Thank you for selecting an APC by Schneider Electric product to protect your electrical equipment.
The MGE
We recommend that you take the time to read this manual to take full advantage of the many features of your UPS
(Uninterruptible Power System).
TM
GalaxyTM 7000 range has been designed with the utmost care.
APC by Schneider Electric pays great attention to the environmental impact of its products.
Measures that have made MGE
◗ the eco-design approach used in product development,
◗ the elimination of harmonic disturbances reinjected into the AC source,
◗ production in an ISO 14001 certified factory,
◗ recycling of the MGE
TM
TM
GalaxyTM 7000 a reference in environmental protection include:
GalaxyTM 7000 at the end of its service life.
To discover the entire range of APC by Schneider Electric products and the options available for the MGE
range, we invite you to visit our web site at www.apc.com or contact your local representative.
TM
GalaxyTM 7000
34020846EN/AD - Page 2
All products in the MGETM GalaxyTM 7000 range are protected by patents. They implement original technology not available to
competitors of APC by Schneider Electric.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning
technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric.
This document may be copied only with the written consent of Schneider Electric or its affiliated companies. Authorised copies
must be marked
The UPS must be installed in a room with restricted access in compliance with standard IEC 60364-4-482).
Only qualified personnel are authorised to enter this restricted access room.
A UPS has its own internal power source (the battery). Consequently, the power outlets may be energised even if the UPS is
disconnected from the AC-power source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
The UPS must be properly earthed.
The battery supplied with the UPS contains small amounts of toxic materials. Caution, replacement of the battery
by a battery of the wrong type can result in an explosion.
To avoid accidents, the instructions below must be observed.
◗ Never operate the UPS if the ambient temperature and relative humidity are higher than the levels specified in the
documentation.
◗ Never burn the battery (risk of explosion).
◗ Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
◗ Comply with all applicable regulations for the disposal of the battery.
◗ Caution, wait five minutes before opening the UPS to allow the capacitors to discharge.
◗ Caution, there is high leakage current: the earthing conductor must be connected first and disconnected last.
◗ The product must be installed on a non-inflammable surface (e.g. concrete).
◗ Caution, battery replacement must be carried out by qualified personnel.
◗ Isolate the Uninterrptible Power Supply (UPS) before working on the circuits upstream.
◗ The UPS can only be used in a controlled indoor environment.
Safety
Product safety
◗ Protection (circuit breaker/switch disconnector) must be installed upstream and be easily accessible.
◗ Never install the UPS near liquids or in an excessively damp environment.
◗ Never let a liquid or foreign body penetrate inside the UPS.
◗ Never block the ventilation grates of the UPS.
◗ Never expose the UPS to direct sunlight or a source of heat.
◗ When replacing battery cells, use the same type and number of cells.
Special precautions
◗ The UPS connection instructions contained in this manual must be followed in the indicated order.
◗ Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the
equipment to be connected to the UPS.
◗ If the UPS must be stored prior to installation, storage must be in a dry place.
◗ The admissible storage temperature range is -25°C to +45°C
◗ If the UPS remains de-energised for a long period, we recommend that you energise the UPS for a period of 24 hours, at least once every
month. This charges the battery, thus avoiding possible irreversible damage.
◗ The UPS is designed for normal climatic and environmental operating conditions concerning the altitude, ambient operating temperature,
relative humidity and ambient transport and storage conditions.
◗ Using the UPS within the given limits guarantees its operation, but may affect the service life of certain components, particularly that of the
battery and its autonomy. The maximum storage time of the UPS is limited due to the need to recharge its integrated battery.
◗ Unusual operating conditions may justify special design or protection measures:
- harmful smoke, dust, abrasive dust,
- humidity, vapour, salt air, bad weather or dripping,
- explosive dust and gas mixture,
- extreme temperature variations,
- poor ventilation,
- conductive or radiant heat from other sources,
- cooling water containing acid or impurities which may cause scale, silt, electrolysis or corrosion of converter parts exposed to water,
- strong electromagnetic fields,
- radioactive levels higher than those of the natural environment,
- fungus, insects, vermin, etc.,
- battery operating conditions.
The UPS must always be installed in compliance with:
◗
◗ the requirements of standard IEC 60364-4-42: Protection from thermal effects.
◗ standard IEC 60364-4-41: protection against electric shock.
◗ standard IEC 60364-4-482: Electrical installations of buildings.
◗ standard NFC 15-100 (in France).
◗ the requirements of standard IEC 62040-1-2:
34020846EN/AD - Page 3
Foreword
Pictograms
Document
Danger, these instruction are
imperative.
Information, advice, help.LED off
Visual indicationLED flashing
ActionLED on
Audio signal.
34020846EN/AD - Page 4
APC by Schneider Electric has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
The cardboard we use comprises over 30% of recycled cardboard.
Sacks and bags are made of polyethylene.
Packing materials are recyclable and bear the appropriate identification symbol .
MaterialsAbbreviationNumber
in the symbol
Polyethylene terephthalatePET01
High-density polyethyleneHDPE02
Polyvinyl chloridePVC03
Low-density polyethyleneLDPE04
Environment
PolypropylenePP05
PolystyrenePS06
Follow all local regulations for the disposal of packing materials.
End of life
APC by Schneider Electric will process products at the end of their service life in compliance with local regulations.
APC by Schneider Electric works with companies in charge of collecting and eliminating our products at the end of their
service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing centre for electrical and electronic waste.
Make the product unusable by cutting the internal supply cables.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning
batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
The "Material Safety Data Sheets" (MSDS) for the batteries are available on our web site*.
(*) For more information or to contact the Product Environmental manager, use the "Environmental Form" on the site:
http://environment.apc.com
34020846EN/AD - Page 5
Contents
1. Installation
1.1 Possible installations .........................................................................................................................10
Single or modular UPS alone .............................................................................................................10
Parallel UPS systems .........................................................................................................................10
Modular UPSs in parallel ...........................................................................................................10
Modular UPSs in parallel with external bypass cabinet .............................................................10
Parallel UPSs with SSC (static-switch cabinet) .........................................................................11
Parallel UPS with SSC and SSC maintenance cabinet ............................................................11
UPS set up as a frequency converter .................................................................................................12
Single UPS ................................................................................................................................12
Parallel UPS systems ................................................................................................................12
Connect the power cables ................................................................................................................. 45
1.10 Connecting the control-wire cables ............................................................................................... 46
Connecting a modular UPS or frequency converter alone. ............................................................... 46
Connecting the UPS units in parallel ................................................................................................. 47
Connecting the modular UPS units in parallel .......................................................................... 47
Connecting the modular UPSs with the external bypass .......................................................... 48
Connecting parallel UPSs with SSC (static-switch cabinet) ..................................................... 49
Connect the components specific to the 2000 kVA light SSC .................................................. 50
Connect the SSC maintenance cabinet .................................................................................... 50
Connecting the EPO function ............................................................................................................ 51
Connecting the dry-contact communication card ............................................................................... 52
1.11 Assembling and connecting the external battery cabinet ........................................................... 53
Assembling the empty battery cabinet ............................................................................................... 53
Mounting the battery circuit-breaker kit ................................................................................... 53
Mounting the shelves ................................................................................................................ 53
Connecting the power cables ............................................................................................................ 54
Connecting the control-wire cables .................................................................................................... 55
Connecting the battery circuit breaker ...................................................................................... 55
Connecting the battery temperature sensor ............................................................................. 56
2. Appendices
34020846EN/AD - Page 7
Contents
2.1 Assembling 2000 kVA SSCs ..............................................................................................................58
2.2 IP 32 option .........................................................................................................................................58
An operating temperature of 35°C is possible,
but battery life will be reduced.
Size the ventilation system taking into
account the values in the table below.
Heat losses to be
evacuated at Pn
SSC cabinets
Power rating in kVA80012002000
Air flow (m³/h)1000NaturalNatural
Heat losses to be
evacuated at Pn
Pn = rated power, for other values please consult the after-sales support or the local office.
kW14.317.222.927.2
Cal./s3418411154736501
kW3.7< 1< 1.5
Cal./s884< 240< 360
34020846EN/AD - Page 18
1.3 Prerequisites
UPS currents
1. Installation
Prerequisites >
UPS cabinets in kVAI rated of Normal
AC in A
250 351 361361490
300 420 433 433588
400 558 577 577784
500 700 722 722980
The table above is for 400 V interphase voltages and a load with a power factor of 0.9.
