Aprilaire 50 User Manual

FURNACE
BLOWER MOTOR
MODEL 50 CURRENT
SENSING RELAY
(IF REQUIRED)
24 VAC FURNACE
OR TRANSFORMER
(10VA MINIMUM)
SHUT-OFF
(SADDLE VALVE)
WATER SUPPLY
YELLOW
24V SOLENOID
VALVE WIRES
IMPORTANT
USE 120 VAC POWER SOURCE OTHER THAN FURNACE MOTOR CIRCUIT. HOWEVER, THE TRANSFORMER CAN BE POWERED OFF THE HOT 120 VAC LINE BEFORE IT ENTERS THE FURNACE.
• DO NOT WIRE TRANSFORMER INTO FURNACE BLOWER CIRCUIT.
IMPORTANT
WHEN MODEL 50 CURRENT SENSING RELAY IS USED:
• WIRE MODEL 50 CURRENT SENSING RELAY INTO 24 VAC HUMIDIFIER CONTROL CIRCUIT ONLY!
DO NOT INSTALL IN TRANSFORMER PRIMARY CIRCUIT.
CONNECT DRAIN LINE HERE
COMMON
HI
LO
YELLOW
WIRES
G
Y
W
C
R
THERMOSTAT
110 VAC
R
C
W
Y
G
FURNACE
OUTDOOR
TEMPERATURE
SENSOR FOR AUTOMATIC
MODE
NORTH, EAST
OR WEST SIDE
OF HOME
ABOVE EXPECTED
SNOW LINE
CONTINUOUSLY POWERED
24 VAC TRANSFORMER
PROVIDED WITH HUMIDIFIER
CONNECT TO
HOT WATERSUPPLY
CONNECT DRAIN LINE HERE
OUTPUTSINPUTSPOWER
GWCRHHODT GfA
ADHC TERMINAL STRIP
B
READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING INSTALLATION
RETURN
SUPPLY
S
RETURN
SUPPLY
S
ATTENTION INSTALLER:
This product must be installed by a qualified heating and air conditioning contractor. Failure to do so could result in serious injury from electrical shock.
This product must be installed in compliance with all local, state and federal codes.
Proper humidification and humidity control also requires that the home be constructed in accordance with local codes and good building practices.
MODEL 500 SERIES HUMIDIFIER
WARNING
1. ELECTRICAL SHOCK HAZARD.
Disconnect electrical power to the furnace before starting installation. Failure to do so could result in serious injury from electrical shock.
SHARP EDGES HAZARD. Sharp
2. edges may cause serious injury from cuts. Use care when making plenum openings and handling ductwork.
RISK OF SCALDING. Water
3. temperature over 125°F can cause severe burns and scald instantly. Shut off the hot water supply before disconnecting or tapping into any hot water supply line.
(SEE STEP 7 ON BACK AND “HUMIDIFIER CONTROL SAFETY AND INSTALLATION INSTRUCTIONS” FOR DETAILED WIRING INSTRUCTIONS)
Model 500
DIGITAL HUMIDIFIER CONTROL
RESEARCH PRODUCTS CORPORATION • P.O. BOX 1467 • MADISON, WI 53701-1467 • CALL 800/334-6011 • FAX 608/257-4357
RISK OF PROPERTY AND EQUIPMENT DAMAGE.
1. Do not install humidifier where freezing temperatures could occur. The water line could freeze and crack causing water damage to the home.
2. Do not install humidifier or bypass connection on the furnace jacket.
3. Do not install humidifier or bypass connection on a plenum face where the blanked off ends of the cooling coil will restrict air movement through the humidifier.
4. Do not set humidity level above recommended or to recommended level if condensation exists on inside windows of any unheated space, as condensation damage may result. Excess humidity can cause moisture accumulation which can allow the possibility for mold growth in the home.
CAUTION
5. Do not connect Model 500 or 500M transformer
6. When installing Humidifier Control on downflow
7. Do not install humidifier where water pressure
8. Do not install humidifier on systems with
Model 500M
MANUAL CONTROL
to blower motor wiring. Premature component failure may result.
furnace, ensure blower continues to run after a heat call is satisfied to eliminate hightemperatures from damaging the Humidifier Control.
exceeds 125 psi, since damage to the humidifier may result. Follow codes in effect concerning pressure reduction.
greater than 0.4 in. wg pressure differential between supply and return plenums.
90-120790-1510
SPECIFICATIONS
UMIDIFIER DIMENSIONS
H
Width (includingsolenoid valve): 155⁄8
INSTALLATION OPTIONSRECOMMENDED WIRING DIAGRAMS
plenum of a forced air handling system and
(including drain spud): 13”
Height
Depth
: 10
1
4
BYPASS DUCT OPENING
6” diameter
PLENUM OPENING
91⁄2”W x 91⁄2”H
WATER FEED RATE
3 gph
ELECTRICAL DATA
24 VAC-60 Hz, 0.5 AMP
The Model 500 and 500M Aprilaire can be
installed on either the supply or return
is easily reversible for installation with
right hand or left hand bypass duct
connections. The humidifier dimensions
and serviceability must be considered when selecting the best location for the humidifier. Here are 2 examples of many
types of installations.
