APC GALAXY 7000 User Manual

MGETM GalaxyTM 7000
250 - 500 kVA
Installation manual
Introduction
Thank you for selecting an APC by Schneider Electric product to protect your electrical equipment.
The MGE We recommend that you take the time to read this manual to take full advantage of the many features of your UPS (Uninterruptible Power System).
TM
GalaxyTM 7000 range has been designed with the utmost care.
APC by Schneider Electric pays great attention to the environmental impact of its products. Measures that have made MGE
the eco-design approach used in product development, the elimination of harmonic disturbances reinjected into the AC source, production in an ISO 14001 certified factory, recycling of the MGE
TM
TM
GalaxyTM 7000 a reference in environmental protection include:
GalaxyTM 7000 at the end of its service life.
To discover the entire range of APC by Schneider Electric products and the options available for the MGE range, we invite you to visit our web site at www.apc.com or contact your local representative.
TM
GalaxyTM 7000
34020846EN/AD - Page 2
All products in the MGETM GalaxyTM 7000 range are protected by patents. They implement original technology not available to competitors of APC by Schneider Electric.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric.
This document may be copied only with the written consent of Schneider Electric or its affiliated companies. Authorised copies must be marked
TM
GalaxyTM 7000 installation manual no. 3402084600".
"MGE
Safety rules
Safety of persons
The UPS must be installed in a room with restricted access in compliance with standard IEC 60364-4-482). Only qualified personnel are authorised to enter this restricted access room. A UPS has its own internal power source (the battery). Consequently, the power outlets may be energised even if the UPS is disconnected from the AC-power source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel. The UPS must be properly earthed. The battery supplied with the UPS contains small amounts of toxic materials. Caution, replacement of the battery by a battery of the wrong type can result in an explosion. To avoid accidents, the instructions below must be observed.
Never operate the UPS if the ambient temperature and relative humidity are higher than the levels specified in the
documentation.
Never burn the battery (risk of explosion). Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin). Comply with all applicable regulations for the disposal of the battery. Caution, wait five minutes before opening the UPS to allow the capacitors to discharge. Caution, there is high leakage current: the earthing conductor must be connected first and disconnected last. The product must be installed on a non-inflammable surface (e.g. concrete). Caution, battery replacement must be carried out by qualified personnel. Isolate the Uninterrptible Power Supply (UPS) before working on the circuits upstream. The UPS can only be used in a controlled indoor environment.
Safety
Product safety
Protection (circuit breaker/switch disconnector) must be installed upstream and be easily accessible.Never install the UPS near liquids or in an excessively damp environment.Never let a liquid or foreign body penetrate inside the UPS.Never block the ventilation grates of the UPS.Never expose the UPS to direct sunlight or a source of heat. When replacing battery cells, use the same type and number of cells.
Special precautions
The UPS connection instructions contained in this manual must be followed in the indicated order.Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the
equipment to be connected to the UPS.
If the UPS must be stored prior to installation, storage must be in a dry place.The admissible storage temperature range is -25°C to +45°CIf the UPS remains de-energised for a long period, we recommend that you energise the UPS for a period of 24 hours, at least once every
month. This charges the battery, thus avoiding possible irreversible damage. The UPS is designed for normal climatic and environmental operating conditions concerning the altitude, ambient operating temperature, relative humidity and ambient transport and storage conditions. Using the UPS within the given limits guarantees its operation, but may affect the service life of certain components, particularly that of the battery and its autonomy. The maximum storage time of the UPS is limited due to the need to recharge its integrated battery. Unusual operating conditions may justify special design or protection measures:
- harmful smoke, dust, abrasive dust,
- humidity, vapour, salt air, bad weather or dripping,
- explosive dust and gas mixture,
- extreme temperature variations,
- poor ventilation,
- conductive or radiant heat from other sources,
- cooling water containing acid or impurities which may cause scale, silt, electrolysis or corrosion of converter parts exposed to water,
- strong electromagnetic fields,
- radioactive levels higher than those of the natural environment,
- fungus, insects, vermin, etc.,
- battery operating conditions.
The UPS must always be installed in compliance with:
the requirements of standard IEC 60364-4-42: Protection from thermal effects. standard IEC 60364-4-41: protection against electric shock. standard IEC 60364-4-482: Electrical installations of buildings. standard NFC 15-100 (in France). the requirements of standard IEC 62040-1-2:
34020846EN/AD - Page 3
Foreword
Pictograms
Document
Danger, these instruction are imperative.
Information, advice, help. LED off
Visual indication LED flashing
Action LED on
Audio signal.
34020846EN/AD - Page 4
APC by Schneider Electric has implemented an environmental-protection policy. Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components. The cardboard we use comprises over 30% of recycled cardboard. Sacks and bags are made of polyethylene. Packing materials are recyclable and bear the appropriate identification symbol .
Materials Abbreviation Number
in the symbol
Polyethylene terephthalate PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Environment
Polypropylene PP 05
Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
APC by Schneider Electric will process products at the end of their service life in compliance with local regulations. APC by Schneider Electric works with companies in charge of collecting and eliminating our products at the end of their service life.
Product
The product is made up of recyclable materials. Dismantling and destruction must take place in compliance with all local regulations concerning waste. At the end of its service life, the product must be transported to a processing centre for electrical and electronic waste. Make the product unusable by cutting the internal supply cables.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries. The battery may be removed to comply with regulations and in view of correct disposal. The "Material Safety Data Sheets" (MSDS) for the batteries are available on our web site*.
(*) For more information or to contact the Product Environmental manager, use the "Environmental Form" on the site: http://environment.apc.com
34020846EN/AD - Page 5
Contents
1. Installation
1.1 Possible installations .........................................................................................................................10
Single or modular UPS alone .............................................................................................................10
Parallel UPS systems .........................................................................................................................10
Modular UPSs in parallel ...........................................................................................................10
Modular UPSs in parallel with external bypass cabinet .............................................................10
Parallel UPSs with SSC (static-switch cabinet) .........................................................................11
Parallel UPS with SSC and SSC maintenance cabinet ............................................................11
UPS set up as a frequency converter .................................................................................................12
Single UPS ................................................................................................................................12
Parallel UPS systems ................................................................................................................12
1.2 Layout ..................................................................................................................................................13
Dimensions .........................................................................................................................................13
Weights ..............................................................................................................................................13
Floor mounting ...................................................................................................................................14
UPS cabinets ...........................................................................................................................14
SSC ...........................................................................................................................................14
External bypass or SSC maintenance cabinets ........................................................................15
Auxiliary cabinets (empty) ........................................................................................................16
Backfeed cabinet .......................................................................................................................16
Position in room ..................................................................................................................................17
UPS cabinets ............................................................................................................................17
SSCs .........................................................................................................................................17
External bypass cabinets ..........................................................................................................17
Battery / auxiliary cabinets ........................................................................................................17
Ventilation ...........................................................................................................................................18
UPS cabinets ............................................................................................................................18
SSC cabinets ............................................................................................................................18
1.3 Prerequisites .......................................................................................................................................19
UPS currents ......................................................................................................................................19
Recommended upstream protection ..................................................................................................19
Normal AC source ...................................................................................................................19
Bypass AC source ...................................................................................................................19
Recommended maximum downstream protection ............................................................................20
Battery protection ...............................................................................................................................20
Recommended residual-current protection ........................................................................................20
Characteristics of the connection terminals ........................................................................................21
UPS cabinets ............................................................................................................................21
SSCs, SSC maintenance, External bypass cabinets ................................................................21
Power cables for single UPSs ............................................................................................................21
Power cables for parallel UPSs ..........................................................................................................22
Normal AC line and battery .......................................................................................................22
Bypass AC line and load ...........................................................................................................22
1.4 System earthing arrangements .........................................................................................................24
Single UPS system .............................................................................................................................24
TNS upstream, TNS downstream .............................................................................................24
TNC upstream, TNC, TNS or TT downstream installation ........................................................25
IT upstream, IT downstream .....................................................................................................25
Parallel UPSs systems .......................................................................................................................25
34020846EN/AD - Page 6
1.5 Adapting the cabinet according to the neutral point connection ..................................................26
UPS cabinet .......................................................................................................................................26
Contents
SSC cabinet or external bypass cabinet ............................................................................................ 26
1.6 Connecting the power cables ........................................................................................................... 27
Single or modular UPS cabinet .......................................................................................................... 27
250 to 400 kVA ......................................................................................................................... 27
500 kVA .................................................................................................................................... 28
Frequency-converter cabinet ............................................................................................................. 29
250 to 400 kVA ......................................................................................................................... 29
500 kVA .................................................................................................................................... 30
Parallel UPS cabinet .......................................................................................................................... 31
250 to 400 kVA ......................................................................................................................... 31
500 kVA .................................................................................................................................... 32
SSC cabinet ....................................................................................................................................... 33
800 kVA .................................................................................................................................... 33
1200 kVA .................................................................................................................................. 34
2000 kVA .................................................................................................................................. 35
2000 kVA light ........................................................................................................................... 37
External bypass cabinet ..................................................................................................................... 39
800 kVA .................................................................................................................................... 39
1200 kVA .................................................................................................................................. 40
2000 kVA .................................................................................................................................. 41
SSC maintenance cabinet ................................................................................................................. 42
800 and 1200 kVA .................................................................................................................... 42
2000 kVA .................................................................................................................................. 43
1.7 Connecting cabinet ECPs (exposed conductive parts) ................................................................. 44
Interconnect the earths and tie down the wires .................................................................................44
1.8 Connecting the synchronization module ........................................................................................ 44
1.9 Connect the backfeed option ........................................................................................................... 45
Block diagram .................................................................................................................................... 45
Connect the power cables ................................................................................................................. 45
1.10 Connecting the control-wire cables ............................................................................................... 46
Connecting a modular UPS or frequency converter alone. ............................................................... 46
Connecting the UPS units in parallel ................................................................................................. 47
Connecting the modular UPS units in parallel .......................................................................... 47
Connecting the modular UPSs with the external bypass .......................................................... 48
Connecting parallel UPSs with SSC (static-switch cabinet) ..................................................... 49
Connect the components specific to the 2000 kVA light SSC .................................................. 50
Connect the SSC maintenance cabinet .................................................................................... 50
Connecting the EPO function ............................................................................................................ 51
Connecting the dry-contact communication card ............................................................................... 52
1.11 Assembling and connecting the external battery cabinet ........................................................... 53
Assembling the empty battery cabinet ............................................................................................... 53
Mounting the battery circuit-breaker kit ................................................................................... 53
Mounting the shelves ................................................................................................................ 53
Connecting the power cables ............................................................................................................ 54
Connecting the control-wire cables .................................................................................................... 55
Connecting the battery circuit breaker ...................................................................................... 55
Connecting the battery temperature sensor ............................................................................. 56
2. Appendices
34020846EN/AD - Page 7
Contents
2.1 Assembling 2000 kVA SSCs ..............................................................................................................58
2.2 IP 32 option .........................................................................................................................................58
2.3 Electrical characteristics ...................................................................................................................59
Selection of protection devices ...........................................................................................................59
Permissible UPS overloads as a function of time ...............................................................................60
2.4 General characteristics of MGE TM Galaxy TM 7000 UPSs ...........................................................61
Battery characteristics ........................................................................................................................62
2.5 Glossary ..............................................................................................................................................63
34020846EN/AD - Page 8
Contents
34020846EN/AD - Page 9
1. Installation

