APC ACCU301 Owners Manual

Uniflair
Direct Expansion InRow®Cooling
ACRD300 and ACCU300 Series
Technical Specifications
Up to 30 kW, CE/UL Certified
https://www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.
Table of Contents
Technical Data.............................................................................................5
Model Identification.....................................................................................5
Overview ...................................................................................................7
Scalable Solution for Critical Environments.................................................10
Standard Features and Options ................................................................. 11
Microprocessor Controller .........................................................................16
Component Identification ..........................................................................19
Performance Specifications....................................................................... 31
Dimensions and Weights...........................................................................36
Refrigeration Piping Diagram.....................................................................46
ACRD300 and ACCU300 Series
Capacities ............................................................................................7
Room Air Distribution ............................................................................7
Compliance Approval ............................................................................8
Working Conditions and Environmental Limits .........................................9
InRow Advantages.............................................................................. 10
Scalable for High Density ....................................................................10
Standard Features .............................................................................. 11
Optional Features ...............................................................................14
Display Interface ................................................................................. 16
Microprocessor Controller....................................................................17
Open Architecture...............................................................................17
Control Type.......................................................................................17
Functions ...........................................................................................17
Control...............................................................................................17
Alarms ...............................................................................................18
External Components.......................................................................... 19
Internal Components...........................................................................21
Electrical Panels .................................................................................25
Cooling Capacity ................................................................................ 31
General Data ...................................................................................... 32
Electrical Data ....................................................................................34
Sound Data ........................................................................................ 35
Indoor Unit ......................................................................................... 36
Outdoor Unit....................................................................................... 37
Service Access ...................................................................................38
Airflow Clearance................................................................................ 39
Piping and Electrical Access Locations ................................................. 40
990-91356B-001 3
Technical Data ACRD300 and ACCU300 Series
REAR
NAME PLATE
na4402b

Technical Data

Model Identification

Indoor Unit
The model number can be found on the outside of the shipping crate and on the name plate located on the unit as shown. Use the table below to verify that the equipment is the right type and voltage.
NOTE: The unit is not to be accessed by the general public.
SKU Voltage Frequency 65
ACRD301S 100–120 V~* /
200–240 V~
ACRD301P 200–240 V~ 50/60 Hz No Dual feed 1 Condensate
*Configure proper voltage before applying power to the cooling unit.
NOTE: All units have a rear-to-front airflow pattern.
50/60 Hz Yes Dual feed 1 Condensate
kAIC
Power Feed Number of
Fan Power
Supplies
Drainage
System
pump
pump
Humidification/
Reheat
No/No
Yes/Yes
990-91356B-001 5
ACRD300 and ACCU300 Series Technical Data
na6990a
NAME PLATE
Outdoor Unit
The model number can be found on the outside of the shipping crate and on the name plate located on the unit as shown. Use the table below to verify that the equipment is the right type and voltage.
NOTE: The unit is not to be accessed by the general public.
SKU Voltage Frequency Power Feed
ACCU300 200–240 V 3~ 50/60 Hz Single feed
ACCU300D 200–240 V 3~ 50/60 Hz Dual feed
ACCU302 380–415 V 3~ 50/60 Hz Single feed
ACCU302D 380–415 V 3~ 50/60 Hz Dual feed
ACCU301 460–480 V 3~ 50/60 Hz Single feed
ACCU301D 460–480 V 3~ 50/60 Hz Dual feed
NOTE: All units are 65 kAIC-ready.
6 990-91356B-001
Technical Data ACRD300 and ACCU300 Series

Overview

The ACRD300 series of indoor units can provide a cooling capacity up to 30 kW based on a half-rack platform (300 mm (12 in.)) with an ACCU300 series outdoor condensing unit. A variable-speed compressor works with EC fans and a fin-tube exchanger to reach the best cooling efficiency.
This modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a variety of spaces.
Critical environmental requirements now reach far beyond the confines of the traditional data center or computer room to encompass a larger suite of applications, referred to as technology rooms. Critical environment applications include the following:
Computer rooms
Telecommunication facilities
Clean rooms
Power equipment
Medical equipment rooms
LAN/WAN environments
Edge data centers
Traditional data centers
A worldwide network by Schneider Electric representatives is fully qualified to provide engineering, sales, installation, and service for our products.