Upflow
Horizontal
90-1079
NOTE
When installing the Aprilaire humidifier with the Aprilaire Digital Humidifier Control or on a heat pump system, use hot water. The heated water supplements the reduced supply air temperature as added heat for evaporation.
READ REVERSE SIDE FIRST! READ REVERSE SIDE FIRST!
12
10
2
7
9
6
11
1
4
3
5
8
– TOP –
READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING INSTALLATION
FURNISHED ITEMS
uilt-in bypass damper
B
4 VAC Transformer
2
Digital HumidifierControl (Model 500 only)
Manual Humidifier Control (Model 500M only)
Humidifier Control Installation Instructions
Mounting screws (sheet metal screws)
odel 50 Current Sensing Relay (if required)
M
Saddle valve
umidifierInstallation Template
H
ITEMS NOT FURNISHED
Water supply line (1⁄4” copper)
Drain line (1⁄2” I.D. hose)
Low voltage wire
ypass ductwork
B
1. Press top & bottom tabs to remove
cover (1). Pull feed tube (3) out of distribution tray (4). Remove Water Panel Evaporator assembly. See Figure 1.
2. Humidifier is supplied with bypass
duct connection on left. For right side bypass, swap location of drain spud (9) and cap (10). Twist to remove spud and cap.
3. Position template on supply or return
plenum. Make sure template is level. Allow clearance for drain line and for servicing. Trace template outline. Cut 9-1/2” x 9-1/2” opening. Avoid injury
from sharp edges.
1. Front Cover
2. Base
3. Feed Tube
4. Water Distribution Tray
5. Water Panel Evaporator
6. Scale Control Insert
7. Integral Damper
8. Damper Handle
9. Drain Spud
10. Hole Plug
11. Nameplate
12. Solenoid Valve
4. Place humidifier base (2) in
opening and secure with 6
®
screws in openings provided.
5. Select location for 6” collar
on opposite plenum to minimize length and number of elbows in bypass duct. Install 6” bypass duct components. Attach duct to humidifier collar using 2 screws in openings provided.
6. Insert Water Panel Evaporator
assembly into base. Make sure bottom of scale control insert (6) is in drain spud. Snap top of evaporator assembly into base.
PARTS LIST
Figure 1 Figure 2 Figure 3
90-1067 90-1068 90-1069
Insert feed tube into distribution tray. See Figure 2. Rotate nameplate (11) if necessary, so it is right side up. Place point bypass damper handle (8) to “WINTER” (open) for heating season and “SUMMER” for cooling season.
7. Control installation and wiring.
Disconnect electrical power to furnace before wiring control.
In order for humidifier to operate, furnace must be on and RH must be below set-point of control. Wiring diagrams illustrate recommended method of detecting furnace operation.
MANUAL HUMIDIFIER CONTROL, MODEL 500M:
Manual Control can be mounted in return duct or on wall in living space. Knob and cover must be removed to mount control. See wiring diagram for 24V control connections.
• For return duct mounting, position template at least 6” upstream of bypass duct connection or humidifier. Avoid
injury from sharp edges when cutting opening. Make sure foam gasket is in
place and secure control to duct using 2 screws in openings provided.
• For wall-mount, select location that will not be affected by drafts or heat sources. Remove and discard foam gasket and secure control to wall over wire access opening using screws & anchors provided.
DIGITAL HUMIDIFIER CONTROL, MODEL 500:
• Select location for control on return duct at least 6” upstream of bypass duct connection or humidifier. Drill 3/4” hole for sensor. Knob and cover must be removed to mount control. Place control on duct with RH sensor extending into duct opening. Make sure gasket is in place around sensor cage. Secure control to duct using 2 screws in openings provided.
• See wiring diagrams on template and control instructions for 24 V control connections.
8. Humidifier will function with cold, hot,
softened or unsoftened water. Hot water (140°F max) is strongly recommended to provide maximum evaporative capacity. Saddle valve provided may be used to tap into water supply. See installation instructions on saddle valve package. Saddle valve is designed to be fully opened or closed. Do not use to regulate flow.
9. Run 1/4” copper tubing from saddle
valve to solenoid valve. DOUBLE-WRENCH TO PREVENT LEAKING. See Figure 3.
10. INSTALL DRAIN IN ACCORDANCE
WITH LOCAL CODES. Run 1/2” I.D. hose
from drain spud to floor drain. Make sure drain has constant downward slope and is not kinked. Do not over-tighten hose clamp onto drain spud. Do not use solvent adhesive on drain spud.
11. Check humidifier operation. Open
saddle valve and turn control to highest setting. Turn on furnace. Allow humidifier to run until water flows from drain. Make sure all electrical connections are secure and all plumbing connections are water­tight. Set control to proper setting.
NOTE: BEFORE LEAVING THE JOB SITE, MAKE SURE:
1. Saddle valve is fully open.
2. All plumbing connections are watertight.
3. Humidifier functions properly.
4. Bypass damper is in proper position.
90-1250
TEMPLATE MU ST BE LEVEL
IMPORTANT! Be sure owner’s manual containing instructions for
operation and warranty information is given to owner in order to avoid
unnecessary calls. Warranty is void unless humidifier is installed by qualified
heatingand air conditioning contractor due to possible misapplication of product.
10008974 B2205116A 4.10