1.1 Possible installations

Single or modular UPS alone

1
Bypass AC
Normal AC

Parallel UPS systems

(8 units maximum)

Modular UPSs in parallel

Q1 Q5N
2
Q4S
D
A B
C
 +
QF1
Q3BP
UPS cabinet (1)
Load
PFC rectifier module A Inverter module B Battery chopper C Static-switch on AC bypass line D
Batteries (2)
1
Bypass AC
Normal AC
Bypass AC
Normal AC
Q4S
D
Q1 Q5N
A B
C
2
 +
QF1
1
Q4S
D
Q1 Q5N
A B
C
2
 +
QF1

Modular UPSs in parallel with external bypass cabinet

Bypass AC
Bypass AC
Normal AC
Bypass AC
3
1
Q4S
Q1 Q5N
A B
2
 +
QF1
1
Q4S
Q3BP ext
D
C
D
Q3BP
Q3BP
Q3BP
Q3BP
Q5N
ext
UPS cabinet (1)
PFC rectifier module A Inverter module B Battery chopper C Static-switch on AC bypass line D
Batteries (2)
Load
UPS cabinet (1)
PFC rectifier module A Inverter module B Battery chopper C Static-switch on AC bypass line D
Batteries (2) External bypass cabinet (3)
Load
34020846EN/AD - Page 10
Normal AC
Q1 Q5N
A B
C
2
 +
QF1

Parallel UPSs with SSC (static-switch cabinet)

1. Installation
Possible installations >
3
Q3BP
Bypass AC
Normal AC
Normal AC
Q4S
1
Q1 Q5N
2
1
Q1
2
A B
 +
QF1
A B
 +
QF1
D
C
+
QF1
C
-
Q5N
Q5N

Parallel UPS with SSC and SSC maintenance cabinet

3
Q3BP
Bypass AC
Q4S
D
Q5N
UPS1 cabinet (1)
PFC rectifier module A Inverter module B
Load
Battery chopper C
Batteries (2)
SSC (3) Static-switch on AC bypass line D
UPS 1 cabinet (1)
PFC module A Inverter module B
Load
Battery chopper C
Normal AC
Normal AC
1
Q1 Q5N
2
1
Q1
2
A B
C
 +
QF1
QF1
A B
C
 +
QF1
+
-
Q5N
Batteries (2)
4
QN
QM
SSC (3) Backup static switch module D
SSC maintenance cabinet (4)
34020846EN/AD - Page 11
1. Installation
Possible installations >

UPS set up as a frequency converter

(with or without battery, maximum eight units)

Single UPS

Normal AC

Parallel UPS systems

Normal AC
Normal AC
2
 +
1
Q1 Q5N
A B
2
 +
QF1
1
Q1 Q5N
A B
2
 +
QF1
1
Q1 Q5N
A B
QF1
+
QF1
C
C
C
Load
Load
UPS cabinet (1)
PFC rectifier module A Inverter module B Battery chopper C
Batteries (2)
UPS cabinet (1)
PFC rectifier module A Inverter module B Battery chopper C
Batteries (2)
34020846EN/AD - Page 12

1.2 Layout

Dimensions

1. Installation
Layout >
Overall dimensions H x W x D in mm
Unpacked cabinet On pallet cabinet
UPS cabinets in kVA
250 - 300 1900 x 1412 x 855 2027 x 1525 x 970
400 1900 x 1412 x 855 2027 x 1525 x 970
500 1900 x 1812 x 855 2027 x 1925 x 970
SSCs in kVA
800 1900 x 1012 x 855 2027 x 1125 x 970

Weights

1200 1900 x 1412 x 855 2027 x 1525 x 970
2000 1900 x 1412 x 855
2000 light 1900 x 1012 x 855 2027 x 1125 x 970
External bypass or SSC maintenance cabinets in kVA
800 1900 x 1012 x 855 2027 x 1125 x 970
1200 1900 x 1412 x 855 2027 x 1525 x 970
2000 1900 x 1412 x 855 2027 x 1525 x 970
Battery /auxiliary cabinets (mm width)
400 1900 x 412 x 855 2027 x 959 x 970
700 1900 x 712 x 855 2027 x 825 x 970
1000 1900 x 1012 x 855 2027 x 1125 x 970
1400 1900 x 1412 x 855 2027 x 1525 x 970
Weight values are purely indicative. See the packing labels for the precise weight of the equipment.
UPS cabinets SSC
1900 x 1012 x 855
2027 x 1525 x 970 2027 x 1125 x 970
Power rating in kVA 250 300 400 500 Power rating in kVA 800 1200 2000 2000 light
Max. weight in kg 960 960 1110 1470 Max. weight in kg 450 720 1430 600
External bypass cabinets or SSC maintenance cabinets
Power rating in kVA 800 1200 2000 Power rating in kVA 400 700 1000 1400
Max. weight in kg 340 450 700 Max. weight in kg 90 135 150 200
For more information on the weight of your system, see the Transport/storage/handling manual (doc. no. 34020840).
Auxiliary cabinets (empty)
34020846EN/AD - Page 13
1. Installation
Layout >

Floor mounting

Normal or false floor.
Dimensions are indicated in millimeters.

UPS cabinets

Top view
855
SSC
800 and 1200 kVA
Top view
250/300/400 kVA : 1412
500 kVA : 1812
250/300/400 kVA : 760
Cable-running zone
290
800 kVA : 1012 1200 kVA : 1412
500 kVA : 1280
Front
33.5
33.5
The four feet of the cabinet are cylindrical, 60
33.5
mm in diameter. The measurements opposite include the cabinet cover panels and the door.
33.5
Max. load on floor per square cm for the feet
UPS cabinet
kg/cm2
in kVA
250 9
300 9
400 10
500 13
69.5
Max. load on floor per square cm for the feet
SSCs in kVA kg/cm2
800 4
855
2000 kVA
855
Top view
Cable-running zone
Front
Cable-running zone
870
800 kVA : 1012 x 260 1200 kVA : 1280 x 260
69.5
2474
Cable-running
Front
1200 8
2000 15
2000 light 6
415 385
zone
415415
Cable-running
zone
33.5
33.5
69.5
34020846EN/AD - Page 14
2000 kVA light
.
1. Installation
Layout > Floor mounting
Top view
1012
855
Cable-running zone
430
870
Front

External bypass or SSC maintenance cabinets

800 and 1200 kVA
Top view
800 kVA : 1012 1200 kVA : 1412
33.5
33.5
33.5
69.5
33.5
Max. load on floor per square cm for the feet
External bypass or
kg/cm2 SSC maintenance cabinet in kVA
800 4
855
2000 kVA
855
Cable-running zone
Front
Top view
415 385
Cable-running
1412
415
zone
Front
800 kVA : 1012 x 260 1200 kVA : 1280 x 260
69.5
Cable-running
zone
33.5
1200 5
2000 8
33.
69
34020846EN/AD - Page 15
1. Installation
Layout > Floor mounting

Auxiliary cabinets (empty)

Top view
855

Backfeed cabinet

Top view
400 : 412 700 : 712 1000 : 1012 1400 : 1412
Cable-running zone
Front
33.5
412
33.5
33.5
33.5
400 mm : 278 x 679 700 mm : 578 x 679 1000 mm : 878 x 679 1400 mm : 1278 x 679
69.5
Max. load on floor per square cm for the feet
Auxiliary
kg/cm2 cabinet in mm
400 0,9
700 1,2
1000 1,3
1400 1,8
855
281
Front
382
Cable-running zone
69.5
34020846EN/AD - Page 16

Position in room

UPS cabinets

The UPS must be installed in a room with restricted access (qualified personnel only).
>500 mm
1. Installation
Layout >
To ensure correct ventilation, leave nothing
on top of the UPS.
Leave one meter of free space in front of the UPS for door opening.