Capacities

Room Air Distribution

Uniflair™Direct Expansion (DX) InRow®units in the ACRD300 series are available as a 300-mm.
Row-based systems are placed in line with rack enclosures. At least one system is used per hot aisle. Air is drawn in through the rear of the system, cooled, and discharged into the cold aisle, thereby neutralizing the sensible heating effects of the data processing equipment. Uniflair Direct Expansion InRow products deliver high volumes of airflow to eliminate hot spots in densely populated environments.
Configuration:
Air-cooled
990-91356B-001 7
ACRD300 and ACCU300 Series Technical Data

Compliance Approval

Indoor Unit
Model UL and cUL RCM CE EAC CCC CMIM
ACRD301S X X X X
ACRD301P X X X
Outdoor Unit
Model UL and cUL RCM CE EAC CCC CMIM
ACCU300 X
ACCU300D X
ACCU301 X
ACCU301D X
ACCU302 X X
ACCU302D X X
8 990-91356B-001
Technical Data ACRD300 and ACCU300 Series

Working Conditions and Environmental Limits

Uniflair Direct Expansion InRow units have a minimum heat load to ensure proper operation. Failure to operate the unit with at least the minimum load will result in one or more of the following conditions:
Unstable unit operation
Decreased operating efficiency
Equipment on/off cycling
Inadequate dehumidification
Increased wear and tear caused by frequent on/off cycles
Decreased group control effectiveness
Potential increase in cost of ownership
Limit Working Conditions—Indoor Units (ACRD301P, ACRD301S)
Refrigerant type R410A
Voltage input tolerance ±10%
Approximate minimum recommended load 8.0 kW (27,297 BTU/hr)
Outdoor ambient temperature without the low ambient temperature kit installed
Outdoor ambient temperature with the low ambient temperature kit installed
Ambient %RH 5 to 80%RH
Altitude 3000 m (9843 ft)
Storage Conditions
Temperature –25°C to +65°C (–13°F to +149°F)
Humidity 5 to 95%RH
NOTE: ACRD301P and ACRD301S are in accordance with the Electromagnetic Compatibility Standard (EMC): EN 55032, EN55024, EN61000-3-2, EN61000-3-3, EN61000-6-3, EN61000-6-1, EN61000-3-11, EN 61000-3-12. ACRD301P and ACRD301S are in accordance with FCC: ANSI C63.4.
NOTE: The SKUs comply with EN61000-3-12 provided that the short-circuit power SSC is greater than or equal to 350 at the interface point between the user supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power SSC greater than or equal to 350.
Limit Working Conditions—Outdoor Units (ACCU300. ACCU300D, ACCU302, ACCU302D, ACCU301, and ACCU301D)
Refrigerant type R410A
Altitude 3000 m (9843 ft)
Storage Conditions
Down to –15°C (+5°F) Up to 48°C (118°F)
Down to –40°C (–40°F) Up to 48°C (118°F)
Temperature –25°C to +65°C (–13°F to +149°F)
Humidity 5 to 95%RH
NOTE: ACCU302 and ACCU302D are in accordance with the Electromagnetic Compatibility Standard (EMC): EN 55032, EN55024, EN61000-3-2, EN61000-3-3, EN61000-6-3, EN61000-6-1, EN61000-3-11, EN 61000-3-12. ACCU300, ACCU300D, ACCU301, and ACCU301D are in accordance with FCC: ANSI C63.4.
NOTE: The SKUs comply with EN61000-3-12 provided that the short-circuit power SSC is greater than or equal to 350 at the interface point between the user supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power SSC greater than or equal to 350.
990-91356B-001 9
ACRD300 and ACCU300 Series Technical Data
na5859a
HOT AISLE

Scalable Solution for Critical Environments

InRow Advantages

The row-based solution improves energy efficiency and cooling ability in a number of ways. First, the Uniflair Direct Expansion InRow unit draws air directly from the hot aisle, allowing the unit to take advantage of higher heat transfer efficiency due to higher temperature differences. It can then discharge room-temperature air directly in front of the servers it is cooling. Placing the unit in the row enables the unit to operate at higher return and supply air temperatures, yielding 100% sensible capacity. This significantly reduces the need for humidification.

Scalable for High Density

The predictable performance of the row-based architecture makes it well-suited for high density applications. The focus on heat removal instead of cold-air delivery is the key to making this approach scalable. The modular design of the Uniflair Direct Expansion InRow unit allows it to be easily added in the row as the demand for cooling increases.
The additional benefit of the row-based architecture is the ability to add hot-aisle containment. Containing the hot aisle further reduces any chance of hot and cold air streams mixing. This provides ultimate predictability and allows the cooling capacity to be matched to the IT heat load.
10 990-91356B-001
Technical Data ACRD300 and ACCU300 Series