For other voltages (380 or 415 V), the current values must be multiplied by 1.05 and 0.96 respectively.
The battery current is an average current for a battery voltage of 488 V (44 blocks at 1.85 V/cell each), at Pn with a power
factor of 0.9.
Recommended upstream protection
Normal AC source
Stick a label with the following text on each upstream circuit breaker / switch-disconnector: "Isolate Uninterruptible
Power Supply (UPS) before working on this circuit".
Selection of protective devices is determined by the maximum continuous current (at 380 V).
Protection ratings are calculated for the maximum continuous current (at 380V).
UPS cabinets in kVACB / switch-disconnector Trip unit
250 NS 630N 3P *STR 23 SE
I rated of Bypass
AC in A
I rated of load
in A
I battery in A
300 NS 630N 3P *STR 23 SE
400 NS 800N 3P *Micrologic 2.0
500 NS 800N 3P * Micrologic 5.0
The circuit breakers / switch-disconnectors recommended above respect the requirements for discrimination with the UPS
fuses.
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
* For short-circuit currents > 40 kA, use a CB/SD with a higher breaking capacity (type L or H).
Bypass AC source
Stick a label with the following text on each upstream circuit breaker / switch-disconnector: "Isolate Uninterruptible
Power Supply (UPS) before working on this circuit".
Selection of protective devices is determined by the maximum continuous current (at 380 V).
Protection ratings are calculated for the maximum continuous current (at 380V).
UPS cabinets in kVA Maximum permissible
250 25 InNS 630N 4P *STR 23 SE
300 21 InNS 630N 4P *STR 23 SE
400 16 InNS 800N 4P *Micrologic 2.0
500 16 InNS 800N 4P *Micrologic 5.0
current for 20 ms
CB / switchdisconnector
Trip unit
The circuit breakers / switch-disconnectors recommended above respect the requirements for discrimination with the UPS
fuses.
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
* For short-circuit currents > 40 kA, use a CB/SD with a higher breaking capacity (type L or H).
34020846EN/AD - Page 19
1. Installation
Prerequisites >
Recommended maximum downstream protection
If these recommendations are not followed, a short-circuit on an output circuit can result in a break in power longer than 20
milliseconds on all the other output circuits.
UPS cabinets in kVA CB / switch-
250 NS 100N
300 NS 100N
400 NS 100N
500 C125N
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
These protective devices ensure discrimination for each circuit downstream of the UPS, with or without a bypass AC input.
Battery protection
UPS cabinets in kVABattery backup time at
disconnector
C120N
C120N
C120N
C120N
NG 125N
C 125H
NS 160N
NG 125N
Pn
Trip unit
TM D 80
C 80A
B 125A
TM D 80
C 80A
B 125A
TM D 100
C 125A
C 125A
D 125A
TM 160D
D 125
Battery CB/switch-disconnector QF1
Typ eTrip unitmagnetic setting in A
250 AllNS630 DC MP11200
300 ≤ 15 min.
> 15 min.
400 ≤ 5 min.
> 5 min.
500 AllC1251N DCP211600
Pn = rated power at a power factor of 0.9, for other values please consult the after-sales support or the local office.
See the necessary precautions during connection of circuit breakers / switch-disconnectors in the installation
manual of the battery circuit-breaker enclosure, doc. no. 34021529.
Recommended residual-current protection
Requirements for residual-current protection.
For common normal and bypass AC inputs
- The same residual-current protection may be used for the two lines.
For separate normal and bypass AC inputs
- A transformer is required upstream of either the normal AC line or the bypass AC line.
- Equip each line with a circuit breaker or switch-disconnector with residual current protection.
See “System earthing arrangements”, page 24.
The recommended minimum residual current protection is 3A, provided the conditions defined in IEC364.4-41 are
respected.
NS630 DC
C1251N DC
NS630 DC
C1251N DC
MP1
P21
MP1
P21
1200
1600
1200
1600
34020846EN/AD - Page 20
Characteristics of the connection terminals
Connections are made to terminals that are pre-drilled or equipped with studs.
Earthing cables connect to the earthing bar.
UPS cabinets
Cabinets in kVAPhase terminalEarthing terminalBattery terminal
Type of studHole diameter in mmHole diameter in mm Hole diameter in mm
250 M10/1313
300 M10/1313
400 M10/1313
500 /131313
SSCs, SSC maintenance, External bypass cabinets
Cabinets in kVAPhase terminalEarthing terminal
Hole diameter in mmHole diameter in mm
1. Installation
Prerequisites >
8001313
12001313
200013 and 1713
Power cables for single UPSs
AC cable sizes are determined for:
the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line voltage drop <3%, installed on
perforated cable trays, XLPE-type insulation, single-layer trefoil formation, THDI between 15% and 33%, 35°C, at 400 V,
grouped in four touching cables.
Battery cable sized are determined for:
copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage drop <1%.
General case
Bypass AC
Normal AC
Frequency converter
Normal AC
UPS
UPS
Load
Load
UPS
cabinets in
kVA
250
300
400
500
Minimum size in mm²
Normal AC
line
1x1501x1501x1501x150
1x2401x2401x2401x185
2x1502x1502x1501x240
2x2402x2402x2402x150
Bypass AC
line
LoadBattery
34020846EN/AD - Page 21
1. Installation
Prerequisites >
Power cables for parallel UPSs
AC cable sizes are determined for:
the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line voltage drop <3%, installed on
perforated cable trays, XLPE-type insulation, single-layer trefoil formation, THDI between 15% and 33%, 35°C, at 400 V,
grouped in four touching cables.
Battery cable sized are determined for:
copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage drop <1%.
Important: the output cables must be at least 6 metres long (L ≥ 6m)
Normal AC line and battery
Bypass AC
Normal AC
Bypass AC
Normal AC
Bypass AC
Normal AC
UPS 1
UPS 2
UPS 3
Bypass AC line and load
Modular UPSs in parallel
Bypass AC
Normal AC
Bypass AC
Normal AC
1
Do not include redundant UPS units.
Power cables between the UPS units and the upstream protective devices must all be of the same size and length.
Power cables between the UPS units and the load must all be of the same size and length.
UPS 1
UPS 2
UPS cabinets
in kVA
L
L
L
Load
250
300
400
500
UPS
L
Load
L
cabinet
s in kVA
250 2250
300 2300
400 2400
500 2500
Minimum size in mm²
Normal AC lineBattery
1x1501x150
1x2401x185
2x1501x240
2x2402x150
Nbr
of
UPS
Total power
1
in kVA
rating
Current on AC
bypass or load in
A
s
3611x150
4331x240
5772x150
7222x240
Min. size for AC
bypass or load in
mm²
Frequency converters
34020846EN/AD - Page 22
Normal AC
UPS 1
L
Load
Normal AC
1
Do not include redundant UPS units.
UPS 2
L
UPS
cabinets in
Nbr of
UPSs
Total power
1
rating
in kVA
kVA
250 2250
300 2300
400 2400
500 2500
Load current in A Minimum size for
load in mm²
3611x150
4331x240
5772x150
7222x240
1. Installation
Prerequisites > Power cables for parallel UPSs
AC cable sizes are determined for:
the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line voltage drop <3%, installed on
perforated cable trays, XLPE-type insulation, single-layer trefoil formation, THDI between 15% and 33%, 35°C, at 400 V,
grouped in four touching cables.
Battery cable sized are determined for:
copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage drop <1%.
Important: the output cables must be at least 6 metres long (L ≥ 6m)
Modular UPSs in parallel with external bypass cabinet
Bypass AC
Bypass cabinet
Normal AC
Normal AC
Normal AC
UPS 1
UPS 2
UPS 3
L
L
L
UPS
cabinet
in kVA
250 2
300 2
Load
400 2
500 2
1
Do not include redundant UPS units.
2
Standard NFC15-100 limits the number of cables to four.
Nbr
of
UPSs
3
4
3
4
3
4
3
4
Total power
1
rating
in
kVA
500
750
1000
600
900
1200
800
1200
1600
1000
1500
2000
Current on
AC bypass or
load in A
722
1083
1443
866
1300
1732
1154
1732
2308
1433
2165
2886
Min. size for AC
bypass or load in
mm²
2x185
3x300
4x240
2x240
4x240
4x300
4X185
4x300
4X500
4x240
4X500
Consult us
2
Power cables between the UPS units and the upstream protective devices must all be of the same size and length.
Power cables between the UPS units and the load must all be of the same size and length.
