The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Piping and Electrical Access Locations ................................................. 40
990-91356B-0013
Technical DataACRD300 and ACCU300 Series
REAR
NAME PLATE
na4402b
Technical Data
Model Identification
Indoor Unit
The model number can be found on the outside of the shipping crate and on the
name plate located on the unit as shown. Use the table below to verify that the
equipment is the right type and voltage.
NOTE: The unit is not to be accessed by the general public.
SKUVoltageFrequency65
ACRD301S100–120 V~* /
200–240 V~
ACRD301P200–240 V~50/60 HzNoDual feed1Condensate
*Configure proper voltage before applying power to the cooling unit.
NOTE: All units have a rear-to-front airflow pattern.
50/60 HzYesDual feed1Condensate
kAIC
Power FeedNumber of
Fan Power
Supplies
Drainage
System
pump
pump
Humidification/
Reheat
No/No
Yes/Yes
990-91356B-0015
ACRD300 and ACCU300 SeriesTechnical Data
na6990a
NAME PLATE
Outdoor Unit
The model number can be found on the outside of the shipping crate and on the
name plate located on the unit as shown. Use the table below to verify that the
equipment is the right type and voltage.
NOTE: The unit is not to be accessed by the general public.
SKUVoltageFrequencyPower Feed
ACCU300200–240 V 3~50/60 HzSingle feed
ACCU300D200–240 V 3~50/60 HzDual feed
ACCU302380–415 V 3~50/60 HzSingle feed
ACCU302D380–415 V 3~50/60 HzDual feed
ACCU301460–480 V 3~50/60 HzSingle feed
ACCU301D460–480 V 3~50/60 HzDual feed
NOTE: All units are 65 kAIC-ready.
6990-91356B-001
Technical DataACRD300 and ACCU300 Series
Overview
The ACRD300 series of indoor units can provide a cooling capacity up to 30 kW
based on a half-rack platform (300 mm (12 in.)) with an ACCU300 series outdoor
condensing unit. A variable-speed compressor works with EC fans and a fin-tube
exchanger to reach the best cooling efficiency.
This modular, row-based computer room cooling system offers efficient,
predictable, and economical cooling for a variety of spaces.
Critical environmental requirements now reach far beyond the confines of the
traditional data center or computer room to encompass a larger suite of
applications, referred to as technology rooms. Critical environment applications
include the following:
•Computer rooms
•Telecommunication facilities
•Clean rooms
•Power equipment
•Medical equipment rooms
•LAN/WAN environments
•Edge data centers
•Traditional data centers
A worldwide network by Schneider Electric representatives is fully qualified to
provide engineering, sales, installation, and service for our products.
Capacities
Room Air Distribution
Uniflair™Direct Expansion (DX) InRow®units in the ACRD300 series are available
as a 300-mm.
Row-based systems are placed in line with rack enclosures. At least one system is
used per hot aisle. Air is drawn in through the rear of the system, cooled, and
discharged into the cold aisle, thereby neutralizing the sensible heating effects of
the data processing equipment. Uniflair Direct Expansion InRow products deliver
high volumes of airflow to eliminate hot spots in densely populated environments.
Configuration:
•Air-cooled
990-91356B-0017
ACRD300 and ACCU300 SeriesTechnical Data
Compliance Approval
Indoor Unit
ModelUL and cULRCMCEEACCCCCMIM
ACRD301SXXXX
ACRD301PXXX
Outdoor Unit
ModelUL and cULRCMCEEACCCCCMIM
ACCU300X
ACCU300DX
ACCU301X
ACCU301DX
ACCU302XX
ACCU302DXX
8990-91356B-001
Technical DataACRD300 and ACCU300 Series
Working Conditions and Environmental Limits
Uniflair Direct Expansion InRow units have a minimum heat load to ensure proper
operation. Failure to operate the unit with at least the minimum load will result in
one or more of the following conditions:
•Unstable unit operation
•Decreased operating efficiency
•Equipment on/off cycling
•Inadequate dehumidification
•Increased wear and tear caused by frequent on/off cycles
•Decreased group control effectiveness
•Potential increase in cost of ownership
Limit Working Conditions—Indoor Units (ACRD301P, ACRD301S)
Outdoor ambient temperature without the low
ambient temperature kit installed
Outdoor ambient temperature with the low
ambient temperature kit installed
Ambient %RH5 to 80%RH
Altitude3000 m (9843 ft)
Storage Conditions
Temperature–25°C to +65°C (–13°F to +149°F)
Humidity5 to 95%RH
NOTE: ACRD301P and ACRD301S are in accordance with the Electromagnetic Compatibility Standard (EMC): EN 55032, EN55024,
EN61000-3-2, EN61000-3-3, EN61000-6-3, EN61000-6-1, EN61000-3-11, EN 61000-3-12.