Standard Features and Options

Standard Features

EcoStruxure
The ACRD300 Series is ready to connect to the world-leading DCIM platform.
Ready
Cabinet
The frame of the ACRD300 series units is constructed of 16-gauge formed steel for maximum strength. The cabinet is serviceable from the front and rear. All exterior panels and corner posts on the frame are powder coated for durability and an attractive finish. The front and rear exterior panels are constructed of 18 gauge perforated steel with 80% open free area. All panels, which include a key latch for safety and security, allow easy access and removal. The footprint of 300 mm takes up less space in the data center.
Condensate Pump
ACRD301S and ACRD301P: A condensate pump is factory wired and piped
internally to the condensate drain pan. Within the condensate pump, there is a dual position float. The first position is used for condensate pump control and the other float generates a condensate pump failure alarm to prevent condensate pan overflow.
Counterflow Cooling Coil/Condensate Pan
Designed for high-sensible heat ratios, the coil is constructed with copper tubes, raised-lance-type aluminum fins, and 18-gauge galvanized steel end plates. Coil headers are equipped with anti-drip shields in the event of condensation. The condensate pan is thermal formed non-ferrous material, and is sloped for positive drainage to provide higher indoor air quality.
Electric Reheat (ACRD301P)
Electric reheat elements are low watt density, wired for single-phase and loaded equally on all three phases, and electrically and thermally protected by both automatic and manual reset thermal cut outs. Reheat elements are stainless steel, fin tubular construction.
Filters
Filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by electrical equipment. Filters are easily replaceable from the rear of the unit. ACRD300 series units use greater-than 20% efficiency ASHRAE 52.1, 12.7 mm (1/2 in.) washable filters that meet HF-1 standards for electronics (MERV 1 per ASHRAE 52.2)
990-91356B-001 11
ACRD300 and ACCU300 Series Technical Data
Humidifier (ACRD301P only)
The humidifier is a self-contained, steam-generating type, factory piped and wired, with a disposable cylinder and an automatic solid state control circuit. Humidifier canisters are replaceable. The humidifier controller communicates directly to the microprocessor controller and provides complete status and control at the operator interface.
Network Management Card
The Network Management Card (NMC) allows communication with the local area network (LAN). In addition, the NMC permits multi-level access to monitoring, control, and event notification features over the building network.
Remote Temperature Sensors
To control the cooling unit based on rack inlet temperature, remote temperature sensors are provided. The ACRD300 series units come equipped with one temperature sensor. These sensors measure temperature at a point 4 m (13 ft) from the connection inside the Uniflair Direct Expansion InRow unit. These sensors are used for remote placement in the field on an adjacent IT rack.
Shutdown Input/Alarm Output
The unit provides one field connection input for remote shutdown and one field connection alarm output.
Power
3.2 rated SCOP (EER)
Substantially lower power consumption
Power by UPS
Due to low current draw, connect the indoor unit secondary power feed to
the UPS for easy power backup.
Selectable Top or Bottom Piping Connections
The cooling unit includes both top and bottom piping connections. All ACRD300 series connections use threaded ring seals for ease of installation and service.
Variable-Speed Fans
Each unit is equipped with variable speed fans to allow for varying heat loads. In order to provide uniform airflow over the cooling coil, the fans provide a draw­through air pattern. ACRD300 series units are equipped with eight direct-drive fan modules. These fans are easily replaceable while the unit is in operation.
R410A Refrigerant
R410A refrigerant does not harm the ozone layer and has a very low contribution to the global warming impact.
Outdoor Condensing Unit
The outdoor condensing unit has a small footprint of 1 m2(10.8 ft2). Moving the compressor to the outdoor condensing unit improves serviceability for the indoor unit and lowers the sound level in the IT space.
12 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
Electronic Expansion Valve
The EEV provides accurate control of the refrigerant superheat in order to ensure an increase in efficiency at low external temperatures because it enables the unit to operate at much lower condensing pressures than would be possible with a traditional mechanical valve.
Display Interface
The standard arrangement of the touch-screen display, RS 485 serial card, and USB connection allows direct connection to BMSs based on serial lines. The USB port allows quick downloads of the unit settings and parameters.
Microprocessor
The control system consists of two sections: the J5 controller containing the regulation software and is installed in the unit electrical panel, and the 4.3-inch, touch-screen display interface on the exterior of the unit.
The control system uses sophisticated algorithms to control the outlet water temperature within a minimal range and to monitor and protect the various unit components. The display interface provides clear information on the unit status and any current alarms.
Low Ambient Kit
The low ambient kit provides the capability to operate in lower temperatures, down to -40°C (-40°F) . Contact Schneider Electric for more details.
The kit can be field supplied or purchased from Schneider Electric.
990-91356B-001 13
ACRD300 and ACCU300 Series Technical Data

Optional Features

Aisle Containment
This containment solution isolates pods (two rows of Uniflair Direct Expansion InRow cooling units sharing a common aisle) from the whole IT environment, increasing cooling efficiency at any density.
Cable Water Detector
A leak detection cable is placed on the floor or sub-floor around all possible leak sources. If water or other conductive liquids contact the cable anywhere along its length, the microprocessor controller announces the leak visually, audibly, and across the network. The 6.1-m (20-ft) cable may be cascaded to make custom lengths up to 24.4 m (80 ft).
Humidity Monitoring
An optional remote sensor is available to monitor the humidity level of the data center.
Dual Power Circuits
Optional integrated redundant power circuits provide full power redundancy.
Compressor Acoustic Hood
An optional compressor acoustic hood reduces the sound level.
Data Partition
Overhead cable distribution between adjacent NetShelter racks allows for removal of the Uniflair Direct Expansion InRow units without disrupting overhead cabling.
Filters
Electrical equipment requires clean, particle-free air, thus making air filtration extremely important. As an optional feature, higher efficiency filters can be purchased for the Uniflair Direct Expansion InRow units. The ACRD300 series units optionally use an 50.8 mm (2 in.) pleated, deep loading, 30% ASHRAE 52.1 filter (MERV 8 per ASHRAE 52.2).
Height Adapters
To match height of the Uniflair Direct Expansion InRow cooling units to various rack heights, height adapters are available for NetShelter 42-U VX and 48-U SX racks.
Network Cable
Various lengths of network cable are available to ship with your cooling system. The network cable is used to interconnect multiple units in a redundant group, as well as to connect the Network Management Card to your LAN.
Power Trough
Overhead power distribution between adjacent NetShelter racks allows for removal of the Uniflair Direct Expansion InRow cooling units without disrupting overhead power cabling.
14 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
Rack Air Containment
This containment solution isolates the airflow of InRow cooling units from the whole IT environment, increasing efficiency while allowing for high density deployment.
990-91356B-001 15
ACRD300 and ACCU300 Series Technical Data
Display Reset
Micro
SD
Service
Port
USB
Console
10/100
na4820a