Parallel UPSs with SSC (static-switch cabinet)
Bypass AC
Normal AC
Normal AC
Normal AC
UPS 1
UPS 2
UPS 3
L
L
L
SSC
UPS
cabinet
in kVA
250 2
300 2
Load
400 2
500 2
1
Do not include redundant UPS units.
2
Standard NFC15-100 limits the number of cables to four.
Nbr
of
UPSs
3
4
3
4
3
4
3
4
Total power
1
in
rating
kVA
500
750
1000
600
900
1200
800
1200
1600
1000
1500
2000
Current on
AC bypass or
load in A
722
1083
1443
866
1300
1732
1154
1732
2308
1433
2165
2886
Min. size for AC
bypass or load in
mm²
2x185
3x300
4x240
2x240
4x240
4x300
4x185
4x300
4X500
4x240
4X500
Consult us
2
34020846EN/AD - Page 23
1. Installation
System earthing arrangements >
1.4 System earthing arrangements
This section lists the main SEAs (system earthing arrangements) and their wiring requirements. For SEAs not listed here,
please contact the technical-support department.
Single UPS system
TNS upstream, TNS downstream
For separate normal and bypass AC lines from a single source.
Without residual-current protection
PE
PE
Load
PE
Bypass AC
Normal AC
L1
L2
L3
N
L1
L2
L3
PFC
SS
INV
L1
L2
L3
N
UPS
MLVS
UPS units used as frequency converters: please contact your technical assistance
With residual-current protection
Galvanic isolation between the normal and bypass AC lines is mandatory.
The recommended minimum residual current protection is 3A, provided the conditions defined in IEC364.4-41 are
respected.
For a transformer on a Bypass AC network
PE
PE
Load
PE
Bypass AC
L1
L2
L3
N
PFC
SS
INV
L1
L2
L3
N
34020846EN/AD - Page 24
Normal AC
(4p)
MLVS
L1
L2
L3
UPS
For a transformer on a Normal AC network
MLVS
PE
Bypass AC
Normal AC
PE
L1
L2
L3
N
L1
L2
L3
PFC
SS
INV
L1
L2
L3
N
PE
Load
Adding a transformer into the Normal AC network reduces the installation’s overall yield.
TNC upstream, TNC, TNS or TT downstream installation
For separate normal and bypass AC lines from a single source.
It is essential to transform the UPS internal PE bar into a PEN bar, See “Adapting the cabinet according to the neutral point
connection”, page 26.
For an installation with a SSC cabinet or an external bypass cabinet, it is essential to transform the cabinet's internal PE
bar into a PEN bar, See “Adapting the cabinet according to the neutral point connection”, page 26.
Unit or modular UPS
The UPS output neutral must be connected to the internal PEN bar (1)
Parallel UPS with SSC cabinet or modular UPSs with external bypass cabinet:
The SSC cabinet output neutral or external bypass cabinet output neutral must be connected to the internal PEN bar for
this cabinet.
The connection between the UPS outputs and the SSC cabinet or the external bypass cabinet must be done in TNC
(connect the PEN cable to the PEN bar).
The load neutral terminal on the UPS, SSC or external bypass cabinet must not be used.
The SLT downstream TNS or TT starts on the MGE ™ Galaxy™ 7000 installation output.
1
Q4S
L1
L2
Bypass AC
PEN
NP
L3
N
PFC
PEN
SS
INV
1. Installation
System earthing arrangements >
PE or PEN
L1
L2
L3
NP:Not Provided
N
Load
PEN
MLVS
IT upstream, IT downstream
For separate normal and bypass AC lines from a single source.
R1
IMD
CPI1
MLVS
Normal AC
Bypass AC
R2
Normal AC
L1
L2
L3
PE
L1
L2
L3
N
PFC
L1
L2
L3
SS
UPS
INV
UPS
PE
L1
L2
L3
N
IMD2
CPI2
Load
In normal operating mode
The CPI1 controls the whole installation including downstream from the UPS. Power to the CPI2 is switched off by the R2
relay which controls voltage presence upstream from the UPS.
If the voltage is cut or the protection is opened upstream:
The R1 relay cuts the CPI1 circuit and the R2 relay closes the CPI2 circuit thus maintaining control downstream of the UPS.
Parallel UPSs systems
Earthing system adaptations are the same as those previously detailed for unitary UPS.
34020846EN/AD - Page 25
1. Installation
Adapting the cabinet according to the neutral point connection >
1.5 Adapting the cabinet according to the neutral point connection
UPS cabinet
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
The protective covers must be removed.
For IT,TNS or TT (PE) upstream
system
1. Disconnect and remove the joiner
(1) on the earthing bar.
For TNC (PEN) upstream, TNC, TNS
or TT downstream system
1. Disconnect and remove the joiner
(1) on the earthing bar.
2. Install the joiner as shown opposite.
1
SSC cabinet or external bypass cabinet
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
The protective covers must be removed.
OFF
OFF
OFF
PENPEN
2
(2) Inverter neutral (N)
For IT,TNS or TT (PE) upstream
system
1. Disconnect and remove the joiner
(1) on the earthing bar.
For TNC (PEN) upstream, TNC, TNS
or TT downstream system
1. Disconnect and remove the joiner
(1) on the earthing bar.
2. Install the joiner (1) as shown
opposite.
34020846EN/AD - Page 26
2
1
(2) SSC neutral (N)
1.6 Connecting the power cables
Dimensions are indicated in millimeters.
For parallel installations with no neutral on the load and network, interconnect the UPS neutrals.
Single or modular UPS cabinet
250 to 400 kVA
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1. Installation
Connecting the power cables >
Key
1
8
2
34 57
6
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1Q4SQ3BPQ5N
OFFOFFOFFOFF
L1 L2 L3
+
N L1 L2 L3 N L1 L2 L3
-
(1) Protective covers
(2) Tie bar
(3) To normal AC line
(4) To the batteries
(5) To bypass AC line
(6) To earth
(7) To the load
(8) Earthing bar
1. Remove the protective covers (1).
1. Check that switches Q1, Q4S,
Q3BP and Q5N are in the OFF
position as shown opposite.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the normal AC conductors
taking care to respect the order, L1,
L2, L3.
470
410
350
260
Normal ACBypass ACBatteryLoad
Earth
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
4. Connect the bypass AC conductors
taking care to respect the order, N*,
L1, L2, L3.
390
5. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
6. Connect the battery.
7. Tie the cables down.
8. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
9. Put the protective covers back in
place.
34020846EN/AD - Page 27
1. Installation
Connecting the power cables > Single or modular UPS cabinet
500 kVA
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1
8
8
2
4573
6
Key
(1) Protective covers
(2) Tie bar
(3) To normal AC line
(4) To the batteries
(5) To bypass AC line
(6) To the earth
(7) To the load
(8) Earthing bar
1. Remove the protective covers (1).
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1Q4SQ3BPQ5N
OFFOFFOFFOFF
N L1 L2 L3 N L1 L2 L3L1 L2 L3
-
+
360
Normal ACBypass ACBatteryLoad
Earth
260
1. Check that switches Q1, Q4S,
Q3BP and Q5N are in the OFF
position as shown opposite.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the normal AC conductors
taking care to respect the order, L1,
390
L2, L3.
4. Connect the bypass AC conductors
taking care to respect the order, N*,
L1, L2, L3.
5. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
6. Connect the battery.
7. Tie the cables down.
34020846EN/AD - Page 28
8. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
9. Put the protective covers back in
place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
Frequency-converter cabinet
250 to 400 kVA
In parallel systems, switches Q4S and Q3BP are absent.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1
1. Installation
Connecting the power cables >
Key
(1) Protective covers
(2) Tie bar
(3) To normal AC line
(4) To the batteries
(5) Earthing bar
(6) To the earth
(7) To the load
2
3475
6
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1Q5N
OFFOFF
-
+
470
410
350
1. Remove the protective covers (1).
1. Check that switches Q1 and Q5N
are in the OFF position as shown
opposite.
N L1 L2 L3L1 L2 L3
2. Connect the normal AC neutral to
the load neutral.
3. Connect the protective conductor
(PE or PEN) to the earth bar.
4. Connect the normal AC conductors
taking care to respect the order, L1,
L2, L3.
5. Connect the load conductors taking
390
care to respect the order, N*, L1, L2,
L3.
260
6. Connect the battery.
7. Tie the cables down.
Normal ACBatteryEarthLoad
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
8. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
9. Put the protective covers back in
place.