ACRD301P and ACRD301S are in accordance with FCC: ANSI C63.4.
NOTE: The SKUs comply with EN61000-3-12 provided that the short-circuit power SSC is greater than or equal to 350 at the interface
point between the user supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit
power SSC greater than or equal to 350.
Limit Working Conditions—Outdoor Units (ACCU300. ACCU300D, ACCU302, ACCU302D, ACCU301, and ACCU301D)
Refrigerant typeR410A
Altitude3000 m (9843 ft)
Storage Conditions
Down to –15°C (+5°F)
Up to 48°C (118°F)
Down to –40°C (–40°F)
Up to 48°C (118°F)
Temperature–25°C to +65°C (–13°F to +149°F)
Humidity5 to 95%RH
NOTE: ACCU302 and ACCU302D are in accordance with the Electromagnetic Compatibility Standard (EMC): EN 55032, EN55024,
EN61000-3-2, EN61000-3-3, EN61000-6-3, EN61000-6-1, EN61000-3-11, EN 61000-3-12.
ACCU300, ACCU300D, ACCU301, and ACCU301D are in accordance with FCC: ANSI C63.4.
NOTE: The SKUs comply with EN61000-3-12 provided that the short-circuit power SSC is greater than or equal to 350 at the interface
point between the user supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit
power SSC greater than or equal to 350.
990-91356B-0019
ACRD300 and ACCU300 SeriesTechnical Data
na5859a
HOT AISLE
Scalable Solution for Critical Environments
InRow Advantages
The row-based solution improves energy efficiency and cooling ability in a number
of ways. First, the Uniflair Direct Expansion InRow unit draws air directly from the
hot aisle, allowing the unit to take advantage of higher heat transfer efficiency due
to higher temperature differences. It can then discharge room-temperature air
directly in front of the servers it is cooling. Placing the unit in the row enables the
unit to operate at higher return and supply air temperatures, yielding 100%
sensible capacity. This significantly reduces the need for humidification.
Scalable for High Density
The predictable performance of the row-based architecture makes it well-suited
for high density applications. The focus on heat removal instead of cold-air
delivery is the key to making this approach scalable. The modular design of the
Uniflair Direct Expansion InRow unit allows it to be easily added in the row as the
demand for cooling increases.
The additional benefit of the row-based architecture is the ability to add hot-aisle
containment. Containing the hot aisle further reduces any chance of hot and cold
air streams mixing. This provides ultimate predictability and allows the cooling
capacity to be matched to the IT heat load.
10990-91356B-001
Technical DataACRD300 and ACCU300 Series
Standard Features and Options
Standard Features
EcoStruxure
The ACRD300 Series is ready to connect to the world-leading DCIM platform.
™
Ready
Cabinet
The frame of the ACRD300 series units is constructed of 16-gauge formed steel
for maximum strength. The cabinet is serviceable from the front and rear. All
exterior panels and corner posts on the frame are powder coated for durability and
an attractive finish. The front and rear exterior panels are constructed of 18 gauge
perforated steel with 80% open free area. All panels, which include a key latch for
safety and security, allow easy access and removal. The footprint of 300 mm
takes up less space in the data center.
Condensate Pump
•ACRD301S and ACRD301P: A condensate pump is factory wired and piped
internally to the condensate drain pan. Within the condensate pump, there is
a dual position float. The first position is used for condensate pump control
and the other float generates a condensate pump failure alarm to prevent
condensate pan overflow.