Microprocessor Controller

Display Interface

Item Description Function
LCD Display
4.3-inch touch-screen color display
Power LED The cooling unit is powered when the LED is illuminated. Unit
firmware is updating when LED is blinking.
Check Log LED
When this LED is illuminated, a new entry has been made to the event log.
Alarm LED
Status LED
Display Reset button
Displays current alarm condition of unit.
Displays current network management card status.
Resets the display microprocessor. This has no effect on the air conditioner controller.
Link-RX/TX (10/100) LED
Micro SD card slot
Displays current network link status.
Memory card expansion slot.
Service port USB-B port used only by service personnel.
USB-A port Supports firmware upgrades.
Serial Configuration port Connects the display to a local computer to configure initial
network settings or access the command line interface (CLI).
16 990-91356B-001
Technical Data ACRD300 and ACCU300 Series

Microprocessor Controller

The microprocessor controller is standard on each system. The easy-to-use touch-screen display allows the operator to select options from the menu-driven interface to control and monitor the connected air conditioning system.

Open Architecture

The Uniflair Direct Expansion InRow cooling protocol is open for integration with all building management systems. Communication interface on the system can be MODBUS RS485 or Ethernet.

Control Type

The controller uses proportional/integral/derivative (PID), a time-proven precision environmental control method. This allows for custom tuning of control variables to achieve desired system response.

Functions

Supply and return air conditions
Operational mode control
Event logging
Alarms
Redundant group control
Fan speed adjustment
Input/Output module programming

Control

The touch-screen LCD display interface is protected by a configurable password and provides access to information and settings for the unit.
Supply Temperature Setpoint: 15.0–30.2°C (59.0–86.4°F)
Cool Setpoint: 18.0–32.2°C (64.4–90.0°F)
Rack Inlet High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
Supply Air High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
Return Air High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
990-91356B-001 17
ACRD300 and ACCU300 Series Technical Data

Alarms

The microprocessor controller shall activate a visible and audible alarm in the following occurrences:
Air filter clogged
Return air sensor fault
Supply air sensor fault
Rack temperature sensor fault
High discharge pressure
Low suction pressure
Fan fault
Water detected (if optional leak detector used)
Check condensate management system
Air filter run hours violation
Group communication fault
Supply air high temperature violation
Return air high temperature violation
Filter DP sensor failure
Suction pressure sensor failure
Discharge pressure sensor failure
Persistent high discharge pressure fault
Rack inlet temperature high violation
Internal communication fault
Condensate pan full
Persistent low suction pressure fault
Compressor drive communication fault
Compressor drive fault
Compressor run hours violation
Condensate pump run hours violation
Idle mode active
High pressure switch active
Compressor high pressure
Excessive compressor cycling
18 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
na6950a

Component Identification

External Components

Indoor Unit—All ACRD30X Units
Item Description
Upper side panel Upper piping connection openings Filters Rear panel Lower side panel Rear casters (non-swiveling) Lower piping connection openings Front casters (swiveling) Leveling feet Front panel Display interface
990-91356B-001 19
ACRD300 and ACCU300 Series Technical Data
na6953c
Outdoor Unit—All ACCU Units
Item Description Item Description
Fan Mounting holes Main disconnect switch handle (field
Signal cable inlet
installed) Electrical panel access doors Liquid receiver outlet Quarter-turn latches
Liquid line inlet Service panel Suction line inlet Power feed A inlet Coil grilles Power feed B inlet Lifting eyebolts (field supplied)
20 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
na6951a

