APC ACRP500, ACRP100, ACRP501, ACRP102, ACRP101 User Manual

...
InRow® RP
Chilled Water/Direct Expansion — 50/60 Hz
AIR-COOLED
ACRP100 ACRP101 ACRP102
CHILLED WATER
Technical Data

American Power Conversion Legal Disclaimer

The information presented in this manual is not warranted by the American Power Conversion Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, American Power Conversion Corporation assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this Publication. The information contained in this Publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction. This Publication has been compiled in good faith by American Power Conversion Corporation. However, no representa­tion is made or warranty given, either express or implied, as to the completeness or accuracy of the information this Publication contains.
IN NO EVENT SHALL AMERICAN POWER CONVERSION CORPORATION, OR ANY PARENT, AFFILIATE OR SUBSIDIARY COMPANY OF AMERICAN POWER CONVERSION CORPORATION OR THEIR RESPECTIVE OFFICERS, DIREC­TORS, OR EMPLOYEES BE LIABLE FOR ANY DIRECT, INDIRECT, CONSE­QUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT, REVENUE, DATA, INFORMATION, OR BUSINESS INTERRUPTION) RESULT­ING FROM, ARISING OUT, OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT, EVEN IF AMERI­CAN POWER CONVERSION CORPORATION HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. AMERICAN POWER CONVERSION CORPORATION RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE.
Copyright, intellectual, and all other proprietary rights in the content (including but not lim­ited to software, audio, video, text, and photographs) rests with American Power Conversion Corporation or its licensors. All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information. This Publication shall not be for resale in whole or in part.
Contents
Overview .......................................................................... 1
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Room Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Compliance Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Chilled Water Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . 1
Air-cooled Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Scalable Solution for Critical Environments ................ 2
InRow Advantages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Scalable for High Density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Hot Aisle Containment System . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Standard Features........................................................... 4
Insulated Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Variable Speed Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Shutdown Input/Alarm Output . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Chilled Water Flow Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2-way/3-way Floating Point Valve (CW Only) . . . . . . . . . . . . . . . . . 4
Counterflow Cooling Coil/Condensate Pan . . . . . . . . . . . . . . . . . . 4
Electric Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
30% ASHRAE 52.1 Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pipe Adapters (CW only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pipe Adapters (Air-Cooled only) . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Selectable Top or Bottom Piping Connections . . . . . . . . . . . . . . . 4
Dual Position Float Condensate Management . . . . . . . . . . . . . . . 5
Network Management Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Bay Kit InRow RP/NetShelter SX . . . . . . . . . . . . . . . . . . . . . . . . . 5
Remote Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Optional Features............................................................ 6
Cable Water Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Network Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
85% ASHRAE 52.1 Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Trough . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Data Partition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Height Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Flex Hose Piping Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Microprocessor Controller ............................................. 7
Microprocessor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Open Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Control Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chilled Water Only Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Air-cooled Only Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
InRow RP Technical Data Manual
i
InRow RP Models ............................................................ 9
Chilled Water Interior Components (front of unit) . . . . . . . . . . . .10
Air-cooled Interior Components (front of unit) . . . . . . . . . . . . . .12
Air-cooled Interior Components (back of unit) . . . . . . . . . . . . . .13
Chilled Water and Air-cooled User Interface Connections . . . . . .14
Chilled Water Electrical Panel . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Air-cooled Electrical Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Chilled Water Performance Specifications 5.5°C (42°F) EWT . . . .17
Chilled Water Performance Specifications 7.2°C (45°F) EWT . . . .18
Chilled Water Performance Specifications 8.9°C (48°F) EWT . . . .19
Chilled Water Performance Specifications 10°C (50°F) EWT . . . .20
Chilled Water Performance Specifications 12.8°C (55°F) EWT . . .21 Chilled Water Performance Specifications 15.5°C (60°F) EWT . . .22
Chilled Water Data - General . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Glycol Correction Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Altitude Correction Factors for InRow Products . . . . . . . . . . . . .24
Air-cooled Performance Specifications . . . . . . . . . . . . . . . . . . . .24
Air-cooled Data - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Sound Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Dimensional Data .......................................................... 27
InRow RP Assembled Module . . . . . . . . . . . . . . . . . . . . . . . . . . .27
SX to VX Height Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
SX to 48U SX Height Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Piping and Mechanical Connections........................... 29
Chilled Water Piping Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Top Chilled WaterPiping Access (top view) . . . . . . . . . . . . . . . .30
Air-cooled Piping Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Air-cooled Piping Access (top) . . . . . . . . . . . . . . . . . . . . . . . . . .33
Air-Cooled Condensers ................................................ 35
Mechanical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
ACCD75201 and ACCD75204 . . . . . . . . . . . . . . . . . . . . . . . . . . .36
ACCD75202 and ACCD75205 . . . . . . . . . . . . . . . . . . . . . . . . . . .36
ACCD75203 and ACCD75206 . . . . . . . . . . . . . . . . . . . . . . . . . . .36
ACCD75207 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
ACCD75208 and ACCD75209 . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Air-cooled Condenser Features . . . . . . . . . . . . . . . . . . . . . . . . .37
Guide Specifications..................................................... 38
Guidelines for Installation ............................................ 44
Room preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Service access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Receiving the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
ii
InRow RP Technical Data Manual