Counterflow Cooling Coil/Condensate Pan
Designed for high-sensible heat ratios, the coil is constructed with copper tubes,
raised-lance-type aluminum fins, and 18-gauge galvanized steel end plates. Coil
headers are equipped with anti-drip shields in the event of condensation. The
condensate pan is thermal formed non-ferrous material, and is sloped for positive
drainage to provide higher indoor air quality.
Electric Reheat (ACRD301P)
Electric reheat elements are low watt density, wired for single-phase and loaded
equally on all three phases, and electrically and thermally protected by both
automatic and manual reset thermal cut outs. Reheat elements are stainless steel,
fin tubular construction.
Filters
Filtration of conditioned air is extremely vital to maintaining the clean, particle-free
environment required by electrical equipment. Filters are easily replaceable from
the rear of the unit. ACRD300 series units use greater-than 20% efficiency
ASHRAE 52.1, 12.7 mm (1/2 in.) washable filters that meet HF-1 standards for
electronics (MERV 1 per ASHRAE 52.2)
990-91356B-00111
ACRD300 and ACCU300 SeriesTechnical Data
Humidifier (ACRD301P only)
The humidifier is a self-contained, steam-generating type, factory piped and wired,
with a disposable cylinder and an automatic solid state control circuit. Humidifier
canisters are replaceable. The humidifier controller communicates directly to the
microprocessor controller and provides complete status and control at the
operator interface.
Network Management Card
The Network Management Card (NMC) allows communication with the local area
network (LAN). In addition, the NMC permits multi-level access to monitoring,
control, and event notification features over the building network.
Remote Temperature Sensors
To control the cooling unit based on rack inlet temperature, remote temperature
sensors are provided. The ACRD300 series units come equipped with one
temperature sensor. These sensors measure temperature at a point 4 m (13 ft)
from the connection inside the Uniflair Direct Expansion InRow unit. These
sensors are used for remote placement in the field on an adjacent IT rack.
Shutdown Input/Alarm Output
The unit provides one field connection input for remote shutdown and one field
connection alarm output.
Power
•3.2 rated SCOP (EER)
◦Substantially lower power consumption
•Power by UPS
◦Due to low current draw, connect the indoor unit secondary power feed to
the UPS for easy power backup.
Selectable Top or Bottom Piping Connections
The cooling unit includes both top and bottom piping connections. All ACRD300
series connections use threaded ring seals for ease of installation and service.
Variable-Speed Fans
Each unit is equipped with variable speed fans to allow for varying heat loads. In
order to provide uniform airflow over the cooling coil, the fans provide a drawthrough air pattern. ACRD300 series units are equipped with eight direct-drive fan
modules. These fans are easily replaceable while the unit is in operation.
R410A Refrigerant
R410A refrigerant does not harm the ozone layer and has a very low contribution
to the global warming impact.
Outdoor Condensing Unit
The outdoor condensing unit has a small footprint of 1 m2(10.8 ft2). Moving the
compressor to the outdoor condensing unit improves serviceability for the indoor
unit and lowers the sound level in the IT space.
12990-91356B-001
Technical DataACRD300 and ACCU300 Series
Electronic Expansion Valve
The EEV provides accurate control of the refrigerant superheat in order to ensure
an increase in efficiency at low external temperatures because it enables the unit
to operate at much lower condensing pressures than would be possible with a
traditional mechanical valve.
Display Interface
The standard arrangement of the touch-screen display, RS 485 serial card, and
USB connection allows direct connection to BMSs based on serial lines. The USB
port allows quick downloads of the unit settings and parameters.
Microprocessor
The control system consists of two sections: the J5 controller containing the
regulation software and is installed in the unit electrical panel, and the 4.3-inch,
touch-screen display interface on the exterior of the unit.
The control system uses sophisticated algorithms to control the outlet water
temperature within a minimal range and to monitor and protect the various unit
components. The display interface provides clear information on the unit status
and any current alarms.