34020846EN/AD - Page 29
1. Installation
Connecting the power cables > Frequency-converter cabinet
500 kVA
In parallel systems with an SSC, switches Q4S and Q3BP are absent.
The AC bypass connection is made in the SSC.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1
Key
(1) Protective covers
(2) Tie bar
(3) To normal AC line
(4) To the batteries
(5) Earthing bar
(6) To the earth
(7) To the load
1. Remove the protective covers (1).
2
34576
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1Q5N
OFFOFF
L1 L2 L3
360
Normal ACBatteryEarthLoad
-
+
N L1 L2 L3
260
1. Check that switches Q1 and Q5N
are in the OFF position as shown
opposite.
2. Connect the normal AC neutral to
the load neutral.
3. Connect the protective conductor
(PE or PEN) to the earth bar.
390
4. Connect the normal AC conductors
taking care to respect the order, L1,
L2, L3.
5. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
6. Connect the battery.
34020846EN/AD - Page 30
7. Tie the cables down.
8. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
9. Put the protective covers back in
place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
Parallel UPS cabinet
250 to 400 kVA
In parallel systems with an SSC, switches Q4S and Q3BP are absent.
The AC bypass connection is made in the SSC.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1. Installation
Connecting the power cables >
Key
1
(1) Protective covers
(2) Tie bar
(3) To normal AC line
(4) To the batteries
(5) Earthing bar
(6) To the earth
(7) To the load
2
3475
6
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1Q5N
OFFOFF
-
+
470
410
350
Normal ACBatteryEarthLoad
1. Remove the protective covers (1).
1. Check that switches Q1 and Q5N
are in the OFF position as shown
opposite.
N L1 L2 L3L1 L2 L3
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the normal AC conductors
taking care to respect the order, L1,
L2, L3.
4. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
390
5. Connect the battery.
6. Tie the cables down.
260
7. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
8. Put the protective covers back in
place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
34020846EN/AD - Page 31
1. Installation
Connecting the power cables > Parallel UPS cabinet
500 kVA
In parallel systems with an SSC, switches Q4S and Q3BP are absent.
The AC bypass connection is made in the SSC.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1
Key
(1) Protective covers
(2) Tie bar
(3) To normal AC line
(4) To the batteries
(5) Earthing bar
(6) To the earth
(7) To the load
1. Remove the protective covers (1).
2
34576
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q1Q5N
OFFOFF
L1 L2 L3
360
Normal ACBatteryEarthLoad
-
+
N L1 L2 L3
260
1. Check that switches Q1 and Q5N
are in the OFF position as shown
opposite.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the normal AC conductors
taking care to respect the order, L1,
390
L2, L3.
4. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
5. Connect the battery.
6. Tie the cables down.
34020846EN/AD - Page 32
7. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
8. Put the protective covers back in
place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
Connections through the top of the cabinets are possible using an auxiliary cabinet 400 mm wide.
SSC cabinet
800 kVA
1. Installation
Connecting the power cables >
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Right-hand view
22
Connection through the bottom
Top view
11
3
Front
view
Front view
5
5
4
OFF
OFF
OFF
A
Key
(1) Front protective covers
(2) Roof protective covers
(3) Earthing bar
(4) To the earth
(5) To the UPSs*
(6) To bypass AC line
(7) To the load
Connections through the top of the
UPS cabinets are possible using an
auxiliary cabinet 400 mm wide.
6
1. Remove the protective covers (1)
and/or (2).
7
*Or to the SSC maintenance cabinet,
See “SSC maintenance cabinet”,
6
7
A
page 42.
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q4S
533
N L1 L2 L3
Earth
UPSs
OFF
Q3BP
OFF
Q5N
OFF
Bypass
AC
N L1 L2 L3
N L1 L2 L3
Load
1060
860
533
** SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
1. Check that switches Q4S, Q3BP
and Q5N are in the OFF position as
shown opposite.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the UPS conductors taking
care to respect the order, N**, L1, L2,
L3.
4. Connect the bypass AC conductors
taking care to respect the order, N**,
L1, L2, L3.
5. Connect the load conductors taking
care to respect the order, N**, L1, L2,
L3.
6. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
7. Put the protective covers back in
place.
34020846EN/AD - Page 33
1. Installation
Connecting the power cables > SSC cabinet
1200 kVA
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Right-hand view
Top view
1
Connection through the top
Connection through the bottom
2
1
1
1
1
3
Front view
Front
view
5
4
OFF
OFF
OFF
A
A
766
6
7
7
Key
(1) Front protective covers
(2) Roof protective covers
(3) Earthing bar
(4) To the earth
(5) To the UPSs*
(6) To bypass AC line
(7) To the load
Connections through the top of the
UPS cabinets are possible using an
auxiliary cabinet 400 mm wide.
1. Remove the protective covers (1)
and/or (2).
*Or to the SSC maintenance cabinet.
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
Q4S
OFF
N L1 L2 L3
Q3BP
OFF
N L1 L2 L3
Q5N
AC
559
N L1 L2 L3
UPSsBypassLoad
Earth
OFF
807
1270
1. Check that switches Q4S, Q3BP
and Q5N are in the OFF position as
shown opposite.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the UPS conductors taking
care to respect the order, N*, L1, L2,
L3.
4. Connect the bypass AC conductors
taking care to respect the order, N*,
L1, L2, L3.
5. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
6. Connect the control-wire cables
(See “Connect the backfeed option”,
page 45.)
7. Put the protective covers back in
place.
34020846EN/AD - Page 34
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
2000 kVA
You must have first assembled both cabinets.
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Right-hand view
Front view
11
Front view
1. Installation
Connecting the power cables > SSC cabinet
A
6
7
1
Connection through the top
Connection through the bottom
Key
(1) Front protective covers
(2) Roof protective covers
(3) Earthing bar
(4) To the earth
(5) To the UPSs*
(6) To bypass AC line
(7) To the load
Top view
OFF
22
OFF
3
54
6
OFF
7
A
*Or to the SSC maintenance cabinet, See “SSC maintenance cabinet”, page 42.
1. Remove the protective covers (1) and/or (2).
34020846EN/AD - Page 35
1. Installation
Connecting the power cables > SSC cabinet > 2000 kVA
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
L1L3 NL2
Q4S
OFF
Q3BP
OFF
L2 L3L1 N
Q5N
1270
N L1 L2 L3
OFF
940
500
Earth
UPSs
Bypass
AC
Load
1. Check that switches Q4S (1), Q3BP (2) and Q5N (3) are in the OFF position as shown opposite.
2. Connect the protective conductor (PE or PEN) to the earth bar.
3. Connect the UPS conductors taking care to respect the order, N*, L1, L2, L3.
4. Connect the bypass AC conductors taking care to respect the order, N*, L1, L2, L3.
5. Connect the load conductors taking care to respect the order, N*, L1, L2, L3.
6. Connect the control-wire cables (See “Connect the backfeed option”, page 45.)
7. Put the protective covers back in place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
34020846EN/AD - Page 36
2000 kVA light
Remove the protective covers
This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Right side view
Front view
1. Installation
Connecting the power cables > SSC cabinet
A
6
Front view
1
4
3
Top entry
Bottom entry
Key:
(1) Front face protective covers
(2) Roof protective covers
(3) Earth bar
(4) UPS current sensor terminal block
(5) To Earth
(6) To AC Bypass
(7) To the load
Top entry is possible by using a 400mm wide auxiliary cabinet.
1 - Remove protective covers (1) and (2).
75
Top view
2
A
34020846EN/AD - Page 37
1. Installation
Connecting the power cables > SSC cabinet > 2000 kVA light
Connect the cables
This operation may only be carried out by authorized staff.
See “Characteristics of the connection terminals”, page 21.
Load
1700
NL1L2L3
530
Earth
AC Bypass
1 -Check customer switches Q4S, Q3BP and Q5N are in the OFF position
2 - Connect the protective conductor (PE or PEN) to the earth bar
Top view
N
L1
L3
L2
3 - Connect the AC Bypass conductors in the following order: N*, L1, L2, L3
4 - Connect the load conductors in the following order: N*, L1, L2, L3
5 - Connect the auxiliary wires ( See “Connect the components specific to the 2000 kVA light SSC”, page 50.)
6 - Refit the protective covers
* upstream earthing system TNC, downstream earthing system TNC, TNS or TT See “Adapting the cabinet according to the
neutral point connection”, page 26.
