Thank you for selecting an APC by Schneider Electric product to protect your electrical equipment.
The MGE
We recommend that you take the time to read this manual to take full advantage of the many features of your UPS
(Uninterruptible Power System).
TM
GalaxyTM 7000 range has been designed with the utmost care.
APC by Schneider Electric pays great attention to the environmental impact of its products.
Measures that have made MGE
◗ the eco-design approach used in product development,
◗ the elimination of harmonic disturbances reinjected into the AC source,
◗ production in an ISO 14001 certified factory,
◗ recycling of the MGE
TM
TM
GalaxyTM 7000 a reference in environmental protection include:
GalaxyTM 7000 at the end of its service life.
To discover the entire range of APC by Schneider Electric products and the options available for the MGE
range, we invite you to visit our web site at www.apc.com or contact your local representative.
TM
GalaxyTM 7000
34020846EN/AD - Page 2
All products in the MGETM GalaxyTM 7000 range are protected by patents. They implement original technology not available to
competitors of APC by Schneider Electric.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning
technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric.
This document may be copied only with the written consent of Schneider Electric or its affiliated companies. Authorised copies
must be marked
The UPS must be installed in a room with restricted access in compliance with standard IEC 60364-4-482).
Only qualified personnel are authorised to enter this restricted access room.
A UPS has its own internal power source (the battery). Consequently, the power outlets may be energised even if the UPS is
disconnected from the AC-power source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
The UPS must be properly earthed.
The battery supplied with the UPS contains small amounts of toxic materials. Caution, replacement of the battery
by a battery of the wrong type can result in an explosion.
To avoid accidents, the instructions below must be observed.
◗ Never operate the UPS if the ambient temperature and relative humidity are higher than the levels specified in the
documentation.
◗ Never burn the battery (risk of explosion).
◗ Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
◗ Comply with all applicable regulations for the disposal of the battery.
◗ Caution, wait five minutes before opening the UPS to allow the capacitors to discharge.
◗ Caution, there is high leakage current: the earthing conductor must be connected first and disconnected last.
◗ The product must be installed on a non-inflammable surface (e.g. concrete).
◗ Caution, battery replacement must be carried out by qualified personnel.
◗ Isolate the Uninterrptible Power Supply (UPS) before working on the circuits upstream.
◗ The UPS can only be used in a controlled indoor environment.
Safety
Product safety
◗ Protection (circuit breaker/switch disconnector) must be installed upstream and be easily accessible.
◗ Never install the UPS near liquids or in an excessively damp environment.
◗ Never let a liquid or foreign body penetrate inside the UPS.
◗ Never block the ventilation grates of the UPS.
◗ Never expose the UPS to direct sunlight or a source of heat.
◗ When replacing battery cells, use the same type and number of cells.
Special precautions
◗ The UPS connection instructions contained in this manual must be followed in the indicated order.
◗ Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the
equipment to be connected to the UPS.
◗ If the UPS must be stored prior to installation, storage must be in a dry place.
◗ The admissible storage temperature range is -25°C to +45°C
◗ If the UPS remains de-energised for a long period, we recommend that you energise the UPS for a period of 24 hours, at least once every
month. This charges the battery, thus avoiding possible irreversible damage.
◗ The UPS is designed for normal climatic and environmental operating conditions concerning the altitude, ambient operating temperature,
relative humidity and ambient transport and storage conditions.
◗ Using the UPS within the given limits guarantees its operation, but may affect the service life of certain components, particularly that of the
battery and its autonomy. The maximum storage time of the UPS is limited due to the need to recharge its integrated battery.
◗ Unusual operating conditions may justify special design or protection measures:
- harmful smoke, dust, abrasive dust,
- humidity, vapour, salt air, bad weather or dripping,
- explosive dust and gas mixture,
- extreme temperature variations,
- poor ventilation,
- conductive or radiant heat from other sources,
- cooling water containing acid or impurities which may cause scale, silt, electrolysis or corrosion of converter parts exposed to water,
- strong electromagnetic fields,
- radioactive levels higher than those of the natural environment,
- fungus, insects, vermin, etc.,
- battery operating conditions.
The UPS must always be installed in compliance with:
◗
◗ the requirements of standard IEC 60364-4-42: Protection from thermal effects.
