APC ACPSC2000, ACPSC3500 User Manual

User Manual
ON/OFF
MODE
TEMP TIME
InRoom SC
InRoom SC
60 Hz
ACPSC2000
ACPSC3500
American Power Conversion Legal Disclaimer
The information presented in this manual is not warranted by the American Power Conversion Corpora­tion to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, American Power Conversion Corpo­ration assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this Publication.
The information contained in this Publication is provided as is and has been prepared solely for the pur­pose of evaluating data center design and construction. This Publication has been compiled in good faith by American Power Conversion Corporation. However, no representation is made or warranty given, either express or implied, as to the completeness or accuracy of the information this Publication contains.
IN NO EVENT SHALL AMERICAN POWER CONVERSION CORPORATION, OR ANY PAR­ENT, AFFILIATE OR SUBSIDIARY COMPANY OF AMERICAN POWER CONVERSION CORPORATION OR THEIR RESPECTIVE OFFICERS, DIRECTORS, OR EMPLOYEES BE LIABLE FOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT, REVENUE, DATA, INFORMATION, OR BUSINESS INTER­RUPTION) RESULTING FROM, ARISING OUT, OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT, EVEN IF AMERICAN POWER CONVERSION CORPORATION HAS BEEN EXPRESSLY ADVISED OF THE POS­SIBILITY OF SUCH DAMAGES. AMERICAN POWER CONVERSION CORPORATION RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE.
Copyright, intellectual, and all other proprietary rights in the content (including but not limited to soft­ware, audio, video, text, and photographs) rests with American Power Conversion Corporation or its licensors. All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information.
This Publication shall not be for resale in whole or in part.
Contents
General Information........................................................ 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About the InRoom SC Portable Cooling Units . . . . . . . . . . . . . . . . . 1
Safety symbols that may be used in this manual . . . . . . . . . . . . . . 2
Cross-reference symbol used in this manual . . . . . . . . . . . . . . . . . 2
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Storing the Cooling Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cooling Unit Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Inspecting the Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Filing a claim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Component Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
ACPSC2000 and ACPSC3500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Power plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation ....................................................................... 9
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Exhaust Duct Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Exhaust kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Manual draining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Continuous draining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operation ....................................................................... 14
Control Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Function Button Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
InRoom SC 60 Hz User Manual
i
Display Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Display Screen Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Function Button and Indicator Light Operation . . . . . . . . . . . . . . . 16
Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Maintenance................................................................... 19
Clean the exterior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Clean the air filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Replace the air filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Empty the condensate drain pan . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Storing while not in use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Caster replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Troubleshooting ............................................................ 22
Spare Parts List ............................................................. 23
Specifications ................................................................ 24
ii
InRoom SC 60 Hz User Manual

General Information

Overview

Save these instructions

This manual contains important instructions that must be followed during the installation of this equipment.

About the InRoom SC Portable Cooling Units

InRoom SC cooling units are portable, compact air conditioners designed for spot-cooling, emergency­cooling, and after-hours cooling of server closets, and data centers.
InRoom SC ACPSC2000 provides 2.9 kW (9,900 BTU) of cooling capacity.
InRoom SC ACPSC3500 provides 3.5 kW (12,000 BTU) of cooling capacity.
If the building’s cooling system has night and weekend thermostat setbacks, is shut down during the off­season or maintenance, or has limited cooling capacity, you may need to consider alternatives to the standard installation.
The cooling units automatically adjust room temperature and reduce moisture while filtering the air. Additional features of the equipment include:
• Electronic control panel with LCD display
• On/Off scheduling
• Remote control operation
• High-efficiency rotary compressor
• Adjustable louvers for air distribution
1InRoom SC 60 Hz User Manual

Safety symbols that may be used in this manual

Electrical Hazard: Indicates an electrical hazard which, if not avoided, could result in
injury or death.
Danger:
substantial damage to product or other property.
Warning: Indicates a hazard which, if not avoided, could result in personal injury or damage to product or other property.
Caution: Indicates a potential hazard which, if not avoided, could result in personal injury or damage to product or other property.
Note: Indicates important information.
Indicates a hazard which, if not avoided, could result in severe personal injury or

Cross-reference symbol used in this manual

More information on this subject can be found in another section of this document.
InRoom SC 60 Hz User Manual2

Safety

Electrical Hazard: Connect the equipment to a 3-wire AC outlet (two poles plus a ground). The
receptacle must be connected to a dedicated, properly grounded 120 volt 60Hz branch circuit rated for 20 amp main protection (fuses/circuit breaker). Connection to any other power source may result in a shock hazard or damage to the cooling unit.
Do not cut or remove the ground from the power cord plug.
Use the cooling unit with the supplied power cord only.
Do not use an extension cord with this cooling unit.
If the plug gets hot, call a qualified electrician.
Do not immerse the cooling unit, cord or plug in water or any other liquid.
Warning: Do not stick anything into the air outlet of the air conditioner.
Close supervision is required when the unit is used near children.
Do not use in a room with poor air circulation.
Caution: Do not place the cooling unit on its side. If the cooling unit has been tipped, place it upright on a flat, solid surface and keep it in this position for a minimum of 12 hours before operating..
Use the cooling unit on a flat surface only.
Do not obstruct the cooling unit air outlets.
For indoor use only.
The equipment contains no internal user-serviceable parts.
Do not place the rear of the cooling unit closer than 500 mm (20 in) to any wall or obstacle.
Do not install the cooling unit where there are fumes or flammable gases, or in an extremely humid space such as a greenhouse.
Do not place objects on top of the cooling unit or sit on the cooling unit.
3InRoom SC 60 Hz User Manual

Storing the Cooling Unit

ON/ O FF
MO
DE S
LE E
P
F AN
TE M P
T IM E
I n R
oom S
C
MODE
TIMER
F AN
S E N D
S L E E P
D
RY Hr .
M i n
ON
/ O F F
+ ° F
­° F
na3397a
If the cooling unit will not be installed immediately, replace the packaging to protect from damage and dust. Store the cooling unit indoors in a climate controlled, dry place.
Caution: Leaving the cooling unit uncovered and exposed to the elements can cause damage and voids the factory warranty.

Cooling Unit Packaging

Recycle the packaging material when possible.
Do not discard packaging material until the cooling unit has been inspected.
Remove the tape securing the air filter and cover to the cooling unit.
InRoom SC 60 Hz User Manual4