34020846EN/AD - Page 38
External bypass cabinet
800 kVA
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1. Installation
Connecting the power cables >
Right-hand view
Connection through the top
Connection through the bottom
Top view
22
11
3
Front
view
Front view
5
5
4
OFF
OFF
A
6 7
Key
(1) Front protective covers
(2) Roof protective covers
(3) Earthing bar
(4) To the earth
(5) To the UPSs
(6) To bypass AC line
(7) To the load
1. Remove the protective covers (1)
and/or (2).
Q1 Q4S Q3BP Q5N
The handle of the Q3BP switch (in
6
7
A
the OFF position) on all UPS units
must be removed.
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
1. Check that switches Q3BP ext and
Q5N ext are in the OFF position as
N L1 L2 L3
Q3BP
ext
N L1 L2 L3
OFF
Q5N
ext
N L1 L2 L3
1060
860
608
UPSsBypass Load
Earth
OFF
533
AC
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
shown opposite.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the UPS conductors taking
care to respect the order, N*, L1, L2,
L3.
4. Connect the bypass AC conductors
taking care to respect the order, N*,
L1, L2, L3.
5. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
6. Put the protective covers back in
place.
34020846EN/AD - Page 39
1. Installation
Connecting the power cables > External bypass cabinet
1200 kVA
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
Right-hand view
Top view
22
1
1
1
Connection through the top
Connection through the bottom
Key
(1) Front protective covers
5
Front view
A
766
(2) Roof protective cover
(3) Earthing bar
(4) To the UPSs
(5) To bypass AC line
(6) To the load
1. Remove the protective covers (1)
6
and/or (2).
1
1
Front
1
view
1
OFF
7
Q1 Q4S Q3BP Q5N
OFF
3
The handle of the Q3BP switch (in
the OFF position) on all UPS units
5
4
7
must be removed.
A
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
1. Check that switches Q3BP ext (1)
and Q5N ext (2) are in the OFF
position as shown opposite.
N L1 L2 L3
Q3BP
ext
N L1 L2 L3
Q5N
ext
1270
807
N L1 L2 L3
OFF
OFF
559
UPSsBypass Load
Earth
AC
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the UPS conductors taking
care to respect the order, N*, L1, L2,
L3.
4. Connect the bypass AC conductors
taking care to respect the order, N*,
L1, L2, L3.
5. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
6. Put the protective covers back in
place.
34020846EN/AD - Page 40
2000 kVA
Remove the protective covers
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
1. Installation
Connecting the power cables > External bypass cabinet
Right-hand
view
Front
view
11
Top view
22
3
Connection through the top
Connection through the bottom
A
6
7
Front view
Key
(1) Front protective covers
(2) Roof protective covers
(3) Earthing bar
(4) To the earth
(5) To the UPSs
(6) To bypass AC line
(7) To the load
1. Remove the protective covers (1)
OFF
and/or (2).
OFF
3
Q1 Q4S Q3BP Q5N
The handle of the Q3BP switch (in
the OFF position) on all UPS units
6
7
A
must be removed.
45
Connecting the power cables
This operation must be carried out by qualified personnel.
See “Characteristics of the connection terminals”, page 21.
1550
650
N L1 L2 L3
Earth
L3L1 NL2
UPSsBypass
AC
Q3BP
ext
OFF
Q5N
ext
OFF
N
L1 L2 L3
Load
1230
1. Check that switches Q3BP ext (1)
and Q5N ext (2) are in the OFF
position as shown opposite.
2. Connect the protective conductor
(PE or PEN) to the earth bar.
3. Connect the UPS conductors taking
care to respect the order, N*, L1, L2,
L3.
4. Connect the bypass AC conductors
taking care to respect the order, N*,
L1, L2, L3.
5. Connect the load conductors taking
care to respect the order, N*, L1, L2,
L3.
6. Put the protective covers back in
place.
* SLT upstream TNC, downstream TNC, TNS or TT, See “Adapting the cabinet according to the neutral point connection”,
page 26.
34020846EN/AD - Page 41
1. Installation
Connecting the power cables >
SSC maintenance cabinet
800 and 1200 kVA
Remove the protective covers
This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Right side view
Top view
22
5
Front view
lKey:
A
766
(1) Front face protective covers
(2) Roof protective cover
(3) Earth bar
(4) To Earth
(5) To the load
(6) To the SSC
(7) To the UPS
1
1
Front
1
1
1
view
1
.
1
3
5
Top entry
4
Bottom entry
Connect the cables
This operation may only be carried out by authorized staff.
See “Characteristics of the connection terminals”, page 21.
N L1 L2 L3
Q3BP
ext
N L1 L2 L3
Q5N
ext
559
N L1 L2 L3
OFF
OFF
OFF
OFF
807
1270
6
1 - Remove protective covers (1) and/
or (2).
7
7
A
1 -Check switches Q3B ext (1) and
Q5N ext (2) are in the OFF position as
shown opposite.
2 - Connect the protective conductor
(PE or PEN) to the earth bar
3 - Connect the UPS conductors in the
following order: L1, L2, L3
4 - Connect the AC Bypass
conductors in the following order: L1,
L2, L3
5 - Connect the load conductors in the
following order: L1, L2, L3
6 - Refit the protective covers
34020846EN/AD - Page 42
LoadNSUPSEarth
2000 kVA
1. Installation
Connecting the power cables > SSC maintenance cabinet
This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Right side view
Top entry
Bottom entry
Front
view
.
3
11
Top view
22
Key:
(1) Front face protective covers
(2) Roof protective covers
6
Front view
A
7
(3) Earth bar
(4) To Earth
(5) To the load
(6) To the SSC
(7) To the UPS
1 - Remove protective covers (1) and/
OFF
or (2).
OFF
3
6
7
45
A
Connect the cables
This operation may only be carried out by authorized staff.
See “Characteristics of the connection terminals”, page 21.
L3L1 NL2
1550
N L1 L2 L3
650
Q3BP
ext
OFF
Q5N
ext
OFF
N
L1 L2 L3
1230
1 -Check switches Q3BP ext (1) and
Q5N ext (2) are in the OFF position as
shown opposite.
2 - Connect the protective conductor
(PE or PEN) to the earth bar
3 - Connect the UPS conductors in the
following order: L1, L2, L3
4 - Connect the AC Bypass
conductors in the following order: L1,
L2, L3
5 - Connect the load conductors in the
following order: L1, L2, L3
Valid for UPS, external-bypass, SSC and battery cabinets
Interconnect the earths and tie down the wires
This operation must be carried out by qualified personnel.
The door must be opened using a Ronis 405 key.
The protective covers must be removed.
Connect the ECPs of all the cabinets
in the installation using an additional
earthing cable (not supplied) with the
characteristics below.
- Minimum size is half that of a phase
earthing conductor, same type of
cable as for phase conductors.
- As short as possible.
Cabinet 1
Main earth
Cabinet 2
Additional earthing cable between cabinets
1.8 Connecting the synchronization module
Refer to the “synchronization module installation manual" no. 34000346
Cabinet 3
34020846EN/AD - Page 44
1.9 Connect the backfeed option
The backfeed option is compulsory if IEC 62040-1-2 is to be complied with.
Block diagram
1. Installation
Connect the backfeed option >
Normal ACNormal AC
Connect the power cables
This operation may only be carried out by authorized staff.
The door must be opened using the Ronis 405 key.
Right side view
Backfeed
Front view
UPS
A
Front view
1
740
590
4235
Key:
(1) Front face protective cover
(2) Earth Bar
(3) To Earth
(4) To AC Normal
(5) To the UPS
1 - Remove protective cover (1)
2 - Connect the protective conductor (PE or PEN) to the earth bar (2)
3 - Connect the AC Normal conductors in the following order: L1, L2, L3 (4)
4 - Connect the UPS conductors in the following order: L1, L2, L3 (5)
5 - Refit the protective cover
A
34020846EN/AD - Page 45
1. Installation
Connecting the control-wire cables >
1.10 Connecting the control-wire cables
The maximum total length of CAN inter-cabinet cables must not exceed 180m.
Connecting a modular UPS or frequency converter alone.
This operation must be carried out by qualified personnel.
The door must be open.
Key
XM2
XM3
XM4
XM5
XM6
XM2
XM3
XM4
XM5
XM6
XM7
1
(1) Connectors
1. Fit a blue plug on connector XM06
in the UPS.
2. Fit a red plug on connector XM7 in
the UPS.
1
XM7
2
34020846EN/AD - Page 46
Connecting the UPS units in parallel
Connecting the modular UPS units in parallel
This operation must be carried out by qualified personnel.
