The UPS display is the user interface to the UPS system, and is located in the control section. This LCD
touch-screen display is used to configure the system, monitor the system, and change the settings. The
display also provides the user with audible and visual alarms.
The screens in the display are organized hierarchically with the UPS Summary screen at the top of the
hierarchy.
The UPS Summary screen provides you with an overview of the UPS system and circuit breakers. It
shows the system status and the power flow through the system and gives access to the system’s summary
screens and the Operation screen.
How to Access Summary Screens from the
External Bypass Static Switch
The Static Bypass Summary screen provides you with an overview of the UPS system and circuit
breakers. It shows the system status and the power flow through the system and gives access to the
system’s Bypass Summary screens and the Operation screen. The Operation screen on the External
Bypass Static Switch has limited functionality compared to the Operation screen on the UPS.
The read-only display screens can be accessed via an Internet Browser by typing the IP address of the
Symmetra MW display into the browser’s address field. Configuration of the Symmetra MW or the
display through the remote display is not supported.
The remote display feature requires Microsoft Internet Explorer 6 SP1 or greater. For best results we
recommend that the Sun JVM version 1.4.2_05 or greater is installed, which is available from the Sun’s
website.
The Netscape browser is not supported.
Note: Operation/configuration must be done at the UPS.
Note: The event log screen can be accessed through the Operation screen. Only the 50 most
recent events in the Event Log screen can be downloaded.
Note: Network settings must be configured before the remote display feature can be used.
How to start a web-based remote session
• Start the web-based remote session
by entering the IP address of the
APC Symmetra MW UPS in the
web browser address field. After a
few seconds, a new window will
open and display the shown screen.
• After a few seconds, a new window
will open and display shown screen.
• Use the mouse to touch the buttons
to see the other screens.
• Close the window or the web
browser to end the remote session.
Note: For security reasons, there is a time limit of 5 minutes for a remote session. The
connection will be disconnected after 5 minutes and reconnection is required.
Note: Only one remote session at a time is allowed.
During online operation, the critical load is supported by the inverters. While the UPS system is operating
in this mode, a single-line diagram will appear on the screen. The green line indicates the power flow
from the utility, through the UPS units, and then to the load.
External Bypass SSW
Delta Inverter
Battery operation
During battery operation, the critical load is supported by the inverters. The main inverter is supplied by
battery power, ensuring uninterrupted support to the load. While the UPS system is operating in battery
operation, a single-line diagram will appear on the screen. The green line indicates the power flow from
the batteries, through the main inverters, and then to the load.
During static bypass operation, the critical load is supplied directly by utility power. A single-line
diagram will appear on the screen with an orange line indicating the power flow through the External
Bypass Static Switch (SSW) to the load.
External Bypass SSW
Delta Inverter
Main Inverter
Battery
Manual bypass operation
During maintenance bypass operation, the critical load is supplied directly by utility power. Maintenance
bypass allows the UPS units to be isolated for maintenance purposes. In maintenance bypass there is no
backup from the UPS system to the load. While the UPS system is operating in this mode, a single-line
diagram will appear on the screen with an orange line indicating the power flow from the utility to the
load through the Q3 breaker.
• Subnet mask: The subnet mask for the
network segment containing the UPS.
• Gateway: The network gateway for the
segment containing the UPS.
– DNS Settings
• Primary DNS server: The IP address of the DNS server to be used by the UPS (optional).
• Secondary DNS server: The IP address of a backup DNS server if the primary server is not
available (optional).
– Host Name Settings
• Host name: The network host name for the system. This uniquely identifies the system on the
network. Standard letters (a-z and A-Z), digits (1-9), and hyphen (-) can be used.
• Domain name: The DNS network domain containing the UPS. Standard letters (a-z and A-Z),
digits (1-9), and hyphen (-) can be used.
– SMTP Settings
• From address: The source address used when sending e-mails.
• SMTP server: The SMTP server responsible for sending e-mails.
–Press Apply Changes to complete the changes and select arrow down to go to the next Network
Configuration screen.
Note: The display will have to be rebooted in order for the changes to the domain name or
DNS servers to take effect.
Configure the E-mail Settings screen:
– Enable E-mail: Select to enable the e-mail
notifications.
– To add a new e-mail recipient, touch the Add
New button, type in the e-mail address and
specify the minimum severity of alarm. All
entries will appear in red until Apply Changes
is pressed.
– To edit or delete an e-mail recipient, select the
recipient from the recipient list, and then
choose to either update or delete it.
Note: The APC Remote Monitoring Service (RMS) will not be activated until the RMS Team
has been contacted. The contact details can be found at http://rms.apc.com.
– Enable APC RMS: Select this checkbox to start using the service. Once selected, information
about your UPS will periodically be sent to APC’s Remote Monitoring Service.
– Use Proxy: Select this checkbox if the Internet connection method uses a HTTP proxy server to
connect to the Internet.
– Proxy server address: Enter the fully qualified IP-address or fully qualified domain name of the
proxy server. If you do not know the server address or port number, contact your network
administrator.
– Proxy server port: Enter the port number of the proxy server.
– Use authentication: Select this checkbox if the proxy server requires a login. Then specify a
Proxy server login (user name) and a Proxy server password.
–Press Apply Changes to complete the changes and select arrow down to go to the next Network
Configuration screen.