◗ standard IEC 60364-4-41: protection against electric shock.
◗ standard IEC 60364-4-482: Electrical installations of buildings.
◗ standard NFC 15-100 (in France).
◗ the requirements of standard IEC 62040-1-2:
34020846EN/AD - Page 3
Foreword
Pictograms
Document
Danger, these instruction are
imperative.
Information, advice, help.LED off
Visual indicationLED flashing
ActionLED on
Audio signal.
34020846EN/AD - Page 4
APC by Schneider Electric has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
The cardboard we use comprises over 30% of recycled cardboard.
Sacks and bags are made of polyethylene.
Packing materials are recyclable and bear the appropriate identification symbol .
MaterialsAbbreviationNumber
in the symbol
Polyethylene terephthalatePET01
High-density polyethyleneHDPE02
Polyvinyl chloridePVC03
Low-density polyethyleneLDPE04
Environment
PolypropylenePP05
PolystyrenePS06
Follow all local regulations for the disposal of packing materials.
End of life
APC by Schneider Electric will process products at the end of their service life in compliance with local regulations.
APC by Schneider Electric works with companies in charge of collecting and eliminating our products at the end of their
service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing centre for electrical and electronic waste.
Make the product unusable by cutting the internal supply cables.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning
batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
The "Material Safety Data Sheets" (MSDS) for the batteries are available on our web site*.
(*) For more information or to contact the Product Environmental manager, use the "Environmental Form" on the site:
http://environment.apc.com
34020846EN/AD - Page 5
Contents
1. Installation
1.1 Possible installations .........................................................................................................................10
Single or modular UPS alone .............................................................................................................10
Parallel UPS systems .........................................................................................................................10
Modular UPSs in parallel ...........................................................................................................10
Modular UPSs in parallel with external bypass cabinet .............................................................10
Parallel UPSs with SSC (static-switch cabinet) .........................................................................11
Parallel UPS with SSC and SSC maintenance cabinet ............................................................11
UPS set up as a frequency converter .................................................................................................12
Single UPS ................................................................................................................................12
Parallel UPS systems ................................................................................................................12
Connect the power cables ................................................................................................................. 45
1.10 Connecting the control-wire cables ............................................................................................... 46
Connecting a modular UPS or frequency converter alone. ............................................................... 46
Connecting the UPS units in parallel ................................................................................................. 47
Connecting the modular UPS units in parallel .......................................................................... 47
Connecting the modular UPSs with the external bypass .......................................................... 48
Connecting parallel UPSs with SSC (static-switch cabinet) ..................................................... 49
Connect the components specific to the 2000 kVA light SSC .................................................. 50
Connect the SSC maintenance cabinet .................................................................................... 50
Connecting the EPO function ............................................................................................................ 51
Connecting the dry-contact communication card ............................................................................... 52
1.11 Assembling and connecting the external battery cabinet ........................................................... 53
Assembling the empty battery cabinet ............................................................................................... 53
Mounting the battery circuit-breaker kit ................................................................................... 53
Mounting the shelves ................................................................................................................ 53
Connecting the power cables ............................................................................................................ 54
Connecting the control-wire cables .................................................................................................... 55
Connecting the battery circuit breaker ...................................................................................... 55
Connecting the battery temperature sensor ............................................................................. 56
2. Appendices
34020846EN/AD - Page 7
Contents
2.1 Assembling 2000 kVA SSCs ..............................................................................................................58
2.2 IP 32 option .........................................................................................................................................58
An operating temperature of 35°C is possible,
but battery life will be reduced.
Size the ventilation system taking into
account the values in the table below.
Heat losses to be
evacuated at Pn
SSC cabinets
Power rating in kVA80012002000
Air flow (m³/h)1000NaturalNatural
Heat losses to be
evacuated at Pn
Pn = rated power, for other values please consult the after-sales support or the local office.
kW14.317.222.927.2
Cal./s3418411154736501
kW3.7< 1< 1.5
Cal./s884< 240< 360
34020846EN/AD - Page 18
1.3 Prerequisites
UPS currents
1. Installation
Prerequisites >
UPS cabinets in kVAI rated of Normal
AC in A
250 351 361361490
300 420 433 433588
400 558 577 577784
500 700 722 722980
The table above is for 400 V interphase voltages and a load with a power factor of 0.9.