The door must be open.
The supplied cables are 10 or 20 m long; The maximum total length must not exceed 180m.
On exiting the cabinet, the cables must run along the earthing and connection cables between cabinets.
1. Installation
Connecting the control-wire cables >
Key
2
3
2
2
Example for two UPSs
UPS 1
XM2
XM3
XM6
2
XM2
XM3
XM4
XM5
XM6
XM7
1
(1) Connectors
(2) Cable ties
(3) Exchange-current and CAN cables
Exchange current
1. Connect the XM2 and XM3
UPS 2
1
1
XM2
XM3
connectors in the two UPS units.
CAN
2. Fit a blue plug on connector XM6 in
UPS1.
3. Connect XM7 in UPS1 to
XM6 in UPS2.
4. Fit a red plug on connector XM7 in
UPS2.
XM6
XM7
3
4
XM7
34020846EN/AD - Page 47
1. Installation
Connecting the control-wire cables > Connecting the UPS units in parallel
Connecting the modular UPSs with the external bypass
This operation must be carried out by qualified personnel.
The door must be open.
The supplied cables are 10 or 20 m long; The maximum total length must not exceed 180m.
To ensure sufficient isolation of exchange-current, CAN and external-bypass cables, they must be run separately
from the power cables.
On exiting the cabinet, the cables must run along the earthing and connection cables between cabinets.
Q1 Q4S Q3BP Q5N
UPS cabinet
2
3
2
2
Bypass cabinet
3
2
2
2
XM2
XM3
XM4
XM5
XM6
XM7
1
2
3
4
5
6
1
COM
Q3BP ext
Q5N ext
The handle of the Q3BP switch (in
the OFF position) on all UPS units
must be removed.
Key
(1) Connectors
(2) Cable ties
1
1
(3) Exchange-current, CAN and
control-wire cables
Key
(1) Connectors
(2) Cable ties
(3) Control-wire cables
UPS 1
XM2
XM3
XM4
XM5
XM6
XM7
External
3
bypass
cabinet
UPS 2
2
UPS 3
222
444
1
1
2
3
COM
Q3BP ext
XM 4 / XM 5
Q5N ext
Q5N customer
Q3BP ext
COM
4
5
Q5N ext
6
1
UPS 4
XM2
XM3
XM5
XM6
XM7
XM7
4
1
Connection with bypass cabinet
Control wires
1. Connect the common, Q3BP ext
and Q5N ext terminals on the terminal
block in the external bypass cabinet to
connector XM4 in UPS4 and XM5 in
UPS1 (cables not supplied).
Exchange current
2. Create a loop between the XM2 and
XM3 connectors in the four UPS units.
All the connectors must be used.
CAN
3. Fit a blue plug on connector XM6 in
5
UPS1.
4. Interconnect the XM6 and XM7
connectors in the four UPS units.
5. Fit a red plug on connector XM7 in
UPS4.
34020846EN/AD - Page 48
Connecting the control-wire cables > Connecting the UPS units in parallel
Connecting parallel UPSs with SSC (static-switch cabinet)
This operation must be carried out by qualified personnel.
The door must be open.
The supplied cables are 10 or 20 m long; The maximum total length must not exceed 180m.
To ensure sufficient isolation of exchange-current and CAN cables, they must be run separately from the power
cables.
On exiting the cabinet, the cables must run along the earthing and connection cables between cabinets.
UPS cabinet
1. Installation
Key
2
3
2
2
SSC
2
2
2
3
2
XM2
XM3
XM4
XM5
XM6
XM7
XM2
XM3
XM4
XM5
XM6
XM7
(1) Connectors
(2) Cable ties
(3) Exchange-current and CAN cables
1
Key
(1) Connectors
(2) Cable ties
(3) Exchange-current and CAN cables
1
UPS 1UPS 2UPS 3UPS 4
XM2
XM3
XM4XM4
XM5
XM6
XM7
1111
2
3333
1
XM 4 / XM 5
Q5N ext
Q5N customer
Q3BP ext
COM
4
1
XM 4 / XM 5
Q5N ext
Q4S ext
Q3BP ext
COM
SSC
XM2
XM3
XM5
XM6
XM7
XM7
Exchange current
1 Create a loop between the XM2 and
XM3 connectors in the four UPS units
and the SSC.
All the connectors must be used.
CAN
2. Fit a blue plug on connector XM6 in
UPS1.
3. Interconnect the XM6 and XM7
connectors in the four UPS units and
the SSC.
4. Fit a red plug on connector XM7 in
the SSC.
4
4
1
34020846EN/AD - Page 49
1. Installation
Connecting the control-wire cables > Connecting the UPS units in parallel
Connect the components specific to the 2000 kVA light SSC
This operation may only be carried out by authorized staff.
The door must be open
The cables (not supplied) must be twisted pairs of AWG18 gauge wire with a maximum length of 100m.
Auxiliary wires (exchange, CAN) and power cables must be separated to ensure sufficient insulation for the
auxiliary wires.
Once outside the cabinet, the cables must follow the earth connections between the cabinets.
1
Key:
(1) UPS current sensor terminal block
Suitable current sensors must be used to ensure correct operation of the installation. Please contact your technical helpline
to select the correct customer current sensors.
Recommendations: 4000/1 CT, class 1, 10 VA
Take care to respect polarity when wiring customer current sensors.
2000 light NS cabinet
Terminal block
P1
4
{
5
{
6
{
1 - Connect the terminal block connectors to the customer current sensors in the customer connection panel.
For the installation to operate properly, the following must be respected:
Customer switches Q4S, Q3BP and Q5N must be electrically wired to behave like those of a SSC that contains switches.
The auxiliary contact of a customer switch must be a normally open contact when the switch is open.
1
P2
2
P1
3
P2
4
P1
5
P2
6
P1
P2
1
P1
P2
2
P1
P2
3
Key:
(1) Current sensor TI7 - Phase 1
(2) Current sensor TI8 - Phase 2
(3) Current sensor TI9 - Phase 3
(4) To the customer connection panel
- phase 1 customer current sensor
(5) To the customer connection panel
- phase 2 customer current sensor
(6) To the customer connection panel
- phase 3 customer current sensor
Connect the SSC maintenance cabinet
34020846EN/AD - Page 50
There are no auxiliary wire connections to be made on the SSC maintenance cabinet.
Connecting the EPO function
This operation must be carried out by qualified personnel.
The door must be open.
The moving door must be open.
The cables (not supplied) must have SELV insulation and the maximum size is 2.5 mm².
To ensure sufficient isolation of control-wire (EPO) cables, they must be run separately from the power cables.
2
3
2
1. Installation
Connecting the control-wire cables >
Key
XM14
XM12
XM10
XM8
XB1
R29
R54
R116 R94 R57
HE1
PT1
C16
VZ5
C15
C10
C14
C12
C13
PT3
C11
PT2
C9
C4
XM9
R32
R28
R25
R31
R27
R26
R30
ET1
R24
R23
XM7
EH1
C3
C7R7C8
NR1
XB2
R2
VT1
R1
C2
VD1
R6
R138
R5
C6
L1
R4
R157
R154
R156
XM5
C5
R159
R155
R158
XM2
XM1
XM3
R11
NR2
C33
R148
R146
VZ1
R10
VD15
C17
R137
R147
C1
VP1
R8
R3
NR3
R9
XM21
XB3
XM25
XB4
R115
R53
R56
R93
R52
R114 R92 R55
VZ6
VZ7
C24
R113
R91
XM11
R112
R90
VZ8
VZ9
VZ10
R111
R89
XM15
R38
R105
R107
R109
R37
XM13
R36
R108
R110
R106
R35
R51
R136
R132
R134
R34
R33
R131R133
R135
R63
R59
R61
XM16
R50
R62
R60
R58
VD5
VD14
1
R49
VD13
XM17XM18
XM22
R22
R88
R79
R104
R87
R78
R103
R77
R102
R86
XB5
R76
R101
R85
1
R75R74
R100
R99
R83R84
R42
R44
VD8
VD6
VD7
XM6
VD4
C23
R73
R72
R127
VT2
R43
VP7
R39
R41
R152
R126
XM24
R125
R46
R45
R71
VP6
VD12
XM4
R48
C20
R124
R123
DI1
VD11
R70
R47
VP5
R122
C19
VD3
VD2
R97
R20
VT3
R98
R96
R15
R82
C32
R121
C18
R69
R81
R19
C22
XM23
K2
VP3
K1
VP4
VP2
R139
R140
VZ4
VD10
R18
R120
VZ11
R80
R95
R12
R66
R68
C21
R17
R14
R65
R119
R142
R118
L2
R67
R143
R16
R64
R13
R117
L3
XM20
XB6
XM19
(1) Connectors
(2) Cable ties
(3) Cables
Caution.