Low Ambient Kit
The low ambient kit provides the capability to operate in lower temperatures, down
to -40°C (-40°F) . Contact Schneider Electric for more details.
The kit can be field supplied or purchased from Schneider Electric.
990-91356B-00113
ACRD300 and ACCU300 SeriesTechnical Data
Optional Features
Aisle Containment
This containment solution isolates pods (two rows of Uniflair Direct Expansion
InRow cooling units sharing a common aisle) from the whole IT environment,
increasing cooling efficiency at any density.
Cable Water Detector
A leak detection cable is placed on the floor or sub-floor around all possible leak
sources. If water or other conductive liquids contact the cable anywhere along its
length, the microprocessor controller announces the leak visually, audibly, and
across the network. The 6.1-m (20-ft) cable may be cascaded to make custom
lengths up to 24.4 m (80 ft).
Humidity Monitoring
An optional remote sensor is available to monitor the humidity level of the data
center.
Dual Power Circuits
Optional integrated redundant power circuits provide full power redundancy.
Compressor Acoustic Hood
An optional compressor acoustic hood reduces the sound level.
Data Partition
Overhead cable distribution between adjacent NetShelter racks allows for removal
of the Uniflair Direct Expansion InRow units without disrupting overhead cabling.
Filters
Electrical equipment requires clean, particle-free air, thus making air filtration
extremely important. As an optional feature, higher efficiency filters can be
purchased for the Uniflair Direct Expansion InRow units. The ACRD300 series
units optionally use an 50.8 mm (2 in.) pleated, deep loading, 30% ASHRAE 52.1
filter (MERV 8 per ASHRAE 52.2).
Height Adapters
To match height of the Uniflair Direct Expansion InRow cooling units to various
rack heights, height adapters are available for NetShelter 42-U VX and 48-U SX
racks.
Network Cable
Various lengths of network cable are available to ship with your cooling system.
The network cable is used to interconnect multiple units in a redundant group, as
well as to connect the Network Management Card to your LAN.
Power Trough
Overhead power distribution between adjacent NetShelter racks allows for
removal of the Uniflair Direct Expansion InRow cooling units without disrupting
overhead power cabling.
14990-91356B-001
Technical DataACRD300 and ACCU300 Series
Rack Air Containment
This containment solution isolates the airflow of InRow cooling units from the
whole IT environment, increasing efficiency while allowing for high density
deployment.
990-91356B-00115
ACRD300 and ACCU300 SeriesTechnical Data
Display
Reset
Micro
SD
Service
Port
USB
Console
10/100
na4820a
Microprocessor Controller
Display Interface
ItemDescriptionFunction
LCD Display
4.3-inch touch-screen color display
Power LEDThe cooling unit is powered when the LED is illuminated. Unit
firmware is updating when LED is blinking.
Check Log LED
When this LED is illuminated, a new entry has been made to the
event log.
Alarm LED
Status LED
Display Reset button
Displays current alarm condition of unit.
Displays current network management card status.
Resets the display microprocessor. This has no effect on the air
conditioner controller.
Link-RX/TX (10/100) LED
Micro SD card slot
Displays current network link status.
Memory card expansion slot.
Service portUSB-B port used only by service personnel.
USB-A portSupports firmware upgrades.
Serial Configuration portConnects the display to a local computer to configure initial
network settings or access the command line interface (CLI).
16990-91356B-001
Technical DataACRD300 and ACCU300 Series
Microprocessor Controller
The microprocessor controller is standard on each system. The easy-to-use
touch-screen display allows the operator to select options from the menu-driven
interface to control and monitor the connected air conditioning system.
Open Architecture
The Uniflair Direct Expansion InRow cooling protocol is open for integration with
all building management systems. Communication interface on the system can be
MODBUS RS485 or Ethernet.
Control Type
The controller uses proportional/integral/derivative (PID), a time-proven precision
environmental control method. This allows for custom tuning of control variables to
achieve desired system response.
Functions
•Supply and return air conditions
•Operational mode control
•Event logging
•Alarms
•Redundant group control
•Fan speed adjustment
•Input/Output module programming
Control
The touch-screen LCD display interface is protected by a configurable password
and provides access to information and settings for the unit.