Internal Components

Indoor Unit
ACRD301S
NOTE: Some components not shown for easier viewing.
Item Description Item Description
Power supply connections (top) Temperature sensor (suction)
Fans
Upper supply air temperature sensor
Solenoid valve Condensate drain pump
Liquid line service port
Cooling coil
Lower supply air temperature
Refrigerant temperature sensor Electronic expansion valve (EEV)
Leveling feet Sight glass
Condensate drain pan
Drain pan float switch
Joining bracket Upper return air temperature sensor
Lower return air temperature sensor
990-91356B-001 21
Gas line service port
Automatic transfer switch (ATS)
Temperature and humidity sensor (optional)
Inlet connection
Outlet connection
Filter drier
Electrical box
ACRD300 and ACCU300 Series Technical Data
na7509a
ACRD301P
NOTE: Some components not shown for easier viewing.
Item Description Item Description
Power supply connections (top) Humidifier
Electric heaters Lower return air temperature sensor
Upper supply air temperature sensor (attached to fan grille)
Solenoid valve Gas line service port
Liquid line service port
Cooling coil Condensate drain pump
Lower supply air temperature (attached to fan grille)
Refrigerant temperature sensor*
Fans
Leveling feet Electronic expansion valve (EEV)
Condensate drain pan Sight glass
Drain pan float switch
Power supply connection (lower)
Joining bracket Upper return air temperature sensor
Temperature sensor (suction)
Automatic transfer switch (ATS)
Temperature and humidity sensor
Inlet connection
Outlet connection
Filter drier
Electrical box
22 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
na7512a
Outdoor Unit
ACCU300, ACCU300D, ACCU301, ACCU301D
Item Description Item Description
Electrical panel Variable-speed compressor Pipe stub for connection to liquid
Variable frequency drive (VFD) receiver Accumulator Interior protection panel
Liquid line connection Liquid receiver cable inlet Suction line connection Oil separator
EMI filter
Service port
High pressure switch
High (discharge) pressure sensor Compressor sight glass Service port Low (suction) pressure sensor
990-91356B-001 23
ACRD300 and ACCU300 Series Technical Data
na7514a
ACCU302, ACCU302D
Item Description Item Description
Electrical panel Variable-speed compressor Pipe stub for connection to liquid
Variable frequency drive (VFD) receiver Accumulator Interior protection panel
Liquid line connection Liquid receiver cable inlet Suction line connection Oil separator
Line reactor and EMI filter
Service port
High pressure switch
High (discharge) pressure sensor Compressor sight glass Service port Low (suction) pressure sensor
24 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
na5053b

Electrical Panels

Indoor Unit
ACRD301S
Item Description
Upper electrical box cover J5 controller Controller cover Power supply 2 (Optional field-installed accessory) Power supply 1
990-91356B-001 25
ACRD300 and ACCU300 Series Technical Data
na7518a
ACRD301P
Item Description Item Description
Upper electrical box cover
Fuse for heater 2 (bottom heater) Humidifier controller fuse (F4) Fuse for heater 1 (top heater) Liquid line solenoid valve fuse (F3) Humidifier controller (CPY) 24-VAC supply transformer fuse (F2) Humidifier electrode contactor Condensate pump fuse (F1) 24-V transformer for CPY J5 controller
Heater 2 contactor
Heater 1 contactor
Power supply 1 Controller cover Power supply 2 (Optional field-installed
accessory) Lower electrical box cover
Humidifier electrode current sensor Humidifier electrode fuse
26 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
0000373723_C
Outdoor Unit
ACCU300
Item Description Item Description
Low temperature kit fuse block Terminal block
Crank case heater switch
Fan motor switch Compressor variable-speed drive
switch Main switch
990-91356B-001 27
ACRD300 and ACCU300 Series Technical Data
0000373722_C
ACCU300D
Item Description Item Description
Low temperature kit fuse block Supply B line monitor Terminal block
Supply A contactor timer Crank case heater switch Supply B contactor timer Fan motor switch Compressor variable-speed drive
ATS circuit fuse
Supply line selector A/B switch Power supply A main switch
Supply A contactor Supply line selector relay Supply B contactor Supply A line monitor
Power supply B main switch
28 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
0000380408_C
ACCU301 and ACCU302
Item Description Item Description
Crank case heater power transformer Crank case heater power transformer
switch
Low temperature kit fuse block Terminal block
Crank case heater switch
Fan motor switch Compressor variable-speed drive
switch Main switch
990-91356B-001 29
ACRD300 and ACCU300 Series Technical Data
0000373721_C
ACCU301D and ACCU302D
Item Description Item Description
Crank case heater power transformer Supply A line monitor Low temperature kit fuse block Supply B line monitor Terminal block
Supply A contactor timer Crank case heater switch Supply B contactor timer Crank case heater power transformer
ATS circuit fuse switch Fan motor switch
Compressor variable-speed drive
Supply line selector A/B
Supply A contactor switch Power supply A main switch
ATS supply A power transformer
Supply B contactor
Power supply B main switch Supply line selector relay ATS supply B power transformer
30 990-91356B-001
Technical Data ACRD300 and ACCU300 Series