SSCs

>600 mm
>300 mm
>600 mm
>1000 mm
Layout example for an SSC with two parallel UPS units
1 2 3 4 5 6 7
The cabinet rests on four cylindrical feet, 60 mm in diameter, positioned in the four corners of the cabinet to spread the weight.
If 500 mm of free space is not maintained above the UPS, abnormal temperature rise may occur.
The UPS can operate correctly back to the wall, but it is preferable to leave some space for easier maintenance.
The distance between the bottom panel and the floor must be less than 10 mm.
Auxiliary cabinet 2 (1) Battery cabinet 2 (2) UPS2 cabinet (3) Auxiliary cabinet 1 (4) Battery cabinet 1(5) UPS1 cabinet (6)
SSC (7)

External bypass cabinets

Layout example for an external bypass cabinet with three UPS units
1 2 3 4

Battery / auxiliary cabinets

Layout example for two battery cabinets with one UPS unit
Layout example for two battery cabinets and two auxiliary cabinets in a parallel system with an SSC
1 2 3 4 5 6 7
UPS1 cabinet (1) UPS2 cabinet (2) UPS3 cabinet (3)
External bypass cabinet (4)
Battery cabinet 1 (1)
321
Battery cabinet 2 (2) UPS cabinet (3)
Auxiliary cabinet 2 (1) Battery cabinet 2 (2) UPS2 cabinet (3) Auxiliary cabinet 1 (4) Battery cabinet 1 (5)
UPS1 cabinet (6) SSC (7)
34020846EN/AD - Page 17
1. Installation
Layout >

Ventilation

UPS cabinets

Power rating in kVA 250 300 400 500
Air flow (m³/h) 6000 6000 6000 8300
The optimum operating-temperature range is
20 to 25°C.
An operating temperature of 35°C is possible, but battery life will be reduced.
Size the ventilation system taking into account the values in the table below.
Heat losses to be evacuated at Pn

SSC cabinets

Power rating in kVA 800 1200 2000
Air flow (m³/h) 1000 Natural Natural
Heat losses to be evacuated at Pn
Pn = rated power, for other values please consult the after-sales support or the local office.
kW 14.3 17.2 22.9 27.2
Cal./s 3418 4111 5473 6501
kW 3.7 < 1 < 1.5
Cal./s 884 < 240 < 360
34020846EN/AD - Page 18

1.3 Prerequisites

UPS currents

1. Installation
Prerequisites >
UPS cabinets in kVA I rated of Normal
AC in A
250 351 361 361 490
300 420 433 433 588
400 558 577 577 784
500 700 722 722 980
The table above is for 400 V interphase voltages and a load with a power factor of 0.9. For other voltages (380 or 415 V), the current values must be multiplied by 1.05 and 0.96 respectively. The battery current is an average current for a battery voltage of 488 V (44 blocks at 1.85 V/cell each), at Pn with a power factor of 0.9.

Recommended upstream protection

Normal AC source

Stick a label with the following text on each upstream circuit breaker / switch-disconnector: "Isolate Uninterruptible Power Supply (UPS) before working on this circuit". Selection of protective devices is determined by the maximum continuous current (at 380 V). Protection ratings are calculated for the maximum continuous current (at 380V).
UPS cabinets in kVA CB / switch-disconnector Trip unit
250 NS 630N 3P * STR 23 SE
I rated of Bypass AC in A
I rated of load in A
I battery in A
300 NS 630N 3P * STR 23 SE
400 NS 800N 3P * Micrologic 2.0
500 NS 800N 3P * Micrologic 5.0
The circuit breakers / switch-disconnectors recommended above respect the requirements for discrimination with the UPS fuses.
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
* For short-circuit currents > 40 kA, use a CB/SD with a higher breaking capacity (type L or H).

Bypass AC source

Stick a label with the following text on each upstream circuit breaker / switch-disconnector: "Isolate Uninterruptible Power Supply (UPS) before working on this circuit". Selection of protective devices is determined by the maximum continuous current (at 380 V). Protection ratings are calculated for the maximum continuous current (at 380V).
UPS cabinets in kVA Maximum permissible
250 25 In NS 630N 4P * STR 23 SE
300 21 In NS 630N 4P * STR 23 SE
400 16 In NS 800N 4P * Micrologic 2.0
500 16 In NS 800N 4P * Micrologic 5.0
current for 20 ms
CB / switch­disconnector
Trip unit
The circuit breakers / switch-disconnectors recommended above respect the requirements for discrimination with the UPS fuses.
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
* For short-circuit currents > 40 kA, use a CB/SD with a higher breaking capacity (type L or H).
34020846EN/AD - Page 19
1. Installation
Prerequisites >

Recommended maximum downstream protection

If these recommendations are not followed, a short-circuit on an output circuit can result in a break in power longer than 20 milliseconds on all the other output circuits.
UPS cabinets in kVA CB / switch-
250 NS 100N
300 NS 100N
400 NS 100N
500 C125N
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
These protective devices ensure discrimination for each circuit downstream of the UPS, with or without a bypass AC input.

Battery protection

UPS cabinets in kVA Battery backup time at
disconnector
C120N C120N
C120N C120N
NG 125N C 125H
NS 160N NG 125N
Pn
Trip unit
TM D 80 C 80A B 125A
TM D 80 C 80A B 125A
TM D 100 C 125A C 125A
D 125A TM 160D D 125
Battery CB/switch-disconnector QF1
Typ e Trip unit magnetic setting in A
250 All NS630 DC MP1 1200
300 15 min.
> 15 min.
400 5 min.
> 5 min.
500 All C1251N DC P21 1600
Pn = rated power at a power factor of 0.9, for other values please consult the after-sales support or the local office.
See the necessary precautions during connection of circuit breakers / switch-disconnectors in the installation manual of the battery circuit-breaker enclosure, doc. no. 34021529.

Recommended residual-current protection

Requirements for residual-current protection.
For common normal and bypass AC inputs
- The same residual-current protection may be used for the two lines.
For separate normal and bypass AC inputs
- A transformer is required upstream of either the normal AC line or the bypass AC line.
- Equip each line with a circuit breaker or switch-disconnector with residual current protection.
See “System earthing arrangements”, page 24.
The recommended minimum residual current protection is 3A, provided the conditions defined in IEC364.4-41 are respected.
NS630 DC C1251N DC
NS630 DC C1251N DC
MP1 P21
MP1 P21
1200 1600
1200 1600
34020846EN/AD - Page 20

Characteristics of the connection terminals

Connections are made to terminals that are pre-drilled or equipped with studs. Earthing cables connect to the earthing bar.

UPS cabinets

Cabinets in kVA Phase terminal Earthing terminal Battery terminal
Type of stud Hole diameter in mm Hole diameter in mm Hole diameter in mm
250 M10 / 13 13
300 M10 / 13 13
400 M10 / 13 13
500 / 13 13 13

SSCs, SSC maintenance, External bypass cabinets

Cabinets in kVA Phase terminal Earthing terminal
Hole diameter in mm Hole diameter in mm
1. Installation
Prerequisites >
800 13 13
1200 13 13
2000 13 and 17 13

Power cables for single UPSs

AC cable sizes are determined for:
the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line voltage drop <3%, installed on perforated cable trays, XLPE-type insulation, single-layer trefoil formation, THDI between 15% and 33%, 35°C, at 400 V, grouped in four touching cables.
Battery cable sized are determined for: copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage drop <1%.
General case
Bypass AC
Normal AC
Frequency converter
Normal AC
UPS
UPS
Load
Load
UPS cabinets in kVA
250
300
400
500
Minimum size in mm²
Normal AC line
1x150 1x150 1x150 1x150
1x240 1x240 1x240 1x185
2x150 2x150 2x150 1x240
2x240 2x240 2x240 2x150
Bypass AC line
Load Battery
34020846EN/AD - Page 21
1. Installation
Prerequisites >

Power cables for parallel UPSs

AC cable sizes are determined for:
the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line voltage drop <3%, installed on perforated cable trays, XLPE-type insulation, single-layer trefoil formation, THDI between 15% and 33%, 35°C, at 400 V, grouped in four touching cables.
Battery cable sized are determined for: copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage drop <1%.
Important: the output cables must be at least 6 metres long (L 6m)

Normal AC line and battery

Bypass AC
Normal AC
Bypass AC
Normal AC
Bypass AC
Normal AC
UPS 1
UPS 2
UPS 3

Bypass AC line and load

Modular UPSs in parallel
Bypass AC
Normal AC
Bypass AC
Normal AC
1
Do not include redundant UPS units.
Power cables between the UPS units and the upstream protective devices must all be of the same size and length. Power cables between the UPS units and the load must all be of the same size and length.
UPS 1
UPS 2
UPS cabinets in kVA
L
L
L
Load
250
300
400
500
UPS
L
Load
L
cabinet s in kVA
250 2 250
300 2 300
400 2 400
500 2 500
Minimum size in mm²
Normal AC line Battery
1x150 1x150
1x240 1x185
2x150 1x240
2x240 2x150
Nbr of UPS
Total power
1
in kVA
rating
Current on AC bypass or load in A
s
361 1x150
433 1x240
577 2x150
722 2x240
Min. size for AC bypass or load in mm²
Frequency converters
34020846EN/AD - Page 22
Normal AC
UPS 1
L
Load
Normal AC
1
Do not include redundant UPS units.
UPS 2
L
UPS cabinets in
Nbr of UPSs
Total power
1
rating
in kVA
kVA
250 2 250
300 2 300
400 2 400
500 2 500
Load current in A Minimum size for
load in mm²
361 1x150
433 1x240
577 2x150
722 2x240
1. Installation
Prerequisites > Power cables for parallel UPSs
AC cable sizes are determined for:
the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line voltage drop <3%, installed on perforated cable trays, XLPE-type insulation, single-layer trefoil formation, THDI between 15% and 33%, 35°C, at 400 V, grouped in four touching cables.
Battery cable sized are determined for: copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage drop <1%.
Important: the output cables must be at least 6 metres long (L 6m)
Modular UPSs in parallel with external bypass cabinet
Bypass AC
Bypass cabinet
Normal AC
Normal AC
Normal AC
UPS 1
UPS 2
UPS 3
L
L
L
UPS cabinet in kVA
250 2
300 2
Load
400 2
500 2
1
Do not include redundant UPS units.
2
Standard NFC15-100 limits the number of cables to four.
Nbr of UPSs
3 4
3 4
3 4
3 4
Total power
1
rating
in
kVA
500 750 1000
600 900 1200
800 1200 1600
1000 1500 2000
Current on
AC bypass or
load in A
722
1083
1443
866
1300
1732
1154
1732
2308
1433
2165
2886
Min. size for AC bypass or load in mm²
2x185 3x300
4x240
2x240 4x240
4x300
4X185 4x300
4X500
4x240 4X500
Consult us
2
Power cables between the UPS units and the upstream protective devices must all be of the same size and length. Power cables between the UPS units and the load must all be of the same size and length.
Parallel UPSs with SSC (static-switch cabinet)
Bypass AC
Normal AC
Normal AC
Normal AC
UPS 1
UPS 2
UPS 3
L
L
L
SSC
UPS cabinet in kVA
250 2
300 2
Load
400 2
500 2
1
Do not include redundant UPS units.
2
Standard NFC15-100 limits the number of cables to four.
Nbr of UPSs
3 4
3 4
3 4
3 4
Total power
1
in
rating kVA
500 750 1000
600 900 1200
800 1200 1600
1000 1500 2000
Current on AC bypass or load in A
722 1083
1443
866 1300
1732
1154 1732
2308
1433 2165
2886
Min. size for AC bypass or load in mm²
2x185 3x300
4x240
2x240 4x240
4x300
4x185 4x300
4X500
4x240 4X500
Consult us
2
34020846EN/AD - Page 23
1. Installation
System earthing arrangements >

1.4 System earthing arrangements

This section lists the main SEAs (system earthing arrangements) and their wiring requirements. For SEAs not listed here, please contact the technical-support department.

