHED
• Mounting screws (sheet metal screws)
• Water supply line (1/4" O.D. copper)
• Drain line (1/2" I.D. hose)
• Low voltage wire
• Bypass ductwork
• Model 50 current sensing relay (if required)
HORIZONTALUPFLOW
Return
FREEZING TEMPERATURES CAN BURST WATER PIPES.
• Do not install humidifier where freezing may occur.
CONDENSATION DAMAGE OR MOLD CAN OCCUR.
• Locate return duct mounted humidifier control at least 6" upstream of humidifier, bypass duct connection, or fresh air intake for accurate humidity sensing.
• Locate wall mount humidifier control in areas unaffected by drafts or heat sources for accurate humidity sensing.
• Reduce the setting on the humidifier control if condensation forms on windows or in unheated spaces.
EQUIPMENT DAMAGE MAY OCCUR.
• Do not install humidifier or bypass connection on the furnace jacket.
• Do not connect the transformer to the blower motor wiring.
• Do not install the humidifier or bypass connection on a plenum face at the blanked end of the cooling coil.
• If water pressure exceeds 125 psi, reduce water pressure with devices allowed by local codes.
• Do not use water with temperature greater than 140°F.
• Do not install humidifier on systems with differential pressure greater than 0.4 w.g. between the supply and return plenums.
• When installing the humidifier control on the return duct of a downflow furnace, ensure the blower continues to run after a heat call is satisfied.
NOTICE
Return
PARTS LIST
1. Front Cover
2. Base
3. Feed Tube
4. Water Distribution Tray
5. Water Panel®
6. Scale Control Insert
7. Integral Damper
8. Damper Handle
9. Drain Spud
10. Hole Plug
11. Nameplate
12. Solenoid Valve
Drain Line
Condensate Pump
Floor Drain or Condensate Pump
Drain Line
90-1079
12
10
4
2
5
3
1
7
8
9
6
TEMPLATE MUST BE LEVEL
11
90-1250
Do not position
Floor Drain or
INSTALLATION INSTRUCTIONS
Sensing Relay (if required)
Accessory Terminals
Connect Drain Line Here
Automatic Mode
Provided with Humidifier
6
5
8a8b9
714
2
3
Press tabs to
remove cover.
90-2248
90-2248
6"
90-1067
Pull feed tube out of
distribution tray, and remove
Water Panel® evaporative assembly. Cut opening using this template.
90-1068 90-2248
Minimize Distance
Level
Template
opening in front of cooling coils.
90-2248
90-1069
Secure base with screws.
Insert feed tube into distribution tray. Turn damper handle to WINTER when in use.
6"
90-2248
90-1666
Location of manual humidifier control in living space.
Locate manual or digital humidifier control on the
return 6" above the humidifier or bypass duct.
MODEL 600 DIGITAL HUMIDIFIER CONTROL WIRING MODEL 600M MANUAL CONTROL WIRING
NOTE: Control will display software revision level i.e. r1, when the
one minute test cycle has completed. Refer to the control installation manual for system checkout instructions.
North, East
or West Side
of Home
Outdoor
Temperature
Sensor for
ADHC Terminal Strip
CR H HODT Gf
OUTPUTSINPUTSPOWER
GW
IMPORTANT: Use 120 VAC power source
other than furnace motor circuit. However, the transformer can be powered off the hot 120 VAC line before it enters the furnace. Do not wire
transformer into furnace blower circuit.
24 VAC Furnace
or Transformer
(10VA Minimum)
Water Supply
Shut-o
(Saddle Valve)
Tighten water line by double wrenching.
Drain Line:
Completed Installation
• Ensure downward slope and no kinks.
Drain Spud Hose Clamp
• Do not over­tighten hose clamp onto
Drain Line
drain spud.
• Do not use
Condensate Pump
solvent adhesive on drain spud.
90-2248
INSTALLATION CHECKLIST
  Saddle valve is
fully open.
  All plumbing
connections are watertight.
Equipment Terminals
AprilairePartners.com
Printed in USA ©2019 Aprilaire – Division of Research Products Corporation 10008975 B2205117F 10.19
Above Expected
Snow Line
R
C
G
Y
W
Thermostat or
Zone Panel
R
C
G
Y
W
Furnace
Continuously Powered
24 VAC Transformer
Yellow
Wires
Water
Supply
110 VAC
P.O. Box 1467 Madison, WI 53701-1467
800.334.6011 F: 608.257.4357
Connect Drain
Line Here
90-1510
COMMON
HI
LO
Furnace
Blower Motor
90-1207
Model 50 Current
IMPORTANT: When Model 50 current sensing relay is used, wire Model 50
current sensing relay into 24 VAC humidifier control circuit only! Do not install
in transformer primary circuit.
TEMPLATE MUST BE LEVEL
Yellow
Wires
  Humidifier
functions properly.
  Bypass damper is
in proper position.
  Owner’s manual
has been given to homeowner.