Performance Specifications

Cooling Capacity

Operating Conditions Sensible Net Capacity – kW
(BTU/h)
GB19413 16.3 (55,600)
ASHRAE 127 Class 3 25 (85,300) 3.2 SCOP
Maximum at 35°C (95°F) Return Air Temperature
Maximum at 40°C (104°F) Return Air Temperature
*If lower than the minimum load, the unit may cycle the compressor.
NOTE: Outdoor air temperature is 35°C (95°F) unless otherwise stated.
NOTE: Data is for evaporator fans, condenser fans, and compressors operating at maximum capacity.
NOTE: Refer to Unicalc for data at other operating conditions.
27 (92,100)
30 (102,400)
Energy Efficiency (W/W)
4.0 AEER
990-91356B-001 31
ACRD300 and ACCU300 Series Technical Data

General Data

Indoor Units
Air System—Fan
Fan Type
EC
Size – mm (in.) 220 (8.7)
Number of Fans
8
Air Volume – CMH (SCFM) 5440 (3200)
Fan Power – W (total)
Emergency Air Volume* – CMH (SCFM)
*
850
6300 (3700)
Cooling Coil
2
Face Area – m
(ft2) 0.51 (5.49)
Rows Deep 3
Filters—Washable (Standard)
Quantity
2
Size – mm (in.) 238 x 933 (9.375 x 36.75)
Depth – mm (in.) 12.7 (0.5)
Efficiency
MERV 1
Filters—Pleated (Optional)
Quantity
2
Size – mm (in.) 238 x 933 (9.375 x 36.75)
Depth – mm (in.) 51 (2)
Efficiency
MERV 8
Physical Data
Height – mm (in.) 1991 (78.39)
Width – mm (in.) 300 (11.81)
Depth – mm (in.) 1095 (43.11)
Connection Sizes (Not Piping Sizes)
Suction Piping 1 1/4 in. (12 UNF), 7/8 in. tube
Liquid Piping
1 in. (14 UNS), 1/2 in. tube
Condensate Drain 4.77 mm (3/16 in.) ID
6.35 mm (1/4 in.) OD
Humidifier Water Supply Line 1/4 in.
Humidification (ACRD301P only)
Flush Cycle
Automatic
Capacity – kg/hr (lb/hr) 3 kg/hr (6.6 lb/hr)
Reheat—Electric (ACRD301P only)
Capacity – kW (BTU/hr) 3 kW (10,200 BTU/hr) @ 220 V
Refrigerant
32 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
Type R410A
Standard Charge for ACRD300x and
11.3 (24.9)
ACRD301x Models – kg (lb)
Standard Charge for ACRD306x and
18.8 (43.0)
ACRD307x Models – kg (lb)
Standard Charge with ACAC75016/ACAC75017
29.3 (64.6)
Installed – kg (lb)
*Emergency air flow is available with dual fan power supplies and a humidity sensor.
Outdoor Units
Air System—Fan
Fan Type
Size – mm (in.) 710 (28.0)
Number of Fans 1
Cooling Coil
Face Area – m
Rows Deep 3
Physical Data
2
(ft2) 3.024 (32.55)
EC
Height – mm (in.) 1555 (61.2)
Width – mm (in.) 1000 (39.4)
Depth – mm (in.) 1000 (39.4)
Connection Sizes (Not Piping Sizes)
Gas Piping 7/8 in. ODF
Liquid Piping
Refrigerant Piping*
Maximum Equivalent Length – m (ft) 120 (393)
Maximum Elevation** – m (ft) 30 (98)
*See the Installation Manual for more information. **Condensing units may be level with or higher than the indoor unit.
See the Installation Manual for more information on refrigerant piping.
1/2 in. ODF
990-91356B-001 33
ACRD300 and ACCU300 Series Technical Data

Electrical Data

Indoor Units
Model
ACRD301S 20.3* / 9.3** 25.0* / 15.0** 16.5–13.8* / 8.0–6.7**
ACRD301P
*Data for units with 100–120-V~ power supplies. **Data for units with 200–240-V~ power supplies.
MCA MOP
41.75 45.0 28.5
FLA
Outdoor Units
Model
ACCU300
ACCU300D 50.05 80 n/a
ACCU301 23.1 40 n/a
ACCU301D
ACCU302 n/a n/a
ACCU302D n/a n/a
MCA MOP
50.05 80
23.1 40
FLA
n/a
n/a
15.8
15.8
34 990-91356B-001
Technical Data ACRD300 and ACCU300 Series