For other voltages (380 or 415 V), the current values must be multiplied by 1.05 and 0.96 respectively.
The battery current is an average current for a battery voltage of 488 V (44 blocks at 1.85 V/cell each), at Pn with a power
factor of 0.9.
Recommended upstream protection
Normal AC source
Stick a label with the following text on each upstream circuit breaker / switch-disconnector: "Isolate Uninterruptible
Power Supply (UPS) before working on this circuit".
Selection of protective devices is determined by the maximum continuous current (at 380 V).
Protection ratings are calculated for the maximum continuous current (at 380V).
UPS cabinets in kVACB / switch-disconnector Trip unit
250 NS 630N 3P *STR 23 SE
I rated of Bypass
AC in A
I rated of load
in A
I battery in A
300 NS 630N 3P *STR 23 SE
400 NS 800N 3P *Micrologic 2.0
500 NS 800N 3P * Micrologic 5.0
The circuit breakers / switch-disconnectors recommended above respect the requirements for discrimination with the UPS
fuses.
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
* For short-circuit currents > 40 kA, use a CB/SD with a higher breaking capacity (type L or H).
Bypass AC source
Stick a label with the following text on each upstream circuit breaker / switch-disconnector: "Isolate Uninterruptible
Power Supply (UPS) before working on this circuit".
Selection of protective devices is determined by the maximum continuous current (at 380 V).
Protection ratings are calculated for the maximum continuous current (at 380V).
UPS cabinets in kVA Maximum permissible
250 25 InNS 630N 4P *STR 23 SE
300 21 InNS 630N 4P *STR 23 SE
400 16 InNS 800N 4P *Micrologic 2.0
500 16 InNS 800N 4P *Micrologic 5.0
current for 20 ms
CB / switchdisconnector
Trip unit
The circuit breakers / switch-disconnectors recommended above respect the requirements for discrimination with the UPS
fuses.
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
* For short-circuit currents > 40 kA, use a CB/SD with a higher breaking capacity (type L or H).
34020846EN/AD - Page 19
1. Installation
Prerequisites >
Recommended maximum downstream protection
If these recommendations are not followed, a short-circuit on an output circuit can result in a break in power longer than 20
milliseconds on all the other output circuits.
UPS cabinets in kVA CB / switch-
250 NS 100N
300 NS 100N
400 NS 100N
500 C125N
Depending on the installation, the CB/SD may be replaced by a CB/SD with a higher breaking capacity.
These protective devices ensure discrimination for each circuit downstream of the UPS, with or without a bypass AC input.
Battery protection
UPS cabinets in kVABattery backup time at
disconnector
C120N
C120N
C120N
C120N
NG 125N
C 125H
NS 160N
NG 125N
Pn
Trip unit
TM D 80
C 80A
B 125A
TM D 80
C 80A
B 125A
TM D 100
C 125A
C 125A
D 125A
TM 160D
D 125
Battery CB/switch-disconnector QF1
Typ eTrip unitmagnetic setting in A
250 AllNS630 DC MP11200
300 ≤ 15 min.
> 15 min.
400 ≤ 5 min.
> 5 min.
500 AllC1251N DCP211600
Pn = rated power at a power factor of 0.9, for other values please consult the after-sales support or the local office.
See the necessary precautions during connection of circuit breakers / switch-disconnectors in the installation
manual of the battery circuit-breaker enclosure, doc. no. 34021529.
Recommended residual-current protection
Requirements for residual-current protection.
For common normal and bypass AC inputs
- The same residual-current protection may be used for the two lines.
For separate normal and bypass AC inputs
- A transformer is required upstream of either the normal AC line or the bypass AC line.
- Equip each line with a circuit breaker or switch-disconnector with residual current protection.
See “System earthing arrangements”, page 24.
The recommended minimum residual current protection is 3A, provided the conditions defined in IEC364.4-41 are
respected.
NS630 DC
C1251N DC
NS630 DC
C1251N DC
MP1
P21
MP1
P21
1200
1600
1200
1600
34020846EN/AD - Page 20
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.