Single UPS system

TNS upstream, TNS downstream

For separate normal and bypass AC lines from a single source.
Without residual-current protection
PE
PE
Load
PE
Bypass AC
Normal AC
L1 L2 L3 N
L1 L2 L3
PFC
SS
INV
L1 L2 L3 N
UPS
MLVS
UPS units used as frequency converters: please contact your technical assistance
With residual-current protection
Galvanic isolation between the normal and bypass AC lines is mandatory. The recommended minimum residual current protection is 3A, provided the conditions defined in IEC364.4-41 are respected.
For a transformer on a Bypass AC network
PE
PE Load
PE
Bypass AC
L1 L2 L3 N
PFC
SS
INV
L1 L2 L3 N
34020846EN/AD - Page 24
Normal AC
(4p)
MLVS
L1 L2 L3
UPS
For a transformer on a Normal AC network
MLVS
PE
Bypass AC
Normal AC
PE
L1 L2 L3 N
L1 L2 L3
PFC
SS
INV
L1 L2 L3 N
PE Load
Adding a transformer into the Normal AC network reduces the installation’s overall yield.

TNC upstream, TNC, TNS or TT downstream installation

For separate normal and bypass AC lines from a single source.
It is essential to transform the UPS internal PE bar into a PEN bar, See “Adapting the cabinet according to the neutral point connection”, page 26. For an installation with a SSC cabinet or an external bypass cabinet, it is essential to transform the cabinet's internal PE bar into a PEN bar, See “Adapting the cabinet according to the neutral point connection”, page 26.
Unit or modular UPS
The UPS output neutral must be connected to the internal PEN bar (1)
Parallel UPS with SSC cabinet or modular UPSs with external bypass cabinet:
The SSC cabinet output neutral or external bypass cabinet output neutral must be connected to the internal PEN bar for this cabinet. The connection between the UPS outputs and the SSC cabinet or the external bypass cabinet must be done in TNC (connect the PEN cable to the PEN bar).
The load neutral terminal on the UPS, SSC or external bypass cabinet must not be used. The SLT downstream TNS or TT starts on the MGE ™ Galaxy™ 7000 installation output.
1
Q4S
L1 L2
Bypass AC
PEN
NP
L3 N
PFC
PEN
SS
INV
1. Installation
System earthing arrangements >
PE or PEN
L1 L2 L3
NP:Not Provided
N
Load
PEN
MLVS

IT upstream, IT downstream

For separate normal and bypass AC lines from a single source.
R1
IMD
CPI1
MLVS
Normal AC
Bypass AC
R2
Normal AC
L1 L2 L3
PE
L1 L2 L3 N
PFC
L1 L2 L3
SS
UPS
INV
UPS
PE
L1 L2 L3 N
IMD2
CPI2
Load
In normal operating mode
The CPI1 controls the whole installation including downstream from the UPS. Power to the CPI2 is switched off by the R2 relay which controls voltage presence upstream from the UPS.
If the voltage is cut or the protection is opened upstream:
The R1 relay cuts the CPI1 circuit and the R2 relay closes the CPI2 circuit thus maintaining control downstream of the UPS.

Parallel UPSs systems

Earthing system adaptations are the same as those previously detailed for unitary UPS.
34020846EN/AD - Page 25
1. Installation
Adapting the cabinet according to the neutral point connection >

1.5 Adapting the cabinet according to the neutral point connection

UPS cabinet

This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key. The protective covers must be removed.
For IT,TNS or TT (PE) upstream system
1. Disconnect and remove the joiner
(1) on the earthing bar.
For TNC (PEN) upstream, TNC, TNS or TT downstream system
1. Disconnect and remove the joiner (1) on the earthing bar.
2. Install the joiner as shown opposite.
1

SSC cabinet or external bypass cabinet

This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key. The protective covers must be removed.
OFF
OFF
OFF
PENPEN
2
(2) Inverter neutral (N)
For IT,TNS or TT (PE) upstream system
1. Disconnect and remove the joiner
(1) on the earthing bar.
For TNC (PEN) upstream, TNC, TNS or TT downstream system
1. Disconnect and remove the joiner (1) on the earthing bar.
2. Install the joiner (1) as shown opposite.
34020846EN/AD - Page 26
2
1
(2) SSC neutral (N)

1.6 Connecting the power cables

Dimensions are indicated in millimeters. For parallel installations with no neutral on the load and network, interconnect the UPS neutrals.

Single or modular UPS cabinet

250 to 400 kVA

Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1. Installation
Connecting the power cables >
Key
1
8
2
3 4 5 7
6
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1 Q4S Q3BP Q5N
OFF OFF OFF OFF
L1 L2 L3
+
N L1 L2 L3 N L1 L2 L3
-
(1) Protective covers (2) Tie bar (3) To normal AC line (4) To the batteries (5) To bypass AC line (6) To earth (7) To the load (8) Earthing bar
1. Remove the protective covers (1).
1. Check that switches Q1, Q4S, Q3BP and Q5N are in the OFF position as shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the normal AC conductors taking care to respect the order, L1, L2, L3.
470
410
350
260
Normal AC Bypass ACBattery Load
Earth
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26. Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
4. Connect the bypass AC conductors taking care to respect the order, N*, L1, L2, L3.
390
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Connect the battery.
7. Tie the cables down.
8. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
9. Put the protective covers back in place.
34020846EN/AD - Page 27
1. Installation
Connecting the power cables > Single or modular UPS cabinet

500 kVA

Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1
8
8
2
4 5 73
6
Key
(1) Protective covers (2) Tie bar (3) To normal AC line (4) To the batteries (5) To bypass AC line (6) To the earth (7) To the load (8) Earthing bar
1. Remove the protective covers (1).
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1 Q4S Q3BP Q5N
OFF OFF OFF OFF
N L1 L2 L3 N L1 L2 L3L1 L2 L3
-
+
360
Normal AC Bypass ACBattery Load
Earth
260
1. Check that switches Q1, Q4S, Q3BP and Q5N are in the OFF position as shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the normal AC conductors taking care to respect the order, L1,
390
L2, L3.
4. Connect the bypass AC conductors taking care to respect the order, N*, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Connect the battery.
7. Tie the cables down.
34020846EN/AD - Page 28
8. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
9. Put the protective covers back in place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.

Frequency-converter cabinet

250 to 400 kVA

In parallel systems, switches Q4S and Q3BP are absent.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1
1. Installation
Connecting the power cables >
Key
(1) Protective covers (2) Tie bar (3) To normal AC line (4) To the batteries (5) Earthing bar (6) To the earth (7) To the load
2
3 4 75
6
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1 Q5N
OFF OFF
-
+
470
410
350
1. Remove the protective covers (1).
1. Check that switches Q1 and Q5N are in the OFF position as shown opposite.
N L1 L2 L3L1 L2 L3
2. Connect the normal AC neutral to the load neutral.
3. Connect the protective conductor (PE or PEN) to the earth bar.
4. Connect the normal AC conductors taking care to respect the order, L1, L2, L3.
5. Connect the load conductors taking
390
care to respect the order, N*, L1, L2, L3.
260
6. Connect the battery.
7. Tie the cables down.
Normal AC Battery Earth Load
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
8. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
9. Put the protective covers back in place.
34020846EN/AD - Page 29
1. Installation
Connecting the power cables > Frequency-converter cabinet

500 kVA

In parallel systems with an SSC, switches Q4S and Q3BP are absent. The AC bypass connection is made in the SSC.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1
Key
(1) Protective covers (2) Tie bar (3) To normal AC line (4) To the batteries (5) Earthing bar (6) To the earth (7) To the load
1. Remove the protective covers (1).
2
3 4 5 76
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1 Q5N
OFF OFF
L1 L2 L3
360
Normal AC Battery Earth Load
-
+
N L1 L2 L3
260
1. Check that switches Q1 and Q5N are in the OFF position as shown opposite.
2. Connect the normal AC neutral to the load neutral.
3. Connect the protective conductor (PE or PEN) to the earth bar.
390
4. Connect the normal AC conductors taking care to respect the order, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Connect the battery.
34020846EN/AD - Page 30
7. Tie the cables down.
8. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
9. Put the protective covers back in place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.

Parallel UPS cabinet

250 to 400 kVA

In parallel systems with an SSC, switches Q4S and Q3BP are absent. The AC bypass connection is made in the SSC.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1. Installation
Connecting the power cables >
Key
1
(1) Protective covers (2) Tie bar (3) To normal AC line (4) To the batteries (5) Earthing bar (6) To the earth (7) To the load
2
3 4 75
6
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1 Q5N
OFF OFF
-
+
470
410
350
Normal AC Battery Earth Load
1. Remove the protective covers (1).
1. Check that switches Q1 and Q5N are in the OFF position as shown opposite.
N L1 L2 L3L1 L2 L3
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the normal AC conductors taking care to respect the order, L1, L2, L3.
4. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
390
5. Connect the battery.
6. Tie the cables down.
260
7. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
8. Put the protective covers back in place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
34020846EN/AD - Page 31
1. Installation
Connecting the power cables > Parallel UPS cabinet

500 kVA

In parallel systems with an SSC, switches Q4S and Q3BP are absent. The AC bypass connection is made in the SSC.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1
Key
(1) Protective covers (2) Tie bar (3) To normal AC line (4) To the batteries (5) Earthing bar (6) To the earth (7) To the load
1. Remove the protective covers (1).
2
3 4 5 76
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1 Q5N
OFF OFF
L1 L2 L3
360
Normal AC Battery Earth Load
-
+
N L1 L2 L3
260
1. Check that switches Q1 and Q5N are in the OFF position as shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the normal AC conductors taking care to respect the order, L1,
390
L2, L3.
4. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
5. Connect the battery.
6. Tie the cables down.
34020846EN/AD - Page 32
7. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
8. Put the protective covers back in place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.