Overview

The modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a variety of spaces.
Critical environmental requirements now reach far beyond the confines of the traditional data center or computer room to encompass a larger suite of applications, referred to as technology rooms. Critical environment applications include:
• Computer rooms
• Telecommunication facilities
• Clean rooms
• Power equipment
• Medical equipment rooms
• LAN/WAN environments
A worldwide network of APC representatives is fully qualified to provide engineering, sales, installation, and service for our products.
APC warrants all parts for 18 months from shipment and 12 months from startup. Extended warranties are available.

Capacity

The InRow RP chilled water configuration is available in one size with a capacity that is up to 60 kW based on the particular application of the unit. The InRow RP air-cooled configuration is available in one size with a capacity that is up to 37 kW.

Room Air Distribution

Row-based systems are placed in line with rack enclosures. At least one system is used per hot aisle. Air is drawn in through the rear of the system, cooled, and discharged into the cold aisle, thereby neutralizing the sensible heating effects of the data processing equipment.The InRow RP delivers high volumes of airflow to eliminate hot spots in densely populated environments.

Configuration

• Chilled Water
• Air-cooled

Compliance Approval

• UL Listed
• VDE
• CE
• C-tick
• C-UL Listed

Chilled Water Standard Features

• Insulated cabinet
• Backward inclined impeller
• Variable speed fans (3)
• Shutdown input/alarm output
• Chilled water flow meter
• 2-way/3-way floating point valve
• Humidifier
• Counter flow cooling coil
• Electric reheat
• Pleated 100 mm (4 in) filter
• NPT to BSPT pipe adapters
• Top or bottom piping
• Condensate management with dual position float
• Network management card
• Baying Kit InRow RP to NetShelter® SX rack
• Remote temperature sensor (3)
• Microprocessor controller
• Automatic transfer switch

Air-cooled Standard Features

• Insulated cabinet
• Backward inclined impeller
• Variable speed fans (2)
• Shutdown input/alarm output
• Humidifier
• Cross circuited cooling coil
• Electric reheat
• Pleated 100 mm (4 in) filter
• Pipe adapters
• Top or bottom piping
• Condensate management with dual position float
• Network management card
• Baying kit InRow RP to NetShelter
• Remote temperature sensor (3)
• Microprocessor controller
• Variable speed reciprocating compressor using VFD control
• Liquid line solenoid valve
• Pressure equalization solenoid
®
SX rack

Accessories

• Cable leak detector
• Baying kit InRow RP to NetShelter VX rack
• NetShelter SX 42U to 48U height adapters
• NetShelter VX 42U height adapters
• Bridge trough power cable shield
• Data cable bridge partition
• Flex hose piping kits
1InRow RP Technical Data Manual

Scalable Solution for Critical Environments

InRow Advantages

The row-based solution improves energy efficiency and cooling ability in a number of ways. First, the InRow RP draws air directly from the hot aisle, allowing the InRow RP to take advantage of higher heat transfer efficiency due to higher temperature differences. It can then discharge room temperature air directly in front of the servers it is cooling. This increases energy efficiency by allowing the chiller to operate at higher leaving water temperatures. Placing the cooling unit in the row enables the unit to operate at higher return and supply air temperatures, yielding 100% sensible capacity. This significantly reduces the need for humidification.