In the UPS or the SSC, the general shutdown causes UPS shutdown and opening of the battery circuit breaker (with
opening of the bypass static switch depending on personalisation settings).
The Emergency Power Off (EPO) notion is applicable to installations where pressing the button also causes the
circuit breakers on the upstream normal AC source and bypass AC source to open.
In parallel configurations, there must be a single general shutdown button with a separate contact for each UPS unit.
1. Remove the jumper on the XM19
1
terminal block (1).
2. Connect the general shutdown NC
XM 20XM 21XM 25
XM 19
contact to terminals 1 and 2 (SELV).
1111
3. Tie the cable down as illustrated.
34020846EN/AD - Page 51
1. Installation
Connecting the control-wire cables >
Connecting the dry-contact communication card
This operation must be carried out by qualified personnel.
The door must be open.
The cables (not supplied) must have SELV insulation.
To ensure sufficient isolation of control-wire (contact signal) cables, they must be run separately from the power
cables.
2
2
3
2
2
Key
(1) Connectors
(2) Cable ties
ET1
L8
C23
R35
C22
L4
L3
C6
L7
VD4
R23
R34
C7
R31
R15
XM4
C21
VP4
XM4
L6
VD3
R14
R22
R32
C16
R29
R13
1
C20
VP3
L5
VD2
R12
R28
R21
C15
R25
R11
C19
VP2
VD1
R10
R26
R20
C14
R9
VP1
R8
C13
R19
XM1
R7
R18
R6
DI2
R5
R17
C12
K6
DI1
C11
C10
XM3
XM3
K5
C18
K4
K3
C5
L2
C4
C2
C9
C17
XM5
L1
K2
C3
XM2
C8
XM2
C1
K1
EP1
(3) Cables
XM 4
XM 3
XM 2
Maximum characteristics of the input
1
IN4
I4
9 V
IN3
I3
9 V
IN2
9 V
IN1
9 V
I2
I1
1
contacts (1)
Switched voltage: 9 V DC (supplied by
the UPS)
Consumption: 20 mA
Cable: 4 x 0.34 mm², diameter 5 ± 0.5
mm
In installations with parallel
devices, the input contacts
must be unique and include
1
OUT6
COM6
O6
OUT6
OUT5
O5
COM5
OUT5
OUT4
O4
COM4
OUT4
1
OUT3
COM3
O3
2
OUT3
OUT2
O2
COM2
device.
Maximum characteristics of the
output contacts (2)
Permissible voltage: SELV only
Permissible current 1 A at 30 V DC
Cable: 4 x 0.93 mm², diameter 6.6 ± 0.3
mm
The dry contacts can be configured,
see "Dry-contact parameters" in user
manual no. 3402084700.
OUT2
OUT1
O1
COM1
OUT1
a separate contact for each
34020846EN/AD - Page 52
Assembling and connecting the external battery cabinet >
1.11 Assembling and connecting the external battery cabinet
Assembling the empty battery cabinet
Mounting the battery circuit-breaker kit
Please contact our Sales department when selecting the battery circuit breaker.
Only one circuit breaker is necessary even if there are several battery cabinets.
1. Secure the plate.
1. Installation
x4
1
XR1
1
2
3
XR1
4
5
2
6
BC-
7
BC+
8
+12V
9
-12V
10
2. Secure connector XR1.
3. Secure the temperature sensor.
3
Mounting the shelves
Assembly of the battery cabinet must be carried out by certified personnel (standard EN 50091-1-2).
The minimum clearance between the top of battery cells and the next shelf is 150 mm.
1
1
1
1. Secure the corner supports (6 screws per
support).
2. Install the shelf.
3. Secure the shelf with two screws in each
corner.
2
3
3
34020846EN/AD - Page 53
1. Installation
Assembling and connecting the external battery cabinet > Connecting the power cables
4. Connect the control-wire cables (See
“Connecting the control-wire cables”,
page 55.).
Connecting the power cables
This operation must be carried out by qualified personnel.
The door must be open.
The protective cover must be removed.
The battery circuit breaker must be open.
12
x2
5
+
B +
-
B-
5. Secure the protective cover after
connecting the batteries to the circuit
breaker.
Key
(1) To the UPS cabinet
(2) To the battery or auxiliary battery
cabinet 2
1. Connect the earthing conductor to
the earthing bar in the battery
cabinet(1).
2. Connect the positive conductor (+)
to the positive terminal.
3. Connect the negative conductor (-)
to the negative terminal.
4. Secure the protective cover after
connecting the batteries to the circuit
breaker.
34020846EN/AD - Page 54
For more information, see the "Battery circuit-breaker kit in a cabinet" installation manual no. 34021530.
Connecting the control-wire cables
Connecting the battery circuit breaker
This operation must be carried out by qualified personnel.
The UPS door must be open.
The moving door of the UPS must be open.
The cables (not supplied) must have SELV insulation and the maximum size is 2.5 mm².
UPS cabinet
2
2
1. Installation
Assembling and connecting the external battery cabinet >
Key
XM14
XM12
XM10
XM8
XB1
R29
R54
R116 R94 R57
HE1
PT1
C16
VZ5
C15
C10
C14
C12
C13
C11
PT3
PT2
C9
C4
XM9
R35
R32
R28
R25
R34
R31
R27
R33
R30
R26
ET1
R24
R23
XM7
R22
EH1
C3
C7R7C8
NR1
XB2
R2
VT1
R1
C2
VD1
R6
R138
R5
C6
L1
R4
R157
R154
R156
XM5
C5
R159
R155
R158
XM2
XM1
XM3
R11
NR2
C33
R148
R146
VZ1
R10
VD15
C17
R137
R147
C1
VP1
R8
R3
NR3
R9
R143
XM21
XB3
XM25
XB4
R115
R53
R56
R93
R52
R114 R92 R55
VZ6
VZ7
C24
R113
R91
R112
XM11
R90
VZ8
VZ9
VZ10
R111
R89
XM15
R38
R105
R107
R109
R37
XM13
R36
R108
R110
R106
R51
R136
R132
R134
R131R133
R135
R63
R59
R61
XM16
R50
R62
R60
R58
VD5
1
VD14
R49
VD13
XM17XM18
XM22
R88
R79
R104
1
R87
R78
R103
R77
R102
R86
XB5
R76
R101
R85
R75R74
R100
R99
R83R84
R42
R44
VD8
VD6
VD7
XM6
VD4
C23
R73
R72
R127
VT2
R43
VP7
R39
R41
R152
R126
XM24
R125
R46
R45
R71
VP6
VD12
XM4
R48
C20
R124
R123
DI1
VD11
R70
R47
VP5
R122
C19
VD3
VD2
R97
R20
VT3
R98
R96
R15
R82
C32
R121
C18
R69
R81
R19
C22
XM23
K2
VP3
K1
VP4
VP2
R139
R140
VZ4
VD10
R18
R120
VZ11
R80
R95
R12
R66
R68
C21
R17
R14
R65
R119
R142
R118
L2
R67
R16
R64
R13
R117
L3
XM20
XB6
XM19
(1) Connectors
(2) Cable ties
(3) To the battery circuit breaker
3
Connecting a single battery circuit breaker
XM 25
XM 19XM 20XM 21
Connecting two battery circuit breakers
XM 25
3
XM 19XM 20XM 21
112345678910
12
Connecting three battery circuit breakers
1. Connect the UPS to the battery circuit
breaker in the auxiliary cabinet as per
the diagram opposite.
1111234
2. Tie down the cable as shown in the
UPS-cabinet diagram.
1. Connect the UPS to the battery circuit
breakers in the auxiliary cabinets as per
the diagram opposite.
2. Tie down the cable as shown in the
3
12
UPS-cabinet diagram.
The controls of circuit breakers 2 and 3 are not separated.
34020846EN/AD - Page 55
1. Installation
Assembling and connecting the external battery cabinet > Connecting the control-wire cables
Connecting the battery temperature sensor
This operation must be carried out by qualified personnel.
The UPS door must be open.
The moving door of the UPS must be open.
The cables (not supplied) must be shielded, twisted-pair cables (STP), with a minimum size of 0.1 mm2 and a maximum
length of 100 m.