SSC cabinet

800 kVA

1. Installation
Connecting the power cables >
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Right-hand view
2 2
Connection through the bottom
Top view
1 1
3
Front view
Front view
5
5
4
OFF
OFF
OFF
A
Key
(1) Front protective covers (2) Roof protective covers (3) Earthing bar (4) To the earth (5) To the UPSs* (6) To bypass AC line (7) To the load
Connections through the top of the UPS cabinets are possible using an auxiliary cabinet 400 mm wide.
6
1. Remove the protective covers (1) and/or (2).
7
*Or to the SSC maintenance cabinet, See “SSC maintenance cabinet”,
6
7
A
page 42.
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q4S
533
N L1 L2 L3
Earth
UPSs
OFF
Q3BP
OFF
Q5N
OFF
Bypass
AC
N L1 L2 L3
N L1 L2 L3
Load
1060
860
533
** SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
1. Check that switches Q4S, Q3BP and Q5N are in the OFF position as shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the UPS conductors taking care to respect the order, N**, L1, L2, L3.
4. Connect the bypass AC conductors taking care to respect the order, N**, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N**, L1, L2, L3.
6. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
7. Put the protective covers back in place.
34020846EN/AD - Page 33
1. Installation
Connecting the power cables > SSC cabinet

1200 kVA

Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Right-hand view
Top view
1
Connection through the top Connection through the bottom
2
1
1
1
1
3
Front view
Front
view
5
4
OFF
OFF
OFF
A
A
766
6
7
7
Key
(1) Front protective covers (2) Roof protective covers (3) Earthing bar (4) To the earth (5) To the UPSs* (6) To bypass AC line (7) To the load
Connections through the top of the UPS cabinets are possible using an auxiliary cabinet 400 mm wide.
1. Remove the protective covers (1) and/or (2).
*Or to the SSC maintenance cabinet.
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q4S
OFF
N L1 L2 L3
Q3BP
OFF
N L1 L2 L3
Q5N
AC
559
N L1 L2 L3
UPSs Bypass Load
Earth
OFF
807
1270
1. Check that switches Q4S, Q3BP and Q5N are in the OFF position as shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the UPS conductors taking care to respect the order, N*, L1, L2, L3.
4. Connect the bypass AC conductors taking care to respect the order, N*, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
7. Put the protective covers back in place.
34020846EN/AD - Page 34
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.

2000 kVA

You must have first assembled both cabinets.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Right-hand view
Front view
1 1
Front view
1. Installation
Connecting the power cables > SSC cabinet
A
6
7
1
Connection through the top
Connection through the bottom
Key
(1) Front protective covers (2) Roof protective covers (3) Earthing bar (4) To the earth (5) To the UPSs* (6) To bypass AC line (7) To the load
Top view
OFF
2 2
OFF
3
54
6
OFF
7
A
*Or to the SSC maintenance cabinet, See “SSC maintenance cabinet”, page 42.
1. Remove the protective covers (1) and/or (2).
34020846EN/AD - Page 35
1. Installation
Connecting the power cables > SSC cabinet > 2000 kVA
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
L1 L3 N L2
Q4S
OFF
Q3BP
OFF
L2 L3L1 N
Q5N
1270
N L1 L2 L3
OFF
940
500
Earth
UPSs
Bypass AC
Load
1. Check that switches Q4S (1), Q3BP (2) and Q5N (3) are in the OFF position as shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the UPS conductors taking care to respect the order, N*, L1, L2, L3.
4. Connect the bypass AC conductors taking care to respect the order, N*, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
7. Put the protective covers back in place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
34020846EN/AD - Page 36

2000 kVA light

Remove the protective covers
This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Right side view
Front view
1. Installation
Connecting the power cables > SSC cabinet
A
6
Front view
1
4
3
Top entry
Bottom entry
Key:
(1) Front face protective covers (2) Roof protective covers (3) Earth bar (4) UPS current sensor terminal block (5) To Earth (6) To AC Bypass (7) To the load
Top entry is possible by using a 400mm wide auxiliary cabinet.
1 - Remove protective covers (1) and (2).
75
Top view
2
A
34020846EN/AD - Page 37
1. Installation
Connecting the power cables > SSC cabinet > 2000 kVA light
Connect the cables
This operation may only be carried out by authorized staff.
See “Characteristics of the connection terminals”, page 21.
Load
1700
N L1 L2 L3
530
Earth
AC Bypass
1 -Check customer switches Q4S, Q3BP and Q5N are in the OFF position
2 - Connect the protective conductor (PE or PEN) to the earth bar
Top view
N
L1
L3
L2
3 - Connect the AC Bypass conductors in the following order: N*, L1, L2, L3
4 - Connect the load conductors in the following order: N*, L1, L2, L3
5 - Connect the auxiliary wires ( See “Connect the components specific to the 2000 kVA light SSC”, page 50.)
6 - Refit the protective covers
* upstream earthing system TNC, downstream earthing system TNC, TNS or TT See “Adapting the cabinet according to the neutral point connection”, page 26.
34020846EN/AD - Page 38

External bypass cabinet

800 kVA

Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1. Installation
Connecting the power cables >
Right-hand view
Connection through the top
Connection through the bottom
Top view
2 2
1 1
3
Front view
Front view
5
5
4
OFF
OFF
A
6 7
Key
(1) Front protective covers (2) Roof protective covers (3) Earthing bar (4) To the earth (5) To the UPSs (6) To bypass AC line (7) To the load
1. Remove the protective covers (1) and/or (2).
Q1 Q4S Q3BP Q5N
The handle of the Q3BP switch (in
6
7
A
the OFF position) on all UPS units must be removed.
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
1. Check that switches Q3BP ext and Q5N ext are in the OFF position as
N L1 L2 L3
Q3BP
ext
N L1 L2 L3
OFF
Q5N
ext
N L1 L2 L3
1060
860
608
UPSs Bypass Load
Earth
OFF
533
AC
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the UPS conductors taking care to respect the order, N*, L1, L2, L3.
4. Connect the bypass AC conductors taking care to respect the order, N*, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Put the protective covers back in place.
34020846EN/AD - Page 39
1. Installation
Connecting the power cables > External bypass cabinet

1200 kVA

Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Right-hand view
Top view
2 2
1
1
1
Connection through the top
Connection through the bottom
Key
(1) Front protective covers
5
Front view
A
766
(2) Roof protective cover (3) Earthing bar (4) To the UPSs (5) To bypass AC line (6) To the load
1. Remove the protective covers (1)
6
and/or (2).
1
1
Front
1
view
1
OFF
7
Q1 Q4S Q3BP Q5N
OFF
3
The handle of the Q3BP switch (in the OFF position) on all UPS units
5
4
7
must be removed.
A
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
1. Check that switches Q3BP ext (1) and Q5N ext (2) are in the OFF position as shown opposite.
N L1 L2 L3
Q3BP
ext
N L1 L2 L3
Q5N
ext
1270
807
N L1 L2 L3
OFF
OFF
559
UPSs Bypass Load
Earth
AC
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the UPS conductors taking care to respect the order, N*, L1, L2, L3.
4. Connect the bypass AC conductors taking care to respect the order, N*, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Put the protective covers back in place.
34020846EN/AD - Page 40

2000 kVA

Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1. Installation
Connecting the power cables > External bypass cabinet
Right-hand view
Front
view
1 1
Top view
2 2
3
Connection through the top
Connection through the bottom
A
6
7
Front view
Key
(1) Front protective covers (2) Roof protective covers (3) Earthing bar (4) To the earth (5) To the UPSs (6) To bypass AC line (7) To the load
1. Remove the protective covers (1)
OFF
and/or (2).
OFF
3
Q1 Q4S Q3BP Q5N
The handle of the Q3BP switch (in the OFF position) on all UPS units
6
7
A
must be removed.
45
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
1550
650
N L1 L2 L3
Earth
L3L1 N L2
UPSs Bypass
AC
Q3BP
ext
OFF
Q5N
ext
OFF
N
L1 L2 L3
Load
1230
1. Check that switches Q3BP ext (1) and Q5N ext (2) are in the OFF position as shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the UPS conductors taking care to respect the order, N*, L1, L2, L3.
4. Connect the bypass AC conductors taking care to respect the order, N*, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Put the protective covers back in place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”, page 26.
34020846EN/AD - Page 41
1. Installation
Connecting the power cables >

SSC maintenance cabinet

800 and 1200 kVA

Remove the protective covers
This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Right side view
Top view
2 2
5
Front view
l Key:
A
766
(1) Front face protective covers (2) Roof protective cover (3) Earth bar (4) To Earth (5) To the load (6) To the SSC (7) To the UPS
1
1
Front
1
1
1
view
1
.
1
3
5
Top entry
4
Bottom entry
Connect the cables
This operation may only be carried out by authorized staff.
See “Characteristics of the connection terminals”, page 21.
N L1 L2 L3
Q3BP
ext
N L1 L2 L3
Q5N
ext
559
N L1 L2 L3
OFF
OFF
OFF
OFF
807
1270
6
1 - Remove protective covers (1) and/ or (2).
7
7
A
1 -Check switches Q3B ext (1) and Q5N ext (2) are in the OFF position as shown opposite.
2 - Connect the protective conductor (PE or PEN) to the earth bar
3 - Connect the UPS conductors in the following order: L1, L2, L3
4 - Connect the AC Bypass conductors in the following order: L1, L2, L3
5 - Connect the load conductors in the following order: L1, L2, L3
6 - Refit the protective covers
34020846EN/AD - Page 42
Load NS UPSEarth