Scalable for High Density

The predictable performance of the row-based architecture makes it well suited for high density applications. The focus on heat removal instead of cold air delivery is the key to making this approach scalable. The modular design of the InRow RP allows it to be easily added in the row as the demand for cooling increases.
The additional benefit of the row-based architecture is the ability to add hot aisle containment. Containing the hot aisle further reduces any chance of hot and cold air streams mixing. This provides ultimate predictability and allows the cooling capacity to be matched to the IT heat load.
InRow RP Technical Data Manual2

Hot Aisle Containment System

na2763b
119.60
34.43
NetShelter NetShelter PDUUPS
NetShelter NetShelter
600
23.62()
na2762d
()
45.50
()
990.60
39.00
600
23.62()
InRow
InRowNetShelter
52.20()
600
23.62()
600
23.62()
600
23.62()
()
52.43
70.81()
Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the densities that can be handled in a single rack enclosure by eliminating mixing of hot and cold air streams. This method, called load neutralization, removes the heat from the hot aisle, cools it, and then returns it to the surrounding room area at or slightly below room temperature. The warmer return air temperatures that are achieved in this application increase the capacity of the air conditioner.
Use of modular ceiling tiles across a 914.4 mm (3 ft) hot aisle that connects two opposite rack enclosures makes expansion quick and simple. Expansion kits, with necessary ceiling tile and all baying hardware, can be ordered to increase the size of the hot aisle by one rack on each side. The end doors can be easily removed and re-attached for expansion.
The enclosed hot aisle prevents any warm return air from mixing with cold supply air. In effect, all surrounding room air can act as supply air to the system. The hot aisle containment system is beneficial in any environment. It can be deployed quickly in any controlled space without expensive additions to the infrastructure, such as raised floor or ductwork.
PDU
1325.88
PDU
600
23.62
1155.70
NetShelter
Dimensions are shown in mm (in).
874.52
()
1331.72 ()
1798.58
3037.80 ()
3InRow RP Technical Data Manual

Standard Features

Insulated Cabinet

The frame is constructed of 1.5 mm (16 gauge) formed steel for maximum strength. Cabinet is serviceable from the front and rear. All exterior panels and corner posts on the frame are powder coated for durability and an attractive finish. Front and rear exterior panel are constructed of 1.2 mm (18 gauge) perforated steel with 69.5% open free area. Insulation is 80.1 kg/m (5 lb/ft3) density and complies with ASTM E84 rating of 25/50. All panels include a key latch for safety and security for easy access and removal.
3

Variable Speed Fans

The InRow RP unit is equipped with variable speed, electrically commutated, 400 mm (15.8-in) backward incline, direct drive fans. The chilled water unit is equipped with three fans while the air-cooled unit has two. In order to provide uniform airflow over the cooling coil, the fans provide a draw-through air pattern. Fans are easily serviced in the field.

Chilled Water Flow Meter

Internal piping of the unit includes a flow meter wired into the microprocessor controller to display chilled water flow and determine operating performance.

2-way/3-way Floating Point Valve (CW Only)

A floating point valve is microprocessor controlled to regulate the amount of chilled water into the cooling coil to maintain desired conditions. The standard valve pressure rating is 4136.8 kPa (600 psig). The maximum operation pressure of the unit is 2068.4 kPa (300 psig). The valve is user configurable to be two-way or three­way.

Counterflow Cooling Coil/ Condensate Pan

Designed for high sensible heat ratios, the coil is constructed with copper tubes, raised lance type aluminum fins, and 1.2 mm (18 gauge) galvanized steel end plates. Coil headers are equipped with anti drip shields in case of condensation. Condensate pan is UL94 V-0 thermal formed non-ferrous material sloped for positive drainage for higher indoor air quality.

Electric Reheat

Electric reheat elements are low watt density, wired for three-phase and loaded equally on all three phases, and electrically and thermally protected by both automatic and manual reset thermal cut outs. Reheat elements are stainless steel, fin tubular construction.