To ensure sufficient isolation of control-wire cables, they must be run separately from the power cables.
UPS cabinet
Key
XM14
XM12
XM10
XM8
XB1
R29
R54
R116 R94 R57
HE1
PT1
C16
VZ5
C15
C10
C14
C12
C13
PT3
C11
PT2
C9
C4
XM9
R32
R28
R25
R31
R27
R26
R30
ET1
R24
R23
XM7
EH1
C3
C7R7C8
NR1
XB2
R2
VT1
R1
C2
VD1
R6
R138
R5
C6
L1
R4
R157
R154
R156
XM5
C5
R159
R155
R158
XM2
XM1
XM3
R11
NR2
C33
R148
R146
VZ1
R10
VD15
C17
R137
R147
C1
VP1
R8
R3
NR3
R9
XM21
XB3
XM25
2
3
2
XB4
R115
R53
R56
R93
R52
R114 R92 R55
VZ6
VZ7
C24
R113
R91
XM11
R112
R90
VZ8
VZ9
VZ10
R111
R89
XM15
R38
R105
R107
R109
R37
XM13
R36
R108
R110
R106
R35
R51
R136
R132
R134
R34
R33
R131R133
R135
R63
R59
R61
XM16
R50
R62
R60
R58
VD5
1
VD14
R49
VD13
XM17XM18
XM22
R22
R88
R79
R104
1
R87
R78
R103
R77
R102
R86
XB5
R76
R101
R85
R75R74
R100
R99
R83R84
R42
R44
VD8
VD6
VD7
XM6
VD4
C23
R73
R72
R127
VT2
R43
VP7
R39
R41
R152
R126
XM24
R125
R46
R45
R71
VP6
VD12
XM4
R48
C20
R124
R123
DI1
VD11
R70
R47
VP5
R122
C19
VD3
VD2
R97
R20
VT3
R98
R96
R15
R82
C32
R121
C18
R69
R81
R19
C22
XM23
K2
VP3
K1
VP4
VP2
R139
R140
VZ4
VD10
R18
R120
VZ11
R80
R95
R12
R66
R68
C21
R17
R14
R65
R119
R142
R118
L2
R67
R143
R16
R64
R13
R117
L3
XM20
XB6
XM19
(1) Connectors
(2) Cable ties
(3) Cables
Connecting a sensor to a single UPS cabinet
UPS
XM 25
-12V
BC -
BC +
+ 12 V
11
XM 21
-12 V
BC
BC+
XR2
Sensor
The sensor may be located in a battery cabinet or in a battery room for batteries on racks.
XR1
+12
12
1. Connect the UPS to the temperature
sensor in the auxiliary cabinet as per the
diagram opposite (Cables not supplied).
2. Tie down the cable as shown in the
UPS-cabinet diagram.
34020846EN/AD - Page 56
Assembling and connecting the external battery cabinet > Connecting the control-wire cables
Connecting a sensor to a number of UPS cabinets
1. Installation
1. Connect the UPSs to the temperature
+ 12 V
UPS n
-12V
sensor in the auxiliary cabinet as per the
diagram opposite (Cables not supplied).
2. Tie down the cable as shown in the
BC -
BC +
+ 12 V
UPS 1
XM 25XM 25XM 25
-12V
BC -
BC +
+ 12 V
UPS 2
-12V
BC -
BC +
UPS-cabinet diagram.
1
XM 21XM 21XM 21
-12 V
+
XR2
XR1
+12
12
Sensor
The sensor may be located in a battery cabinet or in a battery room for batteries on racks.
34020846EN/AD - Page 57
2. Appendices
2.1 Assembling 2000 kVA SSCs
Right hand side cabinet
Rear view
Left hand side cabinet
Side view
X 3
1
1
Right hand side cabinet
12
6
11
234
1 - Place the cabinets in their definitive
position
2 - Adjust the front feet to ensure the
cabinets are vertical and the doors
aligned.
3 - Remove the two inter-cabinet
uprights (1) located behind the right
hand side cabinet.
3 - Unbolt the 7 fishplates (2) (3) (4)
4 - Align the fishplates horizontally
5 - Fit the 3 upper-part fishplates L1, L2,
L3 (2) between the 2 cabinets
6 - Fit the neutral fishplate (3) between
the 2 cabinets
7 - Fit the 3 lower-part fishplates L1, L2,
L3 (4) between the 2 cabinets
8 - Connect the the two earthing braids
(5) between the front uprights of both
cabinets
2.2 IP 32 option
Refer to the "IP 32" manual no. 3460028300 for more details on this option
X 1
X 3
9 - Connect the auxiliary wires between
the connectors (6) of both cabinets
10 - Fit the inter-cabinet uprights (1)
between the two cabinets
15
13
14
34020846EN/AD - Page 58
2.3 Electrical characteristics
Selection of protection devices
Upstream
CB
BYPASS AC
NORMAL AC
(not supplied)
Downstream
CB
(not supplied)
Q4S
output
fuses
input
fuses
2. Appendices
Electrical characteristics >
Upstream
CB
(not supplied)
Load
Q1
Q5N
When sizing the upstream circuit breakers, the parameters presented below must be taken into account.
Time/current curves for UPS input and output fuses
10
10
10
10
1
10
10
10
t (s)
4
3
2
250-300 kVA : 630A
400 kVA : 800A
500 kVA : 1000A
-
1
-
2
-
3
-
4
10
10
10
2
10
3
10
I (A)
4
UPS short-circuit current with inverter coupled and bypass AC source out of tolerances
Sn250 kVA300 kVA400 kVA500 kVA
In (at 400 V) 361 A433 A577 A721 A
Isc1085 A1085 A1446 A1975 A
34020846EN/AD - Page 59
2. Appendices
Electrical characteristics >
Line-current values
Rated
power of
each UPS
unit
250 kVA368 A441 A530 A630 A
300 kVA442 A530 A636 A630 A
400 kVA587 A706 A848 A800 A
500 kVA735 A881 A1058 A1000 A
Continuous input
current at U=400V
Input current for load PF =
0.9, U = 400 V at 1.25 In
overload limited to 10 min.
Permissible UPS overloads as a function of time
I/In
2,2
2
1,8
1,6
1,4
1,2
Input current for load PF =
0.9, U = 400 V at 1.5 In
overload limited to 30 sec.
20°C30°C35°C40°C
Input/output fuse
ratings
1
1010,1
1030
10
2
600
10
3
10
4
10
t (s)
5
34020846EN/AD - Page 60
2. Appendices
General characteristics of MGE TM Galaxy TM 7000 UPSs >
2.4 General characteristics of MGE
UPS power in kVA250300400500
Normal AC input
Number of conductors3 phases
Reference voltage at Pn380 V to 415 V
Reference frequency45 Hz to 66 Hz
THDITypically 3% at Pn
Power factor> 0.99
Bypass AC input
Number of conductors3 phases + neutral
Reference voltage at Pn380 V to 415 V
Reference frequency45 Hz to 66 Hz
Load output
Number of conductors3 phases + neutral
Set phase-to-phase voltages380 V / 400 V / 415 V
Set phase-to-neutral voltages220 V / 230 V / 240 V
TM
Galaxy TM 7000 UPSs
Voltage variation± 1%
Adjustable frequencies and tolerance
(on battery power)
Voltage variation for 0 to 100% load
step change
Permissible overloads150% for 30 seconds, 125% for 10 minutes
THDU Ph-to-Ph and Ph-to-N for
nonlinear load
Battery
Standard battery technologySealed lead-acid battery (gas-recombination)
UPS
Active power (kW) 112225135270180360225450
Efficiency94.194949494.1949494.3
Heat losses in kW
Heat losses in calories/s
Storage temperature range-25°C to +45°C
Operating temperature range at Pn0°C to 35°C
50 Hz or 60 Hz ± 0.1 Hz
± 1%
< 2% Ph-to-Ph
(Valve Regulated Lead Acid type)
PN/2PNPN/2PNPN/2PNPN/2PN
7
1673
14.3
3418
8.6
2055
17.2
4111
11.2
2676
22.9
5473
14.3
3418
27.2
6500
Relative humidity45% to 75%
Maximum operating altitude without
derating
Noise level (dBa)75
Product standardsIEC 62040
Safety standardsIEC 62040-1-2
Protection standardsIEC 62040-3
EMC standardsIEC 62040-2
< 1000 m
34020846EN/AD - Page 61
2. Appendices
General characteristics of MGE TM Galaxy TM 7000 UPSs >