•Supply Temperature Setpoint: 15.0–30.2°C (59.0–86.4°F)
•Cool Setpoint: 18.0–32.2°C (64.4–90.0°F)
•Rack Inlet High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
•Supply Air High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
•Return Air High Temperature Threshold: 10.0–65.6°C (50.0–150.1°F)
990-91356B-00117
ACRD300 and ACCU300 SeriesTechnical Data
Alarms
The microprocessor controller shall activate a visible and audible alarm in the
following occurrences:
•Air filter clogged
•Return air sensor fault
•Supply air sensor fault
•Rack temperature sensor fault
•High discharge pressure
•Low suction pressure
•Fan fault
•Water detected (if optional leak detector used)
•Check condensate management system
•Air filter run hours violation
•Group communication fault
•Supply air high temperature violation
•Return air high temperature violation
•Filter DP sensor failure
•Suction pressure sensor failure
•Discharge pressure sensor failure
•Persistent high discharge pressure fault
•Rack inlet temperature high violation
•Internal communication fault
•Condensate pan full
•Persistent low suction pressure fault
•Compressor drive communication fault
•Compressor drive fault
•Compressor run hours violation
•Condensate pump run hours violation
•Idle mode active
•High pressure switch active
•Compressor high pressure
•Excessive compressor cycling
18990-91356B-001
Technical DataACRD300 and ACCU300 Series
na6950a
Component Identification
External Components
Indoor Unit—All ACRD30X Units
ItemDescription
Upper side panel
Upper piping connection openings
Filters
Rear panel
Lower side panel
Rear casters (non-swiveling)
Lower piping connection openings
Front casters (swiveling)
Leveling feet
Front panel
Display interface
990-91356B-00119
ACRD300 and ACCU300 SeriesTechnical Data
na6953c
Outdoor Unit—All ACCU Units
ItemDescriptionItemDescription
FanMounting holes
Main disconnect switch handle (field
*Data for units with 100–120-V~ power supplies.
**Data for units with 200–240-V~ power supplies.
MCAMOP
41.7545.028.5
FLA
Outdoor Units
Model
ACCU300
ACCU300D50.0580n/a
ACCU30123.140n/a
ACCU301D
ACCU302n/an/a
ACCU302Dn/an/a
MCAMOP
50.0580
23.140
FLA
n/a
n/a
15.8
15.8
34990-91356B-001
Technical DataACRD300 and ACCU300 Series
Sound Data
Indoor Units—All Units
Fan Speed
%
30430 (900)36.536.144.746.340.335.822.949.8
40610 (1300)36.242.152.651.247.745.934.356.4
50780 (1650)30.248.854.761.553.152.042.863.4
60940 (2000)32.955.256.062.357.756.248.365.4
701110 (2350)33.860.359.365.762.159.552.969.2
801240
901390
1001510
130**1750
*Weighted Sound Pressure (dBA) data is measured in a semi-anechoic room in accordance with ISO 3745, at 1.8-m (6.0-ft) distance from
the unit and 1-m (3.3-ft) height.
**130% speed is only for the emergency free-cooling option. When the return temperature rises above the set temperature, the emergency
free-cooling will allow the fans to run at 130% and provide more airflow. When it is planned to have a unit operate at 130% speed, the unit
must have two power supplies and the humidity sensor.
Airflow –
l/s (SCFM)
34.661.863.571.964.163.056.873.9
(2700)
35.154.367.972.368.165.960.175.4
(2950)
43.153.870.073.370.168.962.977.1
(3200)
44.855.177.574.474.170.363.680.9
(3700)
Weighted Sound Pressure dBA* at Frequency – Hz re: 20μPa
1252505001000200040008000dBA*
Lp Sound
Pressure – dB
re: 20μPa
Outdoor Units—All Units
Fan Speed
%
705400Without39.656.354.856.655.855.547.263.0
1006000Without41.754.855.456.556.657.948.463.6
705400With38.352.752.354.351.250.141.159.5
1006000With41.453.654.555.853.253.643.361.4
*Weighted Sound Pressure (dBA) data is measured in a semi-anechoic room in accordance with ISO 3745, at 2.0-m (6.6-ft) distance from
the unit and 1-m (3.3-ft) height.
