APC ACF102BLK User Manual

NetworkAIR® Rack Air
Removal Unit
ACF102BLK
Installation
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Tools required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Receiving inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Remove the rear doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Install the fan frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Install the fan assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Optional Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connect the power supply . . . . . . . . . . . . . . . . . . . . . . . . 10
How to set the fans based on wattage . . . . . . . . . . . . . . . . 11
Temperature override . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
How to set the temperature override . . . . . . . . . . . . . . . . . 13
How to set the fans based on temperature . . . . . . . . . . . . . 14
Alarm Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
LED legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
How to Communicate Using the A-Link . . . . . . . . . . . . . . . . . . 16
How to connect to the A-Link . . . . . . . . . . . . . . . . . . . . . . 16
Warranty and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Limited warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Warranty limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Obtaining service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Rack Air Removal Unit Installation i
Life-Support Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
General policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Examples of life-support devices . . . . . . . . . . . . . . . . . . . . 20
Specifications — ACF102BLK . . . . . . . . . . . . . . . . . . . . . . . . . . 21
ii Rack Air Removal Unit Installation

General Information

Introduction

The American Power Conversion NetworkAIR® Rack Air Removal Unit removes heat generated by
the exhaust of equipment contained in a NetShelter VX or NetShelter EP EIA 19-inch enclosure. The
three fans provide increased air flow needed to cool densely-packed equipment and allow air to
bypass obstacles in the rear of the enclosure such as power and data cables. An optional duct kit
removes the heat entirely from the data center.

Features

Features of the Rack Air Removal Unit:
• Variable fan settings — based on power load and user-definable exhaust temperature
• Dual input connectors — for redundant power
• Three individually fused fans — allows unit to be used for redundancy or higher capacity
• Alarm LEDs — system status, fan status, and thermal control status
• Duct kit — for removal of heat from the air-conditioned space (optional)
• Integrated smoke detector (optional)
• APC Environmental Management System — for remote control and monitoring of the Rack Air
Removal Unit (optional)
NetworkAIR Rack Air Removal Unit Installation 1

Safety Information

H
For computer-room use only.
Install the Rack Air Removal Unit only on racks that are loaded with equipment,
Warning
counter-weighted, or stabilized to avoid tipping of the rack.
Inspect the Rack Air Removal Unit for damage before installation.
Disconnect power to the Rack Air Removal Unit before installing it into the rack.
Failure to do so may result in personal injury or damage to equipment.
Do not apply power to the unit until the installation is complete. The Rack Air
Removal Unit contains moving parts, which are potentially hazardous when
operated outside of the rack.
Do not attempt to move a heavily-loaded enclosure by yourself. Doing so
introduces risk of injury due to muscle strain or to tipping of the enclosure.
Fully-loaded enclosures require at least two people to move safely.
Do not attempt to install the Rack Air Removal Unit by yourself. Doing so
introduces risk of injury due to muscle strain or to tipping of the enclosure. The
Rack Air Removal Unit requires at least three people to install safely.
eavy
Check that the power cord plugs and sockets are in good condition before
installation.
Connect the Rack Air Removal Unit to 230V IEC C-13 outlet. The outlet must
be connected to appropriate branch circuit/mains protection (fuse or circuit
breaker). Connection to any other type of outlet may result in a shock hazard.
This equipment contains potentially hazardous voltages. Do not attempt to
disassemble the unit.
Always install and operate the Rack Air Removal Unit as shown in this manual.
Installing the Rack Air Removal Unit requires three people. Do not attempt to lift
the Rack Air Removal Unit without assistance.
2 NetworkAIR Rack Air Removal Unit Installation

Before You Begin

Inventory

Item Description Quantity
Fan assembly
Exhaust vent
Fan frame
Power cords (IEC 320)
5/32" hex wrench
M5 hex wrench
Cord retainer
Hinge screw
1
1
1
2
1
1
2
1
NetworkAIR Rack Air Removal Unit Installation 3
Before You Begin

Tools required

5/32" hex wrench
(provided)
i
M5 hex wrench
(provided)

Receiving inspection

Inspect the package and contents for shipping damage, and make sure that all parts were sent. Report
any damage immediately to the shipping agent, and report missing contents, damage, or other
problems immediately to APC or your APC reseller.
4 NetworkAIR Rack Air Removal Unit Installation

Installation

Remove the rear doors

To avoid personal injury or damage to the enclosure, one person should support
Warning
1. If necessary, move the rack to allow
2. Open the rear doors and pull down
3. Repeat this step with the other rear
the door while another removes it from the frame.
for at least 30 inches of clearance to
install the Rack Air Removal Unit.
on the spring-loaded hinge pin
attached to the top of the door. Lift
the door from its frame and set it
safely aside.
door.
4. Using the included M5 hex wrench,
remove the door bumpers at the top
and bottom of the door frame.
NetworkAIR Rack Air Removal Unit Installation 5