Configure the APC ISX Manager Settings screen:
– Enable ISX manager discovery: Press the field
to enable the APC ISX Manager to discover
your Symmetra MW.
checkbox to enable or disable the APC Q
breaker prefix.
– Enable audible alarms: Use this checkbox to
enable or disable the audible alarms.
How to configure the Battery Test Settings screen
Press the Battery Test Settings button on the
User Configuration screen to access the Display
Settings screen.
Change the battery test settings. From the Battery
Test Settings screen, two different battery tests
can be performed and the battery monitor can be
reset.
– Battery monitor test: Setting this value to True
results in an automatic battery monitor test
occurring dependant in the battery test options
configured by the service engineer.
– Battery capacity test: Setting this value to True
results in the batteries being discharged until a
Battery Low Voltage Level is reached. This
test can only be performed manually. The test is used to cycle the batteries in order to calibrate
the backup time with the current load and battery modules installed.
– Battery monitor reset: In the event of a weak battery or another battery problem, use this button
The Predictive Maintenance screens display the stress status and the Expected Remaining Lifetime (ERL)
of the critical components of the Symmetra MW UPS system.
Warning: Only personnel trained in the construction and operation of the equipment,
and the electrical and mechanical hazards involved, may install or remove system
components.
How to access Predictive Maintenance screens
Press the Operation button in the bottom
left corner to access the Operation screen.
Inverter DC Capacitors screen
The Inverter DC Capacitor screen displays the actual status and Expected Remaining Lifetime (ERL) of
the Inverter DC Capacitors. You can sort the data by pressing any of the column labels.
• Stress Status: Shows the actual status of the
Inverter DC Capacitors. The possible values
are:
– Normal (displayed in green)
– Stressed (displayed in yellow)
– Major Stress (displayed in red)
• ERL (months): Predicts the expected
remaining lifetime of the particular
component.
The Inverter AC Capacitor screen displays the actual status and Expected Remaining Lifetime (ERL) of
the Inverter AC Capacitors. You can sort the data by pressing any of the column labels.
• Stress Status: Shows the actual status of the
Inverter AC Capacitors. The possible values
are:
– Normal (displayed in green)
– Stressed (displayed in yellow)
– Major Stress (displayed in red)
• ERL (months): Predicts the expected
remaining lifetime of the particular
component.
Top Fans screen
The Top Fans screen displays the actual status and Expected Remaining Lifetime (ERL) of the Top Fans.
You can sort the data by touching any of the column labels.
• Stress Status: Shows the actual status of the
Top Fans. The possible values are:
– Normal (displayed in green)
– Stressed (displayed in yellow)
– Major Stress (displayed in red)
• ERL (months): Predicts the expected
remaining lifetime of the particular
component.
The Inverter Fans screen displays the actual status and Expected Remaining Lifetime (ERL) of the
Inverter Fans. You can sort the data by pressing any of the column labels.
• Stress Status: Shows the actual status of the
Inverter Fans. The possible values are:
– Normal (displayed in green)
– Stressed (displayed in yellow)
– Major Stress (displayed in red)
• ERL (months): Predicts the expected
remaining lifetime of the particular
component.
Main Static Switch Fans screen
The Main Static Switch Fans screen displays the actual status and Expected Remaining Lifetime (ERL)
of the Main Static Switch Fans. You can sort the data by pressing any of the column labels.
• Stress Status: Shows the actual status of the
Main Static Switch Fans. The possible values
are:
– Normal (displayed in green)
– Stressed (displayed in yellow)
– Major Stress (displayed in red)
• ERL (months): Predicts the expected
remaining lifetime of the particular
component.
Check the air filters at regular intervals (every three months under normal working conditions) for
accumulated dust on the surface facing the finishing panels. Change all filters at the same time.
Pull the lower part of the top finishing panel off the UPS.
Lift the finishing panel off the dead front panel and remove.
Follow this procedure until all panels in one column have been removed. Use the same procedure
for the next column of panels until all panels have been removed from the UPS system.
The color of the top of the screen changes from blue to red when an alarm situation occurs and the alarm
symbol is shown at the top of the screen.
Alarm button
Touching the alarm button will display the Active Alarms screen showing all active
alarms, along with a methodology for addressing each alarm.Touching the alarm button
or any other display button will automatically silence the alarm.
Alarm levels
There are three different alarm levels.
Info. Informational Alarm. No immediate action required. Check the cause of the alarm at next
maintenance visit.
Warning. Warning Alarm. Example: The UPS system may have gone into bypass. The load remains
supported, but action must be taken. Call Technical Support. The area on the right side of the top screen
alternates between blue and red.
Severe. Severe Alarm. Take immediate action. Call Technical Support. The red area of the top of the
screen alternates between blue and red.
How to silence the alarm
Touch the Alarm Button or any other display button to silence the alarm.
Note: The Active Alarms screen includes a recommended action for resolving each problem.
Only active alarms will appear in this list.
Previous alarms are stored in the Event Log,
which contains a detailed record of the
system’s last 1024 events. Press the Event
Log button to go to the Event Log.
How to view the event log
The event log can be accessed either by pressing the Event Log button on the Active Alarms screen (see
“How to view active alarms” on page 26) or by following this procedure:
Press the Operation button in the bottom
left corner to access the Operation screen.
The Event Log screen contains a detailed record of the system’s latest 1024 events. This includes