30% ASHRAE 52.1 Filter

The filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by electrical equipment. The system uses a 30% efficient, 100 mm (4 in), deep loading, pleated filter. Deeper filters produce a lower pressure drop, requiring less energy during normal operation. The filter is moisture resistant up to a 100% relative humidity. Filters are easily replaceable from the rear of the unit. (MERV 8 per ASHRAE 52.2, EN779 G4)

Pipe Adapters (CW only)

Standard pipe connections are
38.1 mm (1 1/2 in) NPSM (manufactured in accordance with ANSI B.1.20.1).

Pipe Adapters (Air-Cooled only)

Standard pipe connections are
31.75 mm (1 1/4 in) 12 UNF female Rotolock (manufactured in accordance with ANSI B1.1). The adapter converts the rotolock to a sweat adapter.

Selectable Top or Bottom Piping Connections

Unit includes both top and bottom piping connections. Top piping connects to internal stubs and routes piping upward out of the unit. Bottom piping connects to internal stubs and routes piping downward out of the unit. All connections utilize unions or rotolok fittings for ease of installation and service

Shutdown Input/Alarm Output

The unit provides one field connection input for remote shutdown and one field connection alarm output.
InRow RP Technical Data Manual4

Dual Position Float Condensate Management

The pump is factory wired and piped internally to the condensate drain pan and humidifier outlet. The pump is capable of pumping a maximum of 18 m (60 ft) at 0.009 l/s (8.45 GPH), which may include a maximum lift of
3.5 m (11.5 ft) of head. A dual position float is included with the unit. One position is used for condensate pump control, the other to alarm condensate pump failure which shuts down the RP to prevent condensate pump overflow.

Network Management Card

Permits multi-level access to monitoring, control, and event notification features over the user’s network.

Bay Kit InRow RP/ NetShelter SX

Baying kits made of 1.5 mm (16 gauge) steel enable baying of the cooling system to APC NetShelter SX enclosures.

Remote Temperature Sensors

To control the unit based on rack inlet temperature, three remote sensors are provided. These sensors measure at 4 m (13 ft) from the connection point inside the RP. The sensors are used for remote placement in the field on adjacent IT racks.

Humidifier

The humidifier is a self-contained, steam-generating type, factory piped and wired, with a disposable cylinder and an automatic solid state control circuit. Humidifier canisters are replaceable. The humidifier controller communicates directly to the microprocessor controller and provides complete status and control at the operator interface.
5InRow RP Technical Data Manual

Optional Features

Cable Water Detector

A leak detection cable is placed on the floor or subfloor around all possible leak sources. If water or other conductive liquids contact the cable anywhere along its length, the microprocessor controller announces the leak visually, audibly, and across the network. The 6.1 m (20 ft) cable may be cascaded to make custom lengths up to 24.4 m (80 ft).

Network Cable

Various lengths of network cable are available to ship with your cooling system. The network cable is used to interconnect multiple cooling units in a redundant group, as well as to connect the network management card to your LAN.

85% ASHRAE 52.1 Filter

Electrical equipment requires clean, particle free air, thus making the filtration of the air extremely important. Optionally, the system uses a 85% efficient, 100 mm (4 in), deep loading, pleated filter. Deeper filters produce a lower pressure drop, requiring less energy during normal operation. The 100% synthetic media will not absorb moisture and is resistant to most common chemicals. The filter is moisture resistant up to a 100% relative humidity. Filters are easily replaceable from the rear of the unit. (MERV 13 per ASHRAE
52.2, EN779 F7)

Power Trough

Overhead power distribution between adjacent NetShelter racks allows for removal of the InRow RP without disrupting overhead power cabling.

Data Partition

Overhead cable distribution between adjacent NetShelter racks allows for removal of the InRow RP without disrupting overhead cabling.

Height Adapters

To match height of the InRow RP to various rack heights, height adapters are available for NetShelter 42U VX and 48U SX racks.