Sound Data

Indoor Units—All Units
Fan Speed
%
30 430 (900) 36.5 36.1 44.7 46.3 40.3 35.8 22.9 49.8
40 610 (1300) 36.2 42.1 52.6 51.2 47.7 45.9 34.3 56.4
50 780 (1650) 30.2 48.8 54.7 61.5 53.1 52.0 42.8 63.4
60 940 (2000) 32.9 55.2 56.0 62.3 57.7 56.2 48.3 65.4
70 1110 (2350) 33.8 60.3 59.3 65.7 62.1 59.5 52.9 69.2
80 1240
90 1390
100 1510
130** 1750
*Weighted Sound Pressure (dBA) data is measured in a semi-anechoic room in accordance with ISO 3745, at 1.8-m (6.0-ft) distance from the unit and 1-m (3.3-ft) height. **130% speed is only for the emergency free-cooling option. When the return temperature rises above the set temperature, the emergency free-cooling will allow the fans to run at 130% and provide more airflow. When it is planned to have a unit operate at 130% speed, the unit must have two power supplies and the humidity sensor.
Airflow –
l/s (SCFM)
34.6 61.8 63.5 71.9 64.1 63.0 56.8 73.9
(2700)
35.1 54.3 67.9 72.3 68.1 65.9 60.1 75.4
(2950)
43.1 53.8 70.0 73.3 70.1 68.9 62.9 77.1
(3200)
44.8 55.1 77.5 74.4 74.1 70.3 63.6 80.9
(3700)
Weighted Sound Pressure dBA* at Frequency – Hz re: 20μPa
125 250 500 1000 2000 4000 8000 dBA*
Lp Sound
Pressure – dB
re: 20μPa
Outdoor Units—All Units
Fan Speed
%
70 5400 Without 39.6 56.3 54.8 56.6 55.8 55.5 47.2 63.0
100 6000 Without 41.7 54.8 55.4 56.5 56.6 57.9 48.4 63.6
70 5400 With 38.3 52.7 52.3 54.3 51.2 50.1 41.1 59.5
100 6000 With 41.4 53.6 54.5 55.8 53.2 53.6 43.3 61.4
*Weighted Sound Pressure (dBA) data is measured in a semi-anechoic room in accordance with ISO 3745, at 2.0-m (6.6-ft) distance from the unit and 1-m (3.3-ft) height.
Compressor
RPM
Acoustic
Hood
Weighted Sound Pressure dBA* at Frequency – Hz re: 20μPa
125 250 500 1000 2000 4000 8000 dBA*
Lp Sound
Pressure – dB
re: 20μPa
990-91356B-001 35
ACRD300 and ACCU300 Series Technical Data
na6955b
1095 (43.11)
300 (11.80)
1991 (78.39)
1137 (44.76)
661 (26.02)
2152 (84.72)

Dimensions and Weights

Indoor Unit

NOTE: Image is an example only to show dimensions of unit: your unit may
differ.
SKU
Net Weight
– kg (lb)
Shipping Weight
– kg (lb)
ACRD301S 160.0 (352.7) 200.0 (440.9)
ACRD301P 173.5 (382.5) 213.5 (470.7)
36 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
A
B
C
A
B
C
na6956a

Outdoor Unit

SKU Unit Dimensions – mm (in.) Shipping Dimensions – mm (in.) Net Weight –
A B C A B C
ACCU300 1000
(39.4)
ACCU300D 1000
(39.4)
ACCU301 1000
(39.4)
ACCU301D 1000
(39.4)
ACCU302 1000
(39.4)
ACCU302D 1000
(39.4)
1000
(39.4)
1000
(39.4)
1000
(39.4)
1000
(39.4)
1000
(39.4)
1000
(39.4)
1555
(61.2)
1555
(61.2)
1555
(61.2)
1555
(61.2)
1555
(61.2)
1555
(61.2)
1136
(44.7)
1136
(44.7)
1136
(44.7)
1136
(44.7)
1136
(44.7)
1136
(44.7)
1085
(42.7)
1085
(42.7)
1085
(42.7)
1085
(42.7)
1085
(42.7)
1085
(42.7)
1745
(68.7)
1745
(68.7)
1745
(68.7)
1745
(68.7)
1745
(68.7)
1745
(68.7)
kg (lb)
267 (588.6) 297 (654.8)
272 (600.0) 305 (672.4)
267 (588.6) 297 (654.8)
272 (600.0) 305 (672.4)
273 (601.9) 303 (668.0)
278 (612.9) 308 (679.0)
Shipping
Weight – kg
(lb)
990-91356B-001 37
ACRD300 and ACCU300 Series Technical Data
na5810a
900 (36.00)
900 (36.00)
1
2
00 (48.00)
1200 (48.00)
SERVICE ACCESS REQUIRED WHEN EQUIPMENT IS INSIDE THE ROW
FREE SPACE NEEDED TO MOVE EQUIPMENT OUTSIDE THE ROW

Service Access

Indoor Unit
A minimum of 900 mm (36 in.) of clear floor space in front of and behind the equipment is recommended for service access. All required normal maintenance is performed from the front and rear of the equipment.
Most of the cooling components in the equipment can be replaced while the unit is installed in row and without the use of heavy lift equipment or a welding torch. However, if it is necessary to remove the unit for repair, use the casters on the equipment to remove it from the row. An area of minimum 1200 mm (48 in.) of clear floor space in front of or behind the equipment is recommended to roll out the equipment.
NOTE: Check local and national codes and regulations for further service access requirements.
NOTE: Image is an example only: your unit may differ.
NOTE: Dimensions are shown in mm (in.).
38 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
1m (39 in.)
1m (39 in.)
1m (39 in.)
1m (39
in
.)
1m (39 in.)
na6963a
na7029a
> 1 m
(3.3 ft)
> 1 m (3.3 ft)
> 3 m (9.8 ft)
Outdoor Unit
A minimum of 1 m (39 in.) of clear space on all sides of the equipment is recommended for service access.