Compressor
RPM
Acoustic
Hood
Weighted Sound Pressure dBA* at Frequency – Hz re: 20μPa
1252505001000200040008000dBA*
Lp Sound
Pressure – dB
re: 20μPa
990-91356B-00135
ACRD300 and ACCU300 SeriesTechnical Data
na6955b
1095 (43.11)
300 (11.80)
1991 (78.39)
1137 (44.76)
661 (26.02)
2152 (84.72)
Dimensions and Weights
Indoor Unit
NOTE: Image is an example only to show dimensions of unit: your unit may
differ.
SKU
Net Weight
– kg (lb)
Shipping Weight
– kg (lb)
ACRD301S160.0 (352.7)200.0 (440.9)
ACRD301P173.5 (382.5)213.5 (470.7)
36990-91356B-001
Technical DataACRD300 and ACCU300 Series
A
B
C
A
B
C
na6956a
Outdoor Unit
SKUUnit Dimensions – mm (in.)Shipping Dimensions – mm (in.)Net Weight –
ABCABC
ACCU3001000
(39.4)
ACCU300D1000
(39.4)
ACCU3011000
(39.4)
ACCU301D1000
(39.4)
ACCU3021000
(39.4)
ACCU302D1000
(39.4)
1000
(39.4)
1000
(39.4)
1000
(39.4)
1000
(39.4)
1000
(39.4)
1000
(39.4)
1555
(61.2)
1555
(61.2)
1555
(61.2)
1555
(61.2)
1555
(61.2)
1555
(61.2)
1136
(44.7)
1136
(44.7)
1136
(44.7)
1136
(44.7)
1136
(44.7)
1136
(44.7)
1085
(42.7)
1085
(42.7)
1085
(42.7)
1085
(42.7)
1085
(42.7)
1085
(42.7)
1745
(68.7)
1745
(68.7)
1745
(68.7)
1745
(68.7)
1745
(68.7)
1745
(68.7)
kg (lb)
267 (588.6)297 (654.8)
272 (600.0)305 (672.4)
267 (588.6)297 (654.8)
272 (600.0)305 (672.4)
273 (601.9)303 (668.0)
278 (612.9)308 (679.0)
Shipping
Weight – kg
(lb)
990-91356B-00137
ACRD300 and ACCU300 SeriesTechnical Data
na5810a
900 (36.00)
900 (36.00)
1
2
00 (48.00)
1200 (48.00)
SERVICE ACCESS REQUIRED
WHEN EQUIPMENT IS
INSIDE THE ROW
FREE SPACE NEEDED TO
MOVE EQUIPMENT
OUTSIDE THE ROW
Service Access
Indoor Unit
A minimum of 900 mm (36 in.) of clear floor space in front of and behind the
equipment is recommended for service access. All required normal maintenance
is performed from the front and rear of the equipment.
Most of the cooling components in the equipment can be replaced while the unit is
installed in row and without the use of heavy lift equipment or a welding torch.
However, if it is necessary to remove the unit for repair, use the casters on the
equipment to remove it from the row. An area of minimum 1200 mm (48 in.) of
clear floor space in front of or behind the equipment is recommended to roll out
the equipment.
NOTE: Check local and national codes and regulations for further service
access requirements.
NOTE: Image is an example only: your unit may differ.
NOTE: Dimensions are shown in mm (in.).
38990-91356B-001
Technical DataACRD300 and ACCU300 Series
1m (39 in.)
1m (39 in.)
1m (39 in.)
1m (39
in
.)
1m (39 in.)
na6963a
na7029a
> 1 m
(3.3 ft)
> 1 m (3.3 ft)
> 3 m (9.8 ft)
Outdoor Unit
A minimum of 1 m (39 in.) of clear space on all sides of the equipment is
recommended for service access.
