Installation Addendum: Rack Side Air Distribution
Mounting rail installation overview
These instructions apply only to shallow vertical-rail spacing applications.
Note
The mounting rails can be adjusted to fit a wide range of enclosure depths. Before installing the rails,
measure the distance between the front and rear vertical-rails of the enclosure. The repositioning of
the rear mounting bracket is necessary when mounting rails are used in shallow vertical-rail
spacing applications.
30.0 in (698.5 to 762 mm)
(no adjustments necessary)
Tools required—not provided
Shallow vertical-rail distance — 16.25 to
19.0 in (412.8 to 482.6 mm)
(relocation of the rear mounting
bracket is necessary)
P2 Phillips screwdriver
Page 2
How to modify the mounting rails
Perform this procedure for both the left and the right mounting brackets.
Note
1. Remove and discard the two adjusting
screws that attach the rear mounting
bracket to the mounting rail.
2. Reposition the rear mounting bracket
by sliding it onto the forward tab of
the mounting rail.
The rear mounting bracket will slide freely on the forward tab of the mounting rail until
the rail assembly is attached to the enclosure.
Note
Refer to the Rack Side Air Distribution installation instructions for information on how to
install the mounting rails in the enclosure.
990-2287-001
*990-2287-001*
12/2004