Flex Hose Piping Kits

For hard piping to the chilled water InRow RP, stainless steel flex piping kits are available. The kits ship with two 0.914 m (3 ft) or 1.828 m (6 ft) pipes, depending on selection. Connections are 1.25 in NPT to 1.5 in NPSM, OFS female.
InRow RP Technical Data Manual6

Microprocessor Controller

?
Status
Check Log
Critical
ESC
Warning
Critical Alarm LED
Warning Alarm LED
Check Log LED
Status LED
Liquid Crystal Display (LCD)
Menu Selection scroll keys
Escape key
Enter key
Help key

Microprocessor Controller

The microprocessor controller is standard on each system. The controller provides precision control for the demanding requirements of:
• Computer rooms
• Telecommunication facilities
• Clean rooms
• Power equipment
• Medical equipment rooms
• LAN/WAN environments
The easy-to-use display allows the operator to select options from the device’s menu-driven interface to control and monitor the connected air conditioning system.

Open Architecture

The InRow RP protocol is open for integration with all building management systems. Communication interface on the system can be MODBUS RS485 or Ethernet.

Control Type

Controller utilizes proportional/ integral/derivative (PID), a time­proven precision environmental control method. This allows for custom tuning of control variables to achieve desired system response.

Functions

• Supply and Return Air Conditions
• Operational Mode Control
• Event Logging
• Alarms
• Redundant Group Control
• Fan Speed Adjustment
• Input/Output Module Programming

Logging

The event log keeps a record of all alarms and events. Each event log contains a time/date stamp as well as operating conditions at the time of occurrence. The controller also displays run time, in hours, for major components (air filters, fans, and condensate pump, as well as humidifier, heater, and compressor for the air-cooled unit).

Control

The backlit, four-line by twenty­character display is password configurable.
7InRow RP Technical Data Manual

Alarms

The microprocessor controller shall activate a visible and audible alarm in the following occurrences:
• Cool Fail
• Rack inlet temperature violation
• Rack inlet temperature sensor fault
• Air filter clogged
• Air filter run hours exceeded
• Filter DP sensor failure
• Supply air sensor fault
• Return air sensor fault
• Supply air high temperature violation
• Return air high temperature violation
• Fan fault
• Fan run hours exceeded
• Water detection fault
• Condensate pump fault
• Condensate run hours exceeded
• Humidifier water conductivity high violation
• Humidifier fault tolerance exceeded
• Humidifier low water
• Humidifier excessive output reduction
• Humidifier drain fault
• Humidifier cylinder full
• Humidifier replace cylinder
• Humidifier RS485 communication fault
• Humidifier run hours violation
• Humidity high/low violation
• Supply humidity sensor fault
• Return humidity sensor fault
• Heater fault
• Heater run hours exceeded
• Heater interlock shutdown
• Group communication fault
• Internal communication fault
• A-link isolation relay fault
• External communication fault
• Input contact fault
• Invalid supply setpoint
• Idle mode active

Chilled Water Only Alarms

• Coil fluid valve actuator fault
• Fluid flow fault
• Entering fluid temperature high violation
• Entering fluid temperature sensor fault
• Leaving fluid temperature sensor fault
• Power source failure
• Fluid calibration

Air-cooled Only Alarms

• High discharge pressure
• Low suction pressure
• High suction pressure
• Compressor drive failure
• Compressor drive warning
• Compressor run hours violation
• Compressor drive RS485 communication fault
• Excessive compressor cycling
• Air flow decreased while compressor off
• Suction pressure sensor failure
• Discharge pressure sensor failure
• High pressure switch active
• Fan speed decreased to avoid high pressure (event only)
• Compressor speed decreased to avoid high pressure (event only)
• Compressor high pressure
• Oil return pump active
InRow RP Technical Data Manual8

InRow RP Models

na1824a
Hinged rear doors
Side panel lock
Removable side panel
Adjustable leveling foot
Casters (all swiveling)
Door handle and lock
Display interface
Hinged front door
9InRow RP Technical Data Manual

Chilled Water Interior Components (front of unit)

na2090a
Electric heater (for reheat)
Fan
Fan guard
Humidifier
Condensate drain pan
Condensate pump
Electrical panel
Supply temperature sensors
Main feed breakers
Ladder diagrams
User interface connectors
Supply humidity sensor
InRow RP Technical Data Manual10
Chilled Water Interior Components (back of unit)
na2105a
Chilled water coil
Chilled water control actuator
Chilled water three-way valve body
Flow meter
Pipe chase
Rear doors
Air filters
Return humidity sensor
Return temperature sensor
11InRow RP Technical Data Manual