Airflow Clearance
The following clearances are required for proper airflow around the outdoor unit.
990-91356B-00139
ACRD300 and ACCU300 SeriesTechnical Data
TOP VIEW
BOTTOM VIEW
(LOOKING UP)
na6957b
56.5 (2.2)
47.8 (1.9)
55.1 (2.2)
73.5 (2.9)
87.3 (3.4)
78.4
(3.1)
123.4 (4.9)
182.8 (7.2)
150.4
(5.9)
190.4 (7.5)
227.0 (8.9)
274.0 (10.8)
148.8 (5.6)
157.9 (6.2)
213.6 (8.4)
102.0 (4.0)
73.5 (2.9)
55.1 (2.2)
62.8 (2.5)
188.8 (7.4)
111 (4.37)
101.7 (4.0)
463.0 (18.2)
88.8
(3.5)
Piping and Electrical Access Locations
Indoor Unit
ACRD301S
40990-91356B-001
Technical DataACRD300 and ACCU300 Series
TOP VIEW
BOTTOM VIEW
(LOOKING UP)
na6958b
ItemDescription
Low voltage input wiring inlets
Power supply 1 inlet
Power supply 2 inlet
Suction line connection—1 1/4 in. (12 UNF)
Liquid line connection—1 in. (14 UNS)
Condensate drain line outlet
Gravity drain connection
990-91356B-00141
ACRD300 and ACCU300 SeriesTechnical Data
TOP VIEW
BOTTOM VIEW
(LOOKING UP)
na6957c
46.0 (1.8)
47.8 (1.9)
55.1 (2.2)
73.5 (2.9)
116.3 (4.6)
78.4
(3.1)
123.4 (4.9)
182.8 (7.2)
137.4 (5.4)
142.1 (5.6)
180.1 (7.1)
148.8 (5.6)
167.9 (6.6)
213.6 (8.4)
73.5 (2.9)
55.1 (2.2)
62.8 (2.5)
188.8 (7.4)
111 (4.37)
101.7 (4.0)
463.0 (18.2)
88.8
(3.5)
104.8 (4.1)
76.3 (3.0)
123.0 (4.8)
224.4 (8.8)
106.9
(4.2)
ACRD301P
42990-91356B-001
Technical DataACRD300 and ACCU300 Series
TOP VIEW
BOTTOM VIEW
(LOOKING UP)
na6958c
ItemDescription
Condensate drain line outlet
Humidifier water supply inlet connection—1/4-in. NPT or 1/4-in. BSPT
Power supply 1 inlet
Power supply 2 inlet
Low voltage input wiring inlets
Suction line connection—1 1/4 in. (12 UNF)
Liquid line connection—1 in. (14 UNS)
Gravity drain connection
990-91356B-00143
ACRD300 and ACCU300 SeriesTechnical Data
na6961a
309.3 (12.2)
371.0 (14.6)
105.6 (4.2)
121.8 (4.8)
169.0 (6.7)
206.5 (8.1)
259.3 (10.2)
Outdoor Unit
44990-91356B-001
Technical DataACRD300 and ACCU300 Series
na6962a
NOTE: Dimensions are shown in mm (in.).
ItemDescription
Power supply 1 inlet
Power supply 2 inlet
Communication cable inlet
Liquid receiver connection outlet
Liquid line connection inlet
Suction line connection inlet
990-91356B-00145
ACRD300 and ACCU300 SeriesTechnical Data
na2543c
BOTTOM PIPINGTOP PIPING
CONDENSING UNIT
CONDENSING UNIT
DX
UNIT
RECEIVER
RECEIVER
HOT GAS
HOT GAS
LIQUID
LIQUID
DX
UNIT
Refrigeration Piping Diagram
ACRD301P, ACRD301S
ItemDescriptionItemDescription
Pitch in direction of refrigerant flow; 4 mm
per m (1/2-in. per 10 ft)
Reduction of piping diameter for vertical
piping run (if necessary)
Shut-off valveS-trap
Head pressure control valveInverted P-trap
Pressure relief valve
Check valve
P-trap
46990-91356B-001