2000 kVA

1. Installation
Connecting the power cables > SSC maintenance cabinet
This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Right side view
Top entry
Bottom entry
Front view .
3
1 1
Top view
2 2
Key:
(1) Front face protective covers (2) Roof protective covers
6
Front view
A
7
(3) Earth bar (4) To Earth (5) To the load (6) To the SSC (7) To the UPS
1 - Remove protective covers (1) and/
OFF
or (2).
OFF
3
6
7
45
A
Connect the cables
This operation may only be carried out by authorized staff.
See “Characteristics of the connection terminals”, page 21.
L3L1 N L2
1550
N L1 L2 L3
650
Q3BP
ext
OFF
Q5N
ext
OFF
N
L1 L2 L3
1230
1 -Check switches Q3BP ext (1) and Q5N ext (2) are in the OFF position as shown opposite.
2 - Connect the protective conductor (PE or PEN) to the earth bar
3 - Connect the UPS conductors in the following order: L1, L2, L3
4 - Connect the AC Bypass conductors in the following order: L1, L2, L3
5 - Connect the load conductors in the following order: L1, L2, L3
6 - Refit the protective covers
Load NS UPS Earth
34020846EN/AD - Page 43
1. Installation
Connecting cabinet ECPs (exposed conductive parts) >

1.7 Connecting cabinet ECPs (exposed conductive parts)

Valid for UPS, external-bypass, SSC and battery cabinets

Interconnect the earths and tie down the wires

This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key. The protective covers must be removed.
Connect the ECPs of all the cabinets in the installation using an additional earthing cable (not supplied) with the characteristics below.
- Minimum size is half that of a phase earthing conductor, same type of cable as for phase conductors.
- As short as possible.
Cabinet 1
Main earth
Cabinet 2
Additional earthing cable between cabinets

1.8 Connecting the synchronization module

Refer to the “synchronization module installation manual" no. 34000346
Cabinet 3
34020846EN/AD - Page 44

1.9 Connect the backfeed option

The backfeed option is compulsory if IEC 62040-1-2 is to be complied with.

Block diagram

1. Installation
Connect the backfeed option >
Normal AC Normal AC

Connect the power cables

This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Right side view
Backfeed
Front view
UPS
A
Front view
1
740
590
423 5
Key:
(1) Front face protective cover (2) Earth Bar (3) To Earth (4) To AC Normal (5) To the UPS
1 - Remove protective cover (1) 2 - Connect the protective conductor (PE or PEN) to the earth bar (2) 3 - Connect the AC Normal conductors in the following order: L1, L2, L3 (4) 4 - Connect the UPS conductors in the following order: L1, L2, L3 (5) 5 - Refit the protective cover
A
34020846EN/AD - Page 45
1. Installation
Connecting the control-wire cables >

1.10 Connecting the control-wire cables

The maximum total length of CAN inter-cabinet cables must not exceed 180m.

Connecting a modular UPS or frequency converter alone.

This operation must be carried out by qualified personnel.
The door must be open.
Key
XM2
XM3
XM4
XM5
XM6
XM2
XM3
XM4
XM5
XM6
XM7
1
(1) Connectors
1. Fit a blue plug on connector XM06 in the UPS.
2. Fit a red plug on connector XM7 in the UPS.
1
XM7
2
34020846EN/AD - Page 46

Connecting the UPS units in parallel

Connecting the modular UPS units in parallel

This operation must be carried out by qualified personnel.
The door must be open. The supplied cables are 10 or 20 m long; The maximum total length must not exceed 180m. On exiting the cabinet, the cables must run along the earthing and connection cables between cabinets.
1. Installation
Connecting the control-wire cables >
Key
2
3
2
2
Example for two UPSs
UPS 1
XM2
XM3
XM6
2
XM2
XM3
XM4
XM5
XM6
XM7
1
(1) Connectors (2) Cable ties (3) Exchange-current and CAN cables
Exchange current
1. Connect the XM2 and XM3
UPS 2
1
1
XM2
XM3
connectors in the two UPS units.
CAN
2. Fit a blue plug on connector XM6 in UPS1.
3. Connect XM7 in UPS1 to XM6 in UPS2.
4. Fit a red plug on connector XM7 in UPS2.
XM6
XM7
3
4
XM7
34020846EN/AD - Page 47
1. Installation
Connecting the control-wire cables > Connecting the UPS units in parallel

Connecting the modular UPSs with the external bypass

This operation must be carried out by qualified personnel.
The door must be open. The supplied cables are 10 or 20 m long; The maximum total length must not exceed 180m.
To ensure sufficient isolation of exchange-current, CAN and external-bypass cables, they must be run separately from the power cables.
On exiting the cabinet, the cables must run along the earthing and connection cables between cabinets.
Q1 Q4S Q3BP Q5N
UPS cabinet
2
3
2
2
Bypass cabinet
3 2 2
2
XM2
XM3
XM4
XM5
XM6
XM7
1 2 3 4 5 6
1
COM Q3BP ext
Q5N ext
The handle of the Q3BP switch (in the OFF position) on all UPS units must be removed.
Key
(1) Connectors (2) Cable ties
1
1
(3) Exchange-current, CAN and control-wire cables
Key
(1) Connectors (2) Cable ties (3) Control-wire cables
UPS 1
XM2
XM3
XM4
XM5
XM6
XM7
External
3
bypass cabinet
UPS 2
2
UPS 3
2 2 2
4 4 4
1
1 2 3
COM Q3BP ext
XM 4 / XM 5
Q5N ext
Q5N customer
Q3BP ext COM
4 5
Q5N ext
6
1
UPS 4
XM2
XM3
XM5
XM6
XM7
XM7
4
1
Connection with bypass cabinet Control wires
1. Connect the common, Q3BP ext and Q5N ext terminals on the terminal block in the external bypass cabinet to connector XM4 in UPS4 and XM5 in UPS1 (cables not supplied).
Exchange current
2. Create a loop between the XM2 and XM3 connectors in the four UPS units. All the connectors must be used.
CAN
3. Fit a blue plug on connector XM6 in
5
UPS1.
4. Interconnect the XM6 and XM7 connectors in the four UPS units.
5. Fit a red plug on connector XM7 in UPS4.
34020846EN/AD - Page 48
Connecting the control-wire cables > Connecting the UPS units in parallel

Connecting parallel UPSs with SSC (static-switch cabinet)

This operation must be carried out by qualified personnel.
The door must be open. The supplied cables are 10 or 20 m long; The maximum total length must not exceed 180m.
To ensure sufficient isolation of exchange-current and CAN cables, they must be run separately from the power cables.
On exiting the cabinet, the cables must run along the earthing and connection cables between cabinets.
UPS cabinet
1. Installation
Key
2
3
2
2
SSC
2
2
2
3
2
XM2
XM3
XM4
XM5
XM6
XM7
XM2
XM3
XM4
XM5
XM6
XM7
(1) Connectors (2) Cable ties (3) Exchange-current and CAN cables
1
Key
(1) Connectors (2) Cable ties (3) Exchange-current and CAN cables
1
UPS 1 UPS 2 UPS 3 UPS 4
XM2
XM3
XM4 XM4
XM5
XM6
XM7
1 1 1 1
2
3 3 3 3
1
XM 4 / XM 5
Q5N ext
Q5N customer
Q3BP ext COM
4
1
XM 4 / XM 5
Q5N ext Q4S ext Q3BP ext COM
SSC
XM2
XM3
XM5
XM6
XM7
XM7
Exchange current 1 Create a loop between the XM2 and
XM3 connectors in the four UPS units and the SSC. All the connectors must be used.
CAN
2. Fit a blue plug on connector XM6 in UPS1.
3. Interconnect the XM6 and XM7 connectors in the four UPS units and the SSC.
4. Fit a red plug on connector XM7 in the SSC.
4
4
1
34020846EN/AD - Page 49
1. Installation
Connecting the control-wire cables > Connecting the UPS units in parallel

Connect the components specific to the 2000 kVA light SSC

This operation may only be carried out by authorized staff.
The door must be open The cables (not supplied) must be twisted pairs of AWG18 gauge wire with a maximum length of 100m.
Auxiliary wires (exchange, CAN) and power cables must be separated to ensure sufficient insulation for the auxiliary wires.
Once outside the cabinet, the cables must follow the earth connections between the cabinets.
1
Key:
(1) UPS current sensor terminal block
Suitable current sensors must be used to ensure correct operation of the installation. Please contact your technical helpline to select the correct customer current sensors. Recommendations: 4000/1 CT, class 1, 10 VA
Take care to respect polarity when wiring customer current sensors.
2000 light NS cabinet
Terminal block
P1
4
{
5
{
6
{
1 - Connect the terminal block connectors to the customer current sensors in the customer connection panel.
For the installation to operate properly, the following must be respected:
Customer switches Q4S, Q3BP and Q5N must be electrically wired to behave like those of a SSC that contains switches. The auxiliary contact of a customer switch must be a normally open contact when the switch is open.
1
P2
2
P1
3
P2
4
P1
5
P2
6
P1
P2
1
P1
P2
2
P1
P2
3
Key:
(1) Current sensor TI7 - Phase 1 (2) Current sensor TI8 - Phase 2 (3) Current sensor TI9 - Phase 3 (4) To the customer connection panel
- phase 1 customer current sensor (5) To the customer connection panel
- phase 2 customer current sensor (6) To the customer connection panel
- phase 3 customer current sensor

Connect the SSC maintenance cabinet

34020846EN/AD - Page 50
There are no auxiliary wire connections to be made on the SSC maintenance cabinet.