Airflow Clearance

The following clearances are required for proper airflow around the outdoor unit.
990-91356B-001 39
ACRD300 and ACCU300 Series Technical Data
TOP VIEW
BOTTOM VIEW (LOOKING UP)
na6957b
56.5 (2.2)
47.8 (1.9)
55.1 (2.2)
73.5 (2.9)
87.3 (3.4)
78.4
(3.1)
123.4 (4.9)
182.8 (7.2)
150.4
(5.9)
190.4 (7.5)
227.0 (8.9)
274.0 (10.8)
148.8 (5.6)
157.9 (6.2)
213.6 (8.4)
102.0 (4.0)
73.5 (2.9)
55.1 (2.2)
62.8 (2.5)
188.8 (7.4)
111 (4.37)
101.7 (4.0)
463.0 (18.2)
88.8
(3.5)

Piping and Electrical Access Locations

Indoor Unit
ACRD301S
40 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
TOP VIEW
BOTTOM VIEW (LOOKING UP)
na6958b
Item Description
Low voltage input wiring inlets Power supply 1 inlet Power supply 2 inlet Suction line connection—1 1/4 in. (12 UNF) Liquid line connection—1 in. (14 UNS) Condensate drain line outlet Gravity drain connection
990-91356B-001 41
ACRD300 and ACCU300 Series Technical Data
TOP VIEW
BOTTOM VIEW (LOOKING UP)
na6957c
46.0 (1.8)
47.8 (1.9)
55.1 (2.2)
73.5 (2.9)
116.3 (4.6)
78.4
(3.1)
123.4 (4.9)
182.8 (7.2)
137.4 (5.4)
142.1 (5.6)
180.1 (7.1)
148.8 (5.6)
167.9 (6.6)
213.6 (8.4)
73.5 (2.9)
55.1 (2.2)
62.8 (2.5)
188.8 (7.4)
111 (4.37)
101.7 (4.0)
463.0 (18.2)
88.8 (3.5)
104.8 (4.1)
76.3 (3.0)
123.0 (4.8)
224.4 (8.8)
106.9
(4.2)
ACRD301P
42 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
TOP VIEW
BOTTOM VIEW (LOOKING UP)
na6958c
Item Description
Condensate drain line outlet Humidifier water supply inlet connection—1/4-in. NPT or 1/4-in. BSPT Power supply 1 inlet Power supply 2 inlet Low voltage input wiring inlets Suction line connection—1 1/4 in. (12 UNF) Liquid line connection—1 in. (14 UNS) Gravity drain connection
990-91356B-001 43
ACRD300 and ACCU300 Series Technical Data
na6961a
309.3 (12.2)
371.0 (14.6)
105.6 (4.2)
121.8 (4.8)
169.0 (6.7)
206.5 (8.1)
259.3 (10.2)
Outdoor Unit
44 990-91356B-001
Technical Data ACRD300 and ACCU300 Series
na6962a
NOTE: Dimensions are shown in mm (in.).
Item Description
Power supply 1 inlet Power supply 2 inlet Communication cable inlet Liquid receiver connection outlet Liquid line connection inlet Suction line connection inlet
990-91356B-001 45
ACRD300 and ACCU300 Series Technical Data
na2543c
BOTTOM PIPING TOP PIPING
CONDENSING UNIT
CONDENSING UNIT
DX
UNIT
RECEIVER
RECEIVER
HOT GAS
HOT GAS
LIQUID
LIQUID
DX
UNIT

Refrigeration Piping Diagram

ACRD301P, ACRD301S
Item Description Item Description
Pitch in direction of refrigerant flow; 4 mm per m (1/2-in. per 10 ft)
Reduction of piping diameter for vertical piping run (if necessary)
Shut-off valve S-trap
Head pressure control valve Inverted P-trap
Pressure relief valve
Check valve
P-trap
46 990-91356B-001
Worldwide Customer Support
Customer support for this or any other product is available at no charge in any of the following ways:
Visit the Schneider Electric Web site to access documents in the Schneider Electric Knowledge Base and to submit customer support requests.
- www.schneider-electric.com (Corporate Headquarters)
Connect to localized Schneider Electric Web sites for specific countries, each of
which provides customer support information.
- www.schneider-electric.com/support/
Global support searching Schneider Electric Knowledge Base and using
esupport.
Contact the Schneider Electric Customer Support Center by telephone or e-mail.
Local, country-specific centers: go to www.schneider-electric.com/support/
contactwww.schneider-electric.com > Support > Operations around the
world for contact information.
For information on how to obtain local customer support, contact the representative or other distributors from whom you purchased your product.
Schneider Electric
35 rue Joseph Monier 92500 Rueil Malmaison France
+ 33 (0) 1 41 29 70 00
https://www.se.com
As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication.
© 2019 – 2021 Schneider Electric. All rights reserved.