Connecting the EPO function

This operation must be carried out by qualified personnel.
The door must be open. The moving door must be open. The cables (not supplied) must have SELV insulation and the maximum size is 2.5 mm².
To ensure sufficient isolation of control-wire (EPO) cables, they must be run separately from the power cables.
2 3 2
1. Installation
Connecting the control-wire cables >
Key
XM14
XM12
XM10
XM8
XB1
R29
R54
R116 R94 R57
HE1
PT1
C16
VZ5
C15
C10
C14
C12
C13
PT3
C11
PT2
C9
C4
XM9
R32
R28
R25
R31 R27 R26
R30
ET1
R24
R23
XM7
EH1
C3
C7R7C8
NR1
XB2
R2 VT1 R1 C2
VD1
R6
R138
R5
C6
L1
R4
R157 R154 R156
XM5
C5
R159
R155
R158
XM2
XM1
XM3
R11
NR2
C33 R148
R146
VZ1
R10
VD15
C17
R137
R147
C1
VP1
R8
R3
NR3
R9
XM21
XB3
XM25
XB4
R115
R53
R56
R93
R52
R114 R92 R55
VZ6
VZ7
C24
R113
R91
XM11
R112
R90
VZ8
VZ9
VZ10
R111
R89
XM15
R38
R105
R107
R109
R37
XM13
R36
R108
R110
R106
R35
R51
R136
R132
R134 R34 R33
R131R133
R135
R63
R59
R61
XM16
R50
R62
R60
R58
VD5
VD14
1
R49
VD13
XM17XM18
XM22
R22
R88
R79
R104
R87
R78
R103
R77
R102
R86
XB5
R76
R101
R85
1
R75R74
R100
R99
R83R84
R42
R44
VD8
VD6
VD7
XM6
VD4
C23
R73
R72
R127
VT2
R43
VP7
R39
R41
R152
R126
XM24
R125
R46
R45
R71
VP6
VD12
XM4
R48
C20
R124 R123
DI1
VD11
R70
R47
VP5
R122
C19
VD3
VD2
R97
R20
VT3
R98
R96
R15
R82
C32
R121
C18
R69
R81
R19
C22
XM23
K2
VP3
K1
VP4
VP2
R139
R140
VZ4
VD10
R18
R120
VZ11
R80
R95
R12
R66
R68
C21
R17
R14
R65
R119
R142
R118
L2
R67
R143
R16
R64
R13
R117
L3
XM20
XB6
XM19
(1) Connectors (2) Cable ties (3) Cables
Caution.
In the UPS or the SSC, the general shutdown causes UPS shutdown and opening of the battery circuit breaker (with opening of the bypass static switch depending on personalisation settings). The Emergency Power Off (EPO) notion is applicable to installations where pressing the button also causes the circuit breakers on the upstream normal AC source and bypass AC source to open. In parallel configurations, there must be a single general shutdown button with a separate contact for each UPS unit.
1. Remove the jumper on the XM19
1
terminal block (1).
2. Connect the general shutdown NC
XM 20XM 21XM 25
XM 19
contact to terminals 1 and 2 (SELV).
1111
3. Tie the cable down as illustrated.
34020846EN/AD - Page 51
1. Installation
Connecting the control-wire cables >

Connecting the dry-contact communication card

This operation must be carried out by qualified personnel.
The door must be open. The cables (not supplied) must have SELV insulation.
To ensure sufficient isolation of control-wire (contact signal) cables, they must be run separately from the power cables.
2 2
3
2
2
Key
(1) Connectors (2) Cable ties
ET1
L8 C23 R35
C22 L4 L3
C6
L7
VD4
R23
R34
C7
R31
R15
XM4
C21
VP4
XM4
L6
VD3
R14
R22
R32
C16
R29
R13
1
C20
VP3
L5
VD2
R12
R28
R21
C15
R25
R11
C19
VP2
VD1
R10
R26
R20 C14 R9
VP1 R8 C13
R19
XM1
R7
R18
R6
DI2
R5
R17
C12
K6
DI1 C11 C10
XM3
XM3
K5
C18
K4
K3
C5 L2 C4 C2
C9
C17
XM5
L1
K2
C3
XM2
C8
XM2
C1
K1
EP1
(3) Cables
XM 4
XM 3
XM 2
Maximum characteristics of the input
1
IN4
I4
9 V IN3
I3
9 V IN2
9 V IN1 9 V
I2
I1
1
contacts (1)
Switched voltage: 9 V DC (supplied by the UPS) Consumption: 20 mA Cable: 4 x 0.34 mm², diameter 5 ± 0.5 mm
In installations with parallel devices, the input contacts must be unique and include
1
OUT6 COM6
O6
OUT6 OUT5
O5
COM5 OUT5
OUT4
O4
COM4 OUT4
1
OUT3 COM3
O3
2
OUT3 OUT2
O2
COM2
device.
Maximum characteristics of the output contacts (2)
Permissible voltage: SELV only Permissible current 1 A at 30 V DC Cable: 4 x 0.93 mm², diameter 6.6 ± 0.3 mm
The dry contacts can be configured, see "Dry-contact parameters" in user manual no. 3402084700.
OUT2 OUT1
O1
COM1 OUT1
a separate contact for each
34020846EN/AD - Page 52
Assembling and connecting the external battery cabinet >

1.11 Assembling and connecting the external battery cabinet

Assembling the empty battery cabinet

Mounting the battery circuit-breaker kit

Please contact our Sales department when selecting the battery circuit breaker. Only one circuit breaker is necessary even if there are several battery cabinets.
1. Secure the plate.
1. Installation
x4
1
XR1
1 2 3
XR1
4 5
2
6
BC-
7
BC+
8
+12V
9
-12V
10
2. Secure connector XR1.
3. Secure the temperature sensor.
3

Mounting the shelves

Assembly of the battery cabinet must be carried out by certified personnel (standard EN 50091-1-2). The minimum clearance between the top of battery cells and the next shelf is 150 mm.
1
1
1
1. Secure the corner supports (6 screws per support).
2. Install the shelf.
3. Secure the shelf with two screws in each corner.
2
3
3
34020846EN/AD - Page 53
1. Installation
Assembling and connecting the external battery cabinet > Connecting the power cables
4. Connect the control-wire cables (See “Connecting the control-wire cables”, page 55.).

Connecting the power cables

This operation must be carried out by qualified personnel.
The door must be open. The protective cover must be removed. The battery circuit breaker must be open.
1 2
x2
5
+
B +
-
B-
5. Secure the protective cover after connecting the batteries to the circuit breaker.
Key
(1) To the UPS cabinet (2) To the battery or auxiliary battery
cabinet 2
1. Connect the earthing conductor to the earthing bar in the battery cabinet(1).
2. Connect the positive conductor (+) to the positive terminal.
3. Connect the negative conductor (-) to the negative terminal.
4. Secure the protective cover after connecting the batteries to the circuit breaker.
34020846EN/AD - Page 54
For more information, see the "Battery circuit-breaker kit in a cabinet" installation manual no. 34021530.

Connecting the control-wire cables

Connecting the battery circuit breaker

This operation must be carried out by qualified personnel.
The UPS door must be open. The moving door of the UPS must be open. The cables (not supplied) must have SELV insulation and the maximum size is 2.5 mm².
UPS cabinet
2
2
1. Installation
Assembling and connecting the external battery cabinet >
Key
XM14
XM12
XM10
XM8
XB1
R29
R54
R116 R94 R57
HE1
PT1
C16
VZ5
C15
C10
C14
C12
C13
C11
PT3
PT2
C9
C4
XM9
R35
R32
R28
R25
R34
R31
R27
R33
R30
R26
ET1
R24
R23
XM7
R22
EH1
C3
C7R7C8
NR1
XB2
R2 VT1 R1 C2
VD1
R6
R138
R5
C6
L1
R4
R157 R154 R156
XM5
C5
R159
R155
R158
XM2
XM1
XM3
R11
NR2
C33
R148
R146
VZ1
R10
VD15
C17
R137
R147
C1
VP1
R8
R3
NR3
R9
R143
XM21
XB3
XM25
XB4
R115
R53
R56
R93
R52
R114 R92 R55
VZ6
VZ7
C24
R113
R91
R112
XM11
R90
VZ8
VZ9
VZ10
R111
R89
XM15
R38
R105
R107
R109
R37
XM13
R36
R108
R110
R106
R51
R136
R132
R134
R131R133
R135
R63
R59
R61
XM16
R50
R62
R60
R58
VD5
1
VD14
R49
VD13
XM17XM18
XM22
R88
R79
R104
1
R87
R78
R103
R77
R102
R86
XB5
R76
R101
R85
R75R74
R100
R99
R83R84
R42
R44
VD8
VD6
VD7
XM6
VD4
C23
R73
R72
R127
VT2
R43
VP7
R39
R41
R152
R126
XM24
R125
R46
R45
R71
VP6
VD12
XM4
R48
C20
R124 R123
DI1
VD11
R70
R47
VP5
R122
C19
VD3
VD2
R97
R20
VT3
R98
R96
R15
R82
C32
R121
C18
R69
R81
R19
C22
XM23
K2
VP3
K1
VP4
VP2
R139
R140
VZ4
VD10
R18
R120
VZ11
R80
R95
R12
R66
R68
C21
R17
R14
R65
R119
R142
R118
L2
R67
R16
R64
R13
R117
L3
XM20
XB6
XM19
(1) Connectors (2) Cable ties (3) To the battery circuit breaker
3
Connecting a single battery circuit breaker
XM 25
XM 19XM 20XM 21
Connecting two battery circuit breakers
XM 25
3
XM 19XM 20XM 21
112345678910
12
Connecting three battery circuit breakers
1. Connect the UPS to the battery circuit breaker in the auxiliary cabinet as per the diagram opposite.
1111234
2. Tie down the cable as shown in the UPS-cabinet diagram.
Key
(1) Circuit breaker 1 (2) Circuit breaker 2 (3) Jumper (not supplied)
1. Connect the UPS to the battery circuit breakers in the auxiliary cabinets as per the diagram opposite.
2. Tie down the cable as shown in the UPS-cabinet diagram.
Key
XM 25
XM 19XM 20XM 21
6789101112
112345
(1) Circuit breaker 1 (2) Circuit breaker 2 (3) Circuit breaker 3
1. Connect the UPS to the battery circuit breakers in the auxiliary cabinets as per the diagram opposite.
2. Tie down the cable as shown in the
3
12
UPS-cabinet diagram.
The controls of circuit breakers 2 and 3 are not separated.
34020846EN/AD - Page 55
1. Installation
Assembling and connecting the external battery cabinet > Connecting the control-wire cables

Connecting the battery temperature sensor

This operation must be carried out by qualified personnel.
The UPS door must be open. The moving door of the UPS must be open. The cables (not supplied) must be shielded, twisted-pair cables (STP), with a minimum size of 0.1 mm2 and a maximum length of 100 m.
To ensure sufficient isolation of control-wire cables, they must be run separately from the power cables.
UPS cabinet
Key
XM14
XM12
XM10
XM8
XB1
R29
R54
R116 R94 R57
HE1
PT1
C16
VZ5
C15
C10
C14
C12
C13
PT3
C11
PT2
C9
C4
XM9
R32
R28
R25
R31 R27 R26
R30
ET1
R24
R23
XM7
EH1
C3
C7R7C8
NR1
XB2
R2
VT1
R1
C2
VD1
R6
R138
R5
C6
L1
R4
R157 R154 R156
XM5
C5
R159
R155
R158
XM2
XM1
XM3
R11
NR2
C33 R148
R146
VZ1
R10
VD15
C17
R137
R147
C1
VP1
R8
R3
NR3
R9
XM21
XB3
XM25
2 3 2
XB4
R115
R53
R56
R93
R52
R114 R92 R55
VZ6
VZ7
C24
R113
R91
XM11
R112
R90
VZ8
VZ9
VZ10
R111
R89
XM15
R38
R105
R107
R109
R37
XM13
R36
R108
R110
R106
R35
R51
R136
R132
R134 R34 R33
R131R133
R135
R63
R59
R61
XM16
R50
R62
R60
R58
VD5
1
VD14
R49
VD13
XM17XM18
XM22
R22
R88
R79
R104
1
R87
R78
R103
R77
R102
R86
XB5
R76
R101
R85
R75R74
R100
R99
R83R84
R42
R44
VD8
VD6
VD7
XM6
VD4
C23
R73
R72
R127
VT2
R43
VP7
R39
R41
R152
R126
XM24
R125
R46
R45
R71
VP6
VD12
XM4
R48
C20
R124
R123
DI1
VD11
R70
R47
VP5
R122
C19
VD3
VD2
R97
R20
VT3
R98
R96
R15
R82
C32
R121
C18
R69
R81
R19
C22
XM23
K2
VP3
K1
VP4
VP2
R139
R140
VZ4
VD10
R18
R120
VZ11
R80
R95
R12
R66
R68
C21
R17
R14
R65
R119
R142
R118
L2
R67
R143
R16
R64
R13
R117
L3
XM20
XB6
XM19
(1) Connectors (2) Cable ties (3) Cables
Connecting a sensor to a single UPS cabinet
UPS
XM 25
-12V
BC -
BC +
+ 12 V
11
XM 21
-12 V
BC
BC+
XR2
Sensor
The sensor may be located in a battery cabinet or in a battery room for batteries on racks.
XR1
+12
12
1. Connect the UPS to the temperature sensor in the auxiliary cabinet as per the diagram opposite (Cables not supplied).
2. Tie down the cable as shown in the UPS-cabinet diagram.
34020846EN/AD - Page 56
Assembling and connecting the external battery cabinet > Connecting the control-wire cables
Connecting a sensor to a number of UPS cabinets
1. Installation
1. Connect the UPSs to the temperature
+ 12 V
UPS n
-12V
sensor in the auxiliary cabinet as per the diagram opposite (Cables not supplied).
2. Tie down the cable as shown in the
BC -
BC +
+ 12 V
UPS 1
XM 25 XM 25 XM 25
-12V
BC -
BC +
+ 12 V
UPS 2
-12V
BC -
BC +
UPS-cabinet diagram.
1
XM 21 XM 21 XM 21
-12 V
+
XR2
XR1
+12
12
Sensor
The sensor may be located in a battery cabinet or in a battery room for batteries on racks.
34020846EN/AD - Page 57
2. Appendices

2.1 Assembling 2000 kVA SSCs

Right hand side cabinet Rear view
Left hand side cabinet
Side view
X 3
1
1
Right hand side cabinet
12
6
11
2 3 4
1 - Place the cabinets in their definitive position
2 - Adjust the front feet to ensure the cabinets are vertical and the doors aligned.
3 - Remove the two inter-cabinet uprights (1) located behind the right hand side cabinet.
3 - Unbolt the 7 fishplates (2) (3) (4)
4 - Align the fishplates horizontally
5 - Fit the 3 upper-part fishplates L1, L2, L3 (2) between the 2 cabinets
6 - Fit the neutral fishplate (3) between the 2 cabinets
7 - Fit the 3 lower-part fishplates L1, L2, L3 (4) between the 2 cabinets
8 - Connect the the two earthing braids (5) between the front uprights of both cabinets

2.2 IP 32 option

Refer to the "IP 32" manual no. 3460028300 for more details on this option
X 1
X 3
9 - Connect the auxiliary wires between the connectors (6) of both cabinets
10 - Fit the inter-cabinet uprights (1) between the two cabinets
15
13
14
34020846EN/AD - Page 58

2.3 Electrical characteristics

Selection of protection devices

Upstream CB
BYPASS AC
NORMAL AC
(not supplied)
Downstream CB (not supplied)
Q4S
output fuses
input fuses
2. Appendices
Electrical characteristics >
Upstream CB (not supplied)
Load
Q1
Q5N
When sizing the upstream circuit breakers, the parameters presented below must be taken into account.
Time/current curves for UPS input and output fuses
10
10
10
10
1
10
10
10
t (s)
4
3
2
250-300 kVA : 630A
400 kVA : 800A
500 kVA : 1000A
-
1
-
2
-
3
-
4
10
10
10
2
10
3
10
I (A)
4
UPS short-circuit current with inverter coupled and bypass AC source out of tolerances
Sn 250 kVA 300 kVA 400 kVA 500 kVA
In (at 400 V) 361 A 433 A 577 A 721 A
Isc 1085 A 1085 A 1446 A 1975 A
34020846EN/AD - Page 59
2. Appendices
Electrical characteristics >
Line-current values
Rated power of each UPS unit
250 kVA 368 A 441 A 530 A 630 A
300 kVA 442 A 530 A 636 A 630 A
400 kVA 587 A 706 A 848 A 800 A
500 kVA 735 A 881 A 1058 A 1000 A
Continuous input current at U=400V
Input current for load PF =
0.9, U = 400 V at 1.25 In overload limited to 10 min.

Permissible UPS overloads as a function of time

I/In
2,2
2
1,8
1,6
1,4
1,2
Input current for load PF =
0.9, U = 400 V at 1.5 In overload limited to 30 sec.
20°C 30°C 35°C 40°C
Input/output fuse ratings
1
1010,1
10 30
10
2
600
10
3
10
4
10
t (s)
5
34020846EN/AD - Page 60
2. Appendices
General characteristics of MGE TM Galaxy TM 7000 UPSs >
2.4 General characteristics of MGE
UPS power in kVA 250 300 400 500
Normal AC input
Number of conductors 3 phases
Reference voltage at Pn 380 V to 415 V
Reference frequency 45 Hz to 66 Hz
THDI Typically 3% at Pn
Power factor > 0.99
Bypass AC input
Number of conductors 3 phases + neutral
Reference voltage at Pn 380 V to 415 V
Reference frequency 45 Hz to 66 Hz
Load output
Number of conductors 3 phases + neutral
Set phase-to-phase voltages 380 V / 400 V / 415 V
Set phase-to-neutral voltages 220 V / 230 V / 240 V
TM
Galaxy TM 7000 UPSs
Voltage variation ± 1%
Adjustable frequencies and tolerance (on battery power)
Voltage variation for 0 to 100% load step change
Permissible overloads 150% for 30 seconds, 125% for 10 minutes
THDU Ph-to-Ph and Ph-to-N for nonlinear load
Battery
Standard battery technology Sealed lead-acid battery (gas-recombination)
UPS
Active power (kW) 112 225 135 270 180 360 225 450
Efficiency 94.1 94 94 94 94.1 94 94 94.3
Heat losses in kW Heat losses in calories/s
Storage temperature range -25°C to +45°C
Operating temperature range at Pn 0°C to 35°C
50 Hz or 60 Hz ± 0.1 Hz
± 1%
< 2% Ph-to-Ph
(Valve Regulated Lead Acid type)
PN/2 PN PN/2 PN PN/2 PN PN/2 PN
7 1673
14.3 3418
8.6 2055
17.2 4111
11.2 2676
22.9 5473
14.3 3418
27.2 6500
Relative humidity 45% to 75%
Maximum operating altitude without derating
Noise level (dBa) 75
Product standards IEC 62040
Safety standards IEC 62040-1-2
Protection standards IEC 62040-3
EMC standards IEC 62040-2
< 1000 m
34020846EN/AD - Page 61
2. Appendices
General characteristics of MGE TM Galaxy TM 7000 UPSs >

Battery characteristics

Sealed lead-acid battery Vented lead-acid battery Ni-Cd battery
Min./max. number of cells 264/288 264/288 428/468
Floating voltage per cell
Min./max. floating voltage 600 V / 654 V 581 V / 634 V 600 V / 655 V
Min. voltage per cell 1.65 V to 1.9 V 1.65 V to 1.9 V Min. threshold
2.27V 2.2V 1.4V
1.1 V
34020846EN/AD - Page 62

2.5 Glossary

2. Appendices
Glossary >
Backup time Time that the connected loads can operate on battery power.
Bypass AC source Source supplying the bypass line. The load can be transferred to the bypass line if an overload
occurs on the UPS output, for maintenance or in the event of a malfunction.
Fin UPS input frequency (normal or bypass AC input).
Inverter UPS module that inputs DC power and outputs AC voltage and current.
Isc Short-circuit current.
Load Devices or equipment connected to the UPS output.
Normal (double conversion) mode
Normal AC source Normal source of power for the UPS.
PE Protective conductor.
PEN Conductor serving as both a protective conductor and a neutral conductor.
PFC Sinusoidal input module used to eliminate the harmonics reinjected in the upstream source by
Relay contacts Contacts supplying information to the user in the form of signals.
SSC Static-switch cabinet.
Uin UPS input voltage (normal or bypass AC input).
Uout UPS output voltage.
UPS Uninterruptible Power System.
The normal UPS operating mode. The AC source supplies the UPS which in turn supplies the connected loads (after electronic double conversion).
the UPS upstream.
34020846EN/AD - Page 63
34020846EN/AD
Loading...